List of Expr Only
List of Expr Only
List of Expr Only
:
Date :
OPEN CIRCUIT CHARACTERISTICS AND LOAD CHARACTERISTICS OF
SEPARATELY EXCITED DC SHUNT GENERATOR
AIM
To obtain the O.C.C of the given separately excited DC shunt generator and hence to
determine Critical field resistance
And To conduct the direct load test on the given DC shunt generator to plot
i) External Characteristics (or Load Characteristics)
ii) Internal Characteristics (or Total Characteristics)
FUSE RATING
APPARATUS REQUIRED
THEORY
A D.C. generator requires an excitation circuit to generate an induced voltage. Depending on
whether the excitation circuit consumes power from the armature of the machine or from separately
required power supply, the generators may be classified as self excited or separately excited
generators respectively
The induced EMF in a DC generator is given by the equation E g = PZN/ 60A volts. Since P,
Z and A are constants the above equation can be rewritten as E g = KN. If the speed of the generator
1
is also maintained constant then Eg =K1 , but the flux is directly proportional to the field current,
hence Eg = K2 If. From the above equation it is clear that the induced EMF is directly proportional to
the field current when speed is maintained constant. The plot between the induced EMF and the
field current is known as open circuit characteristics of the DC generator. The typical shape of this
characteristic is shown in figure.
The induced EMF when the field current is zero is known as residual voltage. This EMF is
due to the presence of a small amount of flux retained in the field poles of the generator called
residual flux. Once the O.C.C is obtained the parameters such as critical field resistance, critical
speed and the maximum voltage to which the machine can build up can be determined. If required
the O.C.C at a different speeds can also be obtained. Critical speed is minimum speed below which
the generator shunt fails to excite.
CIRCUIT DIAGRAM
To Find Ra
2
NAME PLATE DETAILS
Voltage : Voltage :
Current : Current :
PRECAUTION
FORMULAE
3
(i) OCC Test
To calculate critical resistance (Rc)
From Magnetization (OCC) Curve, if the field resistance (Excitation Current) is increased, at
one point the resistance (Excitation Current) line becomes a tangent to the OCC. This value of
the resistance is called the critical resistance. And the critical resistance is obtained by E / I f
1. The circuit connections are made as per the circuit diagram in the shown figure.
2. Keeping the motor field rheostat in its minimum position, generator field rheostat in
maximum position; and the starter in its OFF position, the main supply is switched ON to
the circuit.
3. The motor is started using the 3-point starter by slowly and carefully moving the starter
handle from its OFF to ON position,
4. The motor is brought to its rated speed by adjusting its rheostat and checked with the help of
a tachometer.
5. With the SPST switch open, the residual voltage is noted.
6. Now the SPST switch is closed and the field rheostat is varied in steps and at each step the
field current (If) and the corresponding induced EMF (Eg) are recorded in the tabular
4
column. This procedure is continued until the generator voltage reaches 125% of its rated
value the speed of the machine is maintained constant.
7. After the experiment is completed the various rheostats are brought back to their original
position in sequence and then main supply is switched OFF.
8. The Critical resistance is found from the graph. [If the field resistance is increased, at one
point the resistance line becomes a tangent to the OCC. This value of the resistance is called
the critical resistance.
LOAD CHARACTERISTICS
1. The circuit connections are made as per the circuit diagram.
2. Keeping the motor field rheostat in its minimum position, generator field rheostat in
maximum position and the starter in its OFF position, the main supply is switched ON to the
circuit.
3. The motor is started using the 3-point starter by slowly and carefully moving the starter
handle from its OFF to ON position.
4. The motor is brought to its rated speed by adjusting its field rheostat and checked with the
help of the tachometer.
5. With the DPST switch open, the generator field rheostat is slowly decreased until the
generator voltage is equal to its rated value (220V). The terminal voltage and the field
current are noted in the tabular column.
6. The DPST switch on the load side is now closed and the load on the generator is gradually
increased in steps by switching on the lamps one by one. At each step the speed of the
generator is checked and maintained constant at its rated value by adjusting the field rheostat
of the motor. After satisfying this condition at each step of loading, the terminal voltage
(VL), field current (If) and the load current (IL) are noted down in the tabular column.
7. This procedure is continued until the generator is loaded to 125% of its rated value.
8. Once the experiment is completed the load on the generator is gradually decreased, the
various rheostats are brought back to their original position in sequence and the main supply
is switched OFF.
5
PROCEDURE FOR MEASUREMENT OF ARMATURE RESISTANCE
OBSERVATION
OPEN CIRCUIT CHARACTERISTICS
6
VL IL If Ia (Ia = IL) Ia Ra(eff) (Volts)
(Amps) (Amps)
(Volts) (Amps) (Volts)
MODEL GRAPH
7
RESULT
Thus the magnetization characteristic curve is drawn. The value of build up voltage and
Critical Resistance is obtained from the graph. And the direct load test on the given DC shunt
generator has been conducted and the internal and external characteristics are plotted.
8
Exp.No: OPEN CIRCUIT AND LOAD CHARACTERISTICS
Date : SELF EXCITED DC SHUNT GENERATOR
AIM
To obtain the open circuit characteristics of a DC Shunt Generator at rated
speed and to determine (i) Critical field resistance at rated speed (ii)Critical Speed (iii)
Voltage built up by the generator at rated speed and (iv) to plot the OCC characteristic
curves
a) To conduct the Load test on the given DC Shunt Generator and plot its internal
and external characteristics.
APPARATUS REQUIRED
PRECAUTIONS:
9
PROCEDURE
OPEN CIRCUIT TEST
LOAD TEST:
1. Fix the armature voltage of the generator to the rated voltage by adjusting the
field rheostat of the generator.
2. Close the DPSTS at the load side of the generator and increase the load in steps
till the rated armature current and at each step the readings of terminal voltage,
load current, and shunt field current are noted.
3. Finally reduce the load insteps and bring the generator and field rheostat to its
original position.
10
EXPRESSION FOR THEORITICAL VALUE:
1.
Critical field resistance ,Rc = Slope of the tangent drawn to the linear portion of the
Rc = …………………. Ohms.
2.
Critical Speed Nc = Rsh * Nrated / R
3.
Voltage build up Egm =Voltage corresponding to the point at which the OCC at rated
11
CIRCUIT DIAGRAM
T
ABULATION
OPEN CIRCUIT TEST
12
LOAD TEST:
TO FIND Ra
Circuit Diagram
13
14
Tabulation
TO FIND Ra:
MODEL GRAPH
RESULT :
Thus the open circuit and load characteristics of self excited DC generator are determined.
15
Exp No.:
Date :
LOAD TEST ON DC SHUNT MOTOR
AIM
To conduct a direct load test on the given dc shunt motor to plot the following performance
characteristics.
3. Torque Vs Speed
FUSE RATING
APPARATUS REQUIERD
S.No. Apparatus Type Range Quantity
1 Voltmeter MC (0-300) V 1
2 Ammeter MC (0-20) A 1
Wire
3 Rheostat 300 / 1.7 A 1
Wound
4 Tachometer Digital -- 1
THEORY
Load test on motor are performed to know about the efficiency, torque and speed characteristics,
which enable us to select an appropriate motor for on application.
The torque equation of a DC Motor is given by
Ta = 0.159 (PZ / A) * Ia N-m
16
P, Z, A being constant the equation reduces to Ta = K Ia
In a DC Shunt motor as is also a constant, then the torque is directly properties armature current.
The speed of a DC motor is given by N = K (V-IaRa) /
Since is constant, the speed is directly proportional to (V Ia R a). As the load on motor
increases, the drop Ia Ra through increases is negligible as Ra is very small and the speed is nearly
constant. Hence a Dc shunt motor is considered as a constant speed motor. If a DC shunt motor is
started on load, it draws a heavy armature current, which in turn will damage the machine itself. Hence
DC shunt motors are always started on no-load.
CIRCUIT DIAGRAM
17
FORMULA
1. Torque T= (S1~S2) * ( R+t/2) * 9.81 N-m
Where R= Radius of the brake drum in m
t= Thickness of the belt in m
S1, S2 = spring balance reading in Kg
2. Input Power (Pin)= VL * IL in Watts
Where VL = Load Voltage in Volts
IL = Load current in amps
3. Output Power (Pout) =(2∏NT)/60 in watts
Where N = speed of the armature in rpm
T = Torque in N-m
4. Percentage of Efficiency (% ) = (Pout/Pin) * 100 %
PRECAUTION
1) Initially, the motor field rheostat is in minimum position.
2) The belt should not be in tight position.
PROCEDURE
1) Connections are given as per the circuit diagram.
2) Switch on DC supply and start the motor with the help of starter.
3) Adjust the field rheostat to rated speed.
4) Note the readings of the ammeter, voltmeter, spring balance reading and speed at the load
conditions.
5) Increase the load gradually by tightening the belt by using hand wheels.
6) Note the readings of ammeter, voltmeter, speed and spring balances.
7) Repeat the steps 5 and 6 at no load to full load of the motor.
8) Decrease the load gradually and set the field rheostat to minimum position.
9) Switch off the supply.
10) Calculate input power, output power, torque and efficiency and draw the performance curves.
18
OBSERVATION
Spring
Input Input Balance Input Output % of
Speed Torque
voltage current S1 power power
S.No. N T efficiency
VL IL (Kg S2 Pin Pout
(rpm) (Kg) (N-m) (W) % (%)
(V) (A) (W)
)
MODEL GRAPH
19
20
RESULT
Thus the load test on DC shunt motor was conducted and its performance characteristics were
drawn.
Exp.No:
Date : SWINBURNE’S TEST
AIM
To conduct no load test on dc shunt motor and to predetermine efficiency while machine
is running as a motor and generator.
APPARATUS REQUIRED
21
PRECAUTIONS:
22
PROCEDURE:
MOTOR:
23
Input Power, Pi = Po + PL (watts)
CIRCUIT DIAGRAM
24
TABULATION TO FIND OUT CONSTANT LOSS (Wco)
CIRCUIT DIAGRAM
TO FIND RA
25
TABULATION TO FIND OUT ARMATURE RESISTANCE
RUNNING AS MOTOR
Armature Resistance (Ra) = Rated current (Ir) =
Load
Armature Armature Total Input Output
current Efficiency
current loss loss power power
Fraction IL = 2 η = Wo/Wi
S. Ia =IL+If Wcu=Ia Ra Wt Wi=VIL Wo=Wi-Wt
of load x*Ir
No
(x) Amps Amps Amps Watts Watts Watts %
26
RUNNING AS GENERATOR
Load
Armature Armature Total Output Input
current Efficiency
current loss loss power power
Fraction IL = 2 η = Wo/Wi
S. Ia =IL+If Wcu=Ia Ra Wt Wo=VIL Wi=Wo+Wt
of load x*Ir
No
(x) Amps Amps Amps Watts Watts Watts %
27
RESULT:
28
Exp No.:
Date :
SPEED CONTROL OF D.C. SHUNT MOTOR
AIM
To determine the variation of speed with (i) Armature voltage control method
(Rheostatic control method) and (ii) Field excitation (Flux control method).
APPARATUS REQUIRED
THEORY
A dc motor is an electrical machine that takes electrical energy and converts it
into mechanical energy.
The speed of the dc motor is given by the relation
V- Ia Ra
N = ------------ rpm.
K
From the above relation, the speed of the dc shunt motor can be varied by varying,
1. The voltage V applied to armature.
2. The armature circuit resistance Ra and
3. The flux
The speed is nearly proportional to armature voltage if the armature drop is small,
while it is inversely proportional to the flux ().
CIRCUIT DIAGRAM
29
Name Plate Details
Power :
Voltage :
Current :
Speed :
PRECAUTIONS
1. While starting and stopping the machine the armature circuit rheostat is kept at
maximum resistance position and the field circuit rheostat is kept at minimum
resistance position.
2. DPST switch is kept open initially.
PROCEDURE
1. The no load current is approximately 15 % of full load current. So the fuse rating
should be 15% of full load current.
2. The type and range of all meters are selected according to the ratings of the motor.
3. The connections are made as per circuit diagram.
4. The armature rheostat is kept at maximum resistance position and the field rheostat is
kept at minimum resistance position initially.
30
5. The speed of the dc shunt motor is directly proportional to armature voltage and
inversely proportional to flux.
6. In the armature voltage control method the flux or field excitation is kept constant and
armature voltage is varied to obtain different speeds.
7. In the field control method the armature voltage is kept constant and flux is varied by
varying the field current to obtain different speeds
31
OBSERVATION
MODEL GRAPH
32
RESULT
Exp No.:
33
Date :
LOAD TEST ON SINGLE-PHASE TRANSFORMER
AIM
To conduct a direct load test on the given single phase transformer to determine
the efficiency and regulation at different load conditions of a resistive load.
FUSE RATING
APPARATUS REQUIRED
THEORY
Direct load test is conducted to determine the efficiency characteristics and regulation
characteristics of the given transformer. An ideal transformer; is supposed to give
constant secondary voltage irrespective of the load current. But practically the secondary
voltage decreases as the transformer is loaded due to primary and secondary impedance
drops. Since these drops are dependent on load current this variation in terminal voltage
is founded using direct loading,
CIRCUIT DIAGRAM
34
FORMULAE
2. Percentage of Regulation =
Where,
35
PRECAUTIONS
2. There should be no load at the time of starting.
3. Autotransformer should be kept at minimum potential.
PROCEDURE
1. The circuit connections are made as per the circuit diagram as shown in
figure.
2. Keeping the autotransformer in its minimum position the main supply is
switched ON.
3. By slowly and carefully operating the Auto transformer the rated voltage is
applied to the Primary side of the transformer.
4. At no load condition voltmeter, Ammeter & wattmeter readings corresponding
to primary and secondary transformer are noted.
5. Now the load is applied to transformer in steps for every increase of load, the
primary and secondary current, voltage and power are noted.
6. The transformer is loaded up to full load and readings are noted. Switch off
the power supply.
7. After the observation of all the readings the load is released gradually to its
initial position
8. The autotransformer is brought to its initial position
9. The supply is switched off
10. The efficiency and the regulation are calculated
36
OBSERVATION
MODEL GRAPH
RESULT
The direct load test has been conducted on the given 1-phase transformer and
the percentage efficiency and regulation are determined at different load condition and
hence the efficiency and regulation graphs are drawn.
37
Exp No.:
Date :
O.C. AND S.C. TESTS ON A SINGLE PHASE TRANSFORMER
AIM
To conduct the open circuit test and short circuit test on a single-phase
transformer and hence to predetermine the efficiency and regulation and also to draw the
equivalent circuit as referred to H.V side.
FUSE RATING
APPARATUS REQUIRED
THEORY
38
such a test is also more. The same performance characteristics can be obtained by
comparatively easier methods, which are known as indirect methods or predetermination
techniques.
To predetermine the efficiency and regulation of transformers, the open circuit
test [(to determine the core loss (iron loss or constant loss)] and short circuit test [to
determine the full load copper loss (variable loss)] are carried out. Assuming the output
and load power factor, the efficiency at different loads are computed. The regulating on
full load for different assumed load power factors can also be computed. The data
obtained from these tests are also useful to find the equivalent circuit parameters. The
results obtained from these tests are almost closer to the actual values obtained by direct
load test.
CIRCUIT DIAGRAM
39
SHORT CIRCUIT TEST
PRECAUTION
EQUIVALENT CIRCUIT
40
Where Voc -- open circuit voltage in volts
Ioc -- open circuit current in amps
13. Efficiency= in %
41
14.
+ for Lagging PF
- for Leading PF
PROCEDURE
I) O.C. TEST
42
TABULATION
OC Test
VOLTAGE CURRENT POWER Woc (W)
TEST
Voc (V) Ioc (A) Obs Act
O.C TEST
SC Test
VOLTAGE CURRENT POWER Wsc (W)
TEST
Vsc (V) Isc (A) Obs Act
S.C. TEST
PREDETERMINATION OF EFFICIENCY
Input power =
Output power =
O/P power + %Efficienc
X*kva*Cos*10
Total losses y
% Of 0 (Watts) Copper Total losses (Watts) =[(O/P)/(I/P
load loss = Woc+ )] * 100 (%)
S.No
=X2*Wsc Copper loss
X (Watts) (Watts)
Cos
Cos=0. Cos Cos= Cos= Cos
=0.
8 =1 0.8 1 =1
8
0.2
0.3
.
.
.
1.2
43
% REGULATION
POWER % Regulation
FACTOR
S.No. Sin φ
Lagging P.F Leading P.F
Cos φ
0.2
0.4
0.6
0.8
1.0
EQUIVALENT CIRCUIT
44
MODEL GRAPH
RESULT
Thus the O.C and S.C tests are conducted on the single phase transformer. The
efficiency, regulation graphs and also the equivalent circuit as referred to H.V side are
drawn.
45
CIRCUIT DIAGRAM TO PREDETERMINE THE REGULATION OF THREE PHASE
ALTERNATOR BY EMF METHOD
3 POINT STARTER
FUSE FUSE
L F A
+
20 A 5A
T
P
D S
P 220Ω T
S 1.5A S
(0-600 V)
T A1 V W
R MI
220 V F1 I
DC MECHANICAL COUPLING T
A (0- 5A)
S MI
SUPPLY C
W
H
I
T
M FUSE
B Y
C
H 5A
F2 F1
F2 A2
FUSE FUSE
-
20A 15 A
500Ω -
1.3A
+
2A
A
SPSTS (0- 2A) MC
46
Exp No:
Date:
AIM:
To predetermine the percentage voltage regulation of three phase alternator by EMF
method.
OBJECTIVE:
This method helps the students in determining the regulation of the alternator without
loading
The student can understand the effect of saturation on regulation
APPARATUS REQUIRED:
THEORY:
= √(
2 2
V cos φ + IR ) + ( V sin φ−IX )
s s
5. For leading power factor EO volts.
47
E0 −V
∗100
7. % Voltage regulation = V
MODEL CHARACTERISTICS
%Regulation
OCC
SCC
48
TABULAR COLUMN 1.2: SHORT CIRCUIT TEST
Where
Φ = load power factor angle.
EO= no load voltage per phase in volts.
V = terminal voltage per phase in volts.
I = full load armature current per phase in amps
PRECAUTIONS:
1. The rating of the fuse should not be more than 120% of rated current.
2. Motor field rheostat should be in minimum position while starting and stopping.
3. Alternator field rheostat should be in maximum position while starting and stopping.
4. Before closing the TPST switch, the alternator rheostat should be brought to maximum
position.
5. TPST switch should be opened during open circuit test.
PROCEDURE:
1. The alternator field rheostat is brought to its original position (i.e.) maximum position.
2. The alternator phases are shorted by closing the TPST switch.
3. Now, alternator field rheostat is varied to obtain the rated current of alternator.
4. The corresponding field current is noted in tabular column1.2
5. % Voltage regulation of three phase alternator can be predetermined using formulas for
different power factors and are tabulated in tabular column1.3
49
TABULAR COLUMN 1.3: PREDETERMINATION OF % VOLTAGE REGULATION OF THREE
PHASE ALTERNATOR
RATED VOLTAGE V = volts
LAGGING LEADING
POWER
S.NO EO in %
FACTOR EO in volts %REGULATION
volts REGULATION
POWER
S.NO EO in volts %REGULATION
FACTOR
Unity
MODEL CALCULATION:
50
RESULT:
51
CIRCUIT DIAGRAM TO PREDETERMINE THE REGULATION OF THREE PHASE
ALTERNATOR BY MMF METHOD
3 POINT STARTER
FUSE FUSE
L F A
+
20 A 5A
T
P
D S
P 220Ω T
S 1.5A S
(0-600 V)
T A1 V W
R MI
220 V F1 I
DC MECHANICAL COUPLING T
A (0- 5A)
S MI
SUPPLY C
W
H
I
T
M FUSE
B Y
C
H 5A
F2 F1
F2 A2
FUSE FUSE
-
20A 5A
500Ω -
1.3A
+
2A
A
SPSTS (0- 2A) MC
52
Exp No:
Date:
OBJECTIVE:
This method helps the students to determining the regulation of the alternator without
loading
The student can understand the effect of saturation on regulation
APPARATUS REQUIRED:
THEORY:
1.
I f = √ I 2
f 1 +I 2
f 2 +2 I f 1 I f 2 cos(180−θ )
(Amps)
From OCC, If1 – Field current required for rated voltage in amps.
From SC, If2 – Field current required for rated current in amps.
θ=90±φ
+ve = lagging; -ve = leading; θ= 90۫ for UPF
E0 −V
∗100
2. Percentage regulation = V
Where
V =Terminal voltage per phase.
E0= Open circuit voltage per phase corresponding to If.
PRECAUTIONS:
1. The rating of the fuse should not be more than 120% of rated current.
2. Motor field rheostat should be in minimum position while starting and stopping.
3. Alternator field rheostat should be in maximum position while starting and stopping.
53
4. Before closing the TPST switch, the alternator rheostat should be brought to maximum
position.
5. TPST switch should be opened during open circuit test.
MODEL CHARACTERISTICS
%Regulation
Short Circuit Current Isc(A)
If Vs Eg
Open circuit Voltage Eg(V)
54
TABULAR COLUMN 1.2: SHORT CIRCUIT TEST
SHORT CIRCUIT CURRENT (ISC)
S.NO FIELD CURRENT (If) amps
amps
PROCEDURE:
1. The alternator field rheostat is brought to its original position (i.e.) maximum
position.
2. The alternator phases are shorted by closing the TPST switch.
3. Now, alternator field rheostat is varied to obtain the rated current of alternator.
4. The corresponding field current is noted in tabular column1.2
5. % Voltage regulation of three phase alternator can be predetermined using formulas
for different power factors and are tabulated in tabular column1.3
55
TABULAR COLUMN 1.3: PREDETERMINATION OF % VOLTAGE REGULATION OF THREE
PHASE ALTERNATOR
Rated Voltage V = volts
LAGGING LEADING
POWER
S.NO EO in %
FACTOR EO in volts %REGULATION
volts REGULATION
POWER
S.NO EO in volts %REGULATION
FACTOR
Unity
MODEL CALCULATION:
56
RESULT:
57
CIRCUIT DIAGRAM FOR LOAD TEST ON 3 PHASE SQUIRREL CAGE INDUCTION MOTOR
W1
600 V/10A/UPF
FUSE C2 LOADING ARRANGEMENT
R A L1
15 A A1
(0- 10A)
T
MI
P
S S1 Kg S2 Kg
T
400 V S (0-600 V)
50 HZ 3ф AC SUPPLYW V A1 C2
MI
I
T
C
H
FUSE A2 A2 C1
L2
Y
15 A B1 BRAKE DRUM
B1 B2
B2
FUSE
L3
B C1
15 A
W2
600 V/10A/UPF
58
Exp No:
Date :
AIM:
To conduct the load test on three phase squirrel cage induction motor and to draw
the performance characteristics.
OBJECTIVE:
The student can understand the performance of the three phase induction motor in
such a way that how the speeds falls, the power factor improves and current increases
in output
APPARATUS REQUIRED:
1. Voltmeter (0-600V) MI 1
2. Ammeter (0-10A) MI 1
3. Wattmeter 600V/10A UPF 2
4. Tachometer - Digital 1
THEORY:
Where,
Ns - Synchronous speed in rpm
R - Radius of brake drum in meter
N - Rotor speed in rpm
59
S1, S2 - spring balance reading in Kg
60
PRECAUTIONS:
1. The rating of the fuse should not be more than 120% of rated current.
2. Ac electrical quantities should be measured by moving iron instruments.
3. There should be no load while starting the machine.
4. Water should be poured to the brake drum when load is applied to reduce the heat.
5. The starter should be in OFF position while making connection.
PROCEDURE
Po Vs ή
Po Vs p.f
Po Vs S
Po Vs N
Po Vs T
Line Current (IL) A
Po Vs IL
Power Factor (p.f)
Torque (T) Nm
% Slip (S)
Torque (T) Nm
(ή)
61
MODEL CALCULATION:
RESULT:
62
CIRCUIT DIAGRAM FOR NO LOAD TEST
W1
600 V/10A/LPF
FUSE
R A
15 A
T (0- 10A) I0
P MI
S
T
400 V S
Vo A1 C2
W
50 HZ 3ф AC SUPPLY V (0-600 V)
I
MI
T
C
H
FUSE A2
C1
Y
15 A
B1 B2
FUSE
B
15 A
W2
600 V/10A/LPF
63
Exp No:
Date:
AIM:
To pre determine the performance characteristics of the given three phase squirrel
cage induction motor from equivalent circuit by conducting no load and blocked rotor
tests.
OBJECTIVE:
This experiment enables the students how to find out the equivalent circuit
parameters and how the performance of the motor can be determined at different load
conditions
APPARATUS REQUIRED:
S.NO APPARATUS NAME RANGE TYPE QUANTITY
1 Ammeter (0-10)A MI 1
2 Voltmeter (0-600)V MI 1
600V/10A LPF 2
3 Wattmeter
150V/10A UPF 2
4 3Ф Auto transformer 400V/(0-470V) - 1
THEORY:
W0
cos φ=
1. √ 3V 0 I 0
2.
I μ =I 0 sin φ 0 in Ampere
I =I cos φ 0 in Ampere
3. w 0
√ 3∗V ph
R0 =
4.
Iw in Ω
√ 3∗V ph
X 0=
5.
Iμ in Ω
W sc
R01 =
6. 3 I 2sc in Ω
√ 3∗V sc
Z 01=
7. I sc in Ω
8.
X 01=√ (Z 201−R 201 )
9.
(
R =R s
L
1−s
2
) in Ω
64
10. R2 = R01 - R1 in Ω Where stator resistance R1 = 4.4 Ω (given)
65
CIRCUIT DIAGRAM FOR BLOCKED ROTOR TEST
W1
150 V/10A/UPF
FUSE
R A
15 A
(0- 10A) Isc
T
MI
P
S S1 Kg S2 Kg
T
400 V S Vsc
W
50 HZ 3ф AC SUPPLY V A1 C2
(0-150 V)
I MI
T
C
H
FUSE A2 C1
Y
15 A BRAKE DRUM
B1 B2
FUSE
B
15 A
W2
150 V/10A/UPF
3Φ Auto-Transformer
(400v/0-470v)
66
11. Z2 = R01 + RL + jX01 in Ω ;I2 = Vph / Z2 in Ampere
'
14. Input power = 3 V L I L cos φ in Watts
Where,
I2= Rotor current referred to stator winding
RL= load resistance of rotor winding referred to stator winding
N −N
% slip= s ∗100
Ns
3I R2
2r ' 2
'
9 .55×
s
T= Ns in Nm
V1
I2 r' = ( R01 + R L ) + jX 01
PRECAUTIONS:
1. The rating of the fuse should not be more than 120% of rated current.
2. Auto transformer should be in minimum position while starting and
ending of the experiments.
3. AC electrical quantities should be measured by moving iron instruments.
4. Ensure that rotor should not be blocked for no load test.
5. Rotor is to be blocked first and then apply rated current through auto
transformer for blocked rotor test
PROCEDURE:
NO LOAD TEST:
67
TABULAR COLUMN 1.1: NO LOAD TEST
MULTIPLYING FACTOR = W1= W2=
VOLTMETER AMMETER WATT READING IN Watrs
S.NO READING IN READING IN
(VOLTS) (V0) (AMPS) (I0) W1 W2 (W1~W2) (W0)
2. -0.08
3. 0.03
4. 0.09
5. 0.1
6. 1.2
7. 1.7
8. 2.0
68
BLOCKED ROTOR TEST:
W0
1. CosΦ = √ L0 L0
3V I
VL
×I SC
2. ISN = V SC
W SC
Φ
3. Cos SC = √3 V LSC I LSC
[ ]
2
I SN
W SC
I SC
4. WSN =
W SN
5. Power scale = l ( AD )
6. Total motor input = PT ¿ power scale
7. Stator copper loss = SR ¿ power scale
8. Rotor copper loss = QR¿ power scale
9. Fixed loss = ST ¿ power scale
10. Total loss = QT ¿ power scale
11. Rotor output = PQ ¿ power scale
12. Rotor input = (PQ+QR) ¿ power scale
QR
13. Slip (s) = PR
PT
14. CosΦ = OP
69
TABULAR COLUMN 1.4: PRE DETERMINATION OF PERFORMANCE CHARACTERISTICS
OF 3Ф SQUIRREL CAGE INDUCTION MOTOR.
OUTPUT INPUT
SPEED I2 IL POWER TORQUE EFFICIENCY
S.NO SLIP POWER POWER
(rpm) (A) (A) FACTOR (Nm) %
(WATTS) (WATTS)
1.
0.02
2.
0.04
3.
0.06
4.
0.08
5.
0.1
70
EQUIVALENT CIRCUIT
MODEL CHARACTERISTICS
Po Vs ή
Po Vs p.f
Po Vs S
Po Vs N
Po Vs T
Line Current (IL) A
Po Vs IL
Power Factor (p.f)
Torque (T) Nm
% Slip (S)
(ή)
TORQUE-SLIP CHARACTERISTICS
Torque (Nm)
Motoring
Breaking Region
Region
Slip (%) Generating
Region
71
MODEL CALCULATION:
RESULT:
72
Exp No:
Date:
AIM
To study about the d.c. motor and induction motor starters
At starting, Eb =0 because speed of motor is zero. Armature current of motor is equal to,
Ia = V- Eb / Ra
so Ia =V/ Ra (Eb = 0)
Since Ra is very small so motor will draw large armature current. To limit the armature current
in safe value we add some external resistance in armature circuit. A mechanism which adds
resistance during starting only is known as starter.
THEORY
There are two types of starters which are commonly used for d.c. shunt motor
1) 3-point starter
2) 4 - point starter
3- POINT STARTER
Three point starter is shown in the figure 1, when motor is started, starting arm is moved
slowly towards the ON position as soon as arm touches the stud no. 1 full starting resistance
get connected in the armature circuit.
3) When the arm travels towards ON position , the starting resistance is gradually removed
from armature circuit . since motor takes full speed, motor develops full back E.M.F. the
starting arm carries a soft iron piece which is held by attraction of the hold on coil. starter
remains in ON position because the electromagnetism formed by NO VOLT COIL
70
FUNCTION OF HOLD ON (NO VOLT COIL)
1) In case of supply failure NO VOLT COIL gets de-energized and the starting arm will be
released to OFF position. This is automatically done by spring action.
Overload coil is a electromagnet connected in series with armature. when current exceeds
beyond certain predetermined value the electromagnet will become strong and it attracts
plunger. Due to this voltage across NO VOLT COIL becomes zero. this will make hold on coil
de –energized due to which arm gets to OFF position and motor gets disconnected from
supply.
1)When motor is in ON position the starting resistance gets remove form armature circuit at the
same time it gets attached to field circuit, which is dangerous to the motor.
2)When we control speed of motor by field control method, resistance in field circuit reduces
field current which increases the speed of motor at the same time there is chance under ON
condition motor could disconnect from supply due to de energisation of HOLD ON COIL, due
to less field current.
4- POINT STARTER
4- point starter with brass arc covers limitations of 3- point starter; using brass arc covers first
limitation. Making field circuit path independent of hold coil circuit by making forth point in
addition with 3-point circuit covers second limitation.When field current is reduced while
controlling speed of motor will not effect on magnetic field of hold on coil because circuit of hold
coil is separate than field coil circuit as shown in the fig.2.
71
72
73
B)STUDY OF INDUCTION MOTOR STARTERS
An auto transformer starter consists of an auto transformer and a switch as shown in the fig.
When the switch S is put on START position, a reduced voltage is applied across the motor
terminals. When the motor picks up speed, say to 80 per cent of its normal speed, the switch is put
to RUN position. Then the auto-transformer is cut out of the circuit and full rated voltage gets
applied across the motor terminals.
The circuit diagram in the fig is for a manual auto-transformer starter. This can be made
push button operated automatic controlled starter so that the contacts switch over from start to run
position as the motor speed picks up to 80% of its speed. Over-load protection relay has not been
shown in the figure. The switch S is air-break type for small motors and oil break type for large
motors. Auto transformer may have more than one tapping to enable the user select any suitable
starting voltage depending upon the conditions.
Series resistors or reactors can be used to cause voltage drop in them and thereby allow low voltage
to be applied across the motor terminals at starting. These are cut out of the circuit as the motor
picks up speed.
The startor phase windings are first connected in star and full voltage is connected across its
free terminals. As the motor picks up speed, the windings are disconnected through a switch and
they are reconnected in delta across the supply terminals. The current drawn by the motor from the
lines is reduced to as compared to the current it would have drawn if connected in delta.The motor
windings, first in star and then in delta the line current drawn by the motor at starting is reduced to
one third as compared to starting current with the windings delta-connected.
In making connections for star-delta starting, care should be taken such that sequence of
supply connections to the winding terminals does not change while changing from star connection
to delta connection. Otherwise the motor will start rotating in the opposite direction, when
connections are changed from star to delta. Star-delta starters are available for manual operation
using push button control. An automatic star – delta starter used time delay relays(T.D.R) through
which star to delta connections take place automatically with some pre-fixed time delay. The delay
time of the T.D.R is fixed keeping in view the starting time of the motor.
74
FULL VOLTAGE OR DIRECT –ON-LINE STARTING
When full voltage is connected across the stator terminals of an induction motor, large
current is drawn by the windings. This is because, at starting the induction motor behaves as a short
circuited transformer with its secondary, i.e. the rotor separated from the primary, i.e. the stator by
a small air-gap.
At starting when the rotor is at standstill, emf is induced in the rotor circuit exactly similar
to the emf induced in the secondary winding of a transformer. This induced emf of the rotor will
circulate a very large current through its windings. The primary will draw very large current from
the supply mains to balance the rotor ampere-turns. To limit the stator and rotor currents at starting
to a safe value, it may be necessary to reduce the stator supply voltage to a low value. If induction
motors are started direct-on-line such a heavy starting current of short duration may not cause harm
to the motor since the construction of induction motors are rugged. Other motors and equipment
connected to the supply lines will receive reduced voltage. In industrial installations, however, if a
number of large motors are started by this method, the voltage drop will be very high and may be
really objectionable for the other types of loads connected to the system. The amount of voltage
drop will not only be dependent on the size of the motor but also on factors like the capacity of the
power supply system, the size and length of the line leading to the motors etc. Indian Electricity
Rule restricts direct on line starting of 3 phase induction motors above 5 hp.
75
76
RESULT:
Thus the construction and working of different starters for starting D.C and three phase
induction motors are studied.
77
Exp.No:
Date:
DIGITAL SIMULATION OF LINEAR SYSTEM
AIM
To digitally simulate time response characteristics of second order system and higher order
MIMO linear systems using state variable formulation.
t r=π−tan−1 √1−ζ ¿ ¿ ¿
ωn √ 1−ζ ¿ in secs
3. Peak Time:
It is the time taken for the response to reach the peak value for the very first time.or It is the
time taken for the response to reach the peak overshoot, Mp.
t p= π
ωn 1− ζ√ 2
in sec
4. Peak Overshoot (Mp)
It is defined as the ratio of the maximum value measured from final value to final value.
Let final value =c(∞) , Maximum value =c(tp)
%Peak overshoot,
78
5. Settling Time (t s)
It is defined as the time taken by the response to reach and stay within a specified error. It is
usually expressed as % of final value. The usual tolerable error is 2% or 5% of the final value.
ln(%error )
t s=
ζω n
79
PROCEDURE
Time
Constant Theoretical Practical
s
tr
tp
%Mp
ts
RESULT
The time response of the second order system and higher order MIMO system are obtained
using the MATLAB. For the second order system the theoretical values and practical values are
compared.
80
Exp.No:
Date:
STABILITY ANALYSIS OF LINEAR SYSTEMS
AIM
To analyze the stability of the linear systems using Bode / Root locus / Nyquist plot, using
MATLAB Software tool.
THEROY
BODE PLOT
The bode plot is the frequency response plot of the transfer function of a system. A Bode
plot consists of two graphs. One is a plot of the magnitude of a sinusoidal transfer function versus
log ω. the other is a plot of the phase angle of sinusoidal transfer function versus log w.
The bode plot can be drawn for both open loop and closed loop transfer function. Usually
the bode plot is drawn for open loop system. The standard representation of the logarithmic
magnitude of open loop transfer function of G(jω) is 20 log|G( jω)|where the base of the
logarithm is 10. The unit used in this representation of the magnitude is the decibel, usually
abbreviated db. The curve are drawn on semi log paper, using the log scale (abscissa) for frequency
and the linear scale (ordinate) for either magnitude (in decibels) or phase angle (in degrees).
The main advantage of the bode plot is that multiplication of magnitudes can be converted
into addition. Also a simple method for sketching an approximate log-magnitude curve is available.
Determination Of Phase And Gain Margin From Bode Plot
The gain margin in db is given by the negative of db magnitude of G(jω) at the phase cross-
over frequency, ωpc. The ωpc is the frequency at which phase of G(jω) is -180 0. if the db magnitude
of G(jω) at ωpc is negative then gain margin is positive and vice versa.
81
% Nyquist plot
s = tf('s');
G=75*(1+0.2*s)/(s*(s^2+16*s+100));
nyquist(G);
axis equal;
82
Let Φgc be the phase angle of G(jω) at gain cross over frequency w gc. The ωgc is the
frequency at which the db magniyude of G(jω) is zero. Now the phase margin, γ is given by, γ
=1800+ Φgc . if Φgc is less than -1800 then phase margin is positive and vice versa.
NYQUIST STABILITY CRITERION
If the G(S) H(S) contour in the G(S) H(S) plane corresponding to Nyquist contour in the s-
plane encircles the point (-1+j0) in the anticlockwise direction as many times as the number of half
s-plan poles of G(S) H(S), then the closed loop system is stable.
In examining the stability of linear control systems using the Nyquist stability criterion, the
following three situations.
1. There is no encirclement of -1+j0 point. This implies that the system is stable if there are no
poles of G(S) H(S) in the right half s-plan. If there are poles on right half s-plane then the
system is unstable.
2. An anticlockwise encirclement or (or encirclements) of -1+j0 point. In this case the system
is stable if the number of anticlockwise encirclement is same as the number of poles of
G(S)H(S) in the right half s-plane. If the number of encirclement is not equal to number of
poles on right half s-plane then the system is unstable.
3. There is a clockwise encirclement (or encirclements) of the -1+j0 point. In this case the
system is always unstable.
ROOT LOCUS
The root locus technique is powerful tool for adjusting the location of closed loop poles to
achive the desired system performance by varing one or more system parameters.
Consider the open loop transfer function of system,
k
G ( S )=
S ( S + P 1 )( S + P 2 )
The closed loop transfer function of the system with unity feedback is given by,
C( S ) K
=
R( S ) S ( S + P 1 )( S + P 2 )+ K
The characteristic equation is given by,
83
% Root locus;
% G is the transfer function
s=tf('s');
G=75*(1+0.2*s)/(s*(s^2+16*s+100));
rlocus(G);
axis equal;
S( S+ P 1 )( S+ P 2 )+ K =0
The roots of characteristic equation is a function of open loop gain K. when the gain K is
varied from 0 to ∞, the roots of characteristic equation will take different values.
The path taken by the roots of characteristic equation when open loop gain K is varied from
0 to ∞ are called root loci.
84
Rules for Construction of Root Locus:
1. The root locus is symmetrical about the real axis.
2. Each branch of the root locus originates from an open loop pole corresponding to K=0
and terminates at either on a finite open loop zero(or open loop zero at infinity)
corresponding to K= ∞. The number of branches of the root locus terminating on
infinity is equal to (n-m),i,e.,the number of open loop poles minus the number of finite
zeros.
3. Segments of the real axis having an odd number of axis open loop poles plus zeros to
their right are parts of the root locus.
4. The (n-m) root locus branches that tend to infinity , do so along straight line asymptotes
making angles with the real axis given by,
0
φ A= ±180 [ 2 q+1 ] ; q=0 , 1, 2 .. .. .( n−m ) .
n−m
5. The point of intersection of the asymptotes with the real axis is at S=σ A where
Where Φ is the net angle contribution at the pole by all other open loop poles and zeros.
Similarly the angle of arrival at a complex open loop zero is given by,
85
PROCEDURE
1. Write programs for the given transfer function.
2. Simulate it using MATLAB software.
3. Observe the waveforms.
4. Calculate the theoretical values for the time domain specifications and compare with the
observed waveforms.
RESULT
The response of the given transfer function using Bode plot, Nyquist Plot & Root locus are
obtained using the MATLAB. The theoretical values and practical values are compared.
86
Ex. No:
Date:
Aim: To Study the effect of P, PI, PID controllers using Mat lab.
In so far were described proportional, integrative and derivative modes of the controllers
and a rational behind their use was explained. However, excerpt for a few tips, an attention was
not given to a question when to use different types of controllers. The rest of this section will
give some answers on that particular topic.
On-off Controller
On-off controller is the simplest controller and it has some important advantages. It is
economical, simple to design and it does not require any parameter tuning. If oscillations will
hamper the operation of the system and if controller parameter tuning is to be avoided, on-off
controller is a good solution. In addition, if actuators work in only two modes (on and off), then
it is almost always only controller that can be used with such actuators. That is a reason why on-
off controllers are often used in home appliances (refrigerators, washers etc.) and in process
industry when control quality requirements are not high (temperature control in buildings etc.).
Additional advantage of on-off controllers is that they in general do not require any maintenance.
P Controller
When P controller is used, large gain is needed to improve steady state error. Stable
system do not have a problems when large gain is used. Such systems are systems with one
energy storage (1st order capacitive systems). If constant steady state error can be accepted with
such processes, than P controller can be used. Small steady state errors can be accepted if sensor
will give measured value with error or if importance of measured value is not too great anyway.
Example of such system is liquid level control in tanks when exact approximate level of liquid
suffice for the proper plant operation. Also, in cascade control sometime it is not important if
there is an error inside inner loop, so P controller can a good solution in such cases.
Derivative mode is not required if the process itself is fast or if the control system as
whole does not have to be fast in response. Processes of 1st order react immediately on the
reference signal change, so it is not necessary to predict error (introduce D mode) or compensate
for the steady state error (introduce I mode) if it is possible to achieve satisfactory steady state
error using only P controller.
PD controller
It is well known that thermal processes with good thermal insulation act almost as
integrators. Since insulation is good and thermal losses are small, the most significant art of the
energy that is led to the system is used temperature rise. Those processes allow 18 for large gains
so that integral mode in the controller is not needed. These processes can be described as
different connections of thermal energy storages. Thermal energy is shifted from one storage into
another. In general, with such processes there is present a process dynamics with large inertia.
Since dynamics is slow, derivative mode is required for control of such processes. Integral mode
would only already slow dynamics make more slowly.
87
The other reason for using PPD controllers in such systems are that is possible to
measure temperature with low level of noise in the measured signal. PD controller is often used
in control of moving objects such are flying and underwater vehicles, ships, rockets etc. One of
the reason is in stabilizing effect of PD controller on sudden changes in heading variable y(t).
Often a "rate gyro" for velocity measurement is used as sensor of heading change of moving
object.
PI controller
PI controllers are the most often type used today in industry. A control without D mode is
used when:
a) fast response of the system is not required
b) large disturbances and noise are present during operation of the process
c) there is only one energy storage in process (capacitive or inductive)
d) there are large transport delays in the system
If there are large transport delays present in the controlled process, error prediction is
required. However, D mode cannot be used for prediction because every information is delayed
till the moment when a change in controlled variable is recorded. In such cases it is better to
predict the output signal using mathematical model of the process in broader sense (process +
actuator). The controller structures that can be used are, for example, Otto-Smith predictor
(controller), PIP controller or so called Internal Model Controller (IMC).
An interesting feature of IMC is that when the model of the process is precise
(A = AM and B = BM), then a feedback signal eM = y – yM is equal to disturbance:
It follows that a control signal is not influenced by the reference signal and control
systems behaves as open loop. A usual problems with stability that arise when closed loop
systems are used are then avoided. Control system with IMC controller will be stable and if IMC
and process are stable. With the exact model of process IMC is actually a feed forward controller
and can designed as such, but, unlike feed forward controllers, it can compensate for unmeasured
disturbances because feedback signal is equal to disturbance, which allows suitable tuning of the
reference value of the controller.
If model of the process is not exact5 (AM = B), then feedback signal eM will
contain not only disturbance d but a modeling error, also. Thus, a feedback will
have its usual role, and stability problem can arise. This requires for parameters6 to be tuned
again so the stability is not lost.
88
PID controller
Derivative mode improves stability of the system and enables increase in gain K and decrease in
integral time constant Ti, which increases speed of the controller response. PID controller is used when
dealing with higher order capacitive processes (processes with more than one energy storage) when
their dynamic is not similar to the dynamics of an integrator (like in many thermal processes). PID
controller is often used in industry, but also in the control of mobile objects (course and trajectory
following included) when stability and precise reference following are required. Conventional autopilot
are for the most part PID type controllers.
It can be seen that P, I and D channels react on the error signal and that they are
unbundled. This is basic structure of PID controller most often found in textbooks. There are
other non-interactive structures.
90
RESULT:
Thus the effect of P, PI, PID controllers using Mat lab are studied.
91
Exp.No: DESIGN AND IMPLEMENTATION OF COMPENSATORS
Date :
AIM
To design a lag compensator in Bode plot (frequency domain) for the system whose transfer function
G(s) = K
s(s+4)(s+80)
FACILITIES REQUIRED
Matlab software
PROGRAM:
sys=tf(num,den)
body(s)
[Gm,Pm,Wcp,Wcg]=mar
hold
92
sys=tf(num,den)
body(s)
[Gm,Pm,Wcp,Wcg]=ma
rgin(sys) margin(sys)
MANUAL CALCULATIONS
To calculate gain Kv
Let s= jω
G(jω) = 9600 = 30
Magnitude plot
Choose a low frequency ωl such that ωl< ωc1 and choose a high frequency ωh>
ωc3.
Let ωl=1 rad/sec and ωh=100 rad/sec
jω
1 4 -20 -20-20= - 40
(1+0.25jω)
1 80 -20 -40-20 = -60
( 1+0.0125 jω)
93
Calculate A at ωl, ωc1, ωc2, and ωh
Let A= | G(jω)| in db
At ω= ωl A= 20 log(30/1)=29.5db
ω= ωc1 , A=20log(30/4)=18db
ω= ωh A = -60log(100/80)+(-34) = - 40 db
These values are plotted in the semilog graph sheet taking frequency along the logarithmic scale and
magnitude in db along the linear scale
ω 1 4 10 50 80 100
Rad/sec
degrees
These values are plotted in the semi log graph sheet taking the same frequency as before along the
logarithmic scale and phase angle in degrees along the linear scale.
94
ii) Determination of phase margin of compensated system
The system requires a phse marginof atleast 33 degrees but the available phase margin is 12 degrees and
so lag compensation should be employed to improve the phase margin.
iii) Choose a suitable value for the phase margin of compensated system.
γo = γd + € = 33 + 5 =38 degrees
Let ωgc = New gain cross over frequency and Φgc = phase of G(jω) at ωgc
From the bode plot the frequency corresponding to a phase of -142deg is 4.7
Agcn
β = 10
β=6.3
95
vi) Determine the transfer function of lag compensator.
1/ βT pc = (6.3*2.13) = 1/13.419
= 6.3(1+2.13s)/(1+13.419s)
vii) Determine the open loop transfer function of the compensated system
(1+13.419s)
The gain of the compensator is nullified by introducing an attenuator in series with the compensator, as
shown in the diagram.
Open loop transfer function of compensated system
Gc(s) = 1 * 6.3(1+2.13s) * 30
6.3 (1+13.419s) s(1+0.25s)(1+0.0125s)
= 30(1+2.13s)
96
s(1+13.419s)(1+0.25s)(1+0.0125s)
97
viii) Determine the actual phase margin of compensated system.
Gc(s) = 30(1+2.13jω)
Actual phase margin of compensated system γo = 180 + Φgcn = 180 – 147 =33 degree
sd)OUTPUT:
Transfer function:
9600
--------------------
s^3 + 84 s^2 + 320 s
Gm = 2.8000
Pm = 13.2591
Wcp = 17.8885
Wcg = 10.5470
63.9 s + 30
------------------------------------
0.042 s^4 + 3.52 s^3 + 13.68 s^2 + s
Gm =15.7613
Pm = 39.3844
Wcp = 16.9235
97
Wcg = 3.5782
e)PLOT
98
RESULT:
AIM
a)APPARATUS REQUIRED
APPARATUS
S.NO TYPE RANGE QUANTITY
(0-10A)&
1 Ammeter MC
(0-2)A Each 1
2 Ammeter MI (0-300MA 1
3 Voltmeter MC (0-300V 1
4 Voltmeter MI (0-300v) 1
100
b)CIRCUIT DIAGRAM
101
c)EXPRESSION FOR THEROTICAL VALUE:
Field resistance(Rt) = V f / It
Where XF=(IF2-R 2)
XF=2fL
TRANSFER FUNCTION
Eg(S)/Ef(S)=[(Kg /Rf)/(1+(Lf/Rf)S]
Vt(S)/Ef(S)=[(Eg/Rf)/{ 1+(Lf/Rf)S{1+(Reff/RL)}
d)PRECAUTION
102
e)PROCEDURE
f)TABULATION
S.No
Field Field Generator Field Load Load
Voltage current voltage resistance current voltage
1.
2.
3.
4.
5.
6.
7.
103
To Find The Field Impendence
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
g)MODEL GRAPH
Gr voltage
Eg
Iy
Field current
104
Lsoad test Characteristics
Load voltage
VL
I
Load current
RESULT:
105
Exp No:
Date
TRANSFER FUNCTION OF ARMATURE AND FIELD
CONTROLLED DC MOTOR
AIM
a)APPARATUS REQUIRED
APPARATUS
S.NO TYPE RANGE QUANTITY
(0-15A)&
1 Ammeter MC
(0-2)A Each 1
2 Ammeter MC (0-10)A 1
3 Ammeter MI (0-10)A 1
4 Voltmeter MC (0-300V 1
5 Voltmeter MI (0-300v) 1
300,1.7
6 Rheostat Wire winding
A& Each 1
9 Techometer - - 1
1. Inertia Constant
I=[(Vav*Iav)/(Nav*ΔN)]*[(60/2π)2)*[(t1*t2)/t1-t2]Kg-m2
106
Where
Vav
=(V1+V2)/2 Iav
=(I1+I2)/2 Nav
=(N1+N2)/2
T1=Time for fall of speed from 1500 to 750 rpm in no load condition in
second T2= Time for fall of speed from 1500 to 500 rpm in load
condition in second
2.
Viscus Friction Coefficient (F)= (2/60)2*(J/2)*(N12~N22)
Where
J = Inertia Constant in kg-m2
=Angular displacement in rad/sec
=(2 Nav/60)
Eb dθ/dt
Eb Kbdθ/dt
107
Taking Laplace transfer function of equation Eb(S)=Kb
Sθ (S) LaSIa(S)+RaIa(S)=E(S)=Eb(S)
(LaS+Ra)Ia(S)=E(S)-Eb Sθ (S)
Then
KT`=ΔT/ΔIa
Theory
amps
E = Applied voltage
108
J=Equivalent moment of inertia of motor and load referred to motor shaft
I0=Equivalent Viscous friction Co-Efficient of motor and load referred to
Air gap flux φ is proportional to the field current because the DC motor
Should operate in linear magnetization curve application
θ If Kf If
(Is2+fs) θ(S)=Im(S)=KTIa(S)
c)PRECAUTION
The field rheostat should be minimum resistance position
The motor armature rheostat should be maximum resistance position
d)PROCEDURE
Connection are made as per circuit diagram
The DC supply is giving by closing of DPST switch
The motor is made to run at the rate speed by adjusting the field rheostat
The DPDT switch is brought to the original position the time taken for falling of
speed from 1500 rate
Once again the DPDT switch is brought to the position 1,2 then the motor is made
to run at rate speed
Then the DPDT switch is changed into position 1,2
Then I and F is calculated by using the formula
109
Connection are made as per circuit diagram
The DC supply is giving by closing of DPST switch
The field current is kept constant
The motor made to run at rate speed
The various value of the spring balance reading noted
Torque is calculated and plotted from the graph by adjusting the slop ,torque
constant KT Determine
110
e)CIRCUIT DIAGRAM
f)TABULATION
111
S.No Field Armature Spring Balance Reading Torque
Current current
S1 S2 S1-S2
g)MODELT GRAPH
in NM
ΔT
ΔIa
Armature
current
112
Circuit Diagram
TABULATION
RESULT:
Thus the transfer functions of armature and field controller DC motor are determined.
113
114