Ic 695 Alg 600
Ic 695 Alg 600
Ic 695 Alg 600
http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/IC695ALG600
Rx3i PacSystem
919-535-3180
sales@pdfsupply.com
13
Module Features
I4
▪
Completely software-configurable, no module jumpers to set
▪
Six hardware analog-to-digital filter frequencies, individually-selectable
by channel
I5 ▪ Rapid channel acquisition times based on filter frequency
▪ Full autocalibration
I6
▪ On-board error-checking
▪ Open-circuit detection for most input types
▪ Short-circuit detection for RTDs.
I6
▪ User-defined scaling
▪ High alarm, low alarm, high-high alarm, low-low alarm detection and
I8 reporting
▪ Module fault reporting
▪ Supports diagnostic point fault contacts in the logic program.
▪ Flash memory for future upgrades
▪ Module Status, Field Status, and TB LEDs
▪ CJC compensation on terminal block
▪ Temperature in Celsius or Fahrenheit
▪ Positive and negative Rate of Change Alarms
▪ Configurable software filters for each input channel
▪ Configurable interrupts for channel alarms and faults
▪ Terminal Block insertion or removal detection
This module must be located in an RX3i Universal Backplane. It cannot be located in an
expansion or remote backplane.
CIMPLICITY® Machine Edition 5.0 SP1A LD-PLC Hotfix 1 or later must be used to configure
and program a PACSystems RX3i system that includes this module. The CPU must be RX3i
model IC695CPU310 Firmware Revision 2.80 (Build ID 43A1) or later.
Specifications: ALG600
Backplane Power Requirements 400 mA maximum @ 5V
350 mA maximum @ 3.3V
CPU Memory Usage 40 bytes (20 words) of input references for channel input data.
40 bytes for enhanced diagnostics
4 bytes for module status reporting.
Power Dissipation within Module 5.4 watts maximum
LEDs One green LED to indicate the module status
One bi-color green/yellow LED to indicate the field status
One bi-color red/green LED to indicate the terminal block status
Channel Acquisition Time 10 msec @ 1000 Hz, 13 msec @ 200 Hz, 27 msec @ 40 Hz, 67 msec
@ 16 Hz, 87 msec @ 12 Hz, 127 msec @ 8 Hz
Channel Update Time The sum of the channel acquisition times for a bank of 4 channels plus
one of the following if applicable:
1. RTD Lead resistance measurement time (equals channel
acquisition time)
2. CJC acquisition time 7 msec.
Input resolution 11 to 16 bits, depending on configured range and A/D filter frequency.
See page 12-17 for details.
Inputs in Ohms Resistance 0-250, 0-500, 0-1000, 0-2000, 0-3000, 0-4000
Platinum 385 100, 200, 500,1000
Platinum 3916 100, 200, 500,1000
Nickel 672 120
Nickel 618 100,200, 500,1000
Nickel-Iron 518 604
Copper 426 10
RTD Inputs Copper 426 -100 to 260 degrees C
Nickel 618 -100 to 260 degrees C
Nickel 672 -80 to 260 degrees C
Nickel-Iron 518 -100 to 200 degrees C
Platinum 385 -200 to 850 degrees C
Platinum 3916 -200 to 630 degrees C
Thermocouple Inputs Type B 300 to 1820 degrees C
Type C 0 to 2315 degrees C
Type E -270 to 1000 degrees C
Type J -210 to 1200 degrees C
Type K -270 to 1372 degrees C
Type N -210 to 1300 degrees C
Type R 0 to 1768 degrees C
Type S 0 to 1768 degrees C
Type T -270 to 400 degrees C
Specifications, continued
Voltage / Current Inputs -10V to +10V, 0V to +10V, 0 V to +5V, 1V to +5V, -50mV to +50mV,
-150mV to +150mV, -20mA to +20mA, 4 to 20 mA, 0 to 20 mA
Configurable Input Filter 8Hz, 12Hz, 16Hz, 40Hz, 200Hz, 1000Hz
Scaling Floating point user scaling.
Max RTD Cable Impedance 25 ohms
RTD Wire Length 1000 ft max w/settling time of 1mSec
Input Impedance >1M ohm for Tc/V/RTD
Current Input Resistance 249 ohms +/- 1%
Open circuit detection time 5 seconds max. Open circuit detection is available for all configurations
except +/-20mA current, 0-20mA current, and +/-10V voltage.
Max Overvoltage +/-14.5VDC continuous
Max Overcurrent 28mA continuous
Normal Mode Noise Rejection 95 dB minimum @ 50/60 Hz with 8 Hz filter
85 dB minimum @ 50/60 Hz with 12 Hz filter
Common Mode Noise Rejection 120dB minimum @ 50/60 Hz with 8 Hz filter
110dB minimum @ 50/60 Hz with 12 Hz filter
Settling time to 5% of Full Scale <80mS
(notch filter dependent)
Calibrated Accuracy at 25°C Better than 0.1% of range (except 10 ohm CU RTD)
Accuracy depends on A/D filter, data format, input noise, and ambient
temperature.
Calibration interval 12 months typical to meet accuracy specifications over time. Module
will allow for user offset to be applied as a periodic calibration
adjustment.
Input Offset Drift with 3.0 milliohm/°C maximum
Temperature 2.0 uV/°C maximum
Gain Drift with Temperature 50 ppm/°C typical (90 ppm/°C maximum)
Module error over Full Temp 0.5% of range typical (depends on range)
range 1.0% of range maximum
Module Scan Time (Assumes 2 ADC’s running in parallel, no CJC or lead resistance)
(notch filter dependent) 10ms per Channel * 4 Channels = 40ms (1KHz filter)
127ms per Channel * 4 Channels = 508ms (8Hz filter)
Channels that are disabled are not scanned, shortening scan time.
Module conversion method Sigma-delta
Isolation Voltage Opto-isolated, transformer isolated
channel to channel +-12.5Vdc channel to channel Tc/V/I/RTD
group to group 250 VAC continuous/1500 VAC for 60 seconds
terminal block to 250 VAC continuous/1500 VAC for 60 seconds
backplane/chassis
Accuracy Specifications
Maximum Error at: +25°C 0°C to +60°C
Configured Input Filter 8, 12, 16Hz 200Hz 1000Hz 8, 12, 16Hz 200Hz 1000Hz
Voltage Inputs* +/- 10.5 V, 0.0 to +10.5 V +/- 5 mV +/- 5.5 mV +/- 7 mV +/- 10 mV +/- 11 mV +/- 14 mV
0 to +5.25 V, +1.0 to +5.25 V +/- 3 mV +/- 3.3 mV +/- 4.2 mV +/- 5 mV +/- 5. mV +/- 7 mV
+/- 155 mV +/- 30 uV +/- 33 uV +/- 42 uV +/- 110 uV +/- 121 uV +/- 154 uV
+/- 55 mV +/- 15 uV +/- 17 uV +/- 21 uV +/- 70 uV +/- 77 uV +/- 98 uV
Current Inputs* +/- 22.5 mA, 0.0 to +22.5 mA, +/- 20 uA +/- 22 uA +/- 28 uA +/- 40 uA +/- 44 uA +/- 56 uA
+3.0 to +22.5 mA
Thermocouple Type J (-180°C to +1200°C) +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 2.3°C +/- 2.6°C +/- 3.3°C
Inputs* Type J (-210°C to -180°C) +/- 0.8°C +/- 0.9°C +/- 1.2°C +/- 3.3°C +/- 3.7°C +/- 4.7°C
Type N (-160°C to +1300°C) +/- 1.0°C +/- 1.1°C +/- 1.4°C +/- 4.5°C +/- 5.0°C +/- 6.3°C
Type N (-210°C to -160°C) +/- 1.8°C +/- 2.0°C +/- 2.6°C +/- 8.0°C +/- 8.8°C +/- 11.2°C
Type T (-190°C to +400°C) +/- 0.9°C +/- 1.0°C +/- 1.3°C +/- 4.0°C +/- 4.4°C +/- 5.6°C
Type T (-270°C to -190°C) +/- 6.7°C +/- 7.4°C +/- 9.4°C +/- 18.0°C +/- 19.8°C +/- 25.2°C
Type K (-200°C to +1372°C) +/- 1.0°C +/- 1.1°C +/- 1.4°C +/- 4.0°C +/- 4.4°C +/- 5.6°C
Type K (-270°C to -200°C) +/- 9.5°C +/- 10.5°C +/- 13.3°C +/- 21.0°C +/- 23.1°C +/- 29.4°C
Type E (-200°C to +1000°C) +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 2.5°C +/- 2.8°C +/- 3.5°C
Type E (-270°C to -200°C) +/- 5.3°C +/- 5.8°C +/- 7.5°C +/- 14.0°C +/- 15.4°C +/- 19.6°C
Type S and R +/- 2.8°C +/- 3.1°C +/- 4.0°C +/- 11.5°C +/- 12.7°C +/- 16.1°C
Type C +/- 1.7°C +/- 1.9°C +/- 2.4°C +/- 7.0°C +/- 7.7°C +/- 9.8°C
Type B +/- 3.3°C +/- 3.7°C +/- 4.5°C +/- 20.0°C +/- 22.0°C +/- 28.0°C
RTD Inputs* 100 Ω Platinum 385 +/- 0.7°C +/- 0.8°C +/- 1.0°C +/- 1.2°C +/- 1.4°C +/- 1.7°C
200 Ω Platinum 385 +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 1.0°C +/- 1.1°C +/- 1.4°C
500 Ω Platinum 385 +/- 0.5°C +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 1.0°C +/- 1.3°C
1000 Ω Platinum 385 +/- 0.5°C +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 1.0°C +/- 1.3°C
100 Ω Platinum 3916 +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 1.1°C +/- 1.2°C +/- 1.6°C
200 Ω Platinum 3916 +/- 0.5°C +/- 0.6°C +/- 0.7°C +/- 0.9°C +/- 1.0°C +/- 1.3°C
500 Ω Platinum 3916 +/- 0.4°C +/- 0.5°C +/- 0.6°C +/- 0.8°C +/- 0.9°C +/- 1.2°C
1000 Ω Platinum 3916 +/- 0.4°C +/- 0.5°C +/- 0.6°C +/- 0.8°C +/- 0.9°C +/- 1.2°C
Nickel 672 +/- 0.3°C +/- 0.4°C +/- 0.5°C +/- 0.5°C +/- 0.6°C +/- 0.7°C
Nickel 618 +/- 0.3°C +/- 0.6°C +/- 0.5°C +/- 0.5°C +/- 0.6°C +/- 0.7°C
Nickel-Iron 518 +/- 0.4°C +/- 0.5°C +/- 0.6°C +/- 0.7°C +/- 0.8°C +/- 1.0°C
Copper 426 +/- 1.0°C +/- 1.1°C +/- 1.4C +/- 2.4 °C +/- 2.7 °C +/- 3.4 °C
Resistance 250 ohms +/- 0.25 Ω +/- 0.28 Ω +/- 0.35 Ω +/- 0.35 Ω +/- 0.39 Ω +/- 0.49 Ω
Inputs* 500 ohms +/- 0.3 Ω +/- 0.33 Ω +/- 0.42 Ω +/- 0.45 Ω +/- 0.5 Ω +/- 0.63 Ω
1000 ohms +/- 0.5 Ω +/- 0.55 Ω +/- 0.7 Ω +/- 0.8 Ω +/- 0.88 Ω +/- 1.2 Ω
2000 ohms +/- 0.9 Ω +/- 1.0 Ω +/- 1.26 Ω +/- 1.5 Ω +/- 1.65 Ω +/- 2.1 Ω
3000 ohms +/- 1.3 Ω +/- 1.43 Ω +/- 1.82 Ω +/- 2.2 Ω +/- 2.42 Ω +/- 3.08 Ω
4000 ohms +/- 1.7 Ω +/- 1.87 Ω +/- 2.38Ω +/- 2.9 Ω +/- 3.19 Ω +/- 4.06 Ω
Cold Junction +/- 1.5°C maximum
Temperature
CJC Sensor +/- 0.3°C maximum 0°C to +80°C
* Accuracy is dependent on the ADC output rate selection, data format, and input noise. In
severe RF environments, accuracy may be degraded by up to +/-2% of full scale.
Sense -
Negative sense not connected on 4-Wire RTD
▪ For current inputs, tie the Return to the associated IN- pin.
▪ For 2 wire RTDs, tie EXC+ and IN+ together at the terminal block.
▪ For 4 wire RTDs, leave one of the negative sense leads unconnected.
▪ For 3 wire RTDs, IN+ = Sense+, IN- = RTD Return, and EXC+ = Excitation current.
Module Parameters
Parameter Default Description
Channel Value Reference %AIxxxxx Starting address for the module’s input data.
Address This defaults to the next available %AI block.
Inputs Default Force Off In the event of module failure or removal, this
parameter specifies the state of the Channel
Value References.
Force Off = Channel Values clear to 0.
Hold Last State = Channel Values hold their
last state.
Channel Value Reference 20 The number of words used for the module’s
Length input data
Diagnostic Reference %Ixxxxx Starting address for the channel diagnostics
Address status data. This defaults to the next available
%I block.
Diagnostic Reference 0 The number of bit reference bits (0 – 320)
Length required for the Channel Diagnostics data.
Default is 0, which means mapping of Channel
Diagnostics is disabled. Change this to a non-
zero value to enable Channel Diagnostics
mapping.
Module Status Reference %Ixxxxx Starting address for the module’s status data.
Address This defaults to the next available %I block.
Module Status Reference 0 The number of bits (0 – 32) required for the
Length Module Status data. Default is 0, which means
mapping of Module Status data is disabled.
Change this to a non-zero value to enable
Module Status data mapping.
CJC Scan Enable Disabled Cold Junction Compensation can be: No Scan,
Scan CJC1, Scan CJC2, Scan Both CJCs. Use
of these parameters is described later in this
section.
Channel Faults w/o Disabled Enabled / Disabled: Controls whether channel
Terminal Block faults and configured alarm responses will be
generated after a Terminal Block removal. The
default setting of Disabled means channel faults
and alarms are suppressed when the Terminal
Block is removed. This parameter does not
affect module faults including the Terminal Block
loss/add fault generation.
I/O Scan Set 1 The scan set 1 – 32 to be assigned to the
module by the RX3i CPU
Channel 1 – 8 Parameters
Parameter Default Description
Range Type Disabled Voltage/Current, Thermocouple, RTD,
Resistance, Disabled
Range (Not for Range Type -10V to +10V For voltage/current: -10V to +10V, 0V to
Disabled) +10V, 0V to +5V, 1V to +5V, -50mV to
+50mV, -150mV to +150mV, -20mA to
+20mA, 4 to 20 mA, 0 to 20 mA
For Thermocouple: B, C, E, J, K, N, R, S, T
For RTD: Platinum 385, 100 ohm / 200
ohm / 500 ohm / 1000 ohm, Platinum 3916,
100 ohm / 200 ohm / 500 ohm / 1000 ohm,
Nickel 672, 120 ohms, Nickel 618, 100
ohms / 200 ohms / 500 ohms / 1000 ohms,
Nickel-Iron 518, 604 ohms, Copper 426, 10
ohms
For Resistance: 0-250 Ohm, 0 – 500 Ohm,
0 – 1000 Ohm, 0 – 2000 Ohm, 0 – 3000
Ohm, 0 – 4000 Ohm
Channel Value Format 32-bit Floating 16-bit integer or 32-bit floating point
Point
Temperature Units (for Celsius Celsius, Fahrenheit
Thermocouple or RTD
Range Type only)
RTD RTD 2 Wire (for RTD Range Type only) RTD 2 or 3 Wire
RTD Lead Resistance Enabled (for RTD Range Type only)Enabled,
Compensation Disabled
High Scale Value (Eng The defaults for Note: Scaling is disabled if both High Scale
Units) the 4 Scaling Eng. Units equals High Scale A/D Units and
parameters Low Scale Eng. Units equals Low Scale
depend on the A/D Units.
configured Range Default is High A/D Limit of selected range
Type and Range. type.
Each Range and
Low Scale Value (Eng Range Type have Default is Low A/D Limit of selected range
Units) a different set of type. Must be lower than the high scaling
defaults. value.
High Scale Value (A/D Default is High A/D Limit of selected range
Units) type. Must be greater than the low scaling
value.
Low Scale Value (A/D Default is Low A/D Limit of selected range
Units) type.
Input Scaling
By default, the module converts a voltage, current, resistance, or temperature input over the
entire span of its configured Range into a floating point value for the CPU. For example, if the
Range of a channel is 4 to 20mA, the module reports channel input values from 4.000 to
20.000. By modifying one or more of the four channel scaling parameters (Low/High Scale
Value parameters) from their defaults, the scaled Engineering Unit range can be changed for a
specific application. Scaling can provide inputs to the PLC that are already converted to their
physical meaning, or convert input values into a range that is easier for the application to
interpret. Scaling is always linear and inverse scaling is possible. All alarm values apply to the
scaled Engineering Units value, not to the A/D input value.
The scaling parameters only set up the linear relationship between two sets of corresponding
values. They do not have to be the limits of the input.
Example 1
For a voltage input, 6.0 volts equals a speed of 20 feet per second, and 1.0 volt equals 0 feet
per second. The relationship in this range is linear. For this example, the input values should
represent speed rather than volts. The following channel configuration sets up this scaling:
0.000
1.000 Voltage (A/D Units) 6.000
For this example, 1.0V to 6.0V is the normal voltage range, but the module will attempt to scale
the inputs for a voltage that lies outside the range. If a voltage of 10.0V were input to the
channel, the module would return a scaled channel value of 36.000. The application should use
alarms or take other precautions for scaled inputs that are outside the acceptable range or
invalid.
Example 2
An existing application uses traditional analog to digital (A/D) count integer values. With scaling
and the optional 16-bit integer input option, a channel can be configured to report integer count
values. In this example, the application should interpret +10V as 32000 counts and -10V as
-32000 counts. The following channel configuration will scale a +/-10V input channel to +/-
32000 counts.
Channel Value Format = 16 Bit Integer
32,000
High Scale Value (Eng Units) = 32000.0
Low Scale Value (Eng Units) = -32000.0
High Scale Value (A/D Units) = 10.000
Counts
Low Scale Value (A/D Units) = -10.000
-32,000 +10,000
-10,000
Voltage
If the Engineering Unit change from the previous sample to current sample is negative, the
module compares the rate change with the Negative Rate of Change parameter.
If the Engineering Unit change between samples is positive, the module compares the results in
comparing the rate change with the Positive Rate of Change parameter value.
In either case, if the rate of change is greater than the configured rate, a rate of change alarm
occurs. The actions taken by the module following the alarm depend on the enabled rate of
change actions that have been set up in the "Diagnostic Reporting Enable", "Fault Reporting
Enable", and "Interrupts Enabled" parameters.
The Rate of Change Sampling Rate parameter determines how frequently the module
compares the Rate of Change. If the Rate of Change Sampling Rate is 0 or any time period
less than the channel update rate, the module compares the Rate of Change for every input
sample of the channel.
Software Filter Integration 0.000 Specifies the amount of time in milliseconds for
Time in milliseconds. the software filter to reach 63.2% of the input
value.
A value of 0 indicates software filter is disabled. A
value of 100 indicates data will achieve 63.2% of
its value in 100ms. Default is disabled
A/D Filter Frequency 40 Hz Low pass A/D hardware filter setting: 8,
12,16,40,200,or 1000Hz. Default is 40Hz.
Frequencies below this are not filtered by
hardware.
Diagnostic Reporting Enable Disabled Diagnostic Reporting Enable options are used to
If Diagnostic Reporting is enable reference memory reporting of alarms into
enabled, the additional the Diagnostic Reference area.
parameters listed below can Fault Reporting Enable options enable fault
be used to enable specific logging of alarms into the I/O Fault Table.
types of alarms.
Interrupts Enable options enable I/O Interrupt
Fault Reporting Enable Disabled trigger when alarm conditions occur.
If Fault Reporting is enabled, These parameters enable or disable the individual
the additional parameters diagnostics features of a channel.
listed below can be used to
When any of these parameters is enabled, the
enable specific types of Faults.
module uses associated parameters to perform
Interrupts Enable Disabled the enabled feature.
If Interrupts are enabled, the
additional parameters listed For example, if Over Range is enabled in the
below can be used to enable “Diagnostic Reporting Enable” menu, the
specific types of Interrupts. module will set the Over Range bit in the
Low Alarm Enable Disabled Diagnostic Reference for the channel.
High Alarm Enable Disabled
If any of these parameters is disabled, the module
Under Range Enable Disabled does not react to the associated alarm conditions.
Over Range Enable Disabled
Open Wire Enable Disabled For example, if Low Alarm Enable is set to
Calibration Fault Enable Disabled Disabled in the “Fault Reporting Enable” menu,
the Low Alarm fault is not logged in the I/O
Low-Low Alarm Enable Disabled Fault Table when Low Alarm is detected on the
High-High Alarm Enable Disabled channel.
Negative Rate of Change Disabled
Detection Enable
Positive Rate of Change Disabled
Detection Enable
Using Alarming
The Diagnostic Reporting Enable, Fault Reporting Enable, and Interrupt Enable configuration
parameters can be used to enable different types of responses for individual channel alarms.
By default, all responses are disabled on every channel. Any combination of alarm enables can
be configured for each channel.
▪ If Diagnostic Reporting is enabled, the module reports channel alarms in reference memory
at the channel's Diagnostic Reference address.
▪ If Fault Reporting is enabled, the module logs a fault log in the I/O Fault table for each
occurrence of a channel alarm.
▪ If Interrupts are enabled, an alarm can trigger execution of an Interrupt Block in the
application program, as explained below.
Using Interrupts
To properly configure an I/O Interrupt, the Interrupt enable bit or bits must be set in the module’s
configuration. In addition, the program block that should be executed in response to the
channel interrupt must be mapped to the corresponding channel's reference address.
Example:
In this example, the Channel Values Reference Address block is mapped to %AI0001-%AI0020.
An I/O Interrupt block should be triggered if a High Alarm condition occurs on channel 2.
▪ Set the High-Alarm Interrupt Enable flag for Channel 2 in the module configuration.
Channel 2's reference address corresponds to %AI00003 (2 Words per channel), so the
interrupt program block Scheduling properties should be set for the "I/O Interrupt" Type and
"%AI0003" as the Trigger.
CJC Parameters
Parameter Default Description
Channel Value Format 16-bit Integer 16-bit integer or 32-bit floating point
Temperature Units Celsius Celsius, Fahrenheit
User Offset (Temperature 0.000 Temperature offset added to CJC values. Range –25 to
Units) +25 degC and -45 to +45 degF in F temp mode.
Diagnostic Reporting Enable Disabled These parameters enable or disable the individual
Under Range Enable Disabled diagnostics features of a CJC input.
Over Range Enable Disabled
Open Wire Enable Disabled
Fault Reporting Enable Disabled
Under Range Enable Disabled
Over Range Enable Disabled
Open Wire Enable Disabled
Interrupts Enable Disabled
Under Range Enable Disabled
Over Range Enable Disabled
Open Wire Enable Disabled
When scanning both CJC inputs, the module subtracts the temperature of CJC2 from the
temperature of CJC1. It then multiplies the difference by a specific multiplier for each channel to
compensate for the position of the channel on the terminal block.
Channel Channel Multiplier Channel Channel Multiplier
1 0.10 5 0.45
2 0.05 6 0.60
3 0.25 7 0.75
4 0.25 8 0.90
For example: if CJC1 is 30 degrees Celsius and CJC2 is 25 degrees Celsius, the compensated
channel 1 terminal block temperature is 30 - [ (30-25) * 0.10 ] = 29.5 degrees Celsius. The
module then adjusts this temperature for the particular thermocouple type to determine the
thermoelectric effect (mV) caused by the connection at the terminal block.
Depending on its configured Channel Value Format, each enabled channel reports a 32-bit
floating point or 16-bit integer value to the CPU.
In the 16-bit integer mode, low word of the 32-bit channel data area contains the 16-bit integer
channel value. The high word (upper 16-bits) of the 32-bit value are set with the sign extension
of the 16-bit integer. This sign-extended upper word allows the 16-bit integer to be read as a
32-bit integer type in logic without losing the sign of the integer. If the 16-bit integer result is
negative, the upper word in the 32-bit channel data has the value 0xFFFF. If the 16-bit integer
result is positive, the upper word is 0x0000.
8 Hz 16 16 127 ms
12 Hz 16 16 87 ms
16 Hz 16 16 67 ms
40 Hz 16 14 27 ms
200 Hz 14 13 13 ms
1000 Hz 11 11 10 ms
Each isolated group provides a CJC input. The CJC input is considered a slow-response input
and will reduce the update rate for the associated channel group when enabled.
The diagnostics data for each channel occupies 2 words (whether the channel is used or not):
Bit Description
1 Low Alarm
2 High Alarm
3 Underrange
4 Overrange
5 Open Wire
6 – 16 Reserved (set to 0).
17 Low-Low Alarm
18 High-High Alarm
19 Negative Rate of Change Alarm
20 Positive Rate of Change Alarm
21 - 32 Reserved (set to 0).
Bit Description
1 Module OK (1 = OK, 0 = failure, or module is not present)
2 Terminal Block Present (1 = Present, 0 = Not present)
3 - 32 Reserved
The module’s TB LED indicates the state of the terminal block. It is green when the Terminal
Block is present or red if it is not.
Faults are automatically logged in the CPU’s I/O Fault table when the terminal block is inserted
or removed from a configured module in the system. The fault type is Field Fault and the fault
description indicates whether the fault is a "Loss of terminal block" or an "Addition of terminal
block". If a Terminal Block is not present while a configuration is being stored, a "Loss of
terminal block" fault is logged.
Bit 1 of the Module Status Reference indicates the status of the terminal block. To enable
Module Status reporting, the Module Status Reference must be configured. During operation,
the PLC must be in an I/O Enabled mode for the current Module Status to be scanned and
updated in reference memory.