AquaForce®

30XV140-500, Series B
Variable Speed Air-Cooled Liquid Chillers
with Greenspeed® Intelligence

Installation Instructions
CONTENTS Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
Page should be performed by trained service personnel. When working
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 on air-conditioning equipment, observe precautions in the
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 literature, tags and labels attached to the unit, and other safety
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 precautions that may apply.
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . 3 available for all brazing operations.
Step 2 — Place, Mount, and Rig the Unit . . . . . . . . . 3
It is important to recognize safety information. This is the safety-
• PLACING UNIT alert symbol . When you see this symbol on the unit and in
• MOUNTING UNIT instructions or manuals, be alert to the potential for personal
• EXPORT SHIPPING RAILS injury.
• RIGGING UNIT
Understand the signal words DANGER, WARNING, CAUTION,
Step 3 — Make Refrigerant, Evaporator Fluid and and NOTE. These words are used with the safety-alert symbol.
Drain Piping Connections . . . . . . . . . . . . . . . . . . 97 DANGER identifies the most serious hazards which will result in
• SPLIT UNIT ASSEMBLY severe personal injury or death. WARNING signifies hazards
• GENERAL which could result in personal injury or death. CAUTION is used
• EVAPORATOR PUMP CONTROL to identify unsafe practices, which may result in minor personal
• PREPARATION FOR YEAR-ROUND OPERATION injury or product and property damage. NOTE is used to highlight
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . 108 suggestions which will result in enhanced installation, reliability,
• BRINE EVAPORATOR OPTION or operation.
• WATER SYSTEM CLEANING
• WATER TREATMENT WARNING
• SYSTEM PRESSURIZATION
• FILLING THE SYSTEM Electrical shock can cause personal injury and death. Shut off
• SET WATER FLOW RATE all power to this equipment during installation. There may be
• FREEZE PROTECTION more than one disconnect switch. Tag all disconnect locations
• PREPARATION FOR WINTER SHUTDOWN to alert others not to restore power until work is completed.
Step 5 — Make Electrical Connections . . . . . . . . . 110
• POWER SUPPLY
• FIELD POWER CONNECTIONS WARNING
• POWER WIRING
• FIELD CONTROL POWER CONNECTIONS Electrical shock can cause personal injury and death. After unit
• CCN COMMUNICATION BUS WIRING power is disconnected, wait at least 20 minutes for the VFD
• BACNET IP OR ETHERNET COMMUNICATION (variable frequency drive) capacitors to discharge before open-
• NON-CCN COMMUNICATION WIRING ing drive.
• FIELD CONTROL OPTION WIRING
• DUAL CHILLER LEAVING WATER SENSOR
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . 166 WARNING
• ENERGY MANAGEMENT MODULE
• UNIT SECURITY/PROTECTION ACCESSORIES DO NOT VENT refrigerant relief valves within a building.
• COMMUNICATION ACCESSORIES Outlet from relief valves must be vented in accordance with
• SERVICE OPTIONS the latest edition of ANSI/ASHRAE (American National Stan-
Step 7 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . . 167 dards Institute/American Society of Heating, Refrigerating and
• DEHYDRATION Air-Conditioning Engineers) 15 (Safety Code for Mechanical
• REFRIGERANT CHARGE Refrigeration). The accumulation of refrigerant in an enclosed
space can displace oxygen and cause asphyxiation. Provide ad-
equate ventilation in enclosed or low overhead areas. Inhala-
SAFETY CONSIDERATIONS tion of high concentrations of vapor is harmful and may cause
Installation and servicing of air-conditioning equipment can be heart irregularities, unconsciousness or death. Misuse can be
hazardous due to system pressure and electrical components. Only fatal. Vapor is heavier than air and reduces the amount of oxy-
trained and qualified service personnel should install, repair, or gen available for breathing. Product causes eye and skin irrita-
service air-conditioning equipment. tion. Decomposition products are hazardous.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300224-01 Printed in U.S.A. Form 30XV-17SI Pg 1 12-21 Replaces: 30XV-11SI
WARNING CAUTION
MAGNETIC FIELD HAZARD This unit uses a microprocessor control system. Do not short
Units equipped with the permanent magnet motor option or jumper between terminations on circuit boards or modules;
contain rotors with powerful magnetic fields. Permanent control or board failure may result.
magnet motor rotors, when removed from the stator, expose Be aware of electrostatic discharge (static electricity) when
surrounding personnel and equipment to powerful magnetic handling or making contact with circuit boards or module con-
fields which may cause serious health hazards to persons with nections. Always touch a chassis (grounded) part to dissipate
pacemakers or defibrillators, hearing aids, metal implants, or body electrostatic charge before working inside control center.
other implanted electronic medical devices, and may impact Use extreme care when handling tools near boards and when
other electronic devices such as mobile phones or connecting or disconnecting terminal plugs. Circuit boards can
smartwatches, watches, credit cards, etc. Persons in a risk easily be damaged. Always hold boards by the edges and
group should consult a physician prior to compressor avoid touching components and connections.
disassembly. Failure to follow these procedures may result in
personal injury or death. This equipment uses, and can radiate, radio frequency energy.
If not installed and used in accordance with the instruction
manual, it may cause interference to radio communications. It
has been tested and found to comply with the limits for a Class
WARNING A computing device pursuant to International Standard in
North America EN 61000-2/3 which are designed to provide
DO NOT USE TORCH to remove any component. System reasonable protection against such interference when operated
contains oil and refrigerant under pressure. in a commercial environment. Operation of this equipment in a
To remove a component, wear protective gloves and goggles residential area is likely to cause interference, in which case
and proceed as follows: the user, at his own expense, will be required to take whatever
measures may be required to correct the interference.
a. Shut off electrical power to unit.
Always store and transport replacement or defective boards in
b. Recover refrigerant to relieve all pressure from system anti-static shipping bag.
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases. CAUTION
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil To prevent potential damage to heat exchanger tubes, always
that may come out of the lines and as a gage for how run fluid through heat exchanger when adding or removing re-
much oil to add to the system. frigerant charge. Use appropriate antifreeze solutions in evapo-
rator fluid loop to prevent the freezing of heat exchanger or in-
e. Carefully un-sweat remaining tubing stubs when neces- terconnecting piping when the equipment is exposed to tem-
sary. Oil can ignite when exposed to torch flame. peratures below 32°F (0°C). Proof of flow switch is factory
Failure to follow these procedures may result in personal inju- installed on all models. Do NOT remove power from this
ry or death. chiller during winter shut down periods without taking precau-
tion to remove all water from heat exchanger. Failure to prop-
erly protect the system from freezing may constitute abuse and
may void warranty.
CAUTION
Standard Tier units (units with S in the 10th position of the
model number) without condenser fan VFDs (units with “-”, CAUTION
“1”, “3”, or “5” in the 13th position of the model number)
must have the condenser fan(s) rotation verified to ensure DO NOT re-use compressor oil or any oil that has been ex-
proper phasing. Correct rotation is counter-clockwise (refer- posed to the atmosphere. Dispose of oil per local codes and
ence arrow on fan cap). Swap any two incoming power leads regulations. DO NOT leave refrigerant system open to air any
to correct condenser fan rotation before starting chiller. Oper- longer than the actual time required to service the equipment.
ating the unit without testing the condenser fan(s) for proper Seal circuits being serviced and charge with dry nitrogen to
phasing could result in equipment damage. prevent oil contamination when timely repairs cannot be com-
pleted. Failure to follow these procedures may result in dam-
age to equipment.

2
INTRODUCTION PLACING UNIT
These instructions cover installation of 30XV140-500 air- Locate the unit so that the condenser airflow is unrestricted
cooled liquid chillers with Greenspeed® intelligence, electronic both above and on the sides of the unit. Airflow and service
controls, and units with factory-installed options (FIOPs). (See clearances are 6 ft (1.8 m) around the unit. Acceptable clear-
Fig. 2.) ance on the sides or ends without control boxes or VFDs can be
reduced to 3 ft (1 m) without sacrificing performance as long as
the remaining three sides are unrestricted. Acceptable clear-
INSTALLATION ance on the side with a control box or VFD can be reduced to
Storage 4 ft (1.3 m) due to NEC regulations, without sacrificing perfor-
mance as long as the remaining three sides are unrestricted.
If the unit is to be stored for a period of time before installation Provide ample room for servicing and removing the evapora-
or start-up, be sure to protect the machine from construction tor. See Fig. 3-24 for required clearances. Local codes for
dirt. Keep protective shipping covers in place until the machine clearances take precedence over the manufacturer’s recom-
is ready for installation. Follow these storage guidelines: mendations when local codes call for greater clearances.
• Store the unit in a clean and dry location. If multiple units are installed at the same site, a minimum sepa-
• Avoid contamination. ration of 10 ft (3 m) between the sides of the machines is re-
• Maintain storage temperature of –13°F to 149°F (–25°C quired to maintain proper airflow and minimize the chances of
to 65°C). condenser air recirculation.
• Before applying power, perform a complete physical in- MOUNTING UNIT
spection. Check for carbon deposits inside the drive, The unit may be mounted on a level pad directly on the base
burned or damaged components, and blown fuses. rails, on a raised mounting rail around the unit, or on vibration
• The unit can be stored for a maximum of 3 years with- isolation springs. (See Fig. 1.) For all units, ensure placement
out power. If the unit is stored for long periods of time area is strong enough to support unit operating weight. (See
without use, special procedures must be performed to Table 1.) Mounting holes are provided for securing the unit to
ensure the safe and efficient operation of the VFD ca- the pad, mounting rail or vibration isolation springs. Bolt the
pacitor banks. If the unit has been stored for more than unit securely to pad or rails. If vibration isolators (field-
3 years without power applied to the drives, contact supplied) are required for a particular installation, refer to unit
Carrier Service to obtain information and instructions weight distribution in Fig. 25 to aid in the proper selection of
for reforming the capacitor banks. isolators. Once installed, the unit must be level to within 1/8 in.
• Perform a Variable Frequency Drive (VFD) static test per ft (1 cm per meter) along the long axis of the unit. This is
before applying power. required for oil return to the compressor(s). For more details
• Ensure a proper operating environment before applying about physical data, see Tables 2 and 3.
power: clean and dry; 5 to 100% humidity, non- NOTE: For units that are point loaded, such as those using rub-
condensing; maximum temperature 126°F (52°C). If ber and shear isolators, the mounting pocket in the base rail
the temperature is below 14°F (–10°C), the drive must must be supported. If the isolator includes a plate that spans
be started with 50% load for 10 minutes. across the mounting pocket, no further support is needed. If the
• When removing from storage, apply power for 3 to 4 isolator is point loaded, add a backup plate to the mounting
hours to exercise capacitors before start-up. plate 1/4 in. thick x 6 in. wide x 8 in. long, centered on unit
mounting plate.
Step 1 — Inspect Shipment
Inspect unit for damage upon arrival. If damage is found, im-
mediately file a claim with the shipping company, and contact
your local Carrier representative.
Step 2 — Place, Mount, and Rig the Unit
When considering a location for the unit, be sure to consult
NEC (National Electrical Code, U.S.A.) and/or local code re-
quirements. Allow sufficient space for airflow, wiring, piping,
and service. (See Fig. 3-24.)
NOTE: To facilitate refrigerant vent piping, all units have fus-
ible plugs with 3/8 in. SAE (Society of Automotive Engineers)
flares and pressure reliefs with 3/4 in. NPT and 3/8 in. SAE
flare fittings (if required by local codes).

Fig. 1 — Isolator

3
XV - 140 6 H C 3

30XV – AquaForce® Air-Cooled Chiller Packaging Options


L – Coil Face Shipping Protection (CFSP)
Design Series 0 – CFSP, Coil Trim Panels
1 – CFSP, Coil Trim Panels, Security Grilles
2 – CFSP, Coil Trim Panels, Security Grilles, Hail Guards (End)
Nominal Capacity 3 – Full Hail Guard
140 250 400 50A/B*
9 – CFSP, Coil Trim Panels, Skid + Bag
160 275 40A/B* B – CFSP, Coil Trim Panels, Security Grilles, Skid + Bag
180 300 450 C – CFSP, Coil Trim Panels, Security Grilles, Hail Guards (End), Skid + Bag
200 325 45A/B* D – Full Hail Guard, Skid, Bag
225 350 500

Voltage Controls Options


1 – 575-3-60 C – 7-in. Touch Pilot™, Remote Connectivity
2 – 380-3-60 D – 7-in. Touch Pilot, EMM, GFI, Remote Connectivity
5 – 208/230-3-60 F – 7-in. Touch Pilot, BACnet† (MS/TP) Translator, Remote Connectivity
6 – 460-3-60 G – 7-in. Touch Pilot, EMM, GFI, BACnet (MS/TP) Translator, Remote Connectivity
9 – 400-3-50 H – 7-in. Touch Pilot, LON Translator, Remote Connectivity
G – 400-3-60 J – 7-in. Touch Pilot, EMM, GFI, LON Translator, Remote Connectivity
H – 380-3-50
J – 415-3-50 Electrical Options
K – 440-3-50 - – Single Point Power, No Control Transformer, Std
0 – Single Point Power with Disconnect, No Control Transformer, Std SCCR
1 – Dual Point Power, No Control Transformer, Std SCCR
Product Tier Configuration 2 – Dual Point Power with Disconnect, No Control Transformer, Std SCCR
S – Standard Tier 3 – Single Point Power, Control Transformer, Std SCCR
M – Mid Tier 4 – Single Point Power with Disconnect, Control Transformer, Std SCCR
H – High Tier 5 – Dual Point Power, Control Transformer, Std SCCR
6 – Dual Point Power with Disconnect, Control Transformer, Std SCCR
7 – Single Point Power, No Control Transformer, High SCCR
Condenser and PM Motor Options
8 – Single Point Power with Disconnect, No Control Transformer, High SCCR
- – Aluminum Fin/Copper Tube 9 – Dual Point Power, No Control Transformer, High SCCR
0 – Copper Fin/Copper Tube B – Dual Point Power with Disconnect, No Control Transformer, High SCCR
1 – Aluminum Fin/Copper Tube, Pre-Coat C – Single Point Power, Control Transformer, High SCCR
2 – Aluminum Fin/Copper Tube, E-Coat D – Single Point Power with Disconnect, Control Transformer, High SCCR
3 – Copper Fin/Copper Tube, E-Coat F – Dual Point Power, Control Transformer, High SCCR
4 – Microchannel G – Dual Point Power with Disconnect, Control Transformer, High SCCR
5 – Microchannel, E-Coat
6 – Aluminum Fin/Copper Tube, PM Compressor Motor Valve & Insulation Options
7 – Copper Fin/Copper Tube, PM Compressor Motor - – No Suction Service Valve, Actuated Discharge Valves,
8 – Aluminum Fin/Copper Tube, Pre-Coat, PM Compressor Motor No Suction Line Insulation
9 – Aluminum Fin/Copper Tube, E-Coat, PM Compressor Motor 0 – Suction Service Valve, Actuated Discharge Valves,
B – Copper Fin/Copper Tube, E-Coat, PM Compressor Motor No Suction Line Insulation
C – Micro Channel, PM Compressor Motor 1 – No Suction Service Valve, Manual Discharge Valves
D – Micro Channel, E-Coat, PM Compressor Motor (Middle East only), No Suction Line Insulation
2 – Suction Service Valve, Manual Discharge Valves
(Middle East only), No Suction Line Insulation
5 – No Suction Service Valve, Actuated Discharge Valves,
Suction Line Insulation
Evaporator and Hydronic Kit Options 6 – Suction Service Valve, Actuated Discharge Valves,
- – Flooded Evaporator, 2 Pass, without Heater, No Pump Suction Line Insulation
0 – Flooded Evaporator, 2 Pass, with Heater, No Pump 7 – No Suction Service Valve, Manual Discharge Valves
(Middle East only), Suction Line Insulation
1 – Flooded Evaporator, 1 Pass, with Heater, No Pump
8 – Suction Service Valve, Manual Discharge Valves
2 – Flooded Evaporator, 2 Pass for Brine Application, with Heater, No Pump (Middle East only), Suction Line Insulation
3 – Flooded Evaporator, 1 Pass for Process Brine Application, with Heater, No Pump
4– Flooded Evaporator, 2 Pass, without Heater, Low Head Pump (N+0)
5– Flooded Evaporator, 2 Pass, with Heater, Low Head Pump (N+0) Condenser Fans and Sound Options
6– Flooded Evaporator, 2 Pass, without Heater, High Head Pump (N+0)
- – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
7– Flooded Evaporator, 2 Pass, with Heater, High Head Pump (N+0)
Std Sound
8– Flooded Evaporator, 2 Pass for Brine Application, with Heater,
0 – Variable Speed Condenser Fans (Std Tier only), Std Sound
Low Head Pump (N+0)
1 – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
9 – Flooded Evaporator, 2 Pass for Brine Application, with Heater,
Low Sound Kit
High Head Pump (N+0)
2 – Variable Speed Condenser Fans (Std Tier only), Low Sound Kit
B – Flooded Evaporator, 3 Pass, with Heater, No Pump 3 – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
C – Flooded Evaporator, 3 Pass for Brine Application, with Heater, No Pump Std Sound, Sound Optimization
D – Flooded Evaporator, 3 Pass, with Heater, Low Head Pump (N+1) 4 – Variable Speed Condenser Fans (Std Tier only), Std Sound, Sound Optimization
F – Flooded Evaporator, 3 Pass, with Heater, High Head Pump (N+1) 5 – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
G – Flooded Evaporator, 3 Pass for Brine Application, with Heater, Low Sound Kit, Sound Optimization
Low Head Pump (N+1) 6 – Variable Speed Condenser Fans (Std Tier only), Low Sound Kit, Sound Optimization
H – Flooded Evaporator, 3 Pass for Brine Application, with Heater, 7 – Variable Speed High Static Fans, Std Sound
High Head Pump (N+1) 8 – Variable Speed High Static Fans, Low Sound Kit
J – Flooded Evaporator, 2 Pass, without Heater, Low Head Pump (N+1) C – ECM Fans, Std Sound
K – Flooded Evaporator, 2 Pass, with Heater, Low Head Pump (N+1) D – ECM Fans, Low Sound Kit
L – Flooded Evaporator, 2 Pass, without Heater, High Head Pump (N+1) F – ECM Fans, Std Sound, Sound Optimization
M – Flooded Evaporator, 2 Pass, with Heater, High Head Pump (N+1) G – ECM Fans, Low Sound Kit, Sound Optimization
N – Flooded Evaporator, 2 Pass for Brine Application, with Heater,
Low Head Pump (N+1)
P – Flooded Evaporator, 2 Pass for Brine Application, with Heater,
High Head Pump (N+1)
R – Remote Evaporator, 2 Pass (requires to be processed via ETO), no pump

LEGEND
CFSP — Coil Face Shipping Protection
EMM — Energy Management Module
GFI — Ground Fault Interrupter
LON — Local Operating Network
SCCR — Short Circuit Current Rating
* 40A, 45A, and 50A are split units that are shipped in two pieces (40A and 40B,
45A and 45B, 50A and 50B). When they arrive at the jobsite, they are com-
bined to form the equivalent of 400, 450, or 500 size units.
† BACnet is a trademark of ASHRAE.

Fig. 2 — AquaForce® Chiller with GreenSpeed® Intelligence Model Number Designation

4
5

Fig. 3 — 30XV 140,160,180 Std Tier; 140 Mid Tier Air-Cooled Chiller
6

Fig. 3 — 30XV 140,160,180 Std Tier; 140 Mid Tier Air-Cooled Chiller (cont)
7

Fig. 3 — 30XV 140,160,180 Std Tier; 140 Mid Tier Air-Cooled Chiller (cont)
8

Fig. 4 — 30XV 140 High Tier; 160,180 Mid Tier; 200 Std Tier Air-Cooled Chiller
9

Fig. 5 — 30XV 140 High Tier; 160,180 Mid Tier; 200 Std Tier Air-Cooled Chiller
10

Fig. 5 — 30XV 140 High Tier; 160,180 Mid Tier; 200 Std Tier Air-Cooled Chiller (cont)
11

Fig. 6 — 30XV 160,180 High Tier; 200 Mid Tier Air-Cooled Chiller
12

Fig. 6 — 30XV 160,180 High Tier; 200 Mid Tier Air-Cooled Chiller (cont)
13

Fig. 6 — 30XV 160,180 High Tier; 200 Mid Tier Air-Cooled Chiller (cont)
14

Fig. 7 — 30XV 200 High Tier Air-Cooled Chiller


15

Fig. 7 — 30XV 200 High Tier Air-Cooled Chiller (cont)


16

Fig. 7 — 30XV 200 High Tier Air-Cooled Chiller (cont)


17

Fig. 8 — 30XV 225 Std Tier Air-Cooled Chiller


18

Fig. 8 — 30XV 225 Std Tier Air-Cooled Chiller (cont)


19

Fig. 8 — 30XV 225 Std Tier Air-Cooled Chiller (cont)


20

Fig. 9 — 30XV 225 Mid Tier Air-Cooled Chiller


21

Fig. 9 — 30XV 225 Mid Tier Air-Cooled Chiller (cont)


22

Fig. 9 — 30XV 225 Mid Tier Air-Cooled Chiller (cont)


23

Fig. 10 — 30XV 225 High Tier Air-Cooled Chiller


24

Fig. 10 — 30XV 225 High Tier Air-Cooled Chiller (cont)


25

Fig. 10 — 30XV 225 High Tier Air-Cooled Chiller (cont)


26

Fig. 11 — 30XV 250,275 Std Tier Air-Cooled Chiller


27

Fig. 11 — 30XV 250,275 Std Tier Air-Cooled Chiller (cont)


28

Fig. 11 — 30XV 250,275 Std Tier Air-Cooled Chiller (cont)


29

Fig. 12 — 30XV 250,275 Mid Tier; 300 Std Tier Air-Cooled Chiller
30

Fig. 12 — 30XV 250,275 Mid Tier; 300 Std Tier Air-Cooled Chiller (cont)
31

Fig. 12 — 30XV 250,275 Mid Tier; 300 Std Tier Air-Cooled Chiller (cont)
32

Fig. 13 — 30XV 250,275 High Tier; 300 Mid Tier; 325 Std Tier Air-Cooled Chiller
33

Fig. 13 — 30XV 250,275 High Tier; 300 Mid Tier; 325 Std Tier Air-Cooled Chiller (cont)
34

Fig. 13 — 30XV 250,275 High Tier; 300 Mid Tier; 325 Std Tier Air-Cooled Chiller (cont)
35

Fig. 14 — 30XV 300 High Tier; 325 Mid Tier Air-Cooled Chiller
36

Fig. 14 — 30XV 300 High Tier; 325 Mid Tier Air-Cooled Chiller (cont)
37

Fig. 14 — 30XV 300 High Tier; 325 Mid Tier Air-Cooled Chiller (cont)
38

Fig. 15 — 30XV 325 High Tier Air-Cooled Chiller


39

Fig. 15 — 30XV 325 High Tier Air-Cooled Chiller (cont)


40

Fig. 15 — 30XV 325 High Tier Air-Cooled Chiller (cont)


41

Fig. 16 — 30XV 350 Standard Tier Air-Cooled Chiller


42

Fig. 16 — 30XV 350 Standard Tier Air-Cooled Chiller (cont)


43

Fig. 16 — 30XV 350 Standard Tier Air-Cooled Chiller (cont)


44

Fig. 17 — 30XV 350 Mid Tier Air-Cooled Chiller


45

Fig. 17 — 30XV 350 Mid Tier Air-Cooled Chiller (cont)


46

Fig. 17 — 30XV 350 Mid Tier Air-Cooled Chiller (cont)


47

Fig. 18 — 30XV 350 High Tier Air-Cooled Chiller


48

Fig. 18 — 30XV 350 High Tier Air-Cooled Chiller (cont)


49

Fig. 18 — 30XV 350 High Tier Air-Cooled Chiller (cont)


50

Fig. 19 — 30XV 400 Standard Tier Air-Cooled Chiller


51

Fig. 19 — 30XV 400 Standard Tier Air-Cooled Chiller (cont)


52

Fig. 19 — 30XV 400 Standard Tier Air-Cooled Chiller (cont)


53

Fig. 20 — 30XV 400 Mid, 450 Standard Tier Air-Cooled Chiller


54

Fig. 20 — 30XV 400 Mid, 450 Standard Tier Air-Cooled Chiller (cont)
55

Fig. 20 — 30XV 400 Mid, 450 Standard Tier Air-Cooled Chiller (cont)
56

Fig. 21 — 30XV 400 High, 450 Mid, 500 Std Tier Air-Cooled Chiller
57

Fig. 21 — 30XV 400 High, 450 Mid, 500 Std Tier Air-Cooled Chiller (cont)
58

Fig. 21 — 30XV 400 High, 450 Mid, 500 Std Tier Air-Cooled Chiller (cont)
59

Fig. 22 — 30XV 450 High, 500 Mid Tier Air-Cooled Chiller


60

Fig. 22 — 30XV 450 High, 500 Mid Tier Air-Cooled Chiller (cont)
61

Fig. 22 — 30XV 450 High, 500 Mid Tier Air-Cooled Chiller (cont)
62

Fig. 23 — 30XV Split Unit 40A-B High, 45A-B Mid, 50A-B Standard Tier Air-Cooled Chiller
63

Fig. 23 — 30XV Split Unit 40A-B High, 45A-B Mid, 50A-B Standard Tier Air-Cooled Chiller (cont)
64

Fig. 23 — 30XV Split Unit 40A-B High, 45A-B Mid, 500A-B Standard Tier Air-Cooled Chiller (cont)
MODULE A
9V

30XV - 45A HIGH


30XV - 50A MID

MODULE B
3V

30XV - 45B HIGH


30XV - 50B MID
65

Fig. 24 — 30XV Split Unit 45A-B High, 50A-B Mid Tier Air-Cooled Chiller
66

Fig. 24 — 30XV Split Unit 45A-B High, 50A-B Mid Tier Air-Cooled Chiller (cont)
67

Fig. 24 — 30XV Split Unit 45A-B High, 50A-B Mid Tier Air-Cooled Chiller (cont)
Table 1 — Unit Mounting Weights
Units with MCHX Condenser Coils — English
30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE NO. POS. 10) A B C D E F G H I J Total
S 1610 1130 2945 2871 1128 1425 — — — — 11,110
140 M 1610 1130 2961 2887 1144 1442 — — — — 11,175
H 1610 1130 2961 2887 1354 1651 232 232 — — 12,058
S 1610 1130 2961 2887 1144 1442 — — — — 11,175
160 M 1610 1130 3008 2934 1400 1698 232 232 — — 12,245
H 1610 1130 3008 2934 1191 1488 416 416 459 459 13,112
S 1610 1130 3008 2934 1191 1488 — — — — 11,362
180 M 1610 1130 3026 2952 1418 1716 232 232 — — 12,317
H 1610 1130 3026 2952 1209 1506 416 416 459 459 13,184
S 1610 1130 3026 2952 1418 1716 232 232 — — 12,317
200 M 1610 1130 3083 3010 1266 1564 416 416 459 459 13,413
H 1610 1130 3083 3010 1266 1564 613 613 657 657 14,202

30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L Total
S 1316 1007 707 541 3014 2767 1996 1835 — — — — 13,185
225 M 1316 1007 707 541 3024 2777 2216 2055 232 232 — — 14,108
H 1316 1007 707 541 3024 2777 2006 1845 416 416 459 459 14,975

30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Total
S 1356 1039 752 576 2739 2750 2843 2811 296 254 — — — — — — 15,415
250 M 1356 1039 752 576 2806 2817 2910 2878 505 463 232 232 — — — — 16,566
H 1356 1039 752 576 2851 2862 2955 2923 296 254 416 416 459 459 — — 17,614
S 1356 1039 752 576 2851 2862 2955 2923 296 254 — — — — — — 15,864
275 M 1356 1039 752 576 2820 2831 2925 2893 505 463 232 232 — — — — 16,624
H 1356 1039 752 576 2820 2831 2925 2893 296 254 416 416 459 459 — — 17,492
S 1356 1039 752 576 2820 2831 2925 2893 505 463 232 232 — — — — 16,624
300 M 1356 1039 752 576 2838 2848 2942 2910 296 254 416 416 459 459 — — 17,560
H 1356 1039 752 576 2838 2848 2942 2910 296 254 626 626 670 670 — — 18,401
S 1356 1039 752 576 2838 2848 2942 2910 296 254 416 416 459 459 — — 17,560
325 M 1356 1039 752 576 2857 2868 2961 2929 296 254 626 626 670 670 — — 18,478
H 1356 1039 752 576 2857 2868 2961 2929 296 254 572 572 572 572 615 615 19,407

30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Total
S 3959 2356 2273 1353 719 596 2442 2827 1616 2128 186 217 — — — — 20,672
350 M 3959 2356 2273 1353 773 651 2704 3089 1679 2191 398 429 235 235 — — 22,326
H 3959 2356 2273 1353 773 651 2704 3089 1679 2191 186 217 397 397 440 440 23,104

30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Q R Total
S 3934 2357 2222 1331 892 772 2724 3500 1318 2041 786 784 550 549 — — — — 23,760
400 M 3934 2357 2222 1331 896 775 2747 3524 1328 2051 786 784 763 761 235 235 — — 24,729
H 3934 2357 2222 1331 896 775 2747 3524 1328 2051 786 784 550 549 397 397 440 440 25,507
S 3934 2357 2222 1331 896 775 2747 3524 1328 2051 786 784 763 761 235 235 — — 24,729
450 M 3934 2357 2222 1331 950 830 3032 3808 1413 2136 786 784 550 549 397 397 440 440 26,356
H 3934 2357 2222 1331 950 830 3032 3808 1413 2136 786 784 550 549 613 613 657 657 27,221
S 3934 2357 2222 1331 950 830 3032 3808 1413 2136 786 784 550 549 397 397 440 440 26,356
500
M 3934 2357 2222 1331 956 835 3068 3845 1429 2152 786 784 550 549 613 613 657 657 27,337

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

68
Table 1 — Unit Mounting Weights (cont)
Units with MCHX Condenser Coils — SI
30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE NO. POS. 10) A B C D E F G H I J Total
S 730 513 1336 1302 512 647 — — — — 5039
140 M 730 513 1343 1310 519 654 — — — — 5069
H 730 513 1343 1310 614 749 105 105 — — 5469
S 730 513 1343 1310 519 654 — — — — 5069
160 M 730 513 1364 1331 635 770 105 105 — — 5554
H 730 513 1364 1331 540 675 189 189 208 208 5948
S 730 513 1364 1331 540 675 — — — — 5154
180 M 730 513 1372 1339 643 778 105 105 — — 5587
H 730 513 1372 1339 548 683 189 189 208 208 5980
S 730 513 1372 1339 643 778 105 105 — — 5587
200 M 730 513 1398 1365 574 709 189 189 208 208 6084
H 730 513 1398 1365 574 709 278 278 298 298 6442

30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L Total
S 597 457 321 245 1367 1255 906 832 — — — — 5981
225 M 597 457 321 245 1372 1260 1005 932 105 105 — — 6399
H 597 457 321 245 1372 1260 910 837 189 189 208 208 6793

30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Total
S 615 471 341 261 1242 1247 1290 1275 134 115 — — — — — — 6992
250 M 615 471 341 261 1273 1278 1320 1306 229 210 105 105 — — — — 7514
H 615 471 341 261 1293 1298 1340 1326 134 115 189 189 208 208 — — 7989
S 615 471 341 261 1293 1298 1340 1326 134 115 — — — — — — 7196
275 M 615 471 341 261 1279 1284 1327 1312 229 210 105 105 — — — — 7541
H 615 471 341 261 1279 1284 1327 1312 134 115 189 189 208 208 — — 7934
S 615 471 341 261 1279 1284 1327 1312 229 210 105 105 — — — — 7541
300 M 615 471 341 261 1287 1292 1334 1320 134 115 189 189 208 208 — — 7965
H 615 471 341 261 1287 1292 1334 1320 134 115 284 284 304 304 — — 8346
S 615 471 341 261 1287 1292 1334 1320 134 115 189 189 208 208 — — 7965
325 M 615 471 341 261 1296 1301 1343 1329 134 115 284 284 304 304 — — 8381
H 615 471 341 261 1296 1301 1343 1329 134 115 260 260 260 260 279 279 8803

30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Total
S 1796 1069 1031 614 326 271 1108 1282 733 965 84 98 — — — — 9377
350 M 1796 1069 1031 614 351 295 1227 1401 761 994 181 195 107 107 — — 10 127
H 1796 1069 1031 614 351 295 1227 1401 761 994 84 98 180 180 200 200 10 480

30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Q R Total
S 1785 1069 1008 604 405 350 1236 1588 598 926 357 356 250 249 — — — — 10 777
400 M 1785 1069 1008 604 406 352 1246 1598 602 930 357 356 346 345 107 107 — — 11 217
H 1785 1069 1008 604 406 352 1246 1598 602 930 357 356 250 249 180 180 200 200 11 570
S 1785 1069 1008 604 406 352 1246 1598 602 930 357 356 346 345 107 107 — — 11 217
450 M 1785 1069 1008 604 431 376 1375 1727 641 969 357 356 250 249 180 180 200 200 11 955
H 1785 1069 1008 604 431 376 1375 1727 641 969 357 356 250 249 278 278 298 298 12 347
S 1785 1069 1008 604 431 376 1375 1727 641 969 357 356 250 249 180 180 200 200 11 955
500
M 1785 1069 1008 604 434 379 1392 1744 648 976 357 356 250 249 278 278 298 298 12 400

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

69
Table 1 — Unit Mounting Weights (cont)
Units with MCHX Condenser Coils and Pump Option — English
30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS
UNIT SIZE NO. POS. 10) A B C D E F G H I J Total
S — — — — — — — — — — —
140 M — — — — — — — — — — —
H 1610 1130 2997 2923 1775 1888 475 328 — — 13,127
S — — — — — — — — — — —
160 M 1610 1130 3044 2970 1822 1935 475 328 — — 13,315
H 1610 1130 3062 2988 1245 1542 1013 699 712 491 14,493
S — — — — — — — — — — —
180 M 1610 1130 3062 2988 1840 1953 475 328 — — 13,386
H 1610 1130 3080 3006 1263 1560 1013 699 712 491 14,565
S — — — — — — — — — — —
200 M 1610 1130 3119 3046 1302 1600 1013 699 712 491 14,722
H 1610 1130 3137 3064 1320 1618 1300 897 1073 740 15,890

30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L Total
S — — — — — — — — — — — — —
225 M — — — — — — — — — — — — —
H 1316 1007 707 541 3078 2831 2060 1899 1013 699 712 491 16,356

30XV TIER (MODEL MOUNTING WEIGHT (lb) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Total
S — — — — — — — — — — — — — — — — —
250 M — — — — — — — — — — — — — — — — —
H 1356 1039 752 576 2905 2916 3009 2977 296 254 1013 699 712 491 — — 18,995
S — — — — — — — — — — — — — — — — —
275 M — — — — — — — — — — — — — — — — —
H 1356 1039 752 576 2874 2885 2979 2947 296 254 1013 699 712 491 — — 18,873
S — — — — — — — — — — — — — — — — —
300 M 1356 1039 752 576 2892 2902 2996 2964 296 254 1013 699 712 491 — — 18.941
H 1356 1039 752 576 2892 2902 2996 2964 296 254 1300 897 1073 740 — — 20,037
S — — — — — — — — — — — — — — — — —
325 M 1356 1039 752 576 2911 2922 3015 2983 296 254 1300 897 1073 740 — — 20,114
H 1356 1039 752 576 2911 2922 3015 2983 296 254 853 853 853 853 896 896 21,306

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

70
Table 1 — Unit Mounting Weights (cont)
Units with MCHX Condenser Coils and Pump Option — SI
30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS
UNIT SIZE NO. POS. 10) A B C D E F G H I J Total
S — — — — — — — — — — —
140 M — — — — — — — — — — —
H 730 513 1359 1326 805 857 215 149 — — 5954
S — — — — — — — — — — —
160 M 730 513 1381 1347 827 878 215 149 — — 6040
H 730 513 1389 1355 565 700 459 317 323 223 6574
S — — — — — — — — — — —
180 M 730 513 1389 1355 835 886 215 149 — — 6072
H 730 513 1397 1364 573 708 459 317 323 223 6607
S — — — — — — — — — — —
200 M 730 513 1415 1381 591 726 459 317 323 223 6678
H 730 513 1423 1390 599 724 590 407 487 336 7208

30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L Total
S — — — — — — — — — — — — —
225 M — — — — — — — — — — — — —
H 597 457 321 245 1396 1284 935 862 459 317 323 223 7419

30XV TIER (MODEL MOUNTING WEIGHT (kg) MCHX CONDENSER COILS


UNIT SIZE NO. POS. 10) A B C D E F G H I J K L M N O P Total
S — — — — — — — — — — — — — — — — —
250 M — — — — — — — — — — — — — — — — —
H 615 471 341 261 1318 1323 1365 1350 134 115 459 317 323 223 — — 8616
S — — — — — — — — — — — — — — — — —
275 M — — — — — — — — — — — — — — — — —
H 615 471 341 261 1304 1309 1351 1337 134 115 459 317 323 223 — — 8561
S — — — — — — — — — — — — — — — — —
300 M 615 471 341 261 1312 1316 1359 1344 134 115 459 317 323 223 — — 8592
H 615 471 341 261 1312 1316 1359 1344 134 115 590 407 487 336 — — 9089
S — — — — — — — — — — — — — — — — —
325 M 615 471 341 261 1320 1325 1368 1353 134 115 590 407 487 336 — — 9123
H 615 471 341 261 1320 1325 1368 1353 134 115 387 387 387 387 406 406 9664

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

71
Table 1 — Unit Mounting Weights (cont)
Units with Al/Cu Condenser Coils — English
30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S 1692 1212 3026 2953 1210 1507 — — — — 11,599
140 M 1694 1215 3045 2972 1228 1526 — — — — 11,680
H 1697 1218 3048 2975 1470 1767 271 271 — — 12,718
S 1697 1217 3048 2974 1231 1528 — — — — 11,694
160 M 1701 1221 3098 3025 1520 1817 275 275 — — 12,930
H 1701 1222 3099 3026 1282 1580 488 488 531 531 13,949
S 1699 1219 3097 3023 1280 1577 — — — — 11,896
180 M 1702 1222 3117 3044 1539 1836 261 261 — — 12,982
H 1702 1223 3118 3045 1301 1599 504 504 547 547 14,090
S 1702 1222 3117 3044 1539 1836 276 276 — — 13,012
200 M 1702 1223 3175 3102 1359 1656 489 489 532 532 14,260
H 1706 1226 3179 3105 1362 1660 718 718 762 762 15,200

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S 1392 1083 783 617 3119 2872 2102 1940 — — — — 13,910
225 M 1393 1084 784 618 3130 2883 2322 2189 280 280 — — 14,965
H 1393 1084 784 618 3130 2883 2112 1951 493 493 536 536 16,013

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 1422 1105 818 642 2834 2845 2967 2935 333 291 — — — — — — 16,191
250 M 1425 1108 821 646 2904 2915 3037 3005 574 532 273 273 — — — — 17,514
H 1426 1109 822 647 2950 2961 3083 3051 337 295 486 486 530 530 — — 18,712
S 1424 1107 820 644 2948 2959 3081 3049 335 293 — — — — — — 16,660
275 M 1426 1109 822 646 2919 2930 3052 3020 575 533 274 274 — — — — 17,582
H 1427 1110 823 647 2920 2931 3053 3021 338 296 487 487 530 530 — — 18,600
S 1426 1109 822 646 2919 2930 3052 3020 575 533 274 274 — — — — 17,582
300 M 1427 1111 824 648 2938 2949 3071 3039 339 297 487 487 531 531 — — 18,679
H 1430 1113 826 651 2941 2951 3074 3042 341 299 729 729 773 773 — — 19,670
S 1427 1111 824 648 2938 2949 3071 3039 339 297 487 487 531 531 — — 18,679
325 M 1431 1114 827 651 2960 2971 3094 3062 342 300 729 729 774 774 — — 19,757
H 1431 1114 827 651 2960 2971 3093 3061 342 300 666 666 666 666 709 709 20,832

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 4058 2455 2372 1452 808 686 2532 2916 1734 2246 227 258 — — — — 21,746
350 M 4061 2458 2375 1455 866 743 2797 3181 1800 2312 471 502 280 280 — — 23,580
H 4061 2459 2376 1455 866 743 2797 3181 1800 2312 230 261 470 470 514 514 24,510

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Q R Total
S 4036 2458 2324 1433 965 844 2854 3631 1390 2114 859 857 623 621 — — — — 25,010
400 M 4037 2459 2325 1434 989 868 2840 3617 1421 2144 860 858 865 864 280 280 — — 26,140
H 4037 2459 2325 1434 989 868 2840 3617 1421 2144 860 858 624 623 471 471 514 514 27,069
S 4037 2459 2325 1434 989 868 2840 3617 1421 2144 860 858 865 864 280 280 — — 26,140
450 M 4038 2461 2326 1435 1045 924 3126 3902 1507 2231 861 859 625 624 472 472 515 515 27,938
H 4040 2463 2328 1437 1047 926 3128 3904 1509 2233 863 861 656 655 718 718 763 763 29,012
S 4038 2461 2326 1435 1045 924 3126 3902 1507 2231 861 859 625 624 472 472 515 515 27,938
500
M 4047 2469 2334 1444 1059 938 3171 3948 1532 2255 870 868 663 661 725 725 769 769 29,247

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

72
Table 1 — Unit Mounting Weights (cont)
Units with Al/Cu Condenser Coils — SI
30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S 767 550 1373 1339 549 683 — — — — 5261
140 M 769 551 1381 1348 557 692 — — — — 5298
H 770 552 1383 1349 667 802 123 123 — — 5769
S 770 552 1382 1349 558 693 — — — — 5304
160 M 771 554 1405 1372 689 824 125 125 — — 5865
H 772 554 1406 1372 582 717 221 221 241 241 6327
S 771 553 1405 1371 581 716 — — — — 5396
180 M 772 554 1414 1381 698 833 118 118 — — 5889
H 772 555 1414 1381 590 725 229 229 248 248 6391
S 772 554 1414 1381 698 833 125 125 — — 5902
200 M 772 555 1440 1407 616 751 222 222 241 241 6468
H 774 556 1442 1409 618 753 326 326 346 346 6894

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S 632 491 355 280 1415 1303 953 880 — — — — 6310
225 M 632 492 356 280 1420 1308 1053 993 127 127 — — 6788
H 632 492 356 280 1420 1308 958 885 223 223 243 243 7263

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 645 501 371 291 1285 1290 1346 1331 151 132 — — — — — — 7344
250 M 646 503 373 293 1317 1322 1378 1363 261 242 124 124 — — — — 7944
H 647 503 373 293 1338 1343 1398 1384 153 134 220 220 240 240 — — 8488
S 646 502 372 292 1337 1342 1397 1383 152 133 — — — — — — 7557
275 M 647 503 373 293 1324 1329 1385 1370 261 242 124 124 — — — — 7975
H 647 503 373 294 1325 1329 1385 1370 153 134 221 221 241 241 — — 8437
S 647 503 373 293 1324 1329 1385 1370 261 242 124 124 — — — — 7975
300 M 647 504 374 294 1333 1338 1393 1378 154 135 221 221 241 241 — — 8473
H 649 505 375 295 1334 1339 1394 1380 155 136 330 330 351 351 — — 8922
S 647 504 374 294 1333 1338 1393 1378 154 135 221 221 241 241 — — 8473
325 M 649 505 375 295 1343 1348 1403 1389 155 136 331 331 351 351 — — 8962
H 649 505 375 295 1343 1348 1403 1389 155 136 302 302 302 302 322 322 9449

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 1841 1114 1076 659 367 311 1148 1323 787 1019 103 117 — — — — 9864
350 M 1842 1115 1077 660 393 337 1269 1443 816 1049 214 228 127 127 — — 10 696
H 1842 1115 1078 660 393 337 1269 1443 816 1049 105 119 213 213 233 233 11 117

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Q R Total
S 1831 1115 1054 650 438 383 1295 1647 631 959 390 389 283 282 — — — — 11 344
400 M 1831 1116 1054 650 449 394 1288 1640 644 973 390 389 393 392 127 127 — — 11 857
H 1831 1116 1054 650 449 394 1288 1641 644 973 390 389 283 282 213 213 233 233 12 278
S 1831 1116 1054 650 449 394 1288 1640 644 973 390 389 393 392 127 127 — — 11 857
450 M 1832 1116 1055 651 474 419 1418 1770 684 1012 391 390 284 283 214 214 234 234 12 672
H 1833 1117 1056 652 475 420 1419 1771 685 1013 392 390 298 297 326 326 346 346 13 159
S 1832 1116 1055 651 474 419 1418 1770 684 1012 391 390 284 283 214 214 234 234 12 672
500
M 1836 1120 1059 655 480 426 1438 1791 695 1023 395 394 301 300 329 329 349 349 13 266

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

73
Table 1 — Unit Mounting Weights (cont)
Units with Al/Cu Condenser Coils and Pump Option — English
30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S — — — — — — — — — — —
140 M — — — — — — — — — — —
H 1697 1218 3084 3011 1892 2004 514 367 — — 13,788
S — — — — — — — — — — —
160 M 1701 1221 3134 3061 1942 2054 517 370 — — 14,000
H 1701 1222 3153 3080 1336 1634 1085 771 784 564 15,330
S — — — — — — — — — — —
180 M 1702 1222 3153 3080 1961 2074 504 357 — — 14,052
H 1702 1223 3172 3099 1355 1653 1101 787 800 580 15,471
S — — — — — — — — — — —
200 M 1702 1223 3229 3156 1413 1710 1086 772 785 565 15,641
H 1706 1226 3233 3159 1416 1714 1406 1003 1178 846 16,887

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S — — — — — — — — — — — — —
225 M — — — — — — — — — — — — —
H 1393 1084 784 618 3184 2937 2166 2005 1090 776 789 568 17,394

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Al/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S — — — — — — — — — — — — — — — — —
250 M — — — — — — — — — — — — — — — — —
H 1426 1109 822 647 3004 3015 3137 3105 337 295 1083 769 782 562 — — 20,093
S — — — — — — — — — — — — — — — — —
275 M — — — — — — — — — — — — — — — — —
H 1427 1110 823 647 2974 2985 3107 3075 338 296 1084 770 783 562 — — 19,981
S — — — — — — — — — — — — — — — — —
300 M 1427 1111 824 648 2992 3003 3125 3093 339 297 1084 771 784 563 — — 20,060
H 1430 1113 826 651 2995 3005 3128 3096 341 299 1403 1000 1176 844 — — 21,306
S — — — — — — — — — — — — — — — — —
325 M 1431 1114 827 651 3014 3025 3148 3116 342 300 1404 1001 1176 844 — — 21,393
H 1431 1114 827 651 3014 3025 3147 3115 342 300 947 947 947 947 989 989 22,732

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

74
Table 1 — Unit Mounting Weights (cont)
Units with Al/Cu Condenser Coils and Pump Option — SI
30XV TIER (MODEL NO. POS. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE 10) A B C D E F G H I J Total
S — — — — — — — — — — —
140 M — — — — — — — — — — —
H 770 552 1399 1366 858 909 233 167 — — 6254
S — — — — — — — — — — —
160 M 771 554 1422 1388 881 932 235 168 — — 6350
H 772 554 1430 1397 606 741 492 350 356 256 6954
S — — — — — — — — — — —
180 M 772 554 1430 1397 889 941 228 162 — — 6374
H 772 555 1439 1405 615 750 499 357 363 263 7018
S — — — — — — — — — — —
200 M 772 555 1465 1431 641 776 493 350 356 256 7095
H 774 556 1466 1433 642 777 638 455 534 384 7660

30XV TIER (MODEL NO. POS. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE 10) A B C D E F G H I J K L Total
S — — — — — — — — — — — — —
225 M — — — — — — — — — — — — —
H 632 492 356 280 1444 1332 983 909 494 352 358 258 7890

30XV TIER (MODEL NO. POS. MOUNTING WEIGHT (kg) Al/Cu CONDENSER COILS
UNIT SIZE 10) A B C D E F G H I J K L M N O P Total
S — — — — — — — — — — — — — — — — —
250 M — — — — — — — — — — — — — — — — —
H 647 503 373 293 1363 1367 1423 1408 153 134 491 349 355 255 — — 9114
S — — — — — — — — — — — — — — — — —
275 M — — — — — — — — — — — — — — — — —
H 647 503 373 294 1349 1354 1409 1395 153 134 492 349 355 255 — — 9063
S — — — — — — — — — — — — — — — — —
300 M 647 504 374 294 1357 1362 1417 1403 154 135 492 350 355 255 — — 9099
H 649 505 375 295 1358 1363 1419 1404 155 136 637 454 533 383 — — 9664
S — — — — — — — — — — — — — — — — —
325 M 649 505 375 295 1367 1372 1428 1413 155 136 637 454 534 383 — — 9704
H 649 505 375 295 1367 1372 1428 1413 155 136 429 429 429 429 429 429 10 311

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

75
Table 1 — Unit Mounting Weights (cont)
Units with Cu/Cu Condenser Coils — English
30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S 1879 1399 3214 3140 1397 1694 — — — — 12,724
140 M 1882 1402 3233 3159 1416 1713 — — — — 12,805
H 1885 1405 3236 3162 1727 2025 342 342 — — 14,124
S 1884 1404 3235 3161 1418 1716 — — — — 12,819
160 M 1888 1408 3286 3212 1777 2075 345 345 — — 14,336
H 1889 1409 3287 3213 1470 1767 628 628 672 672 15,636
S 1887 1407 3284 3211 1468 1765 — — — — 13,021
180 M 1889 1410 3305 3231 1797 2094 346 346 — — 14,418
H 1890 1410 3306 3232 1489 1786 629 629 673 673 15,717
S 1889 1410 3305 3231 1797 2094 362 346 — — 14,433
200 M 1890 1410 3363 3289 1546 1843 629 629 673 673 15,947
H 1893 1414 3366 3293 1550 1847 929 929 973 973 17,167

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S 1533 1224 924 758 3330 3083 2312 2151 — — — — 15,316
225 M 1534 1225 925 759 3341 3094 2632 2470 351 351 16,681
H 1533 1225 925 759 3341 3094 2422 2261 633 633 677 677 18,179

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 1562 1246 959 783 3045 3055 3248 3216 403 361 — — — — — — 17,878
250 M 1566 1249 962 786 3115 3126 3318 3286 715 673 343 343 — — — — 19,482
H 1567 1250 963 787 3161 3172 3364 3332 408 365 627 627 670 670 — — 20,961
S 1564 1248 961 785 3159 3170 3362 3330 405 363 — — — — — — 18,347
275 M 1567 1250 963 787 3130 3141 3334 3302 716 674 344 344 — — — — 19,550
H 1567 1250 964 788 3131 3142 3334 3302 408 366 627 627 671 671 — — 20,849
S 1567 1250 963 787 3130 3141 3334 3302 716 674 344 344 — — — — 19,550
300 M 1568 1251 964 789 3149 3160 3352 3320 409 367 628 628 672 672 — — 20,928
H 1571 1254 967 791 3151 3162 3355 3323 412 369 939 939 984 984 — — 22,201
S 1568 1251 964 789 3149 3160 3352 3320 409 367 628 628 672 672 — — 20,928
325 M 1571 1254 968 792 3171 3182 3375 3343 412 370 940 940 984 984 — — 22,288
H 1571 1254 967 792 3171 3182 3374 3342 412 370 854 854 854 854 896 896 23,644

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 4269 2666 2583 1663 996 873 2719 3103 1992 2504 298 328 — — — — 23,995
350 M 4271 2669 2586 1666 1053 931 2984 3368 2057 2569 612 643 350 350 26,111
H 4272 2670 2586 1666 1053 931 2985 3369 2058 2570 301 332 611 611 654 654 27,321

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Q R Total
S 4247 2669 2534 1643 1106 985 3135 3912 1531 2254 1000 997 764 762 — — — — 27,540
400 M 4248 2670 2535 1644 1176 1056 3028 3804 1608 2332 1001 998 1076 1075 351 351 — — 28,951
H 4248 2670 2536 1645 1177 1056 3028 3804 1608 2332 1001 998 765 763 611 611 655 655 30,162
S 4248 2670 2535 1644 1176 1056 3028 3804 1608 2332 1001 998 1076 1075 351 351 — — 28,951
450 M 4249 2671 2537 1646 1232 1111 3313 4090 1695 2418 1002 999 766 764 612 612 656 656 31,030
H — — — — — — — — — — — — — — — — — — —
S 4249 2671 2537 1646 1232 1111 3313 4090 1695 2418 1002 999 766 764 612 612 656 656 31,030
500
M — — — — — — — — — — — — — — — — — — —

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

76
Table 1 — Unit Mounting Weights (cont)
Units with Cu/Cu Condenser Coils — SI
30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S 852 635 1458 1424 634 769 — — — — 5771
140 M 854 636 1466 1433 642 777 — — — — 5808
H 855 637 1468 1434 784 918 155 155 — — 6406
S 855 637 1467 1434 643 778 — — — — 5814
160 M 856 639 1490 1457 806 941 156 156 — — 6503
H 857 639 1491 1457 667 802 285 285 305 305 7092
S 856 638 1490 1456 666 801 — — — — 5906
180 M 857 639 1499 1466 815 950 157 157 — — 6540
H 857 640 1499 1466 675 810 286 286 305 305 7129
S 857 639 1499 1466 815 950 164 157 — — 6547
200 M 857 640 1525 1492 701 836 286 286 305 305 7233
H 859 641 1527 1494 703 838 421 421 441 441 7787

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S 695 555 419 344 1511 1399 1049 976 — — — — 6947
225 M 696 556 419 344 1516 1403 1194 1121 159 159 — — 7566
H 696 555 419 344 1515 1403 1099 1026 287 287 307 307 8246

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 709 565 435 355 1381 1386 1473 1459 183 164 — — — — — — 8109
250 M 710 566 436 357 1413 1418 1505 1491 324 305 156 156 — — — — 8837
H 711 567 437 357 1434 1439 1526 1511 185 166 284 284 304 304 — — 9508
S 710 566 436 356 1433 1438 1525 1510 184 165 — — — — — — 8322
275 M 711 567 437 357 1420 1425 1512 1498 325 306 156 156 — — — — 8868
H 711 567 437 357 1420 1425 1512 1498 185 166 285 285 304 304 — — 9457
S 711 567 437 357 1420 1425 1512 1498 325 306 156 156 — — — — 8868
300 M 711 568 437 358 1428 1433 1521 1506 186 166 285 285 305 305 — — 9493
H 712 569 439 359 1429 1434 1522 1507 187 168 426 426 446 446 — — 10 070
S 711 568 437 358 1428 1433 1521 1506 186 166 285 285 305 305 — — 9493
325 M 713 569 439 359 1438 1443 1531 1516 187 168 426 426 447 447 — — 10 109
H 713 569 439 359 1438 1443 1531 1516 187 168 387 387 387 387 407 407 10 725

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S 1936 1209 1172 754 452 396 1233 1408 903 1136 135 149 — — — — 10 884
350 M 1937 1211 1173 756 478 422 1354 1528 933 1165 278 292 159 159 — — 11 844
H 1938 1211 1173 756 478 422 1354 1528 933 1166 136 150 277 277 297 297 12 393

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Q R Total
S 1926 1211 1150 745 502 447 1422 1774 694 1023 453 452 346 346 — — — — 12 492
400 M 1927 1211 1150 746 534 479 1373 1725 729 1058 454 453 488 487 159 159 — — 13 132
H 1927 1211 1150 746 534 479 1373 1726 730 1058 454 453 347 346 277 277 297 297 13 681
S 1927 1211 1150 746 534 479 1373 1725 729 1058 454 453 488 487 159 159 — — 13 132
450 M 1927 1212 1151 746 559 504 1503 1855 769 1097 454 453 347 347 278 278 297 297 14 075
H — — — — — — — — — — — — — — — — — — —
S 1927 1212 1151 746 559 504 1503 1855 769 1097 454 453 347 347 278 278 297 297 14 075
500
M — — — — — — — — — — — — — — — — — — —

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

77
Table 1 — Unit Mounting Weights (cont)
Units with Cu/Cu Condenser Coils and Pump Option — English
30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S — — — — — — — — — — —
140 M — — — — — — — — — — —
H 1885 1405 3272 3198 2149 2262 585 437 — — 15,193
S — — — — — — — — — — —
160 M 1888 1408 3322 3248 2199 2312 588 441 — — 15,406
H 1889 1409 3341 3267 1524 1821 1225 912 925 704 17,017
S — — — — — — — — — — —
180 M 1889 1410 3341 3267 2218 2331 589 442 — — 15.487
H 1890 1410 3360 3286 1543 1840 1226 913 926 705 17,098
S — — — — — — — — — — —
200 M 1890 1410 3399 3325 1582 1879 1226 913 926 705 17,256
H 1893 1414 3420 3347 1604 1901 1617 1214 1389 1057 18,855

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S — — — — — — — — — — — — —
225 M — — — — — — — — — — — — —
H 1533 1225 925 759 3395 3148 2476 2315 1230 916 929 709 19,560

30XV TIER (MODEL NO. MOUNTING WEIGHT (lb) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S — — — — — — — — — — — — — — — — —
250 M — — — — — — — — — — — — — — — — —
H 1567 1250 963 787 3215 3226 3418 3386 408 365 1224 910 923 702 — — 22,342
S — — — — — — — — — — — — — — — — —
275 M — — — — — — — — — — — — — — — — —
H 1567 1250 964 788 3185 3196 3388 3356 408 366 1224 910 924 703 — — 22,230
S — — — — — — — — — — — — — — — — —
300 M 1568 1251 964 789 3203 3214 3406 3374 409 367 1225 911 924 704 — — 22,309
H 1571 1254 967 791 3205 3216 3409 3377 412 369 1614 1211 1387 1054 — — 23,837
S — — — — — — — — — — — — — — — — —
325 M 1571 1254 968 792 3225 3236 3429 3397 412 370 1615 1212 1387 1055 — — 23,924
H 1571 1254 967 792 3225 3236 3428 3396 412 370 1134 1134 1134 1134 1177 1177 25,543

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

78
Table 1 — Unit Mounting Weights (cont)
Units with Cu/Cu Condenser Coils and Pump Option — SI
30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J Total
S — — — — — — — — — — —
140 M — — — — — — — — — — —
H 855 637 1484 1451 975 1026 265 198 — — 6892
S — — — — — — — — — — —
160 M 856 639 1507 1473 998 1049 267 200 — — 6988
H 857 639 1515 1482 691 826 556 414 419 319 7719
S — — — — — — — — — — —
180 M 857 639 1515 1482 1006 1057 267 200 — — 7025
H 857 640 1524 1490 700 835 556 414 420 320 7756
S — — — — — — — — — — —
200 M 857 640 1542 1508 718 852 556 414 420 320 7827
H 859 641 1552 1518 727 862 733 551 630 479 8553

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L Total
S — — — — — — — — — — — — —
225 M — — — — — — — — — — — — —
H 696 555 419 344 1540 1428 1123 1050 558 416 422 322 8872

30XV TIER (MODEL NO. MOUNTING WEIGHT (kg) Cu/Cu CONDENSER COILS
UNIT SIZE POS. 10) A B C D E F G H I J K L M N O P Total
S — — — — — — — — — — — — — — — — —
250 M — — — — — — — — — — — — — — — — —
H 711 567 437 357 1458 1463 1550 1536 185 166 555 413 419 319 — — 10 134
S — — — — — — — — — — — — — — — — —
275 M — — — — — — — — — — — — — — — — —
H 711 567 437 357 1445 1450 1537 1522 185 166 555 413 419 319 — — 10 084
S — — — — — — — — — — — — — — — — —
300 M 711 568 437 358 1453 1458 1545 1530 186 166 556 413 419 319 — — 10 119
H 712 569 439 359 1454 1459 1546 1532 187 168 732 549 629 478 — — 10 812
S — — — — — — — — — — — — — — — — —
325 M 713 569 439 359 1463 1468 1555 1541 187 168 733 550 629 478 — — 10 852
H 713 569 439 359 1463 1468 1555 1541 187 168 515 515 515 515 534 534 11 586

LEGEND

MCHX — Microchannel Heat Exchanger


NOTE: See Fig. 25 for mounting weight reference points.

79
30XV140-200

A C E
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
140 X X R 4V
160 X B
180 X O
X

B D F

A C E G
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
140 X R 5V
160 X B
O
180 X X
200 X
B D F H

A C E G I
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
160 X R 6V
180 X B
O
200 X
X

B D F H J

A C E G I
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
200 X R
B
7V
O
X

B D F H J

NOTES:
1. Letters indicate the general location of the mounting weight
locations on the base of the unit.
2. See Table 1 for mounting weight at reference points.

Fig. 25 — Unit Mounting Weight Reference Points

80
30XV225

A C E G
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
225 X
R 5V
B
O
X

B D F H

A C E G I
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
225 X R 6V
B
O
X

B D F H J

A C E G I K
P
UNIT 30XV TIER (MODEL NO. POS. 10) O
SIZE S M H W
E
225 X R
B
7V
O
X

B D F H J L

NOTES:
1. Letters indicate the general location of the mounting weight
locations on the base of the unit.
2. See Table 1 for mounting weight at reference points.

Fig. 25 — Unit Mounting Weight Reference Points (cont)

81
30XV250-325

A C E G I
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
250 X E
275 X R 6V
B
O
X

B D F H J

A C E G I K
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
250 X E
275 X R
B
7V
300 X O
X

B D F H J L

A C E G I K M
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
250 X E
275 X R
8V
B
300 X
O
325 X X

B D F H J L N

A C E G I K M
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
300 X E
325 X R
9V
B
O
X

B D F H J L N

A C E G I K M O
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
325 X E
R
B
10V
O
X

B D F H J L N P

NOTES:
1. Letters indicate the general location of the mounting weight
locations on the base of the unit.
2. See Table 1 for mounting weight at reference points.

Fig. 25 — Unit Mounting Weight Reference Points (cont)

82
30XV350-500

A C E G I K
UNIT 30XV TIER (MODEL NO. POS. 10) P
O
SIZE S M H W
E
350 X R
8V
B
O
X

B D F H J L

A C E G I K M
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
350 X E
R
9V
400 X B
O
X

B D F H J L N

A C E G I K M O
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H O
W
350 X E
R
10V
400 X B
O
450 X X

B D F H J L N P

A C E G I K M O Q
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H
O
W
400, 40A X E
R
11V
450, 45A X B
O
500, 50A X X

B D F H J L N P R

A C E G I K M O Q
UNIT 30XV TIER (MODEL NO. POS. 10) P
SIZE S M H
O
W
450, 45A X E
R
12V
500, 50A X B
O
X

B D F H J L N P R

NOTES:
1. Letters indicate the general location of the mounting weight
locations on the base of the unit.
2. See Table 1 for mounting weight at reference points.

Fig. 25 — Unit Mounting Weight Reference Points (cont)

83
Table 2 — Physical Data — English
30XV 140T-180T
UNIT 30XV WITH FLOODED EVAPORATOR 140 160 180
TIER (MODEL NO. POS. 10) S M H S M H S M H
CHASSIS DIMENSIONS (in.) (Note 1)
Length 207.6 207.6 254.6 207.6 254.6 301.6 207.6 254.6 301.6
Width 88.0
Height 98.9
OPERATING WEIGHT (lb) (Note 2)
Al-Cu Condenser Coil 11,599 11,680 12,718 11,694 12,930 13,949 11,896 12,982 14,090
Cu-Cu Condenser Coil 12,724 12,805 14,124 12,819 14,336 15,636 13,021 14,418 15,717
MCHX Condenser Coil 11,110 11,175 12,058 11,175 12,245 13,112 11,362 12,317 13,184
Al-Cu Condenser Coil with Pump Option — — 13,788 — 14,000 15,330 — 14,052 15,471
Cu-Cu Condenser Coil with Pump Option — — 15,193 — 15,406 17,017 — 15,487 17,098
MCHX Condenser Coil with Pump Option — — 13,127 — 13,315 14,493 — 13,386 14,565
SHIPPING WEIGHT (lb) (Note 3)
Al-Cu Condenser Coil 11,426 11,492 12,530 11,506 12,720 13,739 11,686 12,755 13,864
Cu-Cu Condenser Coil 12,551 12,617 13,936 12,631 14,126 15,425 12,811 14,191 15,490
MCHX Condenser Coil 10,937 10,987 11,870 10,987 12,035 12,902 11,152 12,090 12,957
Al-Cu Condenser Coil with Pump Option — — 13,456 — 13,646 14,904 — 13,681 15,029
Cu-Cu Condenser Coil with Pump Option — — 14,862 — 15,052 16,591 — 15,117 16,656
MCHX Condenser Coil with Pump Option — — 12,796 — 12,961 14,067 — 13,016 14,122
REFRIGERANT TYPE (Standard Evaporator) R-134a EXV Controlled System
Refrigerant Charge (lb) Ckt A/ Ckt B (RTPF) 152/157 160/165 180/185 162/177 190/200 208/218 172/182 195/205 213/223
Refrigerant Charge (lb) Ckt A/ Ckt B (MCHX) 100/105 110/115 115/120 110/125 125/135 130/140 120/130 130/140 135/145
REFRIGERANT TYPE (Brine Evaporator) R-134a EXV Controlled System
Refrigerant Charge (lb) Ckt A/ Ckt B (RTPF) 167/172 177/182 195/200 187/197 205/215 223/233 192/202 210/220 228/238
Refrigerant Charge (lb) Ckt A/ Ckt B (MCHX) 115/120 125/130 130/135 135/145 140/150 145/155 140/150 145/155 150/160
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2
Full Load Capacity Split Ckt A / Ckt B (Note 4) 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50
Oil Charge (gal) Ckt A/Ckt B 5.5/5.5 5.5/5.5 5.5/5.5 5.5/5.5 5.5/5.5 5.5/5.5 5.5/5.5 5.5/5.5 5.5/5.5
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (gal.) 21 23 23 23 25 25 25 27 27
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300 300 300 300 300 300 300 300 300
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-Pass), Inlet and Outlet, Victaulic (in.) 5/5 5/5 5/5 5/5 5/5 5/5 5/5 5/5 5/5
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet, Victaulic (in.) 5/— 5/— 5/— 5/— 5/— 5/— 5/— 5/— 5/—
Fresh Water/Process Brine
3 Pass, Inlet and Outlet, Victaulic (in.) 4/4 4/4 4/4 4/4 5/4 5/4 5/4 5/4 5/4
Fresh Water/Comfort Brine
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Fresh Water
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 5/5 5/5 5/5 5/5 5/5 5/5 6/6 6/6 6/6
Victaulic (in.) Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Fans (Ckt A/ Ckt B) 4/4 4/4 5/5 4/4 5/5 6/6 4/4 5/5 6/6
Total Airflow (cfm) RTPF Coil 105,120 105,120 131,400 105,120 131,400 157,680 105,120 131,400 157,680
Total Airflow (cfm) MCHX Coil 116,000 116,000 145,000 116,000 145,000 174,000 116,000 145,000 174,000
CONDENSER COILS
No. Coils (Ckt A/ Ckt B) 4/4 4/4 5/5 4/4 5/5 6/6 4/4 5/5 6/6
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels,
Cu — Copper but no other options or accessories are included. The shipping
Al — Aluminum weight is equal to the operating weight (indicated above) minus
EXV — Electronic Expansion Valve the weight of the water in the evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a
RTPF — Round Tube/Plate Fin full load condition. The actual capacity split at most operating con-
ditions will not match these values.
NOTES: 5. The minimum capacity is less than 15% for units sized at full
capacity. Please use the chiller selection program to determine
1. More precise dimensions are available on the certified prints. actual minimum capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, 6. Standard-tier models without the variable speed condenser fan
but no other options or accessories are included. Selected options option have a maximum speed of 840 rpm.
and accessories will slightly alter the unit weight. See Fig. 25 for
the mounting weight detail.

84
Table 2 — Physical Data — English (cont)
30XV 200T-250T
UNIT 30XV WITH FLOODED EVAPORATOR 200 225 250
TIER (MODEL NO. POS. 10) S M H S M H S M H
CHASSIS DIMENSIONS (in.) (Note 1)
Length 254.6 301.6 348.6 251.7 298.7 345.7 298.7 345.7 392.7
Width 88.0
Height 98.9
OPERATING WEIGHT (lb) (Note 2)
Al-Cu Condenser Coil 13,012 14,260 15,200 13,910 14,965 16,013 16,191 17,514 18,712
Cu-Cu Condenser Coil 14,433 15,947 17,167 15,316 16,681 18,179 17,878 19,482 20,961
MCHX Condenser Coil 12,317 13,413 14,202 13,185 14,108 14,975 15,415 16,566 17,614
Al-Cu Condenser Coil with Pump Option — 15,641 16,887 — — 17,394 — — 20,093
Cu-Cu Condenser Coil with Pump Option — 17,256 18,855 — — 19,560 — — 22,342
MCHX Condenser Coil with Pump Option — 14,722 15,890 — — 16,356 — — 18,995
SHIPPING WEIGHT (lb) (Note 3)
Al-Cu Condenser Coil 12,785 14,004 14,943 13,627 14,667 15,715 15,893 17,117 18,316
Cu-Cu Condenser Coil 14,207 15,690 16,911 15,033 16,383 17,881 17,580 19,085 20,565
MCHX Condenser Coil 12,090 13,157 13,946 12,902 13,810 14,677 15,117 16,170 17,217
Al-Cu Condenser Coil with Pump Option — 15,169 16,415 — — 16,880 — — 19,481
Cu-Cu Condenser Coil with Pump Option — 16,856 18,383 — — 19,046 — — 21,730
MCHX Condenser Coil with Pump Option — 14,322 15,418 — — 15,842 — — 18,382
REFRIGERANT TYPE (Standard Evaporator) R-134a EXV Controlled System
Refrigerant Charge (lb) Ckt A/ Ckt B (RTPF) 195/205 213/223 231/241 253/187 276/210 294/228 238/248 266/276 284/294
Refrigerant Charge (lb) Ckt A/ Ckt B (MCHX) 130/140 135/145 140/150 175/135 185/145 190/150 160/170 175/185 180/190
REFRIGERANT TYPE (Brine Evaporator) R-134a EXV Controlled System
Refrigerant Charge (lb) Ckt A/ Ckt B (RTPF) 215/225 233/243 251/261 273/207 296/230 314/248 258/268 276/286 294/304
Refrigerant Charge (lb) Ckt A/ Ckt B (MCHX) 150/160 155/165 160/170 195/155 205/165 210/170 180/190 185/195 190/200
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2
Full Load Capacity Split Ckt A / Ckt B (Note 4) 50/50 50/50 50/50 60/40 60/40 60/40 50/50 50/50 50/50
Oil Charge (gal) Ckt A/Ckt B 5.5/5.5 5.5/5.5 5.5/5.5 6.0/5.5 6.0/5.5 6.0/5.5 6.0/6.0 6.0/6.0 6.0/6.0
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (gal.) 27 31 31 34 36 36 36 48 48
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300 300 300 300 300 300 300 300 300
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-Pass), Inlet and Outlet, Victaulic (in.) 5/5 6/6 6/6 6/6 6/6 6/6 6/6 8/8 8/8
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet, Victaulic (in.) 5/— 8/6 8/— 8/— 8/— 8/— 8/— 8/8 8/—
Fresh Water/Process Brine
3 Pass, Inlet and Outlet, Victaulic (in.) 5/5 5/5 5/5 6/6 6/6 6/6 6/6 8/6 8/6
Fresh Water/Comfort Brine
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Fresh Water
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Fans (Ckt A/ Ckt B) 5/5 6/6 7/7 6/4 7/5 8/6 6/6 7/7 8/8
Total Airflow (cfm) RTPF Coil 131,400 157,680 183,960 131,400 157,680 183,960 157,680 183,960 210,240
Total Airflow (cfm) MCHX Coil 145,000 174,000 203,000 145,000 174,000 203,000 174,000 203,000 232,000
CONDENSER COILS
No. Coils (Ckt A/ Ckt B) 5/5 6/6 7/7 6/4 7/5 8/6 6/6 7/7 8/8
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels,
Cu — Copper but no other options or accessories are included. The shipping
Al — Aluminum weight is equal to the operating weight (indicated above) minus
EXV — Electronic Expansion Valve the weight of the water in the evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a
RTPF — Round Tube/Plate Fin full load condition. The actual capacity split at most operating con-
ditions will not match these values.
NOTES: 5. The minimum capacity is less than 15% for units sized at full
capacity. Please use the chiller selection program to determine
1. More precise dimensions are available on the certified prints. actual minimum capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, 6. Standard-tier models without the variable speed condenser fan
but no other options or accessories are included. Selected options option have a maximum speed of 840 rpm.
and accessories will slightly alter the unit weight. See Fig. 25 for
the mounting weight detail.

85
Table 2 — Physical Data — English (cont)
30XV 275T-325T
UNIT 30XV WITH FLOODED EVAPORATOR 275 300 325
TIER (MODEL NO. POS. 10) S M H S M H S M H
CHASSIS DIMENSIONS (in.) (Note 1)
Length 298.7 345.7 392.7 345.7 392.7 439.7 392.7 439.7 486.7
Width 88.0
Height 98.9
OPERATING WEIGHT (lb) (Note 2)
Al-Cu Condenser Coil 16,660 17,582 18,600 17,582 18,679 19,670 18,679 19,757 20,832
Cu-Cu Condenser Coil 18,347 19,550 20,849 19,550 20,928 22,201 20,928 22,288 23,644
MCHX Condenser Coil 15,864 16,624 17,492 16,624 17,560 18,401 17,560 18,478 19,407
Al-Cu Condenser Coil with Pump Option — — 19,981 — 20,060 21,306 — 21,393 22,732
Cu-Cu Condenser Coil with Pump Option — — 22,230 — 22,309 23,837 — 23,924 25,543
MCHX Condenser Coil with Pump Option — — 18,873 — 18,941 20,037 — 20,114 21,306
SHIPPING WEIGHT (lb) (Note 3)
Al-Cu Condenser Coil 16,263 17,164 18,183 17,164 18,237 19,228 18,237 19,287 20,362
Cu-Cu Condenser Coil 17,950 19,132 20,432 19,132 20,486 21,759 20,486 21,818 23,174
MCHX Condenser Coil 15,467 16,207 17,074 16,207 17,118 17,959 17,118 18,008 18,937
Al-Cu Condenser Coil with Pump Option — — 19,348 — 19,402 20,648 — 20,707 22,046
Cu-Cu Condenser Coil with Pump Option — — 21,597 — 21,651 23,179 — 23,238 24,857
MCHX Condenser Coil with Pump Option — — 18,239 — 18,283 19,379 — 19,428 20,620
REFRIGERANT TYPE (Standard Evaporator) R-134a EXV Controlled System
Refrigerant Charge (lb) Ckt A/ Ckt B (RTPF) 248/258 271/281 289/299 271/281 294/304 312/322 294/304 317/327 335/340
Refrigerant Charge (lb) Ckt A/ Ckt B (MCHX) 170/180 180/190 185/195 180/190 190/200 195/205 190/200 200/210 205/210
REFRIGERANT TYPE (Brine Evaporator) R-134a EXV Controlled System
Refrigerant Charge (lb) Ckt A/ Ckt B (RTPF) 258/268 281/291 299/309 291/301 314/324 332/342 314/324 337/347 355/360
Refrigerant Charge (lb) Ckt A/ Ckt B (MCHX) 180/190 190/200 195/205 200/210 210/220 215/225 210/220 220/230 225/230
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2
Full Load Capacity Split Ckt A / Ckt B (Note 4) 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50
Oil Charge (gal), Ckt A / Ckt B 6.0/6.0 6.0/6.0 6.0/6.0 6.0/6.0 6.0/6.0 6.0/6.0 6.0/6.0 6.0/6.0 6.0/6.0
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (gal.) 48 50 50 50 53 53 53 56 56
Maximum Refrigerant Pressure (psig) 220 220 220 220 220 220 220 220 220
Maximum Water-Side Pressure (psig) 300 300 300 300 300 300 300 300 300
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-Pass), Inlet and Outlet, Victaulic (in.) 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet, Victaulic (in.) 8/— 8/— 8/— 8/— 8/8 8/— 8/— 8/— 8/—
Fresh Water/Process Brine
3 Pass, Inlet and Outlet, Victaulic (in.) 8/8 8/8 8/8 6/6 6/6 6/6 6/6 8/6 8/6
Fresh Water/Comfort Brine
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Fresh Water
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Fans (Ckt A / Ckt B) 6/6 7/7 8/8 7/7 8/8 9/9 8/8 9/9 10/10
Total Maximum Airflow (cfm) RTPF Coil 157,680 183,960 210,240 183,960 210,240 236,520 210,240 236,520 262,800
Total Maximum Airflow (cfm) MCHX Coil 174,000 203,000 232,000 203,000 232,000 261,000 232,000 261,000 290,000
CONDENSER COILS
No. Coils (Ckt A / Ckt B) 6/6 7/7 8/8 7/7 8/8 9/9 8/8 9/9 10/10
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels,
Cu — Copper but no other options or accessories are included. The shipping
Al — Aluminum weight is equal to the operating weight (indicated above) minus
EXV — Electronic Expansion Valve the weight of the water in the evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a
RTPF — Round Tube/Plate Fin full load condition. The actual capacity split at most operating con-
ditions will not match these values.
NOTES: 5. The minimum capacity is less than 15% for units sized at full
capacity. Please use the chiller selection program to determine
1. More precise dimensions are available on the certified prints. actual minimum capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, 6. Standard-tier models without the variable speed condenser fan
but no other options or accessories are included. Selected options option have a maximum speed of 840 rpm.
and accessories will slightly alter the unit weight. See Fig. 25 for
the mounting weight detail.

86
Table 2 — Physical Data — English (cont)
30XV 350T-500T
UNIT 30XV WITH 350 400 450 500
FLOODED EVAPORATOR
TIER (MODEL NO. POS. 10) S M H S M H S M H S M
CHASSIS DIMENSIONS (in.)
(Note 1)
Length 405.7 452.7 499.7 452.7 499.7 546.6 499.7 546.6 593.7 546.6 593.7
Width 88.0
Height 98.9
OPERATING WEIGHT (lb)
(Note 2)
Al-Cu Condenser Coil 21,746 23,580 24,510 25,010 26,140 27,069 26,140 27,938 29,012 27,938 29,247
Cu-Cu Condenser Coil 23,995 26,111 27,321 27,540 28,951 30,162 28,951 31,030 — 31,030 —
MCHX Condenser Coil 20,672 22,326 23,104 23,760 24,729 25,507 24,729 26,356 27,221 26,356 27,337
SHIPPING WEIGHT (lb)
(Note 3)
Al-Cu Condenser Coil 21,232 23,034 23,963 24,463 25,567 26,496 25,567 27,241 28,315 27,241 28,510
Cu-Cu Condenser Coil 23,481 25,564 26,774 26,993 28,379 29,589 28,379 30,334 — 30,334 —
MCHX Condenser Coil 20,158 21,779 22,557 23,213 24,156 24,935 24,156 25,660 26,525 25,660 26,600
REFRIGERANT TYPE (Standard R-134a EXV Controlled System
Evaporator)
Refrigerant Charge (lb) 367/286 405/329 423/347 382/382 405/405 423/423 405/405 438/438 456/456 438/438 481/481
Ckt A/ Ckt B (RTPF)
Refrigerant Charge (lb) 250/195 275/225 280/230 265/265 275/275 280/280 275/275 295/295 300/300 295/295 325/325
Ckt A/ Ckt B (MCHX)
REFRIGERANT TYPE R-134a EXV Controlled System
(Brine Evaporator)
Refrigerant Charge (lb) 387/326 405/344 423/362 392/392 410/410 428/428 425/425 443/443 461/461 458/458 476/476
Ckt A/ Ckt B (RTPF)
Refrigerant Charge (lb) 270/235 275/240 280/245 275/275 280/280 285/285 295/295 300/300 305/305 315/315 320/320
Ckt A/ Ckt B (MCHX)
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2 2 2
Full Load Capacity Split 60/40 60/40 60/40 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50
Ckt A / Ckt B (Note 4)
Oil Charge (gal), 7.5/6.0 7.5/6.0 7.5/6.0 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5
Ckt A / Ckt B
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (gal.) 62 66 66 66 69 69 69 83 83 83 88
Maximum Refrigerant Pressure 220 220 220 220 220 220 220 220 220 220 220
(psig)
Maximum Water-Side 300 300 300 300 300 300 300 300 300 300 300
Pressure (psig)
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-pass), Inlet and


Outlet, Victaulic (in.) 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet,
Victaulic (in.) 8/— 8/— 8/— 8/— 8/8 8/— 8/— 8/— 8/— 8/— 8/8
Fresh Water/Process Brine
3 Pass, Inlet and Outlet,
Victaulic (in.) 8/6 6/6 6/6 6/8 6/8 6/8 6/6 6/6 6/6 6/6 6/6
Fresh Water/Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Fans (Ckt A / Ckt B) 9/7 10/8 11/9 9/9 10/10 11/11 10/10 11/11 12/12 11/11 12/12
Total Maximum Airflow (cfm) 210,240 236,520 262,800 236,520 262,800 289,080 262,800 289,080 315,360 289,080 315,360
RTPF Coil
Total Maximum Airflow (cfm) 232,000 261,000 290,000 261,000 290,000 319,000 290,000 319,000 348,000 319,000 348,000
MCHX Coil
CONDENSER COILS
No. Coils (Ckt A / Ckt B) 9/7 10/8 11/9 9/9 10/10 11/11 10/10 11/11 12/12 11/11 12/12
LEGEND 4. The capacity split is indicative of both compressors operating at a full load
Cu — Copper condition. The actual capacity split at most operating conditions will not
Al — Aluminum match these values.
EXV — Electronic Expansion Valve 5. The minimum capacity is less than 15% for units sized at full capacity.
MCHX — Microchannel Heat Exchanger Please use the chiller selection program to determine actual minimum
RTPF — Round Tube/Plate Fin capacity values.
6. Standard-tier models without the variable speed condenser fan option have
a maximum speed of 840 rpm.
NOTES:
1. More precise dimensions are available on the certified prints.
2. Unit operating weight includes the base unit plus coil trim panels, but no
other options or accessories are included. Selected options and accessories
will slightly alter the unit weight. See Fig. 25 for the mounting weight detail.
3. Unit shipping weight includes the base unit plus coil trim panels, but no other
options or accessories are included. The shipping weight is equal to the
operating weight (indicated above) minus the weight of the water in the
evaporator.

87
Table 3 — Physical Data — SI
30XV 140T-180T
UNIT 30XV WITH FLOODED EVAPORATOR 140 160 180
TIER (MODEL NO. POS. 10) S M H S M H S M H
CHASSIS DIMENSIONS (mm) (Note 1)
Length 5273 5273 6467 5273 6467 7661 5273 6467 7661
Width 2236
Height 2513
OPERATING WEIGHT (kg) (Note 2)
Al-Cu Condenser Coil 5261 5298 5769 5304 5865 6327 5396 5889 6391
Cu-Cu Condenser Coil 5771 5808 6406 5814 6503 7092 5906 6540 7129
MCHX Condenser Coil 5039 5069 5469 5069 5554 5948 5154 5587 5980
Al-Cu Condenser Coil with Pump Option — — 6254 — 6350 6954 — 6374 7018
Cu-Cu Condenser Coil with Pump Option — — 6892 — 6988 7719 — 7025 7756
MCHX Condenser Coil with Pump Option — — 5954 — 6040 6574 — 6072 6607
SHIPPING WEIGHT (kg) (Note 3)
Al-Cu Condenser Coil 5183 5213 5684 5219 5770 6232 5301 5786 6288
Cu-Cu Condenser Coil 5693 5723 6321 5729 6407 6997 5811 6437 7026
MCHX Condenser Coil 4961 4984 5384 4984 5459 5852 5058 5484 5877
Al-Cu Condenser Coil with Pump Option — — 6104 — 6190 6760 — 6206 6817
Cu-Cu Condenser Coil with Pump Option — — 6741 — 6827 7525 — 6857 7555
MCHX Condenser Coil with Pump Option — — 5804 — 5879 6381 — 5904 6406
REFRIGERANT TYPE (Standard Evaporator) R-134a EXV Controlled System
Refrigerant Charge (kg) Ckt A/ Ckt B (RTPF) 69/71 73/75 82/84 73/80 86/91 94/99 78/83 88/93 97/101
Refrigerant Charge (kg) Ckt A/ Ckt B (MCHX) 45/48 50/52 52/54 50/57 57/61 59/64 54/59 59/64 61/66
REFRIGERANT TYPE (Brine Evaporator) R-134a EXV Controlled System
Refrigerant Charge (kg) Ckt A/ Ckt B (RTPF) 76/78 80/83 88/91 85/89 93/98 101/106 87/92 95/100 103/108
Refrigerant Charge (kg) Ckt A/ Ckt B (MCHX) 52/54 57/59 59/61 61/66 64/68 66/70 64/68 66/70 68/73
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2
Full Load Capacity Split Ckt A / Ckt B (Note 4) 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50
Oil Charge (L), Ckt A / Ckt B 20.8/20.8 20.8/20.8 20.8/20.8 20.8/20.8 20.8/20.8 20.8/20.8 20.8/20.8 20.8/20.8 20.8/20.8
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (L) 78 85 85 85 95 95 95 103 103
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068 2068 2068
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-Pass), Inlet and Outlet, Victaulic (in.) 5/5 5/5 5/5 5/5 5/5 5/5 5/5 5/5 5/5
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet, Victaulic (in.) Fresh 5/— 5/— 5/— 5/— 5/6 5/— 5/— 5/— 5/—
Water/Process Brine
3 Pass, Inlet and Outlet, Victaulic (in.) Fresh 4/4 4/4 4/4 4/4 5/4 5/4 5/4 5/4 5/4
Water/Comfort Brine
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Fresh Water
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 5/5 5/5 5/5 5/5 5/5 5/5 6/6 6/6 6/6
Victaulic (in.) Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (r/s) 19 19 19 19 19 19 19 19 19
No. Fans (Ckt A/ Ckt B) 4/4 4/4 5/5 4/4 5/5 6/6 4/4 5/5 6/6
Total Airflow (L/s) RTPF Coil 49 406 49 406 61 758 49 406 61 758 74 110 49 406 61 758 74 110
Total Airflow (L/s) MCHX Coil 54 520 54 520 68 150 54 520 68 150 81 780 54 520 68 150 81 780
CONDENSER COILS
No. Coils (Ckt A/ Ckt B) 4/4 4/4 5/5 4/4 5/5 6/6 4/4 5/5 6/6
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels, but no other
Cu — Copper options or accessories are included. The shipping weight is equal to the
Al — Aluminum operating weight (indicated above) minus the weight of the water in the
EXV — Electronic Expansion Valve evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a full load
RTPF — Round Tube/Plate Fin condition. The actual capacity split at most operating conditions will not
match these values.
5. The minimum capacity is less than 15% for units sized at full capacity.
NOTES: Please use the chiller selection program to determine actual minimum
1. More precise dimensions are available on the certified prints. capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, but no 6. Standard-tier models without the variable speed condenser fan option have
other options or accessories are included. Selected options and accessories a maximum speed of 14 r/s.
will slightly alter the unit weight. See Fig. 25 for the mounting weight detail.

88
Table 3 — Physical Data — SI (cont)
30XV 200T-250T
UNIT 30XV WITH FLOODED EVAPORATOR 200 225 250
TIER (MODEL NO. POS. 10) S M H S M H S M H
CHASSIS DIMENSIONS (mm) (Note 1)
Length 6467 7661 8855 6392 7586 8780 7586 8780 9974
Width 2236
Height 2513
OPERATING WEIGHT (kg) (Note 2)
Al-Cu Condenser Coil 5902 6468 6894 6310 6788 7263 7344 7944 8488
Cu-Cu Condenser Coil 6547 7233 7787 6947 7566 8246 8109 8837 9508
MCHX Condenser Coil 5587 6084 6442 5981 6399 6793 6992 7514 7989
Al-Cu Condenser Coil with Pump Option — — 7660 — — 7890 — — 9114
Cu-Cu Condenser Coil with Pump Option — — 8553 — — 8872 — — 10134
MCHX Condenser Coil with Pump Option — — 7208 — — 7419 — — 8616
SHIPPING WEIGHT (kg) (Note 3)
Al-Cu Condenser Coil 5799 6352 6778 6181 6653 7128 7209 7764 8308
Cu-Cu Condenser Coil 6444 7117 7671 6819 7431 8110 7974 8657 9328
MCHX Condenser Coil 5484 5968 6326 5852 6264 6657 6857 7334 7810
Al-Cu Condenser Coil with Pump Option — — 7446 — — 7656 — — 8836
Cu-Cu Condenser Coil with Pump Option — — 8339 — — 8639 — — 9856
MCHX Condenser Coil with Pump Option — — 6993 — — 7186 — — 8338
REFRIGERANT TYPE (Standard Evaporator) R-134a EXV Controlled System
Refrigerant Charge (kg) Ckt A/ Ckt B (RTPF) 89/93 97/101 105/109 115/85 125/95 133/103 108/112 121/125 129/133
Refrigerant Charge (kg) Ckt A/ Ckt B (MCHX) 59/64 61/66 64/68 79/61 84/61 86/68 73/77 79/84 82/86
REFRIGERANT TYPE (Brine Evaporator) R-134a EXV Controlled System
Refrigerant Charge (kg) Ckt A/ Ckt B (RTPF) 98/102 106/110 114/118 124/94 134/104 142/112 117/122 125/130 133/138
Refrigerant Charge (kg) Ckt A/ Ckt B (MCHX) 68/73 70/75 73/77 88/70 93/75 95/77 82/86 84/88 86/91
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2
Full Load Capacity Split Ckt A / Ckt B (Note 4) 50/50 50/50 50/50 60/40 60/40 60/40 50/50 50/50 50/50
Oil Charge (L) Ckt A / Ckt B 20.8/20.8 20.8/20.8 20.8/20.8 22.7/20.8 22.7/20.8 22.7/20.8 22.7/22.7 22.7/22.7 22.7/22.7
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (L) 103 116 116 128 135 135 135 180 180
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068 2068 2068
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-pass), Inlet and Outlet, Victaulic (in.) Fresh 5/5 6/6 6/6 6/6 6/6 6/6 6/6 8/8 8/8
Water/Comfort Brine
1 Pass, Inlet and Outlet, Victaulic (in.) Fresh Water/ 5/— 8/6 8/— 8/— 8/— 8/— 8/— 8/8 8/—
Process Brine
3 Pass, Inlet and Outlet, Victaulic (in.) Fresh Water/ 5/5 5/5 5/5 6/6 6/6 6/6 6/6 8/6 8/6
Comfort Brine
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Fresh Water
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (r/s) 19 19 19 19 19 19 19 19 19
No. Fans (Ckt A/ Ckt B) 5/5 6/6 7/7 6/4 7/5 8/6 6/6 7/7 8/8
Total Airflow (L/s) RTPF Coil 61 758 74 110 86 461 61 758 74 110 86 461 74 110 86 461 98 813
Total Airflow (L/s) MCHX Coil 68 150 81 780 95 410 68 150 81 780 95 410 81 780 95 410 109 040
CONDENSER COILS
No. Coils (Ckt A/ Ckt B) 5/5 6/6 7/7 6/4 7/5 8/6 6/6 7/7 8/8
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels, but no other
Cu — Copper options or accessories are included. The shipping weight is equal to the
Al — Aluminum operating weight (indicated above) minus the weight of the water in the
EXV — Electronic Expansion Valve evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a full load
RTPF — Round Tube/Plate Fin condition. The actual capacity split at most operating conditions will not
match these values.
5. The minimum capacity is less than 15% for units sized at full capacity.
NOTES: Please use the chiller selection program to determine actual minimum
1. More precise dimensions are available on the certified prints. capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, but no 6. Standard-tier models without the variable speed condenser fan option have
other options or accessories are included. Selected options and accessories a maximum speed of 14 r/s.
will slightly alter the unit weight. See Fig. 25 for the mounting weight detail.

89
Table 3 — Physical Data — SI (cont)
30XV 275T-325T
UNIT 30XV WITH FLOODED EVAPORATOR 275 300 325
TIER (MODEL NO. POS. 10) S M H S M H S M H
CHASSIS DIMENSIONS (mm) (Note 1)
Length 7586 8780 9974 8780 9974 11,168 9974 11,168 12,362
Width 2236
Height 2513
OPERATING WEIGHT (kg) (Note 2)
Al-Cu Condenser Coil 7557 7975 8437 7975 8473 8922 8473 8962 9449
Cu-Cu Condenser Coil 8322 8868 9457 8868 9493 10 070 9493 10 109 10 725
MCHX Condenser Coil 7196 7541 7934 7541 7965 8346 7965 8381 8803
Al-Cu Condenser Coil with Pump Option — — 9063 — 9099 9664 — 9704 10 311
Cu-Cu Condenser Coil with Pump Option — — 10 084 — 10 119 10 812 — 10 852 11 586
MCHX Condenser Coil with Pump Option — — 8561 — 8592 9089 — 9123 9664
SHIPPING WEIGHT (kg) (Note 3)
Al-Cu Condenser Coil 7377 7786 8248 7786 8272 8722 8272 8749 9236
Cu-Cu Condenser Coil 8142 8678 9268 8678 9292 9870 9292 9896 10 511
MCHX Condenser Coil 7016 7351 7745 7351 7765 8146 7765 8168 8590
Al-Cu Condenser Coil with Pump Option — — 8776 — 8800 9366 — 9393 10 000
Cu-Cu Condenser Coil with Pump Option — — 9796 — 9821 10 514 — 10 540 11 275
MCHX Condenser Coil with Pump Option — — 8273 — 8293 8790 — 8812 9353
REFRIGERANT TYPE (Standard Evaporator) R-134a EXV Controlled System
Refrigerant Charge (kg) Ckt A/ Ckt B (RTPF) 112/117 123/127 131/136 123/127 133/138 142/146 133/138 144/148 152/154
Refrigerant Charge (kg) Ckt A/ Ckt B (MCHX) 77/82 82/86 84/88 82/86 86/91 88/93 86/91 91/95 93/95
REFRIGERANT TYPE (Brine Evaporator) R-134a EXV Controlled System
Refrigerant Charge (kg) Ckt A/ Ckt B (RTPF) 117/122 127/132 136/140 132/137 142/147 151/155 142/147 153/157 161/163
Refrigerant Charge (kg) Ckt A/ Ckt B (MCHX) 82/86 86/91 88/93 91/95 95/100 98/102 95/100 100/104 102/104
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2
Full Load Capacity Split Ckt A / Ckt B (Note 4) 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50
Oil Charge (Liters), Ckt A / Ckt B 22.7/22.7 22.7/22.7 22.7/22.7 22.7/22.7 22.7/22.7 22.7/22.7 22.7/22.7 22.7/22.7 22.7/22.7
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (L) 180 189 189 189 201 201 201 213 213
Maximum Refrigerant Pressure (kPa) 1517 1517 1517 1517 1517 1517 1517 1517 1517
Maximum Water-Side Pressure (kPa) 2068 2068 2068 2068 2068 2068 2068 2068 2068
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-pass), Inlet and Outlet, Victaulic (in.) 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet, Victaulic (in.) Fresh 8/— 8/— 8/— 8/— 8/8 8/— 8/— 8/— 8/—
Water/Process Brine
3 Pass, Inlet and Outlet, Victaulic (in.) Fresh 8/8 8/8 8/8 6/6 6/6 6/6 6/6 8/6 8/6
Water/Comfort Brine
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Fresh Water
Std (2-Pass) & 3-Pass w/Pump, Inlet and Outlet, 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/6
Victaulic (in.) Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (r/s) 19 19 19 19 19 19 19 19 19
No. Fans (Ckt A / Ckt B) 6/6 7/7 8/8 7/7 8/8 9/9 8/8 9/9 10/10
Total Airflow (L/s) RTPF COIL 74 110 86 461 98 813 86 461 98 813 111 164 98 813 111 164 123 516
Total Airflow (L/s) MCHX COIL 81 780 95 410 109 040 95 410 109 040 122 670 109 040 122 670 136 300
CONDENSER COILS
No. Coils (Ckt A / Ckt B) 6/6 7/7 8/8 7/7 8/8 9/9 8/8 9/9 10/10
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels, but no other
Cu — Copper options or accessories are included. The shipping weight is equal to the
Al — Aluminum operating weight (indicated above) minus the weight of the water in the
EXV — Electronic Expansion Valve evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a full load
RTPF — Round Tube/Plate Fin condition. The actual capacity split at most operating conditions will not
match these values.
5. The minimum capacity is less than 15% for units sized at full capacity.
NOTES: Please use the chiller selection program to determine actual minimum
1. More precise dimensions are available on the certified prints. capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, but no 6. Standard-tier models without the variable speed condenser fan option have
other options or accessories are included. Selected options and accessories a maximum speed of 14 r/s.
will slightly alter the unit weight. See Fig. 25 for the mounting weight detail.

90
Table 3 — Physical Data — SI (cont)
30XV 350T-500T
UNIT 30XV WITH 350 400 450 500
FLOODED EVAPORATOR
TIER (MODEL NO. POS. 10) S M H S M H S M H S M
CHASSIS DIMENSIONS (mm)
(Note 1)
Length 10 304 11 498 12 692 11 498 12 692 13 883 12 692 13 883 15 080 13 883 15 080
Width 2236
Height 2513
OPERATING WEIGHT (kg)
(Note 2)
Al-Cu Condenser Coil 9864 10 696 11 117 11 344 11 857 12 278 11 857 12 672 13 159 12 672 13 266
Cu-Cu Condenser Coil 10 884 11 844 12 393 12 492 13 132 13 681 13 132 14 075 — 14 075 —
MCHX Condenser Coil 9377 10 127 10 480 10 777 11 217 11 570 11 217 11 955 12 347 11 955 12 400
SHIPPING WEIGHT (kg)
(Note 3)
Al-Cu Condenser Coil 9631 10 448 10 869 11 096 11 597 12 019 11 597 12 357 12 844 12 357 12 932
Cu-Cu Condenser Coil 10 651 11 596 12 145 12 244 12 872 13 421 12 872 13 759 — 13 759 —
MCHX Condenser Coil 9144 9879 10 232 10 529 10 957 11 310 10 957 11 639 12 032 11 639 12 066
REFRIGERANT TYPE (Standard R-134a EXV Controlled System
Evaporator)
Refrigerant Charge (kg) 166/130 184/149 192/157 173/173 184/184 192/192 184/184 199/199 207/207 199/199 218/218
Ckt A/ Ckt B (RTPF)
Refrigerant Charge (kg) 113/88 125/102 127/104 120/120 125/125 127/127 125/125 134/134 136/136 134/134 147/147
Ckt A/ Ckt B (MCHX)
REFRIGERANT TYPE (Brine R-134a EXV Controlled System
Evaporator)
Refrigerant Charge (kg) 176/148 184/156 192/164 178/178 186/186 194/194 193/193 201/201 209/209 208/208 216/216
Ckt A/ Ckt B (RTPF)
Refrigerant Charge (kg) 122/107 125/109 127/111 125/125 127/127 129/129 134/134 136/136 138/138 143/143 145/145
Ckt A/ Ckt B (MCHX)
COMPRESSOR Semi-Hermetic Twin Rotary Screw
Quantity 2 2 2 2 2 2 2 2 2 2 2
Full Load Capacity Split 60/40 60/40 60/40 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50
Ckt A / Ckt B (Note 4)
Oil Charge (L), Ckt A / Ckt B 28.4/22.7 28.4/22.7 28.4/22.7 28.4/28.4 28.4/28.4 28.4/28.4 28.4/28.4 28.4/28.4 28.4/28.4 28.4/28.4 28.4/28.4
Minimum Capacity (%) (Note 5) <15 <15 <15 <15 <15 <15 <15 <15 <15 <15 <15
EVAPORATOR
Net Fluid Volume (L) 233 248 248 248 260 260 260 316 316 316 334
Maximum Refrigerant 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517
Pressure (kPa)
Maximum Water-Side 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068
Pressure (kPa)
WATER CONNECTIONS
Drain (NPT, in.) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Standard (2-pass), Inlet and


Outlet, Victaulic (in.) 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8 8/8
Fresh Water/Comfort Brine
1 Pass, Inlet and Outlet,
Victaulic (in.) 8/— 8/— 8/— 8/— 8/8 8/— 8/— 8/— 8/— 8/— 8/8
Fresh Water/Process Brine
3 Pass, Inlet and Outlet,
Victaulic (in.) 8/6 6/6 6/6 6/8 6/8 6/8 6/6 6/6 6/6 6/6 6/6
Fresh Water/Comfort Brine
CONDENSER FANS (Note 6) Shrouded Axial Type, Vertical Discharge
Maximum Fan Speed (r/s) 19 19 19 19 19 19 19 19 19 19 19
No. Fans (Ckt A / Ckt B) 9/7 10/8 11/9 9/9 10/10 11/11 10/10 11/11 12/12 11/11 12/12
Total Airflow (L/s) RTPF COIL 98 813 111 164 123 516 111 164 123 516 135 868 123 516 135 868 148 219 135 868 148 219
Total Airflow (L/s) MCHX COIL 109 040 122 670 136 300 122 670 136 300 149 930 136 300 149 930 163 560 149 930 163 560
CONDENSER COILS
No. Coils (Ckt A / Ckt B) 9/7 10/8 11/9 9/9 10/10 11/11 10/10 11/11 12/12 11/11 12/12
LEGEND 3. Unit shipping weight includes the base unit plus coil trim panels, but no other
Cu — Copper options or accessories are included. The shipping weight is equal to the
Al — Aluminum operating weight (indicated above) minus the weight of the water in the
EXV — Electronic Expansion Valve evaporator.
MCHX — Microchannel Heat Exchanger 4. The capacity split is indicative of both compressors operating at a full load
RTPF — Round Tube/Plate Fin condition. The actual capacity split at most operating conditions will not
match these values.
5. The minimum capacity is less than 15% for units sized at full capacity.
NOTES: Please use the chiller selection program to determine actual minimum
1. More precise dimensions are available on the certified prints. capacity values.
2. Unit operating weight includes the base unit plus coil trim panels, but no 6. Standard-tier models without the variable speed condenser fan option have
other options or accessories are included. Selected options and accessories a maximum speed of 14 r/s.
will slightly alter the unit weight. See Fig. 25 for the mounting weight detail.

91
EXPORT SHIPPING RAILS suspension point so that angle from horizontal is not less than
Units with the export packaging option will include steel shipping 45 degrees. Raise and set unit down carefully. See Fig. 27-30 for
rails. These should be removed prior to mounting the unit. There rigging centers of gravity.
are mounting bolts on the outside of the base frame and in the low- For shipping, some domestic units and all export units are
er top section of the frame. If sound enclosure is included, the top mounted on steel skids under entire base of unit. Skid can be re-
cover may need to be removed to access all of the bolts. The bag moved before unit is moved to installation site. Lift the unit from
retainer rail is used to secure the bag for shipping. These may be above to remove skid. See Fig. 27-30 for rigging centers of grav-
removed before or after mounting the unit. (See Fig. 26.) ity. If the unit was shipped with a shipping bag, the bag must be
removed to gain access to the rigging holes in the base rail.
RIGGING UNIT
If overhead rigging is not available, the unit can be moved on roll-
The 30XV units with Greenspeed® intelligence are designed for ers or dragged. When unit is moved on rollers, the unit skid, if
overhead rigging and it is important that this method be used. equipped, must be removed. To lift the unit, use jacks at the rig-
Holes are provided in frame base channels, marked for rigging ging points. Use a minimum number of rollers to distribute the
(see rigging label on unit). Field-supplied shackles are required to load such that the rollers are no more than 6 ft (1.8 m) apart. If the
facilitate lifting. Secure the shackles to the base rails at the points unit is to be dragged, lift the unit as described above, and place
noted on the rigging label.(See Fig. 27-30) unit on a pad. Apply moving force to the pad, and not the unit.
Do not use a forklift truck to move the units. When in its final location, raise the unit and remove the pad. If the
Use spreader bars to keep cables or chains clear of unit sides. As unit was shipped with protection, it must be removed before start-
further protection, plywood sheets may be placed against sides up. The shipping bag for export units must be removed before
of unit, behind cables or chains. Run cables or chains to a central start-up.

BAG RETAINER RAIL

EXPORT SHIPPING RAIL

EXPORT SKID BOLTS

BAG RETAINER RAIL

BAG RETAINER BOLTS

EXPORT SKID BOLTS

EXPORT SKID

Fig. 26 — Export Shipping Rails

92
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING. DO NOT FORK THESE UNITS IF NO SKID IS SUPPLIED.

NOTE:
1. 1.50 dia (38.1mm) lifting holes provided for field-supplied clevis.
2. Rig with a minimum of 25 ft (7620mm) length chain or cables.
3. If central lifting point is used, it must be a minimum of 13 ft (3962mm) above the top of the unit.
4. Spreader bars made from steel or double nailed, and notched 2x6s approximately 8 ft (2438mm) long, must be placed just above the top of the unit and coils.
5. If overhead rigging is not available, the unit can be moved on roller or dragged. When unit is moved on roller, the unit steel skid, if equipped, must be removed.
To lift the unit, use jacks at rigging points. Use a minimum of one roller every 6 ft (1829mm) to distribute the load. If the unit is to be dragged, lift the unit as
described above, and place unit on a pad. Apply moving force to the pad, not the unit. When in its final location, raise the unit and remove the pad.
6. Check the unit model number, position 11 to determine the unit weight as per condenser option.
7. Check the bill of the lading to determine shipping weight of the unit.

Max Max Max Max Max Max


Shipping Wt Shipping Wt Shipping Wt Shipping Wt Shipping Wt Shipping Wt
Center of Gravity
w/o with w/o with w/o with
Packaging Packaging Packaging Packaging Packaging Packaging
Model Lifting Holes
Model Number Model Model Model Model Model Model
Number Position number number number number number number
position position position position position position B
10 C
11= 4,5 11= 4,5 11= 1,2 11= 1,2 11= 0,3 11= 0,3

M CHX * MCHX* Al/CU** Al/CU** CU/CU*** CU/CU*** A1 A2 A3 A4 A5 A6 A7 A8 A9 MCHX* AL/CU** CU/CU***


lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm
S 10937 4961 12161 5516 16.1 409 7 8. 0 19 82 78. 0 1 982 92.5 2349 92.5 2350 92.7 2354 45.6 1158
30XVA140 M 10987 4984 12211 5539 11492 5213 12717 5768 12617 5723 13905 6307 16.1 409 78.0 1982 78.0 1982 92.5 2350 92.6 2352 92.7 2355 45.6 1157

H 11870 5384 13217 5995 12530 5684 13878 6295 13936 6321 15347 6962 16.1 409 78.0 1982 78.0 1982 47.0 1194 103.0 2616 103.8 2636 105.2 2673 45.7 1162

S 10987 4984 12211 5539 11506 5219 12731 5775 12631 5729 13919 6314 16.1 409 78.0 1982 78.0 1982 91.9 2335 92.0 2337 92.2 2342 45.6 1157
30XVA160 M 12035 5459 13382 6070 12720 5770 14068 6381 14126 6407 15537 7048 16.1 409 78.0 1982 78.0 1982 102.4 2602 103.3 2623 104.7 2660 45.7 1161

H 12902 5852 14356 6512 13739 6232 15193 6891 15425 6997 16943 7685 16.1 409 78.0 1982 78.0 1982 47.0 1194 115.2 2927 116.8 2968 119.6 3037 45.8 1163

S 11152 5059 12376 5614 11686 5301 12911 5856 12811 5811 14099 6395 16.1 409 78.0 1982 78.0 1982 92.4 2348 92.5 2350 92.7 2353 45.5 1156
30XVA180 M 12090 5484 13437 6095 12755 5786 14103 6397 14191 6437 15602 7077 16.1 409 78.0 1982 78.0 1982 47.0 1194 103.4 2627 104.2 2647 105.6 2682 45.7 1161

H 12957 5877 14411 6537 13864 6289 15318 6948 15490 7026 17008 7715 16.1 4 09 78 . 0 198 2 7 8.0 1982 32.0 813 62.0 15 75 115 .4 2932 117.1 2973 119.8 3042 45.8 1163

S 12090 5484 13437 6095 12785 5799 14133 6411 14207 6444 15618 7084 16.1 409 78.0 1982 78.0 1982 102.7 2609 103.6 2630 105.0 2667 45.7 1161
30XVA200 M 13157 5968 14611 6628 14004 6352 15458 7012 15690 7117 17208 7806 16.1 409 78.0 1982 78.0 1982 47.0 1194 115.4 2932 117.0 2972 119.7 3040 45.8 1162

H 13946 6326 15557 7057 14943 6778 16555 7509 16911 7671 18587 8431 16.1 409 7 8.0 1982 78 . 0 1982 32.0 8 13 62.0 1575 1 28.6 32 6 7 131.1 3330 135.1 3431 45.9 1165

S 12902 5852 14535 6593 13627 6181 15261 6922 15033 6819 16794 7618 16.1 409 62.0 1575 32.0 813 109.0 2769 124.7 3166 124.3 3157 123.6 3140 46.7 1187
30XVA225 M 13810 6264 15568 7062 14667 6653 16426 7451 16383 7431 18269 8287 16.1 409 62 .0 157 5 32 .0 813 109.0 27 6 9 47. 0 119 4 1 34 .4 3 41 4 134 .8 3424 135.5 3441 46.8 1189

H 14677 6657 16541 7503 15715 7128 17578 7974 17881 8111 19872 9014 16.1 409 62. 0 1 57 5 32. 0 81 3 10 9.0 2 7 69 32. 0 8 13 62.0 1 5 75 14 5.8 3 7 04 1 47. 0 3733 149.0 3784 46.8 1189

S 15117 6857 16979 7702 1 5 893 7209 17756 8054 17580 7974 19571 8877 16.1 409 6 2.0 1575 3 2. 0 81 3 109.0 2769 4 7 .0 1 194 137.7 3 4 97 13 7. 9 3502 138.2 3510 45.4 1152

*30XVA250
Condenser
M
coil (MCHX): Microchannel (MCHX) Design
16170 7335 18156 8235 17117 7764 19103 8665 19085 8657 21263 9645 16.1 4 09 62. 0 1 575 32 .0 813 109.0 2769 4 7. 0 1194 47.2 1 200 1 48. 8 3 779 149.9 3809 151.3 3843 45.5 1155

**Condenser
H
coil (Al/CU): Aluminum fins/Copper Tubing
17217 7810 19309 8758 18316 8308 20408 9257 20565 9328 22849 10364 16.1 40 9 6 2.0 15 75 3 2.0 81 3 1 09 .0 2 76 9 47 .0 1194 32.0 8 13 62.0 15 75 1 6 0.8 408 3 162.6 4130 165.5 4203 45.6 1157

***Condenser
S 1coil (CU/CU):
5467 7 016 17329 786Copper
1 16263 737fins/Copper
7 18126 8222 1795Tubing
0 8142 19941 9045 16.1 40 9 62 .0 1 57 5 32. 0 81 3 1 09.0 2 7 69 47.0 119 4 1 38.7 35 2 2 1 39. 2 3535 139.0 3531 45.4 1154
30XVA275 M 16207 7351 18193 8252 17164 7786 19150 8687 19132 8678 21246 9637 16.1 409 6 2.0 1 5 75 3 2.0 81 3 109.0 2 76 9 47 .0 1194 47.2 12 0 0 1 48.7 37 7 8 149 .9 3808 151.3 3842 45.6 1157

H 17074 7745 19166 8694 18183 8248 20275 9197 20432 9268 22716 10304 16.1 40 9 62 . 0 15 75 32 . 0 81 3 1 09. 0 2 769 47.0 11 94 813 6 2. 0 1575 1 60.7 4 081 162.5 4128 165.4 4201 45.6 1159

S 16207 7351 18193 8252 17164 7786 19150 8687 19132 8678 21246 9637 16.1 4 09 6 2 .0 15 75 32. 0 81 3 1 0 9.0 2 7 69 47.0 119 4 47 . 2 1200 148.9 3783 150 . 1 3812 151.4 3846 45.6 1157
30XVA300 M 17118 7765 19210 8714 18237 8272 20329 9221 20486 9292 22770 10328 16.1 409 62. 0 1 57 5 32. 0 81 3 10 9.0 2 7 69 47.0 119 4 3 2.0 81 3 62.0 157 5 1 61. 3 40 9 8 163 .2 4144 165.9 4215 45.7 1162

H 17959 8146 20208 9166 19228 8722 21478 9742 21759 9870 24200 10977 16.1 4 09 62.0 15 75 3 2. 0 81 3 109.0 2769 4 7 .0 1 194 32.0 813 109 . 0 276 9 17 4.3 4 4 26 1 76. 8 4491 181.1 4599 45.8 1164

S 17118 7765 19210 8714 18237 8272 20329 9221 20486 9292 22770 10328 16.1 4 09 62. 0 1 575 32 .0 813 109 .0 2769 47 . 0 1194 32.0 813 6 2. 0 1575 160.4 40 75 16 2. 3 4123 165.2 4196 45.6 1157
30XVA325 M 18008 8168 20257 9189 19287 8749 21537 9769 21818 9896 24259 11004 16.1 409 62 .0 15 7 5 32 .0 8 13 10 9.0 2 76 9 47 .0 1 194 3 2.0 8 13 109 .0 27 69 174.4 4429 176 .9 4494 181.2 4601 45.8 1164

H 18937 8590 21315 9668 20362 9236 22740 10315 23174 10512 25744 11677 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 32.0 813 78.0 1982 78.0 1982 188.4 4786 191.7 4869 197.3 5012 45.9 1166

NOTE:
For unit sizes 30XV140-325 with pump option see Fig. 28.

Fig. 27 — Unit Rigging Label Detail 30XV140-325

93
Max Shipping Max Shipping Max Shipping
Max Shipping Wt Max Shipping Wt Max Shipping Wt
Wt w/o Wt with Wt with Center of Gravity
with Packaging w/o Packaging w/o Packaging
Packaging Packaging Packaging
Model Lifting Holes
Model Number Model number Model number Model number Model number Model number Model number
Number Position position position position position position position
11=4,5 11=4,5 11=1,2 11=1,2 11=0,3 11=0,3
B
10 C
12=4 thru P 12=4 thru P 12=4 thru P 12=4 thru P 12=4 thru P 12=4 thru P

MCHX* MCHX* Al/CU** Al/CU** CU/CU*** CU/CU*** A1 A2 A3 A4 A5 A6 A7 A8 A9 MCHX* AL/CU** CU/CU***


lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm
30XVA140 H 12796 5804 14143 6415 13456 6104 14804 6715 14862 6741 16273 7381 16.1 409 78.0 1982 78.0 1982 47.0 1194 103.0 2616 103.8 2636 105.2 2673 45.7 1162

M 12961 5879 14308 6490 13646 6190 14994 6801 15052 6827 16463 7468 16.1 409 78.0 1982 78.0 1982 102.4 2602 103.3 2623 104.7 2660 45.7 1161
30XVA160
H 14067 6381 15521 7040 14904 6760 16358 7420 16591 7525 18109 8214 16.1 409 78.0 1982 78.0 1982 47.0 1194 115.2 2927 116.8 2968 119.6 3037 45.8 1163
M 13016 5904 14363 6515 13681 6206 15029 6817 15117 6857 16528 7497 16.1 409 78.0 1982 78.0 1982 47.0 1194 103.4 2627 104.2 2647 105.6 2682 45.7 1161
30XVA180
H 14122 6406 15576 7065 15029 6817 16483 7477 16656 7555 18174 8243 16.1 409 78.0 1982 78.0 1982 32.0 813 62.0 1575 115.4 2932 117.1 2973 119.8 3042 45.8 1163
M 14322 6497 15776 7156 15169 6880 16623 7540 16856 7646 18374 8334 16.1 409 78.0 1982 78.0 1982 47.0 1194 115.4 2932 117.0 2972 119.7 3040 45.8 1162
30XVA200
H 15418 6993 17029 7724 16415 7446 18027 8177 18383 8339 20059 9099 16.1 409 78.0 1982 78.0 1982 32.0 813 62.0 1575 128.6 3267 131.1 3330 135.1 3431 45.9 1165
30XVA225 H 15842 7186 17706 8031 16880 7657 18743 8502 19046 8639 21038 9543 16.1 409 62.0 1575 32.0 813 109.0 2769 32.0 813 62.0 1575 145.8 3704 147.0 3733 149.0 3784 46.8 1189

30XVA250 H 18382 8338 20474 9287 19481 8836 21573 9785 21730 9857 24014 10893 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 32.0 813 62.0 1575 160.8 4083 162.5 4128 165.5 4203 45.6 1157
30XVA275 H 18239 8273 20331 9222 19348 8776 21440 9725 21597 9796 23881 10832 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 813 62.0 1575 160.7 4081 162.4 4126 165.4 4201 45.6 1159
M 18283 8293 20375 9242 19402 8801 21494 9749 21651 9821 23935 10857 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 32.0 813 62.0 1575 161.3 4098 163.1 4142 165.9 4215 45.7 1162
30XVA300
H 19379 8790 21628 9810 20648 9366 22898 10386 23179 10514 25620 11621 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 32.0 813 109.0 2769 174.3 4426 176.8 4492 181.1 4599 45.8 1164
M 19428 8812 21677 9833 20707 9393 22957 10413 23238 10540 25679 11648 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 32.0 813 109.0 2769 174.4 4429 177.0 4495 181.2 4601 45.8 1164
30XVA325
H 20620 9353 22998 10432 22046 10000 24423 11078 24857 11275 27427 12441 16.1 409 62.0 1575 32.0 813 109.0 2769 47.0 1194 32.0 813 78.0 1982 78.0 1982 188.4 4786 191.9 4873 197.3 5012 45.9 1166

* Condenser coil (MCHX): Microchannel (MCHX) Design


** Condenser coil (Al/CU): Aluminum fins/Copper Tubing
*** Condenser coil (CU/CU): Copper fins/Copper Tubing

Fig. 28 — Unit Rigging Label Supplement


30XV140-325 with Pump Option

94
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING. DO NOT FORK THESE UNITS IF NO SKID IS SUPPLIED.

NOTE:
1. 1.50 dia (38.1mm) lifting holes provided for field-supplied clevis.
2. Rig with a minimum of 25 ft (7620mm) length chain or cables.
3. If central lifting point is used, it must be a minimum of 13 ft (3962mm) above the top of the unit.
4. Spreader bars made from steel or double nailed, and notched 2x6s approximately 8 ft (2438mm) long, must be placed just above the top of the unit and coils.
5. If overhead rigging is not available, the unit can be moved on roller or dragged. When unit is moved on roller, the unit steel skid, if equipped, must be removed.
To lift the unit, use jacks at rigging points. Use a minimum of one roller every 6 ft (1829mm) to distribute the load. If the unit is to be dragged, lift the unit as
described above, and place unit on a pad. Apply moving force to the pad, not the unit. When in its final location, raise the unit and remove the pad.
6. Check the unit model number, position 11 to determine the unit weight as per condenser option.
7. Check the bill of the lading to determine shipping weight of the unit.

13' Minimum
(3982 mm)

A1
A7
A6
A5
A4
C A3
A2
A1 B

Max Max Max Max Max Max


Shipping Wt. Shipping Wt. Shipping Wt. Shipping Wt. Shipping Wt. Shipping Wt. Center of Gravity
w/o with w/o with w/o with
Packaging Packaging Packaging Packaging Packaging Packaging
Lifting Holes
Model Model Model Model Model Model
number number number number number number
B C
Model position position position position position position
Number 11 = 4,5 11 = 4,5 11 = -,1,2 11 = -,1,2 11 = 0,3 11 = 0,3
Model Position MCHX* MCHX* Al/CU** Al/CU** CU/CU*** CU/CU*** A1 A2 A3 A4 A5 A6 A7 A8 A9 MCHX* AL/CU** CU/CU***
Number 10 lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm
S 20158 9144 22027 9991 21232 9631 23101 10478 23481 10651 25542 11586 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 47.0 1194 16.1 409 0.0 157.0 3987 158.6 4029 161.6 4105 47.5 1206
30XVA350 M 21779 9879 23781 10787 23034 10448 25036 11356 25564 11596 27758 12591 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 47.0 1194 47.0 1194 47.0 1194 170.9 4341 173.3 4401 177.2 4502 47.5 1207
H 22557 10232 24694 11201 23963 10869 26099 11839 26774 12145 29103 13201 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 47.0 1194 47.0 1194 32.0 813 16.1 409 182.9 4646 186.1 4728 191.5 4865 47.5 1207
S 23213 10529 24984 11333 24463 11096 26234 11899 26993 12244 29020 13163 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 179.3 4554 181.1 4599 184.1 4676 46.0 1169
30XVA400 M 24156 10957 26061 11821 25567 11597 27472 12461 28379 12872 30539 13853 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 47.0 1194 190.6 4841 193.2 4907 197.6 5019 46.1 1171
H 24935 11310 26968 12233 26496 12019 28530 12941 29589 13421 31879 14460 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 32.0 813 62.01 1575 202.9 5153 206.4 5241 212.1 5387 46.1 1172
S 24156 10957 26054 11818 25567 11597 27465 12458 28379 12872 30532 13849 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 47.0 1194 190.5 4839 193.1 4905 197.5 5017 46.1 1171

30XVA450 M 25660 11639 27686 12558 27241 12357 29268 13276 30334 13759 32616 14795 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 32.0 813 62.01 1575 203.5 5168 206.9 5255 212.4 5396 46.2 1174
H 26525 12032 28691 13014 28315 12844 30482 13827 - - - - 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 32.0 813 109 2769 216.2 5491 220.4 5599 - - 46.3 1175

S 25660 11639 27686 12558 27241 12357 29268 13276 30334 13759 32616 14795 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 32.0 813 62.01 1575 203.5 5168 206.9 5255 212.4 5396 46.2 1174
30XVA500
M 26600 12066 28766 13048 28510 12932 30677 13915 - - - - 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 32.0 813 109 2769 216.2 5492 220.8 5607 - - 46.3 1175

30XV50034101 Rev C
* Condenser coil (MCHX): Microchannel (MCHX) Design
**Condenser coil (Al/CU): Aluminum fins/Copper Tubing
***Condenser coil (CU/CU): Copper fins/Copper Tubing

Fig. 29 — Unit Rigging Label Detail 30XV350-500

95
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING. DO NOT FORK THESE UNITS IF NO SKID IS SUPPLIED.

NOTE: REMARQUE:
1. 1.50 dia (38.1mm) lifting holes provided for field supplied clevis. 1

2. Rig with a minimum of 25 ft (7620mm) length chain or cabels. 2


3 If central lifting point is used, it must be minimum of 13 ft. (3962mm) above the top of the unit. 3
4. Spreader bars made from steel or double nailed, and notched 2x6's approximately 8 ft.(2438mm) long, must be placed 4
just above the top of the unit and coils.
5. If overhead rigging is not available, the unit can be moved on roller or dragged. When unit is moved on roller, the unit 5
steel skid, if equippled, must be removed. To lift the unit, use jacks at rigging points. Use a minimum of one roller every 6
ft. (1829mm) to distribuite the load. If the unit is to be dragged, lift the unit as described above, and place unit on a pad.
Apply moving force to the pad, not the unit. When in its final location. raise the unit and remove the pad.
6. Check the unit model number, position 11 to determine the unit weight as per condenser option. 6
7. Check the bill of the lading to determine shipping weight of the unit. 7

Max Max Max Max Max Max


Shipping Wt Shipping Wt Shipping Wt Shipping Wt Shipping Wt Shipping Wt
Center of Gravity
w/o with w/o with w/o with
Packaging Packaging Packaging Packaging Packaging Packaging
Model Lifting Holes
Model Number Model Model Model Model Model Model
Number Position number number number number number number
position position position position position position B
10
11=4 ,5 11=4 ,5 11= - ,1,2 11= - ,1,2 11= 0,3 11= 0,3
C

MCHX* MCHX* Al/CU** Al/CU** CU/CU*** CU/CU*** A1 A2 A3 A4 A5 A6 A7 MCHX* AL/CU** CU/CU***


lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs lbs Kgs in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm
30XVA40A H 23132 10493 24902 11296 24433 11083 26203 11886 27185 12331 29212 13250 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 179.3 4554 181.1 4599 184.1 4676 46.0 1169

30XVA45A M 23857 10821 25627 11625 25178 11421 26948 12224 27930 12669 29957 13588 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 179.3 4554 181.1 4599 184.1 4676 46.0 1169

30XVA45A H 23897 10840 25668 11643 25266 11461 27037 12264 28270 12823 30297 13743 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 179.3 4554 181.1 4599 184.1 4676 46.0 1169

30XVA50A S 23857 10821 25627 11625 25178 11421 26948 12224 27930 12669 29957 13588 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 179.3 4554 181.1 4599 184.1 4676 46.0 1169

30XVA50A M 23972 10874 25743 11677 25461 11549 27232 12352 28465 12912 30492 13831 16.1 409 109.0 2769 32.0 813 78.0 1982 78.0 1982 32.0 813 62.0 1575 179.3 4554 181.1 4599 184.1 4676 46.0 1169

30XVA40B H 1803 818 2057 933 2064 936 2318 1051 2404 1090 2658 1206 16.1 409 62.0 1575 49.3 1253 49.3 1253 49.3 1253 43.9 1115

30XVA45B M 1803 818 2057 933 2064 936 2318 1051 2404 1090 2658 1206 16.1 409 62.0 1575 49.3 1253 49.3 1253 49.3 1253 43.9 1115

30XVA45B H 2628 1192 3040 1379 3049 1383 3461 1570 3559 1615 3971 1801 16.1 409 109.0 2769 72.9 1852 72.9 1852 72.9 1852 43.9 1115

30XVA50B S 1803 818 2057 933 2064 936 2318 1051 2404 1090 2658 1206 16.1 409 62.0 1575 49.3 1253 49.3 1253 49.3 1253 43.9 1115
30XVA50B M 2628 1192 3040 1379 3049 1383 3461 1570 3559 1615 412 186.7 16.1 409 109.0 2769 72.9 1852 72.9 1852 72.9 1852 43.9 1115

* Condenser coil (MCHX): Microchannel (MCHX) Design


**Condenser coil (Al/CU): Aluminum fins/Copper Tubing
***Condenser coil (CU/CU): Copper fins/Copper Tubing

Fig. 30 — Unit Rigging Detail 30XV400-500 Split Units

96
Step 3 — Make Refrigerant, Evaporator Fluid Brazing
and Drain Piping Connections
CAUTION
CAUTION
The ball valves on the liquid and discharge line must remain
Units are designed for Victaulic-type water-side connections. closed prior to brazing the mating tubes and pulling a vacuum
If chilled water piping is to be welded to the water nozzles, re- on this area for both liquid and discharge side. Do not open the
move the chilled water flow switch, entering and leaving water valves until indicated in the brazing instructions below. Failure
thermistors before welding connecting piping. Reinstall flow to follow the steps below could result in a release of refrigerant
switch and thermistors after welding is complete. Failure to re- or air and moisture in the system. Work should be performed
move these devices may cause unit damage. by a skilled HVAC technician.
The gas and liquid lines must be brazed together using standard re-
frigeration practices. The interconnecting tubes are in the control
CAUTION panel in a box. Be sure plastic caps are removed from ball valves
on unit and connecting tubes. Figure 32 shows the orientation of
Factory-supplied insulation is not flammable but can be dam- the tubes. If the joint is inaccessible by reaching from under the
aged by welding sparks and open flame. Protect insulation braces, remove the rails. The tube with the male connection may
with a wet canvas cover. Failure to protect insulation may need to be trimmed to fit. Make sure the ball valves remain closed
cause unit damage. until the brazing and vac process is complete. Ball valves should
be protected from heat by using a wet rag. Schrader cores and fus-
SPLIT UNIT ASSEMBLY ible plugs should also be removed from the interconnecting tubes
The 30XV 400H, 450M, 450H, 500S, and 500M units are offered supplied in the kit prior to brazing. Nitrogen purge must be applied
as two separate modules from the factory as an option. This allows during brazing. Schrader taps on ball valves can be used for a con-
the units to fit in containers for export shipping. Table 4 shows the nection.
module designation. After brazing is complete:
Table 4 — Split Unit Sizes • Leak check.
UNIT SIZE MODULE A MODULE B • Pull vacuum on the connection tube to at least 500 microns.
400 40A 40B
• Hold vacuum for 5 minutes to confirm braze integrity.
450 45A 45B
500 50A 50B
• Open all 4 ball valves to complete the connection process.
These modules must be assembled in the field including brazing NOTE: A nitrogen purge can be applied to this section. Connec-
and wiring. A split unit installation kit is provided for this process. tions are at each ball valve.
The kit is located in the control box of module A. Steps for this as- Ball Valve Wiring
sembly are below. The 450H and 500M units have an automated discharge ball valve
Module Placement on the B module. (See Fig. 33.) A cable is tied on the end of the A
Place the modules in the final installation location in the orienta- module. Route the cable to the ball valve and connect to the actua-
tion shown in Fig. 31. The ball valves, open on one end, should be tor using the plugs. Secure the cable using wire ties, making sure
facing each other. There may be a 0 to 2.0 in. (0 to 50.8 mm) gap the cable is not against tubes or sharp edges.
between the units. Units may be ordered with manual ball valves instead of the auto-
mated valve option. For this case, there is no wiring required for
the valves.

MODULE A MODULE B

Fig. 31 — Split Unit Module Placement

97
Apply wet rag to all ball valves to
prevent damage. Remove Schrader
valve core and fusible plug prior
to brazing.
NOTE: Use a barrier or remove the
cross rail before brazing to prevent
damage to the cross rail.

LIQUID CONNECTION TUBES Trim this tube if required


for fitup.

GAS CONNECTION TUBES


Fig. 32 — Brazing Gas and Liquid Lines

AUTOMATED DISCHARGE
BALL VALVE

Fig. 33 — Automated Discharge Ball Valve

Fan VFD Wiring, 400H, 450M, and 500S (with Fan VFD Fan VFD Wiring, 450H, 500M
Option) To connect power to fan drive B2, use the conduit tied to the end
The fan cable for fan motors on module B is tied at end of module of the A module. Route this conduit to drive B2. (See Fig. 35.)
A. Route the cable through the wiring rail similar to existing fan Connect to bottom of drive and route wires to terminal block.
cables on module A. To get around the corner posts, bring the ca- Connect wires to L1, L2, L3, and ground. Torque lugs to
bles out of the rail, around the corner posts, and back into the rail. 16 in.-lbs. The drive cover is removed with a T20 bit.
Use conduit included in the installation kit, 30XV70001001, to Fan Cable Wiring, 500S (without Fan VFD Option)
cover the section of the wiring outside of the rail. The kit is located
in the control panel of module A unit. The cables will be routed The fan cable for fan motors on module B is tied at end of the
through the bottom of the B2 fan drive using the existing strain re- module A unit. Route through the wiring rail similar to existing
lief. (See Fig. 34.) Terminate wires on the motor wiring terminal fan cables on module A. To get around the corner posts, bring the
board inside drive. The terminal board is color-coded to match fan cables out of the rail, around the corner posts, and back into the
motor wires. Torque lugs to 16 in.-lbs. The drive cover is removed rail. Use the conduit included in the split unit installation kit to
with a T20 bit. cover the section of wiring outside of the rail. The cables will be
routed to the fan wiring box. Route cables into fan wiring box.
(See Fig. 36.) Plug fan cables to matching plugs in box. The plugs
are labeled for identification.

98
FAN DRIVE B2

MODULE B MODULE A

Fig. 34 — Fan VFD Wiring, 400H, 450M, and 500S

FAN DRIVE B2

MODULE B MODULE A

Fig. 35 — Fan VFD Wiring, 450H and 500M

FAN WIRING
BOX

MODULE B MODULE A

NOTE: If unit has grilles or louvered panels


these will have to be removed in order to access
the fan wiring box.

Fig. 36 — Fan Cable Wiring, 500S

99
GENERAL tank is added to the system, it should be properly vented so
The Victaulic connections allow clamp-on connection of water that the tank can be completely filled and all air eliminated.
lines to the evaporators in all 30XV units. See Fig. 3-24 and Failure to do so could cause lack of pump stability and poor
Fig. 37 for typical piping and wiring. See Table 5 for 30XV system operation. Any storage tank that is placed in the water
unit operating range and Tables 6-8 for minimum and maxi- loop should have internal baffles to allow thorough mixing of
mum water flow. A flow sensor is factory-installed in the side the fluid. (See Fig. 39.)
of the entering fluid nozzle. (See Fig. 38.) System Piping
Minimum Loop Volume Proper system design and installation procedures should be fol-
The preferred minimum loop volume is dependent on the lowed closely. The system must be constructed with pressure
type of application. In order to obtain leaving water tempera- tight components and thoroughly tested for installation leaks.
ture stability for comfort cooling applications, a minimum of Installation of water systems should follow sound engineering
3 gallons per ton (3.25 liters per kW) is required on all unit practice as well as applicable local and industry standards. Im-
sizes. For process cooling applications, applications where properly designed or installed systems may cause unsatisfacto-
high stability is critical, or operation at ambient temperatures ry operation and/or system failure. Consult a water treatment
below 32°F (0°C) is expected, the loop volume should be in- specialist or appropriate literature for information regarding fil-
creased to 6 to 10 gallons per ton (6.46 to 10.76 liters per kW) tration, water treatment, and control devices. Figures 40 and 41
of cooling. In order to achieve this volume, it may be neces- show a typical installation and components.
sary to add a water storage tank to the water loop. If a storage

(POWER CONNECTIONS FROM WALL


TO END OF UNIT NOT SHOWN)

FIELD-SUPPLIED FIELD-SUPPLIED
FUSED DISCONNECT FUSED DISCONNECT
UNIT POWER CONTROL POWER

PRESSURE/
TEMPERATURE TAPS*

VIBRATION BALANCING VALVE/


ELIMINATORS* SHUT OFF*
20-MESH
STRAINER*
PUMP SHUTOFF DRAIN
VALVE* SHUTOFF VALVE

LEGEND NOTES:
1. Chiller must be installed level to maintain proper compressor oil return.
FD — Fused Disconnect 2. Piping shown are general points-of-connection guides only and are not
intended for a specific installation. Wiring and piping shown are for a quick
Airflow Through Condenser overview of system and are not in accordance with recognized standards.
Chilled Water Piping 3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System
Power Wiring Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigerating, and Air-Conditioning Engineers) handbook for details.
*Field-installed. 5. A 20 mesh strainer is required within 10 ft (3 m) of the evaporator.

Fig. 37 — 30XV Typical Piping and Wiring

100
Table 5 — Operating Temperature Limits Applicable to All Sizes
TEMPERATURE F C
Maximum Ambient Temperature 125 51.7
Minimum Ambient Temperature* 32 0.0
Maximum Evaporator EWT† 95 35.0
Maximum Evaporator LWT 60 15.6
Minimum Evaporator LWT 38** 3.3**
Maximum Evaporator Glycol EWT† 95 35.0
Minimum Evaporator Glycol LWT — Comfort Cooling Evaporator 30 16.7
Minimum Evaporator Glycol LWT — Process Cooling Evaporator 14 –9.4
LEGEND * Lowest allowable ambient temperature for the standard unit to start and
EWT — Entering Fluid (Water) Temperature operate is 32°F (0°C). With the inclusion of wind baffles and variable
LWT — Leaving Fluid (Water) Temperature speed fans (field fabricated and installed), the unit is capable to start as
low as 0°F (–17.8°C) and to operate as low as –20°F (–29°C) ambient
temperature.
†For sustained operation, EWT should not exceed 70°F (21.1°C).
**Unit requires brine fluid for operation below this temperature.

Table 6 — Min/Max Water Flow — Standard (2-Pass) Evaporator


MINIMUM FLOW RATE MAXIMUM FLOW RATE
30XV TIERS
(gpm) (L/s) (gpm) (L/s)
140 All 170.4 10.8 681.6 43.0
160 All 193.2 12.2 772.8 48.8
180 All 204.0 12.9 816.0 51.5
200 All 236.4 14.9 945.6 59.7
225 All 266.4 16.8 1065.6 67.2
250 All 308.4 19.5 1233.6 77.8
275 All 327.6 20.7 1310.4 82.7
300 All 349.2 22.0 1396.8 88.1
325 All 379.2 23.9 1516.8 95.7
350 All 419.0 26.4 1676.0 105.7
400 All 483.0 30.5 1932.0 121.9
450 All 543.5 34.3 2174.0 137.2
500 All 600.0 37.9 2400.0 151.4

Table 7 — Min/Max Water Flow — 1-Pass Evaporator


MINIMUM FLOW RATE MAXIMUM FLOW RATE
30XV TIERS
(gpm) (L/s) (gpm) (L/s)
140 All 340.8 21.6 1363.2 86.0
160 All 386.4 24.4 1545.6 97.6
180 All 408.0 25.8 1632.0 103.0
200 All 472.8 29.8 1891.2 119.4
225 All 532.8 33.6 2131.2 134.4
250 All 616.8 39.0 2467.2 155.6
275 All 655.2 41.4 2620.8 165.4
300 All 698.4 44.0 2793.6 176.2
325 All 758.4 47.8 3033.6 191.4
350 All 838.0 52.8 3352.0 211.4
400 All 966.0 61.0 3864.0 243.8
450 All 1087.0 68.6 4348.0 274.4
500 All 1200.0 75.8 4800.0 302.8

101
Table 8 — Min/Max Water Flow — 3-Pass Evaporator
MINIMUM FLOW RATE MAXIMUM FLOW RATE
30XV TIERS
(gpm) (L/s) (gpm) (L/s)
140 All 113.6 7.2 454.3 28.7
160 All 128.8 8.1 515.1 32.5
180 All 136.0 8.6 543.4 34.3
200 All 157.6 9.9 630.3 39.8
225 All 177.6 11.2 710.3 44.8
250 All 205.6 13.0 822.3 51.9
275 All 218.4 13.8 873.5 55.1
300 All 232.8 14.6 931.1 58.7
325 All 252.8 15.9 1011.1 63.8
350 All 279.3 17.6 1117.2 70.4
400 All 322.0 20.3 1287.9 81.2
450 All 362.3 22.9 1443.2 91.5
500 All 400.0 25.3 1599.8 100.9

BAD GOOD

BAD GOOD

FLOW SWITCH

Fig. 38 — Flow Switch Location Fig. 39 — Tank Baffling

102
Air Separation The outlet (supply) water connection is on the top. When single
For proper system operation, it is essential that water loops be pass evaporator is selected, it will have nozzles on either end of
installed with proper means to manage air in the system. Free the evaporator. The nozzle opposite the control box side is en-
air in the system can cause noise, reduce terminal output, stop tering water. The evaporator has water-side Victaulic-type con-
flow, or even cause pump failure due to pump cavitation. For nections (follow connection directions as provided by the
closed systems, equipment should be provided to eliminate all coupling manufacturer). Provide proper support for the piping.
air from the system. If accessory security grilles have been added, holes must be cut
in the grilles for field piping and insulation. See Fig. 41 for a
The amount of air that water can hold in solution depends on typical piping diagram of a 30XV unit with Greenspeed®
the pressure and temperature of the water/air mixture. Air is intelligence. A drain connection is located at the leaving water
less soluble at higher temperatures and at lower pressures. (supply) end of evaporator. See Fig. 3-24 for connection loca-
Therefore, separation can best be done at the point of highest tion. Insulate the drain piping (in the same manner as the
water temperature and lowest pressure. Typically, this point chilled water piping) for at least 12 in. (305 mm) from the unit.
would be on the suction side of the pump as the water is re-
turning from the system or terminals. This is generally the op- Dual Chiller Control
timal place to install an air separator, if possible. The Carrier Controller allows 2 chillers (piped in parallel or se-
1. Install automatic air vents at all high points in the sys- ries) to operate as a single chilled water plant with standard
tem. (If the 30XV unit is located at the high point of the control functions coordinated through the master chiller
system, a vent can be installed on the piping leaving the controller. This standard Carrier Controller feature requires a
communication link between the 2 chillers on the CCN bus.
heat exchanger on the 1/4 in. NPT female port.)
2. Install an air separator in the water loop, at the place Dual Chiller Leaving Water Sensor
where the water is at higher temperatures and lower If the dual chiller algorithm is used, and the machines are
pressures — usually in the chilled water return piping. installed in parallel, a dual chilled water sensor must be in-
On a primary-secondary system, the highest tempera- stalled for each module. Install the well in the common
ture water is normally in the secondary loop, close to leaving water header. (See Fig. 42.) The connection size
for the thermowell is 1/4 in. NPT. A dual chiller accessory
the decoupler. Preference should be given to that point kit (P/N 00EFN900044000A) is available.
on the system. (See Fig. 40). In-line or centrifugal air
separators are readily available in the field. Parallel Dual Chiller Operation
Parallel chiller operation is the recommended option for dual
If it is not possible to install air separators at the place of the chiller control. In this case, each chiller must control its own
highest temperature and lowest pressure, preference should be dedicated pump or isolation valve. Balancing valves are rec-
given to the points of highest temperature. It is important that ommended to ensure proper flow in each chiller. Two
the pipe be sized correctly so that free air can be moved to the field-supplied and installed dual chiller leaving water tempera-
point of separation. Generally, a water velocity of at least 2 ft ture sensors are required, one for each module, for this function
per second (0.6 m per second) will keep free air entrained and to operate properly.
prevent it from forming air pockets.
Consider adding additional isolation valves to isolate each
Automatic vents should be installed at all physically elevated chiller to allow for service on a machine, and still allow for par-
points in the system so that air can be eliminated during system tial capacity from the other chiller. (See Fig 42.)
operation. Provisions should also be made for manual venting
during the water loop fill. Series Dual Chiller Operation
Units Field Piping Series chiller operation is an alternate control method
supported by the Carrier Controller control system. Certain ap-
When facing the evaporator side of the unit, the inlet (return) plications might require that the two chillers be connected in
water connection is on the bottom. It is required that a field- series.
supplied strainer with a minimum size of 20 mesh be installed
within 10 ft (3.05 m) of the evaporator inlet to prevent debris Consider adding additional piping and isolation valves to iso-
from damaging internal tubes of the evaporator. late each chiller to allow for service on a machine, and still
allow for partial capacity from the other chiller. (See Fig. 43.)
NOTE: Units supplied with factory installed pumps include a
strainer. An additional strainer is not required.
Distribution Pump a30-4002ef
Chiller 1

Chiller 2

Zone 1

Zone 2

Zone 3

Decoupler Expansion
Tank(s)

Air Separator
with Vent

NOTE: Expansion tanks for 30XV hydronic kits must be installed for chillers piped in parallel in the primary water loop.
Fig. 40 — Typical Air Separator and Expansion Tank Location on Primary-Secondary Systems

103
V
V T1 PP Chilled Water Out

HEATER
HEATER

Chilled Water In
D FS PP T2
D

LEGEND
D — Drain, 3/4-in. NPT
FS — Flow Switch
PP — Pipe Plug, 1/4-in. NPT
T1 — Leaving Water Thermistor
T2 — Entering Water Thermistor
V — Vent, 3/8-in. NPT
— 20
20Mesh
MeshStainer
Strainer required within 10 ft (3 m) of evaporator
— Relief Valve

Fig. 41 — Typical Piping Diagram for 30XV Units with Greenspeed® Intelligence

CONTROL
BOX

MASTER CHILLER PUMP & CHECK VALVE

OPT
M

OR MOTORIZED VALVE
OPT

LEGEND
CONTROL
BOX LWT — Leaving Water Temperature
OPT — Optional
SLAVE CHILLER
PUMP & CHECK VALVE Field-Installed Communication Bus (slashes
indicate number of conductor wires)
Field-Installed Wiring
OPT Optional Piping
M

Isolation Valve
OR MOTORIZED VALVE
OPT
M Motorized Valve

Check Valve
DUAL CHILLER
LWT SENSORS
& WELLS

Fig. 42 — Parallel Dual Chiller Operation

104
CONTROL
BOX

SLAVE CHILLER

PUMP

OPT OPT

CONTROL
OPT

BOX

MASTER CHILLER

OPT
LEGEND
OPT OPT

OPT — Optional
Field-Installed Communication Bus (slashes
indicate number of conductor wires)
Field-Installed Wiring
Optional Piping

Isolation Valve

Fig. 43 — Series Dual Chiller Operation

105
PREPARATION FOR YEAR-ROUND OPERATION
IMPORTANT: Automatic vents should be located in accessible In areas where the piping or unit is exposed to 32F (0C) or
locations for maintenance purposes and should be protected from lower ambient temperatures, freeze-up protection is required using
freezing. inhibited glycol or other suitable corrosion-resistant antifreeze
solution and electric heater tapes. Heater tapes on piping should
EVAPORATOR PUMP CONTROL have a rating for area ambient temperatures and be covered with a
suitable thickness of closed-cell insulation. Route power for the
It is required that evaporator pump control be utilized on all heater tapes from a separately fused disconnect. Mount the discon-
chillers unless the chilled water pump runs continuously or the nect within sight from the unit per local or NEC (National Electric
chilled water system contains a suitable antifreeze solution. Code) codes. Identify disconnect at heater tape power source with
a warning that power must not be turned off except when servic-
ing unit.
CAUTION
Applications that utilize fresh water as the circulated fluid re- IMPORTANT: Adding antifreeze solution is the only certain
quire that the circulating pump be controlled directly by the means of protecting the unit from freeze-up if heater fails or
chiller. Operation with fresh water is not fail-safe should there electrical power is interrupted or lost while temperatures are
be a loss of power to the chiller or to the circulating pump. below 32F (0C).
Freeze damage due to power loss or disabling chiller pump
control in fresh water systems will impair or otherwise nega- A drain connection is located at the bottom of the evaporator head.
tively affect the warranty. See Fig. 41 for connection location. Install shut-off valves to the
drain line before filling the system with fluid.
Refer to the control and power wiring schematic beginning on Low Ambient Temperature Head Pressure Control
page 111 for proper connection of the evaporator pump (PMP1
and PMP2). The evaporator pump output will remain energized For units intended to operate in low ambient conditions,
for 30 seconds after all compressors stop due to an OFF field-fabricated and field-installed wind baffle is required if the
command. In the event a freeze protection alarm is generated, the wind velocity is anticipated to be greater than 5 mph (8 km/h).
evaporator pump output will be energized regardless of the evapo- Wind baffle should be constructed with minimum 18-gauge galva-
rator pump control software configuration. The evaporator pump nized sheet metal or other suitable corrosion-resistant material
output is also energized when certain alarms are generated. A with cross breaks for strength. (See Fig. 45.) Use field-supplied
thermal flow sensor is factory installed in the entering fluid nozzle screws to attach baffle to the corner posts of the machine. Be sure
to prevent operation without flow through the evaporator. (See to hem or turn a flange on all edges to eliminate sharp edges on the
Fig. 44.) The flow sensor is factory wired. baffles.
Proper software configuration of the evaporator pump control pa-
rameters is required to prevent possible evaporator freeze-up. WARNING
Refer to the Controls, Start-Up, Operation, Service and Trouble-
shooting guide for more information. Disconnect all power to the unit before performing mainte-
nance or service. Electrical shock and personal injury could
0.30 in. (7.7 mm)

result.
1/4 in. NPT

4.2 in. (107 mm)


HEX WRENCH
7/8 in. (22 mm) 0.87 in. CAUTION
(22 mm)
To avoid damage to the refrigerant coils and electrical compo-
M12X1

nents, use extreme care when drilling screw holes and


screwing in fasteners.
Fig. 44 — Thermal Flow Sensor Mount baffle opposite control box end. It is recommended that the
upper notches be used for mounting the baffle. This reduces the
If evaporator pump control is not utilized, it is required that the risk of damaging the coil while drilling a mounting hole. Loosen
chiller be electrically interlocked with the chilled water pump the upper corner post bolts and slide the baffle under the bolt and
starter. The interlock should be wired to terminals TB5-27 and washer. Tighten the bolt. Drill holes in the bottom of the flange of
TB5-28. It is also recommended that the evaporator pump output the baffle and mount with two screws to secure the bottom of the
be used as an override to the chilled water pump control circuit to baffle to the corner post.
provide additional freeze protection. See the Field Control and
Power Wiring figure beginning on page 111. For units with facto-
ry supplied pumps, the pump design points and minimum flow
must be set up for the site design conditions for proper operation.
Refer to the Controls, Start-Up, Operation, Service, and Trouble-
shooting guide for more information.

106
Cross break these faces.
Hem these 3 edges both top
and bottom.

305 [12.0]

See Detail A

1245 [49.0]

1880 [74.0]
180 [7.0]

18 [0.75]

70 [2.75]
18 [0.75] 31 [1.25]

21 [0.88]

Detail A
Typical Both Flanges
NOTES:
1. Place baffle on end opposite the control box.
2. Material: 18 ga. Corrosion Resistant Sheet Metal.
3. Dimensions are in mm [inches].

Fig. 45 — Field-Fabricated and Field-Installed Wind Baffle

107
Step 4 — Fill the Chilled Water Loop treatment specialist should be obtained to develop and monitor
a treatment program.
IMPORTANT: Before starting unit, be sure all of the air has been SYSTEM
purged from the system.
POT FEEDER AND
TRANSFER PUMP
DILUTED
CLEANING
CAUTION AGENT

In low ambient (below 32°F [0°C]) and/or low leaving fluid


temperature applications (below 40°F [4.4°C]), a suitable anti- x
freeze solution of the proper concentration for the specific op- TEMPORARY
PUMP
30XV UNIT
erating conditions must be used as the fluid circulated through
the evaporator to prevent freezing and damage to the system. x
Failure to operate the system with an antifreeze solution of the
proper concentration will impair or otherwise negatively affect
TEMPORARY
BYPASS
the warranty should damage result from freezing. TO DRAIN

Fig. 46 — Typical Set Up for Cleaning Process


The maximum evaporator water side pressure is 300 psig
(2068 kPa). Check the pressure rating for all of the chilled water
devices installed. Do not exceed the lowest pressure rated device. SYSTEM
POT FEEDER AND
BRINE EVAPORATOR OPTION DILUTED
TRANSFER PUMP
SIDE
Add sufficient inhibited glycol or other suitable corrosion-resistant STREAM
CLEANING
AGENT
antifreeze solution to prevent evaporator freeze-up. FILTER

WATER SYSTEM CLEANING x


Proper water system cleaning is of vital importance. Excessive TEMPORARY 30XV UNIT
particulates in the water system can cause excessive pump seal
PUMP

wear, reduce or stop flow, and cause damage of other components. x


Ideally, the chilled water loop will be cleaned before the unit is TEMPORARY
connected. BYPASS
a30-4412 TO DRAIN
1. Install a temporary bypass around the chiller to avoid
circulating dirty water and particulates into the chiller Fig. 47 — Cleaning Using a Side Stream Filter
during the flush. Use a temporary circulating pump during
the cleaning process. Also, be sure that there is capability
to fully drain the system after cleaning. (See Fig. 46.) CAUTION
2. Be sure to use a cleaning agent that is compatible with all
system materials. Be especially careful if the system Water must be within design flow limits, clean, and treated to
contains any galvanized or aluminum components. Both ensure proper chiller performance and reduce the potential of
tube damage due to corrosion, scaling, erosion, and algae. Car-
detergent-dispersant and alkaline-dispersant cleaning rier assumes no responsibility for chiller damage resulting
agents are available. from untreated or improperly treated water.
3. It is recommended to fill the system through a water meter.
This provides a reference point for the future for loop vol- NOTE: Do not use automobile anti-freeze, or any other fluid that
ume readings, and it also establishes the correct quantity of is not approved for heat exchanger duty. Only use appropriately
cleaner needed in order to reach the required concentration. inhibited glycols, concentrated to provide adequate protection for
4. Use a feeder/transfer pump to mix the solution and fill the the temperature considered.
system. Circulate the cleaning system for the length of SYSTEM PRESSURIZATION
time recommended by the cleaning agent manufacturer. A proper initial cold fill pressure must be established before filling
a. After cleaning, drain the cleaning fluid and flush the sys- of the unit. The initial cold fill pressure is the pressure applied at
tem with fresh water. the filling point to fill a system to its highest point, plus a mini-
b. A slight amount of cleaning residue in the system can mum pressure at the top of the system (4 psig minimum
help keep the desired, slightly alkaline, water pH of 8 to [27.6 kPa]) to operate air vents and positively pressurize the sys-
9. Avoid a pH greater than 10, since this will adversely tem. The expansion tank is very important to system pressuriza-
affect pump seal components. tion. The expansion tank serves several purposes:
c. A side stream filter is recommended (see Fig. 47) during 1. Provides NPSHR (Net Positive Suction Head Required)
the cleaning process. Filter side flow rate should be for the pump to operate satisfactorily.
enough to filter the entire water volume every 3 to 4 2. Sets system pressure.
hours. Change filters as often as necessary during the 3. Accommodates expansion/contraction of water due to
cleaning process. temperature changes.
d. Remove temporary bypass when cleaning is complete. 4. Acts as a pressure reference for the pump.
WATER TREATMENT The expansion tank pressure must be set BEFORE the system is
filled. Follow the manufacturer’s recommendation for instructions
Fill the fluid loop with water (or brine) and a corrosion-resistant on setting the pressure in the expansion tank.
inhibitor suitable for the water of the area. Consult the local water
treatment specialist for characteristics of system water and a rec- Once the system is pressurized, the pressure at the connection
ommended inhibitor for the evaporator fluid loop. point of the expansion tank to water piping will not change unless
the water loop volume changes (either due to addition/ subtraction
Untreated or improperly treated water may result in corrosion, of water or temperature expansion/contraction). The pressure at
scaling, erosion, or algae. The services of a qualified water

108
this point remains the same regardless of whether or not the pump are for fresh water and “clean” heat exchangers; they do not apply
is running. to heat exchangers with fouling.
Since the expansion tank acts as a reference point for the pump, FREEZE PROTECTION
there cannot be two reference points (two expansion tanks) in a
system, unless manifolded together as seen in Fig. 40. It is per- The 30XV units with Greenspeed® intelligence are provided with
missible to install the expansion tank(s) in a portion of the return a flow switch to protect against freezing situations that occur from
water line that is common to all pumps, providing that the tank is no water flow. While the flow switch is helpful in preventing
properly sized for combined system volume. freezing during no-flow situations, it does not protect the chiller in
case of power failure during sub-freezing ambient temperatures,
If the application involves two or more chillers in a or in other cases where water temperature falls below the freezing
primary-secondary system, a common place for mounting the mark. Appropriate concentrations of inhibited propylene or
expansion tank is in the chilled water return line, just before the ethylene glycol or other suitable inhibited antifreeze solution
decoupler. See Fig. 40 for placement of expansion tank in should be considered for chiller protection where ambient tem-
primary-secondary systems. peratures are expected to fall below 32F (0°C). Consult a local
If a diaphragm expansion tank is utilized (a flexible diaphragm water treatment specialist on characteristics of the system water
physically separates the water/air interface) it is not and add a recommended inhibitor to the chilled water. The Carrier
recommended to have any air in the water loop. See the section warranty does not cover damage due to freezing.
on air separation on page 103 for instructions on providing air NOTE: Do not use automobile antifreeze, or any other fluid that is
separation equipment. not approved for heat exchanger duty. Only use appropriately in-
FILLING THE SYSTEM hibited glycols, concentrated to provide adequate protection for
the temperature considered.
The initial fill of the chilled water system must accomplish three
goals: Use electric heater tape for the external piping, if unit will be ex-
posed to freezing temperatures and is not protected with a suitable
1. The entire piping system must be filled with water. antifreeze solution.
2. The pressure at the top of the system must be high enough
to vent air from the system (usually 4 psig [27.6 kPa] is For units equipped with evaporator heaters, ensure that power is
available to the chiller at all times, even during the off-season, so
adequate for most vents). that the evaporator heaters have power. Also make sure that the
3. The pressure at all points in the system must be high enough piping heater tape has power.
to prevent flashing in the piping or cavitation in the pump.
Units with evaporator heaters are protected from freezing down to
The pressure created by an operating pump affects system pres- 0°F (–18C) through the evaporator heaters and control algo-
sure at all points except one — the connection of the expansion rithms. If the unit controls the chilled water pump and valves, al-
tank to the system. This is the only location in the system where lowing flow through the evaporator, the unit is protected from
pump operation will not give erroneous pressure indications freezing down to –20F (–29C). The Carrier warranty does not
during the fill. Therefore, the best location to install the fill con- cover damage due to freezing.
nection is close to the expansion tank. An air vent should be in-
stalled close by to help eliminate air that enters during the fill PREPARATION FOR WINTER SHUTDOWN
procedure. When filling the system, ensure the following: If the unit is not operational during the winter months, at the end
1. Remove temporary bypass piping and cleaning/flushing of cooling season complete the following steps.
equipment.
2. Check to make sure all drain plugs are installed. CAUTION
Normally, a closed system needs to be filled only once. The actual
filling process is a fairly simple procedure. All air should be Failure to remove power before draining heater equipped
purged or vented from the system. Thorough venting at high evaporator and factory supplied pump system will result in
points and circulation at room temperature for several hours is heater failure.
highly recommended.
1. If the evaporator will not be drained, do not shut off power
NOTE: Local codes concerning backflow devices and other pro- disconnect during off-season shutdown. If evaporator is to
tection of the city water system should be consulted and followed be drained, first open the circuit breaker for the heater,
to prevent contamination of the public water supply. This is criti-
cal when antifreeze is used in the system. CB-7, or shut off power during off-season shutdown.
2. Draining the fluid from the system is highly recom-
SET WATER FLOW RATE mended. Units have a drain plug mounted on the bottom of
Once the system is cleaned, pressurized, and filled, the flow rate the evaporator head at each end of the evaporator.
through the chiller needs to be established. Follow the manufac- 3. Isolate the evaporator from the rest of the system with
turer’s recommendations for setting the balancing valve. Local water shutoff valves.
codes may prohibit restricting the amount of water using the bal- 4. Replace the drain plug and completely fill the evaporator
ancing valve for a given motor horsepower. with a mixture of water and a suitable corrosion-inhibited
NOTE: Carrier recommends a differential pressure gauge when anti-freeze solution such as propylene glycol. The concen-
measuring pressures across the pumps or balancing valves. This tration should be adequate to provide freeze protection to
provides for greater accuracy and reduces error build-up that often 15°F (8.3°C) below the expected low ambient temperature
occurs when subtracting pressures made by different gauges. conditions. Antifreeze can be added through the vent on
A rough estimate of water flow can also be obtained from the top of the evaporator head.
pressure gauges across the 30XV heat exchanger. 5. Leave the evaporator filled with the antifreeze solution for the
For units with the factory installed pumps, the water flow rate will winter. Be sure to deenergize heaters (if installed) as
be set with the pump speed control. See Troubleshooting Guide explained in Step 1 to prevent damage if the evaporator is
for pump operation. drained. Use an approved method of disposal when removing
The Controls, Start-Up Operation, Service, and Troubleshooting antifreeze solution.
guide includes graphs that show the relationship between gpm and At the beginning of the next cooling season, be sure that there is
heat exchanger pressure drop. It should be noted that these curves refrigerant pressure on each circuit before refilling evaporator, add

109
recommended inhibitor, and reset the CB-7 (circuit breaker for the all conduits from a conditioned space to the power box(es) be
heater) (if opened) or restore power. sealed to prevent airflow and moisture into the control box.
If system does not have charge at this time, find and repair the The 30XV units with Greenspeed intelligence require 1 or 2 pow-
leak. Always assure water is flowing in the evaporator before er supplies, depending on the unit and power option selected. See
charging or evacuating the unit. Tables 10-38 for chiller electrical data. Evaporator heaters, if
factory-installed, are wired in the control circuit. Heaters on
Step 5 — Make Electrical Connections chillers with the optional control transformer will be capable of
operation only when the main power supply to the chiller is on. On
WARNING chillers with separate control power, the heaters are capable of op-
eration whenever the control power is supplied.
Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation. There may be IMPORTANT: The 30XV units with Greenspeed® intelligence
more than one disconnect switch. Tag all disconnect locations rated 400V, 415V and 440V will have compressors rated at
to alert others not to restore power until work is completed. 380V. The compressor VFD will have proper configuration to
accept 400V, 415V or 440V line power as applicable and out-
POWER SUPPLY put 380V to the compressor.
The electrical characteristics of the available power supply must
agree with the unit nameplate rating. Supply voltage must be
within the limits shown. See Table 9 for power entry option. See IMPORTANT: The 30XV units with Greenspeed® intelligence
Tables 10-38 for electrical and configuration data. rated 575V will have compressors rated at 460V. The compres-
sor VFD will have proper configuration to accept 575V line
FIELD POWER CONNECTIONS power and output 460V to the compressor.
All power wiring must comply with applicable local and national
codes. Install field-supplied, branch circuit fused disconnect(s) of UNITS WITH PUMP OPTION
a type that can be locked off or open. Disconnect(s) must be For units with the factory installed pump option, pump heaters use
located within sight and readily accessible from the unit in compli- the same control output as the evaporator heaters. Ensure that the
ance with NEC Article 440-14 (U.S.A.). See Tables 10-38 for unit heaters cannot be energized without water in the pump manifolds.
electrical data. (See Fig. 48.)
FIELD CONTROL POWER CONNECTIONS
IMPORTANT: The 30XV units with Greenspeed® intelligence See Fig. 48. All units require 115-1-60 control circuit power, un-
have a factory-installed option available for a non-fused discon- less the control transformer option is installed.
nect for unit power supply. If the unit is equipped with this op-
tion, all field power wiring should be made to the non-fused dis- A field-supplied remote on-off switch or control relay can be
connect since no terminal blocks are supplied. wired into TB5-9 and TB5-10. Contacts must be rated for dry-
circuit applications capable of handling a 24-vac at 50 mA load.
Maximum wire sizes that the unit terminal block or non-fused
disconnect are listed in Table 9. CAUTION
POWER WIRING
Do not use interlocks or other safety device contacts connected
All power wiring must comply with applicable local and nation- between TB5-9 and TB5-10 as remote on-off. Connection of
al codes. Install field-supplied branch circuit fused disconnect safeties or other interlocks between these 2 terminals will re-
per NEC of a type that can be locked OFF or OPEN. Disconnect sult in an electrical bypass if the ENABLE-OFF-REMOTE
must be within sight and readily accessible from the unit in com- contact switch is in the ENABLE position. If remote on-off
pliance with NEC Article 440-14. In the power box, 7/8 in. unit control is required, a field-supplied relay must be installed
knockouts are provided for power entry. The holes will need to in the unit control box and wired as shown in Fig. 48. Failure
be enlarged to accept the appropriate conduit. NEC also requires to wire the remote on-off as recommended may result in tube
freeze damage.

110
CARRIER CONTROLLER DISPLAY

Fig. 48 — Field Control and Power Wiring

111
Fig. 48 — Field Control and Power Wiring (cont)

112
COMPRESSOR A VFD

COMPRESSOR B VFD

Fig. 48 — Field Control and Power Wiring (cont)

113
Table 9 — Power Entry Options
NO. OF
POWER ENTRY 30XV DISCONNECT
VOLTAGE CONDUCTORS LUG RANGE
OPTION UNIT SIZE OPTION
PER PHASE
208/230V NO 4 #2AWG - 750 KCMIL
140-200
380-575V NFD 2 2/0 - 500 KCMIL
140-325 380-575V NO 2 #2AWG - 600 KCMIL
380-440V NFD 4 4/0 - 500 KCMIL
SINGLE POINT 225-325
460-575V NFD 3 (or 2) 3/0 - 400 KCMIL or (500 KCMIL - 750 KCMIL)
POWER
380-440V NO 6 #2AWG - 750 KCMIL
460-575V NO 4 #2AWG - 750 KCMIL
350-500
380-440V NFD 6 #2AWG - 600 KCMIL
460-575V NFD 4 4/0 - 500 KCMIL
208/230V NO 3 3/0 - 400 KCMIL
140-200 380-575V NO 1 or (2) 2/0-500 KCMIL or (2/0-250 KCMIL)
380-575V NFD 1 or (2) 2/0-500 KCMIL or (2/0-250 KCMIL)

DUAL POINT 380-575V NO 2 #2AWG - 500 KCMIL


225-325
POWER 380-575V NFD 2 #2AWG - 500 KCMIL
380V NO 4 #2AWG - 750 KCMIL
350-500 460-575V NO 2 #2AWG - 600 KCMIL
380-575V (HSCCR) NO 3 3/0 - 400 KCMIL

LEGEND
AWG — American Wire Gage
HSCCR — High Short Circuit Current Rating
NFD — Non-fused Disconnect
NO — None

114
Legend and Notes for Tables 10-38 NOTES:
1. MCA and MOCP values shown are inclusive of control power transformer
LEGEND loads. Chillers are occasionally selected without a control power trans-
MCA — Minimum Circuit Amps former. In such cases, be sure to use the Carrier chiller selection software to
MOCP — Maximum Overcurrent Protection obtain the proper values of electrical data (those that will appear on the
chiller nameplate). In some cases, the MOCP value may be lower when a
VFD — Variable Frequency Drive control power transformer is not incorporated into the unit selection.
2. Units are suitable for use on electrical systems where voltage supplied to
the unit terminals is not below or above the listed minimum and maximum
limits. Maximum allowable phase imbalance is: voltage, 2%; amps 10%.
3. Evaporator heater (where applicable) is wired into the control circuit so it is
always operable as long as the control power supply disconnect is on, even
if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75°C copper wire.
5. Based on the operational characteristics of a VFD, the “inrush” current nor-
mally associated with a chiller is limited and will be lower than the MCA rat-
ing of the chiller.
6. Wiring for main field supply must be rated 75°C minimum. Use copper for all
units. Refer to Power Entry Options table.
7. On 60 Hz units, some electrical values will be lower when a chiller is
selected without a control power transformer. Refer to the chiller selection
program.
8. Data for units without control transformer option can be viewed in Ecat.

115
Table 10 — 60 Hz Single Point Power Standard Tier Fixed Speed Fan Motors with Control Power Transformer

UNIT VOLTAGE NO HYDRONIC PACKAGE CONTROL CIRCUIT


NO. OF
UNIT 30XV Supplied COND Voltage MCA
V(3 Ph) Hz FANS MCA MOCP FUSE SIZE 1 Ph, and
Min Max 60 Hz MOCP
208/230 60 187 253 8 578.7 800 700 115 60
380 60 342 418 8 317.1 400 350 115 60
140 400 60 360 440 8 302.4 400 350 115 60
460 60 414 506 8 261.6 350 300 115 60
575 60 518 633 8 210.6 250 250 115 60
208/230 60 187 253 8 679.9 800 800 115 60
380 60 342 418 8 371.1 500 450 115 60
160 400 60 360 440 8 354.1 450 400 115 60
460 60 414 506 8 306.6 400 350 115 60
575 60 518 633 8 246.6 300 300 115 60
208/230 60 187 253 8 781.2 1000 1000 115 60
380 60 342 418 8 427.3 600 500 115 60
180 400 60 360 440 8 408.1 500 450 115 60
460 60 414 506 8 353.1 450 400 115 60
575 60 518 633 8 282.6 350 350 115 60
208/230 60 187 253 10 810.1 1000 1000 115 60
380 60 342 418 10 443.5 600 500 115 60
200 400 60 360 440 10 421.8 500 500 115 60
460 60 414 506 10 366.3 500 450 115 60
575 60 518 633 10 294.2 400 350 115 60
380 60 342 418 10 517.8 700 600 115 60
400 60 360 440 10 492.1 700 600 115 60
225
460 60 414 506 10 426.9 600 500 115 60
575 60 518 633 10 342.4 500 400 115 60
380 60 342 418 12 581.3 800 700 115 60
400 60 360 440 12 552.5 700 700 115 60
250
460 60 414 506 12 478.9 600 600 115 60
575 60 518 633 12 383.7 500 450 115 60
380 60 342 418 12 624.0 800 700 115 60
400 60 360 440 12 593.0 800 700 115 60
275
460 60 414 506 12 514.6 700 600 115 60
575 60 518 633 12 413.0 500 500 115 60
380 60 342 418 14 640.2 800 800 115 60
400 60 360 440 14 608.9 800 700 115 60
300
460 60 414 506 14 528.3 700 600 115 60
575 60 518 633 14 424.5 500 500 115 60
380 60 342 418 16 701.4 800 800 115 60
400 60 360 440 16 667.5 800 800 115 60
325
460 60 414 506 16 579.3 800 700 115 60
575 60 518 633 16 465.3 600 600 115 60
380 60 342 418 16 831.3 1200 1000 115 60
400 60 360 440 16 789.9 1000 1000 115 60
350
460 60 414 506 16 685.8 1000 800 115 60
575 60 518 633 16 550.0 800 700 115 60
380 60 342 418 18 893.8 1200 1000 115 60
400 60 360 440 18 850.6 1000 1000 115 60
400
460 60 414 506 18 737.5 1000 1000 115 60
575 60 518 633 18 592.0 800 700 115 60
380 60 342 418 20 1033.7 1200 1200 115 60
400 60 360 440 20 983.5 1200 1200 115 60
450
460 60 414 506 20 853.7 1200 1000 115 60
575 60 518 633 20 684.6 800 800 115 60
380 60 342 418 22 1136.6 1200 1200 115 60
400 60 360 440 22 1080.7 1200 1200 115 60
500
460 60 414 506 22 937.8 1200 1200 115 60
575 60 518 633 22 749.4 1000 1000 115 60
See Legend and Notes on page 115.

116
Table 11 — 60 Hz Single Point Power Standard Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE NO HYDRONIC PACKAGE CONTROL CIRCUIT
NO. OF
UNIT 30XV Supplied COND Standard Condenser Fans High Static Condenser Fans Voltage MCA
V(3 Ph) Hz FANS 1 Ph, and
Min Max MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE 60 Hz MOCP
208/230 60 187 253 8 689.4 800 800 699.8 800 800 115 60
380 60 342 418 8 377.4 500 450 383.0 500 450 115 60
160 400 60 360 440 8 359.4 450 400 364.9 500 400 115 60
460 60 414 506 8 311.5 400 350 316.3 400 350 115 60
575 60 518 633 8 251.1 300 300 255.1 350 300 115 60
208/230 60 187 253 8 790.7 1000 1000 801.1 1000 1000 115 60
380 60 342 418 8 433.7 600 500 439.3 600 500 115 60
180 400 60 360 440 8 411.1 500 500 416.6 500 500 115 60
460 60 414 506 8 357.2 450 400 362.0 500 400 115 60
575 60 518 633 8 287.1 350 350 291.1 400 350 115 60
208/230 60 187 253 10 823.1 1000 1000 836.1 1000 1000 115 60
380 60 342 418 10 452.0 600 500 459.0 600 600 115 60
200 400 60 360 440 10 428.9 500 500 435.8 500 500 115 60
460 60 414 506 10 372.0 500 450 378.0 500 450 115 60
575 60 518 633 10 299.2 400 350 304.2 400 350 115 60
380 60 342 418 10 519.1 700 600 526.1 700 600 115 60
400 60 360 440 10 494.2 700 600 501.1 700 600 115 60
225
460 60 414 506 10 428.3 600 500 434.3 600 500 115 60
575 60 518 633 10 342.7 500 400 347.7 500 400 115 60
380 60 342 418 12 598.7 800 700 607.1 800 700 115 60
400 60 360 440 12 568.2 700 700 576.5 700 700 115 60
250
460 60 414 506 12 493.0 600 600 500.2 600 600 115 60
575 60 518 633 12 396.0 500 450 402.0 500 450 115 60
380 60 342 418 12 618.9 800 700 627.3 800 700 115 60
400 60 360 440 12 588.5 800 700 596.7 800 700 115 60
275
460 60 414 506 12 510.6 700 600 517.8 700 600 115 60
575 60 518 633 12 409.5 500 450 415.5 500 500 115 60
380 60 342 418 14 659.8 800 800 669.6 800 800 115 60
400 60 360 440 14 628.7 800 700 638.4 800 700 115 60
300
460 60 414 506 14 544.9 700 600 553.3 700 700 115 60
575 60 518 633 14 437.4 600 500 444.4 600 500 115 60
380 60 342 418 16 727.6 1000 800 738.8 1000 1000 115 60
400 60 360 440 16 691.5 800 800 702.5 800 800 115 60
325
460 60 414 506 16 600.2 800 700 609.8 800 700 115 60
575 60 518 633 16 481.0 600 600 489.0 600 600 115 60
380 60 342 418 16 846.4 1200 1000 857.6 1200 1000 115 60
400 60 360 440 16 805.0 1000 1000 816.0 1000 1000 115 60
350
460 60 414 506 16 698.7 1000 800 708.3 1000 800 115 60
575 60 518 633 16 559.2 800 700 567.2 800 700 115 60
380 60 342 418 18 897.4 1200 1000 910.0 1200 1000 115 60
400 60 360 440 18 853.9 1000 1000 866.3 1000 1000 115 60
400
460 60 414 506 18 740.4 1000 1000 751.2 1000 1000 115 60
575 60 518 633 18 592.5 800 700 601.5 800 700 115 60
380 60 342 418 20 1066.5 1200 1200 1080.5 1200 1200 115 60
400 60 360 440 20 1013.4 1200 1200 1027.2 1200 1200 115 60
450
460 60 414 506 20 880.9 1200 1000 892.9 1200 1000 115 60
575 60 518 633 20 705.8 800 800 715.8 800 800 115 60
380 60 342 418 22 1150.1 1600 1600 1165.5 1600 1600 115 60
400 60 360 440 22 1091.9 1200 1200 1107.1 1200 1200 115 60
500
460 60 414 506 22 949.3 1200 1200 962.5 1200 1200 115 60
575 60 518 633 22 760.7 1000 1000 771.7 1000 1000 115 60
See Legend and Notes on page 115.

117
Table 12 — 60 Hz Single Point Power Standard Tier Fan Motors with Control Power Transformer, with
Electrically Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
CONTROL
UNIT VOLTAGE NO HYDRONIC PACKAGE
NO. OF CIRCUIT
UNIT 30XV Supplied COND ECM Fans Voltage MCA
V(3 Ph) Hz FANS 1 Ph, and
Min Max MCA MOCP FUSE SIZE 60 Hz MOCP
380 60 342 418 8 361.2 450 400 115 60
160 400 60 360 440 8 344.0 450 400 115 60
460 60 414 506 8 298.1 400 350 115 60
380 60 342 418 8 414.7 500 500 115 60
180 400 60 360 440 8 393.1 500 450 115 60
460 60 414 506 8 341.5 450 400 115 60
380 60 342 418 10 432.7 500 500 115 60
200 400 60 360 440 10 410.5 500 450 115 60
460 60 414 506 10 356.1 450 400 115 60
380 60 342 418 10 496.5 700 600 115 60
225 400 60 360 440 10 472.7 600 600 115 60
460 60 414 506 10 409.7 500 500 115 60
380 60 342 418 12 572.7 700 700 115 60
250 400 60 360 440 12 543.6 700 600 115 60
460 60 414 506 12 471.7 600 600 115 60
380 60 342 418 12 591.9 800 700 115 60
275 400 60 360 440 12 562.8 700 700 115 60
460 60 414 506 12 488.3 600 600 115 60
380 60 342 418 14 631.3 800 700 115 60
300 400 60 360 440 14 601.6 800 700 115 60
460 60 414 506 14 521.4 700 600 115 60
380 60 342 418 16 696.4 800 800 115 60
325 400 60 360 440 16 661.8 800 800 115 60
460 60 414 506 16 574.4 700 700 115 60

See Legend and Notes on page 115.

118
Table 13 — 60 Hz Single Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS
NO. OF NO HYDRONIC 7.5 HP Pump, N+0, 10 HP Pump, N+0, 10 HP Pump, — N+0,
UNIT Supplied
COND PACKAGE Low Static Low Static High Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE SIZE
208/230 60 187 253 8 594.9 800 700 — — — — — — — — —
380 60 342 418 8 325.7 400 400 — — — — — — — — —
140 400 60 360 440 8 309.9 400 350 — — — — — — — — —
460 60 414 506 8 269.0 350 300 — — — — — — — — —
575 60 518 633 8 215.1 250 250 — — — — — — — — —
208/230 60 187 253 10 654.4 800 800 715.7 800 800 — — — 729.7 800 800
380 60 342 418 10 357.5 450 400 — — — — — — — — —
160 400 60 360 440 10 341.1 450 400 — — — — — — — — —
460 60 414 506 10 295.0 400 350 323.7 400 400 — — — 333.7 400 400
575 60 518 633 10 236.2 300 300 259.1 300 300 — — — 267.1 350 300
208/230 60 187 253 10 737.6 1000 1000 799.0 1000 1000 — — — 813.0 1000 1000
380 60 342 418 10 404.8 500 450 — — — — — — — — —
180 400 60 360 440 10 383.9 500 450 — — — — — — — — —
460 60 414 506 10 332.8 450 400 361.5 450 400 — — — 371.5 450 450
575 60 518 633 10 267.7 350 300 290.6 350 350 — — — 298.6 350 350
208/230 60 187 253 12 826.0 1000 1000 — — — 937.4 1200 1200 937.4 1200 1200
380 60 342 418 12 452.4 600 500 — — — — — — — — —
200 400 60 360 440 12 431.0 500 500 — — — — — — — — —
460 60 414 506 12 372.7 500 450 — — — 430.0 500 500 430.0 500 500
575 60 518 633 12 299.3 400 350 — — — 345.1 450 400 345.1 450 400
380 60 342 418 12 506.4 700 600 — — — — — — — — —
400 60 360 440 12 481.2 600 600 — — — — — — — — —
225
460 60 414 506 12 417.1 600 500 — — — — — — — — —
575 60 518 633 12 334.0 450 400 — — — — — — — — —
380 60 342 418 14 572.0 700 700 — — — — — — — — —
400 60 360 440 14 545.5 700 600 — — — — — — — — —
250
460 60 414 506 14 472.3 600 600 — — — — — — — — —
575 60 518 633 14 378.9 500 450 — — — — — — — — —
380 60 342 418 14 612.5 800 700 — — — — — — — — —
400 60 360 440 14 581.5 800 700 — — — — — — — — —
275
460 60 414 506 14 505.1 600 600 — — — — — — — — —
575 60 518 633 14 403.6 500 450 — — — — — — — — —
380 60 342 418 16 639.9 800 700 — — — — — — — — —
400 60 360 440 16 608.2 800 700 — — — — — — — — —
300
460 60 414 506 16 527.3 700 600 — — — 584.6 700 700 603.2 800 700
575 60 518 633 16 422.5 500 500 — — — 468.3 600 600 483.2 600 600
380 60 342 418 18 696.5 800 800 — — — — — — — — —
400 60 360 440 18 662.0 800 800 — — — — — — — — —
325
460 60 414 506 18 575.2 700 700 — — — 632.5 800 700 651.1 800 800
575 60 518 633 18 461.6 600 600 — — — 507.4 600 600 522.3 600 600
380 60 342 418 18 787.0 1000 1000 — — — — — — — — —
400 60 360 440 18 748.5 1000 1000 — — — — — — — — —
350
460 60 414 506 18 648.9 800 800 — — — — — — — — —
575 60 518 633 18 518.8 700 600 — — — — — — — — —
380 60 342 418 20 891.0 1200 1000 — — — — — — — — —
400 60 360 440 20 846.9 1000 1000 — — — — — — — — —
400
460 60 414 506 20 734.9 1000 1000 — — — — — — — — —
575 60 518 633 20 588.8 800 700 — — — — — — — — —
380 60 342 418 22 1062.3 1200 1200 — — — — — — — — —
400 60 360 440 22 1008.7 1200 1200 — — — — — — — — —
450
460 60 414 506 22 875.9 1200 1000 — — — — — — — — —
575 60 518 633 22 699.9 800 800 — — — — — — — — —
380 60 342 418 24 1118.9 1200 1200 — — — — — — — — —
400 60 360 440 24 1064.7 1200 1200 — — — — — — — — —
500
460 60 414 506 24 924.0 1200 1200 — — — — — — — — —
575 60 518 633 24 739.0 1000 1000 — — — — — — — — —
See Legend and Notes on page 115.

119
Table 13 — 60 Hz Single Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
UNIT VOLTAGE STANDARD CONDENSER FANS
NO. OF 7.5 HP Pump, N+1, 10 HP Pump, N+1, 10 HP Pump, N+1,
UNIT Supplied
COND Low Static Low Static High Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE
208/230 60 187 253 8 — — — — — — — — —
380 60 342 418 8 — — — — — — — — —
140 400 60 360 440 8 — — — — — — — — —
460 60 414 506 8 — — — — — — — — —
575 60 518 633 8 — — — — — — — — —
208/230 60 187 253 10 — — — — — — — — —
380 60 342 418 10 — — — — — — — — —
160 400 60 360 440 10 — — — — — — — — —
460 60 414 506 10 — — — — — — — — —
575 60 518 633 10 — — — — — — — — —
208/230 60 187 253 10 — — — — — — — — —
380 60 342 418 10 — — — — — — — — —
180 400 60 360 440 10 — — — — — — — — —
460 60 414 506 10 — — — — — — — — —
575 60 518 633 10 — — — — — — — — —
208/230 60 187 253 12 — — — 973.4 1200 1200 973.4 1200 1200
380 60 342 418 12 — — — — — — — — —
200 400 60 360 440 12 — — — — — — — — —
460 60 414 506 12 — — — 448.6 500 500 448.6 500 500
575 60 518 633 12 — — — 360.0 450 400 360.0 450 400
380 60 342 418 12 — — — — — — — — —
400 60 360 440 12 — — — — — — — — —
225
460 60 414 506 12 — — — — — — — — —
575 60 518 633 12 — — — — — — — — —
380 60 342 418 14 — — — — — — — — —
400 60 360 440 14 — — — — — — — — —
250
460 60 414 506 14 — — — — — — — — —
575 60 518 633 14 — — — — — — — — —
380 60 342 418 14 — — — — — — — — —
400 60 360 440 14 — — — — — — — — —
275
460 60 414 506 14 — — — — — — — — —
575 60 518 633 14 — — — — — — — — —
380 60 342 418 16 — — — — — — — — —
400 60 360 440 16 — — — — — — — — —
300
460 60 414 506 16 — — — 603.2 800 700 — — —
575 60 518 633 16 — — — 483.2 600 600 — — —
380 60 342 418 18 — — — — — — — — —
400 60 360 440 18 — — — — — — — — —
325
460 60 414 506 18 — — — 651.1 800 800 — — —
575 60 518 633 18 — — — 522.3 600 600 — — —
380 60 342 418 18 — — — — — — — — —
400 60 360 440 18 — — — — — — — — —
350
460 60 414 506 18 — — — — — — — — —
575 60 518 633 18 — — — — — — — — —
380 60 342 418 20 — — — — — — — — —
400 60 360 440 20 — — — — — — — — —
400
460 60 414 506 20 — — — — — — — — —
575 60 518 633 20 — — — — — — — — —
380 60 342 418 22 — — — — — — — — —
400 60 360 440 22 — — — — — — — — —
450
460 60 414 506 22 — — — — — — — — —
575 60 518 633 22 — — — — — — — — —
380 60 342 418 24 — — — — — — — — —
400 60 360 440 24 — — — — — — — — —
500
460 60 414 506 24 — — — — — — — — —
575 60 518 633 24 — — — — — — — — —
See Legend and Notes on page 115.

120
Table 13 — 60 Hz Single Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
UNIT VOLTAGE HIGH STATIC CONDENSER FANS
NO. OF NO HYDRONIC 7.5 HP Pump, N+0, 10 HP Pump, N+0, 10 HP Pump, N+0,
UNIT Supplied
COND PACKAGE Low Static Low Static High Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE SIZE
208/230 60 187 253 8 605.3 800 700 — — — — — — — — —
380 60 342 418 8 331.3 450 400 — — — — — — — — —
140 400 60 360 440 8 315.4 400 350 — — — — — — — — —
460 60 414 506 8 273.8 350 300 — — — — — — — — —
575 60 518 633 8 219.1 250 250 — — — — — — — — —
208/230 60 187 253 10 667.4 800 800 728.7 800 800 — — — 742.7 800 800
380 60 342 418 10 364.5 450 400 — — — — — — — — —
160 400 60 360 440 10 348.0 450 400 — — — — — — — — —
460 60 414 506 10 301.0 400 350 329.7 400 400 — — — 339.7 400 400
575 60 518 633 10 241.2 300 300 264.1 350 300 — — — 272.1 350 300
208/230 60 187 253 10 750.6 1000 1000 812.0 1000 1000 — — — 826.0 1000 1000
380 60 342 418 10 411.8 500 450 — — — — — — — — —
180 400 60 360 440 10 390.8 500 450 — — — — — — — — —
460 60 414 506 10 338.8 450 400 367.5 450 400 — — — 377.5 500 450
575 60 518 633 10 272.7 350 300 295.6 350 350 — — — 303.6 400 350
208/230 60 187 253 12 841.6 1000 1000 — — — 953.0 1200 1200 953.0 1200 1200
380 60 342 418 12 460.8 600 600 — — — — — — — — —
200 400 60 360 440 12 439.2 500 500 — — — — — — — — —
460 60 414 506 12 379.9 500 450 — — — 437.2 500 500 437.2 500 500
575 60 518 633 12 305.3 400 350 — — — 351.1 450 400 351.1 450 400
380 60 342 418 12 514.8 700 600 — — — — — — — — —
400 60 360 440 12 489.5 700 600 — — — — — — — — —
225
460 60 414 506 12 424.3 600 500 — — — — — — — — —
575 60 518 633 12 340.0 450 400 — — — — — — — — —
380 60 342 418 14 581.8 700 700 — — — — — — — — —
400 60 360 440 14 555.1 700 700 — — — — — — — — —
250
460 60 414 506 14 480.7 600 600 — — — — — — — — —
575 60 518 633 14 385.9 500 450 — — — — — — — — —
380 60 342 418 14 622.3 800 700 — — — — — — — — —
400 60 360 440 14 591.1 800 700 — — — — — — — — —
275
460 60 414 506 14 513.5 700 600 — — — — — — — — —
575 60 518 633 14 410.6 500 450 — — — — — — — — —
380 60 342 418 16 651.1 800 800 — — — — — — — — —
400 60 360 440 16 619.3 800 700 — — — — — — — — —
300
460 60 414 506 16 536.9 700 600 — — — 594.2 700 700 612.8 800 700
575 60 518 633 16 430.5 500 500 — — — 476.3 600 600 491.2 600 600
380 60 342 418 18 709.1 800 800 — — — — — — — — —
400 60 360 440 18 674.4 800 800 — — — — — — — — —
325
460 60 414 506 18 586.0 700 700 — — — 643.3 800 700 661.9 800 800
575 60 518 633 18 470.6 600 600 — — — 516.4 600 600 531.3 700 600
380 60 342 418 18 799.6 1000 1000 — — — — — — — — —
400 60 360 440 18 760.9 1000 1000 — — — — — — — — —
350
460 60 414 506 18 659.7 800 800 — — — — — — — — —
575 60 518 633 18 527.8 700 600 — — — — — — — — —
380 60 342 418 20 905.0 1200 1000 — — — — — — — — —
400 60 360 440 20 860.7 1000 1000 — — — — — — — — —
400
460 60 414 506 20 746.9 1000 1000 — — — — — — — — —
575 60 518 633 20 598.8 800 700 — — — — — — — — —
380 60 342 418 22 1077.7 1200 1200 — — — — — — — — —
400 60 360 440 22 1023.9 1200 1200 — — — — — — — — —
450
460 60 414 506 22 889.1 1200 1000 — — — — — — — — —
575 60 518 633 22 710.9 800 800 — — — — — — — — —
380 60 342 418 24 1135.7 1200 1200 — — — — — — — — —
400 60 360 440 24 1081.3 1200 1200 — — — — — — — — —
500
460 60 414 506 24 938.4 1200 1200 — — — — — — — — —
575 60 518 633 24 751.0 1000 1000 — — — — — — — — —
See Legend and Notes on page 115.

121
Table 13 — 60 Hz Single Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
CONTROL
UNIT VOLTAGE HIGH STATIC CONDENSER FANS
CIRCUIT
NO. OF
UNIT 7.5 HP Pump, N+0, 10 HP Pump, N+0, 10 HP Pump, N+0,
Supplied COND Voltage MCA
30XV Low Static Low Static High Static
V(3 Ph) Hz FANS 1 Ph, and
FUSE FUSE FUSE 60 Hz MOCP
Min Max MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE
208/230 60 187 253 8 — — — — — — — — — 115 60
380 60 342 418 8 — — — — — — — — — 115 60
140 400 60 360 440 8 — — — — — — — — — 115 60
460 60 414 506 8 — — — — — — — — — 115 60
575 60 518 633 8 — — — — — — — — — 115 60
208/230 60 187 253 10 — — — — — — — — — 115 60
380 60 342 418 10 — — — — — — — — — 115 60
160 400 60 360 440 10 — — — — — — — — — 115 60
460 60 414 506 10 — — — — — — — — — 115 60
575 60 518 633 10 — — — — — — — — — 115 60
208/230 60 187 253 10 — — — — — — — — — 115 60
380 60 342 418 10 — — — — — — — — — 115 60
180 400 60 360 440 10 — — — — — — — — — 115 60
460 60 414 506 10 — — — — — — — — — 115 60
575 60 518 633 10 — — — — — — — — — 115 60
208/230 60 187 253 12 — — — 989.0 1200 1200 989.0 1200 1200 115 60
380 60 342 418 12 — — — — — — — — — 115 60
200 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 — — — 455.8 500 500 455.8 500 500 115 60
575 60 518 633 12 — — — 366.0 450 400 366.0 450 400 115 60
380 60 342 418 12 — — — — — — — — — 115 60
400 60 360 440 12 — — — — — — — — — 115 60
225
460 60 414 506 12 — — — — — — — — — 115 60
575 60 518 633 12 — — — — — — — — — 115 60
380 60 342 418 14 — — — — — — — — — 115 60
400 60 360 440 14 — — — — — — — — — 115 60
250
460 60 414 506 14 — — — — — — — — — 115 60
575 60 518 633 14 — — — — — — — — — 115 60
380 60 342 418 14 — — — — — — — — — 115 60
400 60 360 440 14 — — — — — — — — — 115 60
275
460 60 414 506 14 — — — — — — — — — 115 60
575 60 518 633 14 — — — — — — — — — 115 60
380 60 342 418 16 — — — — — — — — — 115 60
400 60 360 440 16 — — — — — — — — — 115 60
300
460 60 414 506 16 — — — 612.8 800 700 — — — 115 60
575 60 518 633 16 — — — 491.2 600 600 — — — 115 60
380 60 342 418 18 — — — — — — — — — 115 60
400 60 360 440 18 — — — — — — — — — 115 60
325
460 60 414 506 18 — — — 661.9 800 800 — — — 115 60
575 60 518 633 18 — — — 531.3 700 600 — — — 115 60
380 60 342 418 18 — — — — — — — — — 115 60
400 60 360 440 18 — — — — — — — — — 115 60
350
460 60 414 506 18 — — — — — — — — — 115 60
575 60 518 633 18 — — — — — — — — — 115 60
380 60 342 418 20 — — — — — — — — — 115 60
400 60 360 440 20 — — — — — — — — — 115 60
400
460 60 414 506 20 — — — — — — — — — 115 60
575 60 518 633 20 — — — — — — — — — 115 60
380 60 342 418 22 — — — — — — — — — 115 60
400 60 360 440 22 — — — — — — — — — 115 60
450
460 60 414 506 22 — — — — — — — — — 115 60
575 60 518 633 22 — — — — — — — — — 115 60
380 60 342 418 24 — — — — — — — — — 115 60
400 60 360 440 24 — — — — — — — — — 115 60
500
460 60 414 506 24 — — — — — — — — — 115 60
575 60 518 633 24 — — — — — — — — — 115 60
See Legend and Notes on page 115.

122
Table 14 — 60 Hz Single Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM FANS
NO. OF NO HYDRONIC 7.5 HP Pump, N+0, 10 HP Pump, N+0, 10 HP Pump, N+0,
UNIT Supplied
COND PACKAGE Low Static Low Static High Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE SIZE
380 60 342 418 8 312.1 400 350 — — — — — — — — —
140 400 60 360 440 8 296.9 400 350 — — — — — — — — —
460 60 414 506 8 257.7 350 300 — — — — — — — — —
380 60 342 418 10 342.9 450 400 — — — — — — — — —
160 400 60 360 440 10 327.2 400 400 — — — — — — — — —
460 60 414 506 10 283.0 350 350 311.7 400 350 — — — 321.7 400 350
380 60 342 418 10 387.8 500 450 — — — — — — — — —
180 400 60 360 440 10 367.8 500 450 — — — — — — — — —
460 60 414 506 10 318.9 400 350 347.6 450 400 — — — 357.6 450 400
380 60 342 418 12 433.8 500 500 — — — — — — — — —
200 400 60 360 440 12 413.2 500 500 — — — — — — — — —
460 60 414 506 12 357.3 450 400 — — — 414.6 500 450 414.6 500 450
380 60 342 418 12 485.1 600 600 — — — — — — — — —
225 400 60 360 440 12 460.9 600 600 — — — — — — — — —
460 60 414 506 12 399.5 500 450 — — — — — — — — —
380 60 342 418 14 548.0 700 600 — — — — — — — — —
250 400 60 360 440 14 522.5 700 600 — — — — — — — — —
460 60 414 506 14 452.4 600 500 — — — — — — — — —
380 60 342 418 14 586.4 800 700 — — — — — — — — —
275 400 60 360 440 14 556.7 700 700 — — — — — — — — —
460 60 414 506 14 483.6 600 600 — — — — — — — — —
380 60 342 418 16 613.0 800 700 — — — — — — — — —
300 400 60 360 440 16 582.7 700 700 — — — — — — — — —
460 60 414 506 16 505.2 600 600 — — — 562.5 700 700 581.1 700 700
380 60 342 418 18 667.4 800 800 — — — — — — — — —
325 400 60 360 440 18 634.3 800 700 — — — — — — — — —
460 60 414 506 18 551.1 700 700 — — — 608.4 800 700 627.0 800 700

Table 14 — 60 Hz Single Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
CONTROL
UNIT VOLTAGE ECM FANS
CIRCUIT
NO. OF
UNIT 7.5 HP Pump, N+1, Low 10 HP Pump, N+1, Low 10 HP Pump, N+1, High
Supplied COND Voltage MCA
30XV Static Static Static
V(3 Ph) Hz FANS 1 Ph, and
FUSE FUSE FUSE 60 Hz MOCP
Min Max MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE
380 60 342 418 8 — — — — — — — — — 115 60
140 400 60 360 440 8 — — — — — — — — — 115 60
460 60 414 506 8 — — — — — — — — — 115 60
380 60 342 418 10 — — — — — — — — — 115 60
160 400 60 360 440 10 — — — — — — — — — 115 60
460 60 414 506 10 — — — — — — — — — 115 60
380 60 342 418 10 — — — — — — — — — 115 60
180 400 60 360 440 10 — — — — — — — — — 115 60
460 60 414 506 10 — — — — — — — — — 115 60
380 60 342 418 12 — — — — — — — — — 115 60
200 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 — — — 433.2 500 500 433.2 500 500 115 60
380 60 342 418 12 — — — — — — — — — 115 60
225 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 — — — — — — — — — 115 60
380 60 342 418 14 — — — — — — — — — 115 60
250 400 60 360 440 14 — — — — — — — — — 115 60
460 60 414 506 14 — — — — — — — — — 115 60
380 60 342 418 14 — — — — — — — — — 115 60
275 400 60 360 440 14 — — — — — — — — — 115 60
460 60 414 506 14 — — — — — — — — — 115 60
380 60 342 418 16 — — — — — — — — — 115 60
300 400 60 360 440 16 — — — — — — — — — 115 60
460 60 414 506 16 — — — 581.1 700 700 — — — 115 60
380 60 342 418 18 — — — — — — — — — 115 60
325 400 60 360 440 18 — — — — — — — — — 115 60
460 60 414 506 18 — — — 627.0 800 700 — — — 115 60
See Legend and Notes on page 115.

123
Table 15 — 60 Hz Single Point Power High Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS
NO. OF 7.5 HP Pump, N+0, 10 HP Pump, N+0,
UNIT Supplied No Hydronic Package
COND Low Static Low Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE
208/230 60 187 253 10 571.1 700 700 632.5 800 700 — — —
380 60 342 418 10 312.5 400 350 — — — — — —
140 400 60 360 440 10 298.4 400 350 — — — — — —
460 60 414 506 10 257.9 300 300 286.6 350 350 — — —
575 60 518 633 10 206.9 250 250 229.9 300 250 — — —
208/230 60 187 253 12 659.8 800 800 721.2 800 800 — — —
380 60 342 418 12 362.4 450 400 — — — — — —
160 400 60 360 440 12 343.2 450 400 — — — — — —
460 60 414 506 12 297.9 400 350 326.6 400 400 — — —
575 60 518 633 12 239.3 300 300 262.2 300 300 — — —
208/230 60 187 253 12 866.8 1000 1000 928.2 1200 1200 — — —
380 60 342 418 12 474.9 600 600 — — — — — —
180 400 60 360 440 12 388.2 500 450 — — — — — —
460 60 414 506 12 336.1 450 400 364.8 450 400 — — —
575 60 518 633 12 268.5 350 300 291.5 350 350 — — —
208/230 60 187 253 14 818.0 1000 1000 — — — 929.3 1200 1200
380 60 342 418 14 448.3 600 500 — — — — — —
200 400 60 360 440 14 426.2 500 500 — — — — — —
460 60 414 506 14 369.2 500 450 — — — 426.5 500 500
575 60 518 633 14 295.6 400 350 — — — 341.5 400 400
380 60 342 418 14 500.8 700 600 — — — — — —
400 60 360 440 14 477.2 600 600 — — — — — —
225
460 60 414 506 14 413.5 500 500 — — — 470.8 600 600
575 60 518 633 14 331.4 450 400 — — — 377.2 500 450
380 60 342 418 16 567.9 700 700 — — — — — —
400 60 360 440 16 540.7 700 600 — — — — — —
250
460 60 414 506 16 468.6 600 600 — — — 525.9 600 600
575 60 518 633 16 375.2 500 450 — — — 421.1 500 500
380 60 342 418 16 603.9 800 700 — — — — — —
400 60 360 440 16 574.5 700 700 — — — — — —
275
460 60 414 506 16 498.5 600 600 — — — 555.8 700 700
575 60 518 633 16 400.0 500 450 — — — 445.8 500 500
380 60 342 418 18 635.7 800 700 — — — — — —
400 60 360 440 18 603.5 800 700 — — — — — —
300
460 60 414 506 18 523.6 700 600 — — — 581.0 700 700
575 60 518 633 18 418.8 500 500 — — — 464.7 600 600
380 60 342 418 20 696.8 800 800 — — — — — —
400 60 360 440 20 664.0 800 800 — — — — — —
325
460 60 414 506 20 575.5 700 700 — — — 632.9 800 700
575 60 518 633 20 460.2 600 600 — — — 506.0 600 600
380 60 342 418 20 794.1 1000 1000 — — — — — —
400 60 360 440 20 753.8 1000 1000 — — — — — —
350
460 60 414 506 20 655.0 800 800 — — — — — —
575 60 518 633 20 524.4 700 600 — — — — — —
380 60 342 418 22 902.6 1200 1000 — — — — — —
400 60 360 440 22 857.9 1000 1000 — — — — — —
400
460 60 414 506 22 745.2 1000 1000 — — — — — —
575 60 518 633 22 596.4 800 700 — — — — — —
380 60 342 418 24 977.2 1200 1200 — — — — — —
400 60 360 440 24 929.7 1200 1200 — — — — — —
450
460 60 414 506 24 807.4 1000 1000 — — — — — —
575 60 518 633 24 646.8 800 800 — — — — — —
See Legend and Notes on page 115.

124
Table 15 — 60 Hz Single Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
UNIT VOLTAGE STANDARD CONDENSER FANS
NO. OF 10 HP Pump, N+0, 7.5 HP Pump, N+1, 10 HP Pump, N+1, 10 HP Pump, N+1,
UNIT Supplied
COND High Static Low Static Low Static High Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE SIZE
208/230 60 187 253 10 646.5 800 700 — — — — — — — — —
380 60 342 418 10 — — — — — — — — — — — —
140 400 60 360 440 10 — — — — — — — — — — — —
460 60 414 506 10 296.6 350 350 — — — — — — — — —
575 60 518 633 10 237.9 300 300 — — — — — — — — —
208/230 60 187 253 12 735.2 800 800 750.2 800 800 — — — 771.2 1000 1000
380 60 342 418 12 — — — — — — — — — — — —
160 400 60 360 440 12 — — — — — — — — — — — —
460 60 414 506 12 336.6 400 400 340.2 400 400 — — — 355.2 450 400
575 60 518 633 12 270.2 350 300 273.1 350 300 — — — 285.1 350 350
208/230 60 187 253 12 942.2 1200 1200 957.2 1200 1200 — — — 978.2 1200 1200
380 60 342 418 12 — — — — — — — — — — — —
180 400 60 360 440 12 — — — — — — — — — — — —
460 60 414 506 12 374.8 450 450 378.4 450 450 — — — 393.4 500 450
575 60 518 633 12 299.5 350 350 302.4 350 350 — — — 314.4 400 350
208/230 60 187 253 14 929.3 1200 1200 — — — 965.3 1200 1200 965.3 1200 1200
380 60 342 418 14 — — — — — — — — — — — —
200 400 60 360 440 14 — — — — — — — — — — — —
460 60 414 506 14 426.5 500 500 — — — 445.1 500 500 445.1 500 500
575 60 518 633 14 341.5 400 400 — — — 356.4 450 400 356.4 450 400
380 60 342 418 14 — — — — — — — — — — — —
400 60 360 440 14 — — — — — — — — — — — —
225
460 60 414 506 14 470.8 600 600 — — — 489.4 600 600 489.4 600 600
575 60 518 633 14 377.2 500 450 — — — 392.1 500 450 392.1 500 450
380 60 342 418 16 — — — — — — — — — — — —
400 60 360 440 16 — — — — — — — — — — — —
250
460 60 414 506 16 525.9 600 600 — — — 544.5 700 600 544.5 700 600
575 60 518 633 16 421.1 500 500 — — — 436.0 500 500 436.0 500 500
380 60 342 418 16 — — — — — — — — — — — —
400 60 360 440 16 — — — — — — — — — — — —
275
460 60 414 506 16 574.4 700 700 — — — 574.4 700 700 — — —
575 60 518 633 16 460.7 600 500 — — — 460.7 600 500 — — —
380 60 342 418 18 — — — — — — — — — — — —
400 60 360 440 18 — — — — — — — — — — — —
300
460 60 414 506 18 599.6 700 700 — — — 599.6 700 700 — — —
575 60 518 633 18 479.6 600 600 — — — 479.6 600 600 — — —
380 60 342 418 20 — — — — — — — — — — — —
400 60 360 440 20 — — — — — — — — — — — —
325
460 60 414 506 20 651.5 800 800 — — — 651.5 800 800 — — —
575 60 518 633 20 520.9 600 600 — — — 520.9 600 600 — — —
380 60 342 418 20 — — — — — — — — — — — —
400 60 360 440 20 — — — — — — — — — — — —
350
460 60 414 506 20 — — — — — — — — — — — —
575 60 518 633 20 — — — — — — — — — — — —
380 60 342 418 22 — — — — — — — — — — — —
400 60 360 440 22 — — — — — — — — — — — —
400
460 60 414 506 22 — — — — — — — — — — — —
575 60 518 633 22 — — — — — — — — — — — —
380 60 342 418 24 — — — — — — — — — — — —
400 60 360 440 24 — — — — — — — — — — — —
450
460 60 414 506 24 — — — — — — — — — — — —
575 60 518 633 24 — — — — — — — — — — — —
See Legend and Notes on page 115.

125
Table 15 — 60 Hz Single Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
UNIT VOLTAGE HIGH STATIC CONDENSER FANS
NO. OF 7.5 HP Pump, N+0, Low 10 HP Pump, N+0, Low 10 HP Pump, N+0, High
UNIT Supplied No Hydronic Package
COND Static Static Static
30XV V(3 Ph) Hz FANS FUSE FUSE FUSE FUSE
Min Max MCA MOCP MCA MOCP MCA MOCP MCA MOCP
SIZE SIZE SIZE SIZE
208/230 60 187 253 10 584.1 700 700 645.5 800 700 — — — 659.5 800 800
380 60 342 418 10 319.5 400 350 — — — — — — — — —
140 400 60 360 440 10 305.3 400 350 — — — — — — — — —
460 60 414 506 10 263.9 350 300 292.6 350 350 — — — 302.6 350 350
575 60 518 633 10 211.9 250 250 234.9 300 300 — — — 242.9 300 300
208/230 60 187 253 12 675.4 800 800 736.8 800 800 — — — 750.8 800 800
380 60 342 418 12 370.8 450 450 — — — — — — — — —
160 400 60 360 440 12 351.4 450 400 — — — — — — — — —
460 60 414 506 12 305.1 400 350 333.8 400 400 — — — 343.8 400 400
575 60 518 633 12 245.3 300 300 268.2 350 300 — — — 276.2 350 300
208/230 60 187 253 12 882.4 1200 1000 943.8 1200 1200 — — — 957.8 1200 1200
380 60 342 418 12 483.3 600 600 — — — — — — — — —
180 400 60 360 440 12 396.4 500 450 — — — — — — — — —
460 60 414 506 12 343.3 450 400 372.0 450 450 — — — 382.0 500 450
575 60 518 633 12 274.5 350 300 297.5 350 350 — — — 305.5 400 350
208/230 60 187 253 14 836.2 1000 1000 — — — 947.5 1200 1200 947.5 1200 1200
380 60 342 418 14 458.1 600 500 — — — — — — — — —
200 400 60 360 440 14 435.9 500 500 — — — — — — — — —
460 60 414 506 14 377.6 500 450 — — — 434.9 500 500 434.9 500 500
575 60 518 633 14 302.6 400 350 — — — 348.5 450 400 348.5 450 400
380 60 342 418 14 510.6 700 600 — — — — — — — — —
400 60 360 440 14 486.9 600 600 — — — — — — — — —
225
460 60 414 506 14 421.9 600 500 — — — 479.2 600 600 479.2 600 600
575 60 518 633 14 338.4 450 400 — — — 384.2 500 450 384.2 500 450
380 60 342 418 16 579.1 700 700 — — — — — — — — —
400 60 360 440 16 551.8 700 700 — — — — — — — — —
250
460 60 414 506 16 478.2 600 600 — — — 535.5 700 600 535.5 700 600
575 60 518 633 16 383.2 500 450 — — — 429.1 500 500 429.1 500 500
380 60 342 418 16 615.1 800 700 — — — — — — — — —
400 60 360 440 16 585.5 700 700 — — — — — — — — —
275
460 60 414 506 16 508.1 600 600 — — — 565.4 700 700 584.0 700 700
575 60 518 633 16 408.0 500 450 — — — 453.8 600 500 468.7 600 600
380 60 342 418 18 648.3 800 800 — — — — — — — — —
400 60 360 440 18 615.9 800 700 — — — — — — — — —
300
460 60 414 506 18 534.4 700 600 — — — 591.8 700 700 610.4 800 700
575 60 518 633 18 427.8 500 500 — — — 473.7 600 600 488.6 600 600
380 60 342 418 20 710.8 800 800 — — — — — — — — —
400 60 360 440 20 677.8 800 800 — — — — — — — — —
325
460 60 414 506 20 587.5 700 700 — — — 644.9 800 700 663.5 800 800
575 60 518 633 20 470.2 600 600 — — — 516.0 600 600 530.9 600 600
380 60 342 418 20 808.1 1000 1000 — — — — — — — — —
400 60 360 440 20 767.6 1000 1000 — — — — — — — — —
350
460 60 414 506 20 667.0 800 800 — — — — — — — — —
575 60 518 633 20 534.4 700 600 — — — — — — — — —
380 60 342 418 22 918.0 1200 1200 — — — — — — — — —
400 60 360 440 22 873.1 1000 1000 — — — — — — — — —
400
460 60 414 506 22 758.4 1000 1000 — — — — — — — — —
575 60 518 633 22 607.4 800 700 — — — — — — — — —
380 60 342 418 24 994.0 1200 1200 — — — — — — — — —
400 60 360 440 24 946.3 1200 1200 — — — — — — — — —
450
460 60 414 506 24 821.8 1000 1000 — — — — — — — — —
575 60 518 633 24 658.8 800 800 — — — — — — — — —
See Legend and Notes on page 115.

126
Table 15 — 60 Hz Single Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
CONTROL
UNIT VOLTAGE HIGH STATIC CONDENSER FANS
CIRCUIT
NO. OF
UNIT 7.5 HP Pump, N+1, Low
Supplied COND 10 HP Pump, N+1, Low Static 10 HP Pump, N+1, High Static Voltage MCA
30XV Static
V(3 Ph) Hz FANS 1 Ph, and
MOC
Min Max MCA FUSE SIZE MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE 60 Hz MOCP
P
208/230 60 187 253 10 — — — — — — — — — 115 60
380 60 342 418 10 — — — — — — — — — 115 60
140 400 60 360 440 10 — — — — — — — — — 115 60
460 60 414 506 10 — — — — — — — — — 115 60
575 60 518 633 10 — — — — — — — — — 115 60
208/230 60 187 253 12 765.8 800 800 — — — 786.8 1000 1000 115 60
380 60 342 418 12 — — — — — — — — — 115 60
160 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 347.4 450 400 — — — 362.4 450 400 115 60
575 60 518 633 12 279.1 350 350 — — — 291.1 350 350 115 60
208/230 60 187 253 12 972.8 1200 1200 — — — 993.8 1200 1200 115 60
380 60 342 418 12 — — — — — — — — — 115 60
180 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 385.6 500 450 — — — 400.6 500 450 115 60
575 60 518 633 12 308.4 400 350 — — — 320.4 400 350 115 60
208/230 60 187 253 14 — — — 983.5 1200 1200 983.5 1200 1200 115 60
380 60 342 418 14 — — — — — — — — — 115 60
200 400 60 360 440 14 — — — — — — — — — 115 60
460 60 414 506 14 — — — 453.5 500 500 453.5 500 500 115 60
575 60 518 633 14 — — — 363.4 450 400 363.4 450 400 115 60
380 60 342 418 14 — — — — — — — — — 115 60
400 60 360 440 14 — — — — — — — — — 115 60
225
460 60 414 506 14 — — — 497.8 600 600 497.8 600 600 115 60
575 60 518 633 14 — — — 399.1 500 450 399.1 500 450 115 60
380 60 342 418 16 — — — — — — — — — 115 60
400 60 360 440 16 — — — — — — — — — 115 60
250
460 60 414 506 16 — — — 554.1 700 600 554.1 700 600 115 60
575 60 518 633 16 — — — 444.0 500 500 444.0 500 500 115 60
380 60 342 418 16 — — — — — — — — — 115 60
400 60 360 440 16 — — — — — — — — — 115 60
275
460 60 414 506 16 — — — 584.0 700 700 — — — 115 60
575 60 518 633 16 — — — 468.7 600 600 — — — 115 60
380 60 342 418 18 — — — — — — — — — 115 60
400 60 360 440 18 — — — — — — — — — 115 60
300
460 60 414 506 18 — — — 610.4 800 700 — — — 115 60
575 60 518 633 18 — — — 488.6 600 600 — — — 115 60
380 60 342 418 20 — — — — — — — — — 115 60
400 60 360 440 20 — — — — — — — — — 115 60
325
460 60 414 506 20 — — — 663.5 800 800 — — — 115 60
575 60 518 633 20 — — — 530.9 600 600 — — — 115 60
380 60 342 418 20 — — — — — — — — — 115 60
400 60 360 440 20 — — — — — — — — — 115 60
350
460 60 414 506 20 — — — — — — — — — 115 60
575 60 518 633 20 — — — — — — — — — 115 60
380 60 342 418 22 — — — — — — — — — 115 60
400 60 360 440 22 — — — — — — — — — 115 60
400
460 60 414 506 22 — — — — — — — — — 115 60
575 60 518 633 22 — — — — — — — — — 115 60
380 60 342 418 24 — — — — — — — — — 115 60
400 60 360 440 24 — — — — — — — — — 115 60
450
460 60 414 506 24 — — — — — — — — — 115 60
575 60 518 633 24 — — — — — — — — — 115 60
See Legend and Notes on page 115.

127
Table 16 — 60 Hz Single Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM FANS
NO. OF
UNIT 7.5 HP Pump, N+0, 10 HP Pump, N+0, 10 HP Pump, N+0,
Supplied COND No Hydronic Package
30XV V(3 Ph) Hz Low Static Low Static High Static
FANS
Min Max MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
380 60 342 418 10 300.2 400 350 — — — — — — — — —
140 400 60 360 440 10 286.6 350 350 — — — — — — — — —
460 60 414 506 10 247.7 300 300 276.4 350 300 — — — 286.4 350 350
380 60 342 418 12 348.1 450 400 — — — — — — — — —
160 400 60 360 440 12 329.7 400 400 — — — — — — — — —
460 60 414 506 12 286.1 350 350 314.9 400 350 — — — 324.9 400 350
380 60 342 418 12 455.0 600 500 — — — — — — — — —
180 400 60 360 440 12 372.4 500 450 — — — — — — — — —
460 60 414 506 12 322.5 400 400 351.2 450 400 — — — 361.2 450 400
380 60 342 418 14 430.4 500 500 — — — — — — — — —
200 400 60 360 440 14 409.2 500 450 — — — — — — — — —
460 60 414 506 14 354.5 450 400 — — — 411.8 500 450 411.8 500 450
380 60 342 418 14 480.3 600 600 — — — — — — — — —
225 400 60 360 440 14 457.7 600 600 — — — — — — — — —
460 60 414 506 14 396.6 500 450 — — — 453.9 600 600 453.9 600 600
380 60 342 418 16 544.6 700 600 — — — — — — — — —
250 400 60 360 440 16 518.6 700 600 — — — — — — — — —
460 60 414 506 16 449.4 600 500 — — — 506.7 600 600 506.7 600 600
380 60 342 418 16 578.8 700 700 — — — — — — — — —
275 400 60 360 440 16 550.6 700 700 — — — — — — — — —
460 60 414 506 16 477.8 600 600 — — — 535.1 700 600 553.7 700 600
380 60 342 418 18 609.6 800 700 — — — — — — — — —
300 400 60 360 440 18 578.8 700 700 — — — — — — — — —
460 60 414 506 18 502.2 600 600 — — — 559.5 700 700 578.1 700 700
380 60 342 418 20 668.3 800 800 — — — — — — — — —
325 400 60 360 440 20 636.8 800 700 — — — — — — — — —
460 60 414 506 20 551.9 700 700 — — — 609.3 800 700 627.9 800 700

Table 16 — 60 Hz Single Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
CONTROL
UNIT VOLTAGE ECM FANS
NO. OF CIRCUIT
UNIT
Supplied COND 7.5 HP Pump, N+1, Low Static 10 HP Pump, N+1, Low Static 10 HP Pump, N+1, High Static Voltage MCA
30XV
V(3 Ph) Hz FANS 1 Ph, and
Min Max MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE 60 Hz MOCP
380 60 342 418 10 — — — — — — — — — 115 60
140 400 60 360 440 10 — — — — — — — — — 115 60
460 60 414 506 10 — — — — — — — — — 115 60
380 60 342 418 12 — — — — — — — — — 115 60
160 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 328.5 400 400 — — — 343.5 400 400 115 60
380 60 342 418 12 — — — — — — — — — 115 60
180 400 60 360 440 12 — — — — — — — — — 115 60
460 60 414 506 12 364.8 450 400 — — — 379.8 450 450 115 60
380 60 342 418 14 — — — — — — — — — 115 60
200 400 60 360 440 14 — — — — — — — — — 115 60
460 60 414 506 14 — — — 430.4 500 500 430.4 500 500 115 60
380 60 342 418 14 — — — — — — — — — 115 60
225 400 60 360 440 14 — — — — — — — — — 115 60
460 60 414 506 14 — — — 472.5 600 600 472.5 600 600 115 60
380 60 342 418 16 — — — — — — — — — 115 60
250 400 60 360 440 16 — — — — — — — — — 115 60
460 60 414 506 16 — — — 525.3 600 600 525.3 600 600 115 60
380 60 342 418 16 — — — — — — — — — 115 60
275 400 60 360 440 16 — — — — — — — — — 115 60
460 60 414 506 16 — — — 553.7 700 600 — — — 115 60
380 60 342 418 18 — — — — — — — — — 115 60
300 400 60 360 440 18 — — — — — — — — — 115 60
460 60 414 506 18 — — — 578.1 700 700 — — — 115 60
380 60 342 418 20 — — — — — — — — — 115 60
325 400 60 360 440 20 — — — — — — — — — 115 60
460 60 414 506 20 — — — 627.9 800 700 — — — 115 60
See Legend and Notes on page 115.

128
Table 17 — 60 Hz Dual Point Power Standard Tier Fixed Speed Fan Motors
with Control Power Transformer
CONTROL
UNIT VOLTAGE NUMBER OF COND
MCA MOCP FUSE SIZE CIRCUIT
UNIT FANS
30XV Supplied Voltage MCA
V(3 Ph) Hz 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
208/230 60 187 253 4 4 324.3 311.4 500 500 400 400 115 60
380 60 342 418 4 4 177.7 170.7 300 250 225 225 115 60
140 400 60 360 440 4 4 169.6 162.6 250 250 200 200 115 60
460 60 414 506 4 4 146.6 140.8 225 225 175 175 115 60
575 60 518 633 4 4 118.0 113.4 200 175 150 150 115 60
208/230 60 187 253 4 4 380.5 367.7 600 600 450 450 115 60
380 60 342 418 4 4 207.7 200.7 350 300 250 250 115 60
160 400 60 360 440 4 4 198.3 191.3 300 300 250 250 115 60
460 60 414 506 4 4 171.6 165.8 250 250 225 200 115 60
575 60 518 633 4 4 138.0 133.4 225 225 175 175 115 60
208/230 60 187 253 4 4 436.8 423.9 700 700 600 600 115 60
380 60 342 418 4 4 238.9 231.9 400 400 300 300 115 60
180 400 60 360 440 4 4 228.3 221.3 350 350 300 300 115 60
460 60 414 506 4 4 197.4 191.6 300 300 250 250 115 60
575 60 518 633 4 4 158.0 153.4 250 250 200 200 115 60
208/230 60 187 253 5 5 452.1 439.3 700 700 600 600 115 60
380 60 342 418 5 5 247.5 240.5 400 400 300 300 115 60
200 400 60 360 440 5 5 235.5 228.5 400 350 300 300 115 60
460 60 414 506 5 5 204.4 198.6 350 300 250 250 115 60
575 60 518 633 5 5 164.2 159.5 250 250 200 200 115 60
380 60 342 418 6 4 343.4 214.4 500 350 450 300 115 60
400 60 360 440 6 4 326.3 203.8 500 350 400 250 115 60
225
460 60 414 506 6 4 283.2 176.6 450 300 350 225 115 60
575 60 518 633 6 4 226.8 142.1 350 225 300 175 115 60
380 60 342 418 6 6 324.7 315.4 500 500 400 400 115 60
400 60 360 440 6 6 308.8 299.5 500 500 400 400 115 60
250
460 60 414 506 6 6 267.5 259.8 450 450 350 350 115 60
575 60 518 633 6 6 214.3 208.2 350 350 300 250 115 60
380 60 342 418 6 6 348.4 339.1 600 500 450 450 115 60
400 60 360 440 6 6 331.3 322.0 500 500 400 400 115 60
275
460 60 414 506 6 6 287.3 279.6 450 450 350 350 115 60
575 60 518 633 6 6 230.6 224.4 350 350 300 300 115 60
380 60 342 418 7 7 357.0 347.7 600 600 450 450 115 60
400 60 360 440 7 7 339.7 330.4 500 500 450 400 115 60
300
460 60 414 506 7 7 294.6 286.9 500 450 350 350 115 60
575 60 518 633 7 7 236.7 230.6 400 400 300 300 115 60
380 60 342 418 8 8 390.6 381.3 600 600 500 500 115 60
400 60 360 440 8 8 371.9 362.6 600 600 450 450 115 60
325
460 60 414 506 8 8 322.6 314.9 500 500 400 400 115 60
575 60 518 633 8 8 259.1 253.0 400 400 350 300 115 60
380 60 342 418 9 7 526.1 375.2 800 600 700 450 115 60
400 60 360 440 9 7 499.8 356.7 800 600 600 450 115 60
350
460 60 414 506 9 7 433.9 309.6 700 500 600 400 115 60
575 60 518 633 9 7 348.2 248.1 600 400 450 300 115 60
380 60 342 418 9 9 497.4 487.4 800 800 600 600 115 60
400 60 360 440 9 9 473.5 463.6 800 800 600 600 115 60
400
460 60 414 506 9 9 410.4 402.1 700 700 500 500 115 60
575 60 518 633 9 9 329.4 322.9 500 500 400 400 115 60
380 60 342 418 10 10 574.7 564.8 800 800 700 700 115 60
400 60 360 440 10 10 547.0 537.0 800 800 700 700 115 60
450
460 60 414 506 10 10 474.6 466.4 800 800 600 600 115 60
575 60 518 633 10 10 380.6 374.0 600 600 500 450 115 60
380 60 342 418 11 11 604.6 594.6 1000 1000 800 800 115 60
400 60 360 440 11 11 575.4 565.5 800 800 700 700 115 60
500
460 60 414 506 11 11 499.0 490.8 800 800 600 600 115 60
575 60 518 633 11 11 399.2 392.7 600 600 500 500 115 60
See Legend and Notes on page 115.

129
Table 18 — 60 Hz Dual Point Power Standard Tier Variable Speed Fan Motors with Control Power Transformer
CONTROL
UNIT VOLTAGE NUMBER OF STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS
CIRCUIT
UNIT COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE Voltage MCA
V(3 Ph) Hz 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
208/230 60 187 253 4 4 384.0 371.2 600 600 450 450 389.2 376.4 600 600 500 450 115 60
380 60 342 418 4 4 210.2 203.2 350 300 250 250 213.0 206.0 350 350 250 250 115 60
160 400 60 360 440 4 4 200.3 193.3 300 300 250 250 203.1 196.1 300 300 250 250 115 60
460 60 414 506 4 4 173.5 167.7 250 250 225 200 175.9 170.1 250 250 225 200 115 60
575 60 518 633 4 4 139.9 135.2 225 225 175 175 141.9 137.2 225 225 175 175 115 60
208/230 60 187 253 4 4 440.3 427.4 700 700 600 600 445.5 432.6 700 700 600 600 115 60
380 60 342 418 4 4 241.5 234.5 400 400 300 300 244.3 237.3 400 400 300 300 115 60
180 400 60 360 440 4 4 229.1 222.0 350 350 300 300 231.8 224.8 350 350 300 300 115 60
460 60 414 506 4 4 198.9 193.1 300 300 250 250 201.3 195.5 300 300 250 250 115 60
575 60 518 633 4 4 159.9 155.2 250 250 200 200 161.9 157.2 250 250 200 200 115 60
208/230 60 187 253 5 5 457.1 444.3 700 700 600 600 463.6 450.8 700 700 600 600 115 60
380 60 342 418 5 5 251.0 244.0 400 400 300 300 254.5 247.5 400 400 300 300 115 60
200 400 60 360 440 5 5 238.3 231.3 400 350 300 300 241.8 234.8 400 350 300 300 115 60
460 60 414 506 5 5 206.6 200.8 300 300 250 250 209.6 203.8 350 300 250 250 115 60
575 60 518 633 5 5 166.2 161.5 250 250 200 200 168.7 164.0 250 250 200 200 115 60
380 60 342 418 6 4 342.9 214.5 500 350 450 300 347.1 217.3 500 350 450 300 115 60
400 60 360 440 6 4 326.1 204.5 500 350 400 250 330.3 207.3 500 350 400 250 115 60
225
460 60 414 506 6 4 283.0 176.8 450 300 350 225 286.6 179.2 450 300 350 225 115 60
575 60 518 633 6 4 226.5 141.5 350 225 300 175 229.5 143.5 350 225 300 175 115 60
380 60 342 418 6 6 332.9 323.6 500 500 400 400 337.1 327.8 500 500 400 400 115 60
400 60 360 440 6 6 316.1 306.8 500 500 400 400 320.3 311.0 500 500 400 400 115 60
250
460 60 414 506 6 6 274.1 266.4 450 450 350 350 277.7 270.0 450 450 350 350 115 60
575 60 518 633 6 6 220.2 214.1 350 350 300 300 223.2 217.1 350 350 300 300 115 60
380 60 342 418 6 6 344.1 334.8 500 500 450 400 348.3 339.0 500 500 450 400 115 60
400 60 360 440 6 6 327.4 318.1 500 500 400 400 331.5 322.2 500 500 400 400 115 60
275
460 60 414 506 6 6 283.9 276.2 450 450 350 350 287.5 279.8 450 450 350 350 115 60
575 60 518 633 6 6 227.7 221.6 350 350 300 300 230.7 224.6 350 350 300 300 115 60
380 60 342 418 7 7 366.2 356.9 600 600 450 450 371.1 361.8 600 600 450 450 115 60
400 60 360 440 7 7 349.2 339.8 500 500 450 450 354.0 344.7 500 500 450 450 115 60
300
460 60 414 506 7 7 302.4 294.7 500 500 400 350 306.6 298.9 500 500 400 400 115 60
575 60 518 633 7 7 242.8 236.6 400 400 300 300 246.3 240.1 400 400 300 300 115 60
380 60 342 418 8 8 403.2 393.9 600 600 500 500 408.8 399.5 600 600 500 500 115 60
400 60 360 440 8 8 383.4 374.1 600 600 450 450 388.9 379.6 600 600 500 450 115 60
325
460 60 414 506 8 8 332.6 324.9 500 500 400 400 337.4 329.7 500 500 400 400 115 60
575 60 518 633 8 8 266.6 260.4 450 400 350 350 270.6 264.4 450 400 350 350 115 60
380 60 342 418 9 7 532.8 381.9 800 600 700 500 539.1 386.8 800 600 700 500 115 60
400 60 360 440 9 7 506.4 363.6 800 600 600 450 512.6 368.4 800 600 700 450 115 60
350
460 60 414 506 9 7 439.8 315.2 700 500 600 400 445.2 319.4 700 500 600 400 115 60
575 60 518 633 9 7 351.6 252.9 600 400 450 300 356.1 256.4 600 400 450 350 115 60
380 60 342 418 9 9 497.2 487.2 800 800 600 600 503.5 493.5 800 800 600 600 115 60
400 60 360 440 9 9 473.3 463.3 800 700 600 600 479.5 469.6 800 800 600 600 115 60
400
460 60 414 506 9 9 410.2 402.0 600 600 500 500 415.6 407.4 700 600 500 500 115 60
575 60 518 633 9 9 328.3 321.7 500 500 400 400 332.8 326.2 500 500 400 400 115 60
380 60 342 418 10 10 590.5 580.5 1000 800 700 700 597.5 587.5 1000 1000 800 700 115 60
400 60 360 440 10 10 561.3 551.4 800 800 700 700 568.2 558.3 800 800 700 700 115 60
450
460 60 414 506 10 10 487.7 479.5 800 800 600 600 493.7 485.5 800 800 600 600 115 60
575 60 518 633 10 10 390.8 384.3 600 600 500 500 395.8 389.3 600 600 500 500 115 60
380 60 342 418 11 11 636.3 626.3 1000 1000 800 800 644.0 634.0 1000 1000 800 800 115 60
400 60 360 440 11 11 604.3 594.4 1000 1000 800 800 611.9 602.0 1000 1000 800 800 115 60
500
460 60 414 506 11 11 525.2 516.9 800 800 700 700 531.8 523.5 800 800 700 700 115 60
575 60 518 633 11 11 420.9 414.3 700 700 500 500 426.4 419.8 700 700 600 500 115 60
See Legend and Notes on page 115.

130
Table 19 — 60 Hz Dual Point Power Standard Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
CONTROL
UNIT VOLTAGE NUMBER OF COND ECM FANS
CIRCUIT
UNIT FANS
30XV Supplied MCA MOCP FUSE SIZE Voltage MCA
V(3 Ph) Hz 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 60 342 418 4 4 201.2 194.2 300 300 250 250 115 60
160 400 60 360 440 4 4 191.8 184.7 300 300 225 225 115 60
460 60 414 506 4 4 167.3 160.3 250 250 200 200 115 60
380 60 342 418 4 4 230.9 223.9 350 350 300 300 115 60
180 400 60 360 440 4 4 219.1 212.0 350 350 300 300 115 60
460 60 414 506 4 4 190.2 184.4 300 300 225 225 115 60
380 60 342 418 5 5 240.3 233.3 400 350 300 300 115 60
200 400 60 360 440 5 5 228.1 221.1 350 350 300 300 115 60
460 60 414 506 5 5 197.7 191.9 300 300 250 250 115 60
380 60 342 418 6 4 328.0 204.9 500 350 400 250 115 60
225 400 60 360 440 6 4 312.0 195.4 500 300 400 250 115 60
460 60 414 506 6 4 270.7 168.9 450 250 350 200 115 60
380 60 342 418 6 6 318.5 309.1 500 500 400 400 115 60
250 400 60 360 440 6 6 302.5 293.1 500 500 400 350 115 60
460 60 414 506 6 6 262.3 254.5 400 400 350 300 115 60
380 60 342 418 6 6 329.1 319.8 500 500 400 400 115 60
275 400 60 360 440 6 6 313.1 303.8 500 500 400 400 115 60
460 60 414 506 6 6 271.5 263.8 450 450 350 350 115 60
380 60 342 418 7 7 350.4 341.0 500 500 450 450 115 60
300 400 60 360 440 7 7 334.1 324.8 500 500 400 400 115 60
460 60 414 506 7 7 289.4 281.7 450 450 350 350 115 60
380 60 342 418 8 8 385.9 376.5 600 600 500 450 115 60
325 400 60 360 440 8 8 366.9 357.6 600 600 450 450 115 60
460 60 414 506 8 8 318.3 310.6 500 500 400 400 115 60

See Legend and Notes on page 115.

131
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer
STANDARD CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT No Hydronic Package 7.5 HP Pump, N+0, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 4 4 331.5 318.7 500 500 400 400 — — — — — —
380 60 342 418 4 4 181.5 174.5 300 250 225 225 — — — — — —
140 400 60 360 440 4 4 172.8 165.8 250 250 225 200 — — — — — —
460 60 414 506 4 4 149.9 144.1 225 225 175 175 — — — — — —
575 60 518 633 4 4 119.9 115.2 175 175 150 150 — — — — — —
208/230 60 187 253 5 5 363.4 350.5 600 500 450 450 395.7 379.5 600 600 500 450
380 60 342 418 5 5 198.5 191.5 300 300 250 225 — — — — — —
160 400 60 360 440 5 5 189.6 182.6 300 300 225 225 — — — — — —
460 60 414 506 5 5 163.8 158.0 250 250 200 200 178.9 171.6 250 250 225 200
575 60 518 633 5 5 131.2 126.5 200 200 175 150 145.1 137.4 225 200 175 175
208/230 60 187 253 5 5 409.6 396.8 600 600 500 500 442.0 425.8 700 700 600 500
380 60 342 418 5 5 224.8 217.8 350 350 300 300 — — — — — —
180 400 60 360 440 5 5 213.3 206.3 350 300 250 250 — — — — — —
460 60 414 506 5 5 184.8 179.0 300 300 225 225 199.9 192.6 300 300 250 225
575 60 518 633 5 5 148.7 144.0 225 225 175 175 160.7 154.9 250 250 200 200
208/230 60 187 253 6 6 459.4 442.4 700 700 600 600 — — — — — —
380 60 342 418 6 6 251.6 242.3 400 400 300 300 — — — — — —
200 400 60 360 440 6 6 239.9 230.6 350 350 300 300 — — — — — —
460 60 414 506 6 6 207.3 199.6 300 300 250 250 — — — — — —
575 60 518 633 6 6 166.5 160.3 250 250 200 200 — — — — — —
380 60 342 418 7 5 332.4 210.3 500 350 400 250 — — — — — —
400 60 360 440 7 5 316.7 198.8 500 300 400 250 — — — — — —
225
460 60 414 506 7 5 274.1 172.8 450 250 350 225 — — — — — —
575 60 518 633 7 5 219.0 139.0 350 225 300 175 — — — — — —
380 60 342 418 7 7 317.4 308.1 500 500 400 400 — — — — — —
400 60 360 440 7 7 302.9 293.6 500 450 400 350 — — — — — —
250
460 60 414 506 7 7 262.1 254.4 400 400 350 300 — — — — — —
575 60 518 633 7 7 210.3 204.1 350 300 250 250 — — — — — —
380 60 342 418 7 7 339.9 330.6 500 500 400 400 — — — — — —
400 60 360 440 7 7 322.9 313.6 500 500 400 400 — — — — — —
275
460 60 414 506 7 7 280.3 272.6 450 450 350 350 — — — — — —
575 60 518 633 7 7 224.0 217.9 350 350 300 300 — — — — — —
380 60 342 418 8 8 354.5 345.2 500 500 450 450 — — — — — —
400 60 360 440 8 8 337.2 327.8 500 500 400 400 — — — — — —
300
460 60 414 506 8 8 292.1 284.4 450 450 350 350 — — — — — —
575 60 518 633 8 8 234.1 227.9 350 350 300 300 — — — — — —
380 60 342 418 9 9 385.3 376.0 600 600 500 450 — — — — — —
400 60 360 440 9 9 366.4 357.1 600 600 450 450 — — — — — —
325
460 60 414 506 9 9 318.2 310.5 500 500 400 400 — — — — — —
575 60 518 633 9 9 255.4 249.2 400 400 300 300 — — — — — —
380 60 342 418 10 8 493.6 355.2 800 600 600 450 — — — — — —
400 60 360 440 10 8 469.4 337.8 700 500 600 400 — — — — — —
350
460 60 414 506 10 8 407.0 292.8 600 450 500 350 — — — — — —
575 60 518 633 10 8 325.4 234.2 500 350 400 300 — — — — — —
380 60 342 418 10 10 493.0 483.0 800 800 600 600 — — — — — —
400 60 360 440 10 10 468.8 458.9 700 700 600 600 — — — — — —
400
460 60 414 506 10 10 406.6 398.4 600 600 500 500 — — — — — —
575 60 518 633 10 10 325.8 319.3 500 500 400 400 — — — — — —
380 60 342 418 11 11 587.5 577.6 800 800 700 700 — — — — — —
400 60 360 440 11 11 558.1 548.1 800 800 700 700 — — — — — —
450
460 60 414 506 11 11 484.4 476.2 800 800 600 600 — — — — — —
575 60 518 633 11 11 387.1 380.6 600 600 500 450 — — — — — —
380 60 342 418 12 12 618.3 608.4 1000 1000 800 800 — — — — — —
400 60 360 440 12 12 588.6 578.6 800 800 700 700 — — — — — —
500
460 60 414 506 12 12 510.6 502.4 800 800 600 600 — — — — — —
575 60 518 633 12 12 408.4 401.9 600 600 500 500 — — — — — —
See Legend and Notes on page 115.

132
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
STANDARD CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+0, Low Static 10 HP Pump, N+0, High Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 4 4 — — — — — — — — — — — —
380 60 342 418 4 4 — — — — — — — — — — — —
140 400 60 360 440 4 4 — — — — — — — — — — — —
460 60 414 506 4 4 — — — — — — — — — — — —
575 60 518 633 4 4 — — — — — — — — — — — —
208/230 60 187 253 5 5 — — — — — — 402.7 386.5 600 600 500 450
380 60 342 418 5 5 — — — — — — — — — — — —
160 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — 183.9 176.6 250 250 225 225
575 60 518 633 5 5 — — — — — — 149.1 141.4 225 225 175 175
208/230 60 187 253 5 5 — — — — — — 449.0 432.8 700 700 600 600
380 60 342 418 5 5 — — — — — — — — — — — —
180 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — 204.9 197.6 300 300 250 250
575 60 518 633 5 5 — — — — — — 164.7 158.9 250 250 200 200
208/230 60 187 253 6 6 498.8 514.4 800 800 600 600 498.8 514.4 800 800 600 600
380 60 342 418 6 6 — — — — — — — — — — — —
200 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 227.4 236.8 350 350 300 300 227.4 236.8 350 350 300 300
575 60 518 633 6 6 182.6 190.1 250 300 225 225 182.6 190.1 250 300 225 225
380 60 342 418 7 5 — — — — — — — — — — — —
400 60 360 440 7 5 — — — — — — — — — — — —
225
460 60 414 506 7 5 — — — — — — — — — — — —
575 60 518 633 7 5 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
250
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
275
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
300
460 60 414 506 8 8 312.2 321.6 500 500 400 400 330.8 321.6 500 500 400 400
575 60 518 633 8 8 250.2 257.7 400 400 300 300 265.0 257.7 400 400 350 300
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
325
460 60 414 506 9 9 338.3 347.7 500 500 400 450 356.9 347.7 500 500 450 450
575 60 518 633 9 9 271.5 279.0 400 450 350 350 286.3 279.0 450 450 350 350
380 60 342 418 10 8 — — — — — — — — — — — —
400 60 360 440 10 8 — — — — — — — — — — — —
350
460 60 414 506 10 8 — — — — — — — — — — — —
575 60 518 633 10 8 — — — — — — — — — — — —
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
400
460 60 414 506 10 10 — — — — — — — — — — — —
575 60 518 633 10 10 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
450
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
500
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

133
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
STANDARD CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 7.5 HP Pump, N+1, Low Static 10 HP Pump, N+1, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 4 4 — — — — — — — — — — — —
380 60 342 418 4 4 — — — — — — — — — — — —
140 400 60 360 440 4 4 — — — — — — — — — — — —
460 60 414 506 4 4 — — — — — — — — — — — —
575 60 518 633 4 4 — — — — — — — — — — — —
208/230 60 187 253 5 5 — — — — — — — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
160 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — — — — — — —
575 60 518 633 5 5 — — — — — — — — — — — —
208/230 60 187 253 5 5 — — — — — — — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
180 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — — — — — — —
575 60 518 633 5 5 — — — — — — — — — — — —
208/230 60 187 253 6 6 — — — — — — 534.8 514.4 800 800 700 600
380 60 342 418 6 6 — — — — — — — — — — — —
200 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 246.0 236.8 350 350 300 300
575 60 518 633 6 6 — — — — — — 197.4 190.1 300 300 225 225
380 60 342 418 7 5 — — — — — — — — — — — —
400 60 360 440 7 5 — — — — — — — — — — — —
225
460 60 414 506 7 5 — — — — — — — — — — — —
575 60 518 633 7 5 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
250
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
275
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
300
460 60 414 506 8 8 — — — — — — 330.8 321.6 500 500 400 400
575 60 518 633 8 8 — — — — — — 265.0 257.7 400 400 350 300
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
325
460 60 414 506 9 9 — — — — — — 356.9 347.7 500 500 450 450
575 60 518 633 9 9 — — — — — — 286.3 279.0 450 450 350 350
380 60 342 418 10 8 — — — — — — — — — — — —
400 60 360 440 10 8 — — — — — — — — — — — —
350
460 60 414 506 10 8 — — — — — — — — — — — —
575 60 518 633 10 8 — — — — — — — — — — — —
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
400
460 60 414 506 10 10 — — — — — — — — — — — —
575 60 518 633 10 10 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
450
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
500
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

134
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+1, High Static No Hydronic Package
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 4 4 — — — — — — 336.7 323.9 500 500 400 400
380 60 342 418 4 4 — — — — — — 184.3 177.3 300 250 225 225
140 400 60 360 440 4 4 — — — — — — 175.6 168.6 250 250 225 200
460 60 414 506 4 4 — — — — — — 152.3 146.5 250 225 200 175
575 60 518 633 4 4 — — — — — — 121.9 117.2 200 175 150 150
208/230 60 187 253 5 5 — — — — — — 369.9 357.0 600 500 450 450
380 60 342 418 5 5 — — — — — — 202.0 195.0 300 300 250 250
160 400 60 360 440 5 5 — — — — — — 193.0 186.0 300 300 225 225
460 60 414 506 5 5 — — — — — — 166.8 161.0 250 250 200 200
575 60 518 633 5 5 — — — — — — 133.7 129.0 200 200 175 175
208/230 60 187 253 5 5 — — — — — — 416.1 403.3 600 600 500 500
380 60 342 418 5 5 — — — — — — 228.3 221.3 350 350 300 300
180 400 60 360 440 5 5 — — — — — — 216.8 209.8 350 350 300 250
460 60 414 506 5 5 — — — — — — 187.8 182.0 300 300 225 225
575 60 518 633 5 5 — — — — — — 151.2 146.5 250 225 200 175
208/230 60 187 253 6 6 534.8 514.4 800 800 700 600 467.2 450.2 700 700 600 600
380 60 342 418 6 6 — — — — — — 255.8 246.5 400 400 300 300
200 400 60 360 440 6 6 — — — — — — 244.0 234.7 400 350 300 300
460 60 414 506 6 6 246.0 236.8 350 350 300 300 210.9 203.2 300 300 250 250
575 60 518 633 6 6 197.4 190.1 300 300 225 225 169.5 163.3 250 250 200 200
380 60 342 418 7 5 — — — — — — 337.3 213.8 500 350 400 300
400 60 360 440 7 5 — — — — — — 321.5 202.3 500 300 400 250
225
460 60 414 506 7 5 — — — — — — 278.3 175.8 450 250 350 225
575 60 518 633 7 5 — — — — — — 222.5 141.5 350 225 300 175
380 60 342 418 7 7 — — — — — — 322.3 313.0 500 500 400 400
400 60 360 440 7 7 — — — — — — 307.7 298.4 500 500 400 350
250
460 60 414 506 7 7 — — — — — — 266.3 258.6 400 400 350 350
575 60 518 633 7 7 — — — — — — 213.8 207.6 350 300 250 250
380 60 342 418 7 7 — — — — — — 344.8 335.5 500 500 450 400
400 60 360 440 7 7 — — — — — — 327.7 318.4 500 500 400 400
275
460 60 414 506 7 7 — — — — — — 284.5 276.8 450 450 350 350
575 60 518 633 7 7 — — — — — — 227.5 221.4 350 350 300 300
380 60 342 418 8 8 — — — — — — 360.1 350.8 500 500 450 450
400 60 360 440 8 8 — — — — — — 342.7 333.4 500 500 400 400
300
460 60 414 506 8 8 — — — — — — 296.9 289.2 450 450 350 350
575 60 518 633 8 8 — — — — — — 238.1 231.9 350 350 300 300
380 60 342 418 9 9 — — — — — — 391.6 382.3 600 600 500 450
400 60 360 440 9 9 — — — — — — 372.6 363.3 600 600 450 450
325
460 60 414 506 9 9 — — — — — — 323.6 315.9 500 500 400 400
575 60 518 633 9 9 — — — — — — 259.9 253.7 400 400 350 300
380 60 342 418 10 8 — — — — — — 500.6 360.8 800 600 600 450
400 60 360 440 10 8 — — — — — — 476.3 343.4 800 500 600 450
350
460 60 414 506 10 8 — — — — — — 413.0 297.6 600 500 500 350
575 60 518 633 10 8 — — — — — — 330.4 238.2 500 400 400 300
380 60 342 418 10 10 — — — — — — 500.0 490.0 800 800 600 600
400 60 360 440 10 10 — — — — — — 475.7 465.8 700 700 600 600
400
460 60 414 506 10 10 — — — — — — 412.6 404.4 600 600 500 500
575 60 518 633 10 10 — — — — — — 330.8 324.3 500 500 400 400
380 60 342 418 11 11 — — — — — — 595.2 585.3 1000 800 700 700
400 60 360 440 11 11 — — — — — — 565.7 555.7 800 800 700 700
450
460 60 414 506 11 11 — — — — — — 491.0 482.8 800 800 600 600
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
500
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

135
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 7.5 HP Pump, N+0, Low Static 10 HP Pump, N+0, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 4 4 — — — — — — — — — — — —
380 60 342 418 4 4 — — — — — — — — — — — —
140 400 60 360 440 4 4 — — — — — — — — — — — —
460 60 414 506 4 4 — — — — — — — — — — — —
575 60 518 633 4 4 — — — — — — — — — — — —
208/230 60 187 253 5 5 402.2 386.0 600 600 500 450 — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
160 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 181.9 174.6 250 250 225 225 — — — — — —
575 60 518 633 5 5 145.7 139.9 225 225 175 175 — — — — — —
208/230 60 187 253 5 5 448.5 432.3 700 700 600 600 — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
180 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 202.9 195.6 300 300 250 250 — — — — — —
575 60 518 633 5 5 163.2 157.4 250 250 200 200 — — — — — —
208/230 60 187 253 6 6 — — — — — — 506.6 522.2 800 800 600 600
380 60 342 418 6 6 — — — — — — — — — — — —
200 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 231.0 240.4 350 350 300 300
575 60 518 633 6 6 — — — — — — 185.6 193.1 250 300 225 225
380 60 342 418 7 5 — — — — — — — — — — — —
400 60 360 440 7 5 — — — — — — — — — — — —
225
460 60 414 506 7 5 — — — — — — — — — — — —
575 60 518 633 7 5 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
250
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
275
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
300
460 60 414 506 8 8 — — — — — — 317.0 326.4 500 500 400 400
575 60 518 633 8 8 — — — — — — 254.2 261.7 400 400 300 350
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
325
460 60 414 506 9 9 — — — — — — 343.7 353.1 500 500 400 450
575 60 518 633 9 9 — — — — — — 276.0 283.5 400 450 350 350
380 60 342 418 10 8 — — — — — — — — — — — —
400 60 360 440 10 8 — — — — — — — — — — — —
350
460 60 414 506 10 8 — — — — — — — — — — — —
575 60 518 633 10 8 — — — — — — — — — — — —
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
400
460 60 414 506 10 10 — — — — — — — — — — — —
575 60 518 633 10 10 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
450
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
500
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

136
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+0, High Static 7.5 HP Pump, N+1, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 4 4 — — — — — — — — — — — —
380 60 342 418 4 4 — — — — — — — — — — — —
140 400 60 360 440 4 4 — — — — — — — — — — — —
460 60 414 506 4 4 — — — — — — — — — — — —
575 60 518 633 4 4 — — — — — — — — — — — —
208/230 60 187 253 5 5 409.2 393.0 600 600 500 500 — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
160 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 186.9 179.6 250 250 225 225 — — — — — —
575 60 518 633 5 5 149.7 143.9 225 225 175 175 — — — — — —
208/230 60 187 253 5 5 455.5 439.3 700 700 600 600 — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
180 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 207.9 200.6 300 300 250 250 — — — — — —
575 60 518 633 5 5 167.2 161.4 250 250 200 200 — — — — — —
208/230 60 187 253 6 6 506.6 522.2 800 800 600 600 — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
200 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 231.0 240.4 350 350 300 300 — — — — — —
575 60 518 633 6 6 185.6 193.1 250 300 225 225 — — — — — —
380 60 342 418 7 5 — — — — — — — — — — — —
400 60 360 440 7 5 — — — — — — — — — — — —
225
460 60 414 506 7 5 — — — — — — — — — — — —
575 60 518 633 7 5 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
250
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
400 60 360 440 7 7 — — — — — — — — — — — —
275
460 60 414 506 7 7 — — — — — — — — — — — —
575 60 518 633 7 7 — — — — — — — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
300
460 60 414 506 8 8 335.6 326.4 500 500 400 400 — — — — — —
575 60 518 633 8 8 269.0 261.7 400 400 350 350 — — — — — —
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
325
460 60 414 506 9 9 362.3 353.1 500 500 450 450 — — — — — —
575 60 518 633 9 9 290.8 283.5 450 450 350 350 — — — — — —
380 60 342 418 10 8 — — — — — — — — — — — —
400 60 360 440 10 8 — — — — — — — — — — — —
350
460 60 414 506 10 8 — — — — — — — — — — — —
575 60 518 633 10 8 — — — — — — — — — — — —
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
400
460 60 414 506 10 10 — — — — — — — — — — — —
575 60 518 633 10 10 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
450
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
500
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

137
Table 20 — 60 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer (cont)
CONTROL
HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF CIRCUIT
UNIT COND FANS 10 HP Pump, N+1, Low Static 10 HP Pump, N+1, High Static
30XV Voltage MCA
Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE 1 Ph, and
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
208/230 60 187 253 4 4 — — — — — — — — — — — — 115 60
380 60 342 418 4 4 — — — — — — — — — — — — 115 60
140 400 60 360 440 4 4 — — — — — — — — — — — — 115 60
460 60 414 506 4 4 — — — — — — — — — — — — 115 60
575 60 518 633 4 4 — — — — — — — — — — — — 115 60
208/230 60 187 253 5 5 — — — — — — — — — — — — 115 60
380 60 342 418 5 5 — — — — — — — — — — — — 115 60
160 400 60 360 440 5 5 — — — — — — — — — — — — 115 60
460 60 414 506 5 5 — — — — — — — — — — — — 115 60
575 60 518 633 5 5 — — — — — — — — — — — — 115 60
208/230 60 187 253 5 5 — — — — — — — — — — — — 115 60
380 60 342 418 5 5 — — — — — — — — — — — — 115 60
180 400 60 360 440 5 5 — — — — — — — — — — — — 115 60
460 60 414 506 5 5 — — — — — — — — — — — — 115 60
575 60 518 633 5 5 — — — — — — — — — — — — 115 60
208/230 60 187 253 6 6 542.6 522.2 800 800 700 600 542.6 522.2 800 800 700 600 115 60
380 60 342 418 6 6 — — — — — — — — — — — — 115 60
200 400 60 360 440 6 6 — — — — — — — — — — — — 115 60
460 60 414 506 6 6 249.6 240.4 350 350 300 300 249.6 240.4 350 350 300 300 115 60
575 60 518 633 6 6 200.4 193.1 300 300 250 225 200.4 193.1 300 300 250 225 115 60
380 60 342 418 7 5 — — — — — — — — — — — — 115 60
400 60 360 440 7 5 — — — — — — — — — — — — 115 60
225
460 60 414 506 7 5 — — — — — — — — — — — — 115 60
575 60 518 633 7 5 — — — — — — — — — — — — 115 60
380 60 342 418 7 7 — — — — — — — — — — — — 115 60
400 60 360 440 7 7 — — — — — — — — — — — — 115 60
250
460 60 414 506 7 7 — — — — — — — — — — — — 115 60
575 60 518 633 7 7 — — — — — — — — — — — — 115 60
380 60 342 418 7 7 — — — — — — — — — — — — 115 60
400 60 360 440 7 7 — — — — — — — — — — — — 115 60
275
460 60 414 506 7 7 — — — — — — — — — — — — 115 60
575 60 518 633 7 7 — — — — — — — — — — — — 115 60
380 60 342 418 8 8 — — — — — — — — — — — — 115 60
400 60 360 440 8 8 — — — — — — — — — — — — 115 60
300
460 60 414 506 8 8 335.6 326.4 500 500 400 400 — — — — — — 115 60
575 60 518 633 8 8 269.0 261.7 400 400 350 350 — — — — — — 115 60
380 60 342 418 9 9 — — — — — — — — — — — — 115 60
400 60 360 440 9 9 — — — — — — — — — — — — 115 60
325
460 60 414 506 9 9 362.3 353.1 500 500 450 450 — — — — — — 115 60
575 60 518 633 9 9 290.8 283.5 450 450 350 350 — — — — — — 115 60
380 60 342 418 10 8 — — — — — — — — — — — — 115 60
400 60 360 440 10 8 — — — — — — — — — — — — 115 60
350
460 60 414 506 10 8 — — — — — — — — — — — — 115 60
575 60 518 633 10 8 — — — — — — — — — — — — 115 60
380 60 342 418 10 10 — — — — — — — — — — — — 115 60
400 60 360 440 10 10 — — — — — — — — — — — — 115 60
400
460 60 414 506 10 10 — — — — — — — — — — — — 115 60
575 60 518 633 10 10 — — — — — — — — — — — — 115 60
380 60 342 418 11 11 — — — — — — — — — — — — 115 60
400 60 360 440 11 11 — — — — — — — — — — — — 115 60
450
460 60 414 506 11 11 — — — — — — — — — — — — 115 60
575 60 518 633 11 11 — — — — — — — — — — — — 115 60
380 60 342 418 12 12 — — — — — — — — — — — — 115 60
400 60 360 440 12 12 — — — — — — — — — — — — 115 60
500
460 60 414 506 12 12 — — — — — — — — — — — — 115 60
575 60 518 633 12 12 — — — — — — — — — — — — 115 60
See Legend and Notes on page 115.

138
Table 21 — 60 Hz Dual Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
ECM FANS
UNIT VOLTAGE NUMBER OF
UNIT No Hydronic Package
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 2
380 60 342 418 4 4 173.9 166.9 250 250 225 — — — — — — 200
140 400 60 360 440 4 4 165.6 158.6 250 250 200 — — — — — — 200
460 60 414 506 4 4 143.6 137.8 225 225 175 — — — — — — 175
380 60 342 418 5 5 190.4 183.4 300 300 225 — — — — — — 225
160 400 60 360 440 5 5 181.8 174.8 250 250 225 — — — — — — 225
460 60 414 506 5 5 157.1 151.3 250 250 200 172.2 164.9 250 250 200 200 200
380 60 342 418 5 5 215.3 208.3 350 350 300 — — — — — — 250
180 400 60 360 440 5 5 204.4 197.4 300 300 250 — — — — — — 250
460 60 414 506 5 5 177.1 171.3 250 250 225 192.2 184.9 300 300 225 225 225
380 60 342 418 6 6 241.3 231.9 350 350 300 — — — — — — 300
200 400 60 360 440 6 6 230.0 220.7 350 350 300 — — — — — — 300
460 60 414 506 6 6 198.7 191.0 300 300 250 — — — — — — 225
380 60 342 418 7 5 318.3 201.2 500 300 400 — — — — — — 250
225 400 60 360 440 7 5 303.2 190.2 500 300 400 — — — — — — 225
460 60 414 506 7 5 262.4 165.3 400 250 350 — — — — — — 200
380 60 342 418 7 7 304.1 294.7 500 450 400 — — — — — — 350
250 400 60 360 440 7 7 290.2 280.8 450 450 350 — — — — — — 350
460 60 414 506 7 7 251.0 243.3 400 400 300 — — — — — — 300
380 60 342 418 7 7 325.4 316.1 500 500 400 — — — — — — 400
275 400 60 360 440 7 7 309.2 299.8 500 500 400 — — — — — — 400
460 60 414 506 7 7 268.4 260.7 450 400 350 — — — — — — 350
380 60 342 418 8 8 339.6 330.2 500 500 400 — — — — — — 400
300 400 60 360 440 8 8 323.0 313.6 500 500 400 — — — — — — 400
460 60 414 506 8 8 279.8 272.1 450 450 350 — — — — — — 350
380 60 342 418 9 9 369.1 359.8 600 600 450 — — — — — — 450
325 400 60 360 440 9 9 351.1 341.7 500 500 450 — — — — — — 450
460 60 414 506 9 9 304.8 297.1 500 500 400 — — — — — — 350

Table 21 — 60 Hz Dual Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
ECM FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+0, Low Static 10 HP Pump, N+0, High Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 4 4 — — — — — — — — — — — —
140 400 60 360 440 4 4 — — — — — — — — — — — —
460 60 414 506 4 4 — — — — — — — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
160 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — 177.2 169.9 250 250 225 200
380 60 342 418 5 5 — — — — — — — — — — — —
180 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — 197.2 189.9 300 300 250 225
380 60 342 418 6 6 — — — — — — — — — — — —
200 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 218.8 228.2 300 350 300 300 218.8 228.2 300 350 300 300
380 60 342 418 7 5 — — — — — — — — — — — —
225 400 60 360 440 7 5 — — — — — — — — — — — —
460 60 414 506 7 5 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
250 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
275 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
300 400 60 360 440 8 8 — — — — — — — — — — — —
460 60 414 506 8 8 299.9 309.3 450 450 350 400 318.5 309.3 500 450 400 400
380 60 342 418 9 9 — — — — — — — — — — — —
325 400 60 360 440 9 9 — — — — — — — — — — — —
460 60 414 506 9 9 324.9 334.3 500 500 400 400 343.5 334.3 500 500 400 400
See Legend and Notes on page 115.

139
Table 21 — 60 Hz Dual Point Power Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
ECM FANS
UNIT VOLTAGE NUMBER OF
UNIT 7.5 HP Pump, N+1, Low Static 10 HP Pump, N+1, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 4 4 — — — — — — — — — — — —
140 400 60 360 440 4 4 — — — — — — — — — — — —
460 60 414 506 4 4 — — — — — — — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
160 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
180 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
200 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 237.4 228.2 350 350 300 300
380 60 342 418 7 5 — — — — — — — — — — — —
225 400 60 360 440 7 5 — — — — — — — — — — — —
460 60 414 506 7 5 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
250 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
275 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
300 400 60 360 440 8 8 — — — — — — — — — — — —
460 60 414 506 8 8 — — — — — — 318.5 309.3 500 450 400 400
380 60 342 418 9 9 — — — — — — — — — — — —
325 400 60 360 440 9 9 — — — — — — — — — — — —
460 60 414 506 9 9 — — — — — — 343.5 334.3 500 500 400 400

Table 21 — 60 Hz Dual Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
CONTROL
ECM FANS
UNIT VOLTAGE NUMBER OF COND CIRCUIT
UNIT FANS 10 HP Pump, N+1, High Static
30XV Voltage MCA
Supplied MCA MOCP FUSE SIZE 1 PH, and
V(3 Ph) Hz 60 Hz MOCP
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 4 4 — — — — — — 115 60
140 400 60 360 440 4 4 — — — — — — 115 60
460 60 414 506 4 4 — — — — — — 115 60
380 60 342 418 5 5 — — — — — — 115 60
160 400 60 360 440 5 5 — — — — — — 115 60
460 60 414 506 5 5 — — — — — — 115 60
380 60 342 418 5 5 — — — — — — 115 60
180 400 60 360 440 5 5 — — — — — — 115 60
460 60 414 506 5 5 — — — — — — 115 60
380 60 342 418 6 6 — — — — — — 115 60
200 400 60 360 440 6 6 — — — — — — 115 60
460 60 414 506 6 6 237.4 228.2 350 350 300 300 115 60
380 60 342 418 7 5 — — — — — — 115 60
225 400 60 360 440 7 5 — — — — — — 115 60
460 60 414 506 7 5 — — — — — — 115 60
380 60 342 418 7 7 — — — — — — 115 60
250 400 60 360 440 7 7 — — — — — — 115 60
460 60 414 506 7 7 — — — — — — 115 60
380 60 342 418 7 7 — — — — — — 115 60
275 400 60 360 440 7 7 — — — — — — 115 60
460 60 414 506 7 7 — — — — — — 115 60
380 60 342 418 8 8 — — — — — — 115 60
300 400 60 360 440 8 8 — — — — — — 115 60
460 60 414 506 8 8 — — — — — — 115 60
380 60 342 418 9 9 — — — — — — 115 60
325 400 60 360 440 9 9 — — — — — — 115 60
460 60 414 506 9 9 — — — — — — 115 60
See Legend and Notes on page 115.

140
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer
STANDARD CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT No Hydronic Package 7.5 HP Pump, N+0, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 5 5 317.1 304.3 500 500 400 400 349.5 333.3 500 500 400 400
380 60 342 418 5 5 173.5 166.5 250 250 225 200 — — — — — —
140 400 60 360 440 5 5 165.8 158.8 250 250 200 200 — — — — — —
460 60 414 506 5 5 143.2 137.4 225 225 175 175 158.3 151.0 225 225 200 175
575 60 518 633 5 5 114.9 110.3 175 175 150 150 127.0 121.1 175 175 150 150
208/230 60 187 253 6 6 365.2 352.4 500 500 450 450 397.6 381.4 600 600 500 450
380 60 342 418 6 6 200.6 193.6 300 300 250 250 — — — — — —
160 400 60 360 440 6 6 190.1 183.1 300 300 225 225 — — — — — —
460 60 414 506 6 6 164.9 159.1 250 250 200 200 180.0 172.7 250 250 225 200
575 60 518 633 6 6 132.5 127.8 200 200 175 150 144.5 138.7 225 200 175 175
208/230 60 187 253 6 6 480.2 467.4 800 700 600 600 512.6 496.4 800 800 600 600
380 60 342 418 6 6 263.1 256.1 400 400 350 350 — — — — — —
180 400 60 360 440 6 6 215.1 208.1 350 300 300 250 — — — — — —
460 60 414 506 6 6 186.1 180.3 300 300 225 225 201.2 193.9 300 300 250 225
575 60 518 633 6 6 148.7 144.1 225 225 175 175 160.8 154.9 250 250 200 200
208/230 60 187 253 7 7 453.8 436.7 700 700 600 600 — — — — — —
380 60 342 418 7 7 248.7 239.4 400 350 300 300 — — — — — —
200 400 60 360 440 7 7 236.7 227.3 350 350 300 300 — — — — — —
460 60 414 506 7 7 204.8 197.1 300 300 250 250 — — — — — —
575 60 518 633 7 7 164.0 157.9 250 250 200 200 — — — — — —
380 60 342 418 8 6 327.0 208.6 500 300 400 250 — — — — — —
400 60 360 440 8 6 312.2 198.1 500 300 400 250 — — — — — —
225
460 60 414 506 8 6 270.1 172.1 400 250 350 225 — — — — — —
575 60 518 633 8 6 216.6 137.8 350 225 300 175 — — — — — —
380 60 342 418 8 8 314.5 305.2 500 500 400 400 — — — — — —
400 60 360 440 8 8 299.7 290.3 450 450 350 350 — — — — — —
250
460 60 414 506 8 8 259.5 251.8 400 400 350 300 — — — — — —
575 60 518 633 8 8 207.8 201.7 300 300 250 250 — — — — — —
380 60 342 418 8 8 334.5 325.2 500 500 400 400 — — — — — —
400 60 360 440 8 8 318.4 309.1 500 500 400 400 — — — — — —
275
460 60 414 506 8 8 276.1 268.4 450 450 350 350 — — — — — —
575 60 518 633 8 8 221.6 215.4 350 350 300 300 — — — — — —
380 60 342 418 9 9 351.5 342.2 500 500 450 450 — — — — — —
400 60 360 440 9 9 333.9 324.6 500 500 400 400 — — — — — —
300
460 60 414 506 9 9 289.5 281.8 450 450 350 350 — — — — — —
575 60 518 633 9 9 231.6 225.5 350 350 300 300 — — — — — —
380 60 342 418 10 10 384.8 375.5 600 600 450 450 — — — — — —
400 60 360 440 10 10 366.9 357.6 600 500 450 450 — — — — — —
325
460 60 414 506 10 10 317.8 310.1 500 500 400 400 — — — — — —
575 60 518 633 10 10 254.2 248.0 400 400 300 300 — — — — — —
380 60 342 418 11 9 506.9 346.0 800 500 600 450 — — — — — —
400 60 360 440 11 9 481.2 328.3 800 500 600 400 — — — — — —
350
460 60 414 506 11 9 418.0 285.5 700 450 500 350 — — — — — —
575 60 518 633 11 9 334.2 229.2 500 350 400 300 — — — — — —
380 60 342 418 11 11 498.8 488.8 800 800 600 600 — — — — — —
400 60 360 440 11 11 474.3 464.4 700 700 600 600 — — — — — —
400
460 60 414 506 11 11 411.8 403.6 600 600 500 500 — — — — — —
575 60 518 633 11 11 329.6 323.1 500 500 400 400 — — — — — —
380 60 342 418 12 12 539.6 529.6 800 800 700 700 — — — — — —
400 60 360 440 12 12 513.6 503.6 800 800 700 600 — — — — — —
450
460 60 414 506 12 12 445.8 437.6 700 700 600 600 — — — — — —
575 60 518 633 12 12 357.2 350.6 600 500 450 450 — — — — — —
See Legend and Notes on page 115.

141
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
STANDARD CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+0, Low Static 10 HP Pump, N+0, High Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 5 5 — — — — — — 356.5 340.3 500 500 450 400
380 60 342 418 5 5 — — — — — — — — — — — —
140 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — 163.3 156.0 250 225 200 200
575 60 518 633 5 5 — — — — — — 131.0 125.1 200 175 150 150
208/230 60 187 253 6 6 — — — — — — 404.6 388.4 600 600 500 450
380 60 342 418 6 6 — — — — — — — — — — — —
160 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 185.0 177.7 250 250 225 225
575 60 518 633 6 6 — — — — — — 148.5 142.7 225 225 175 175
208/230 60 187 253 6 6 — — — — — — 519.6 503.4 800 800 600 600
380 60 342 418 6 6 — — — — — — — — — — — —
180 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 206.2 198.9 300 300 250 250
575 60 518 633 6 6 — — — — — — 164.8 158.9 250 250 200 200
208/230 60 187 253 7 7 493.1 508.7 700 700 600 600 493.1 508.7 700 700 600 600
380 60 342 418 7 7 — — — — — — — — — — — —
200 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 224.9 234.3 350 350 300 300 224.9 234.3 350 350 300 300
575 60 518 633 7 7 180.1 187.6 250 250 225 225 180.1 187.6 250 250 225 225
380 60 342 418 8 6 — — — — — — — — — — — —
400 60 360 440 8 6 — — — — — — — — — — — —
225
460 60 414 506 8 6 290.2 209.3 450 300 350 250 290.2 209.3 450 300 350 250
575 60 518 633 8 6 232.7 167.6 350 250 300 200 232.7 167.6 350 250 300 200
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
250
460 60 414 506 8 8 279.6 289.0 450 450 350 350 279.6 289.0 450 450 350 350
575 60 518 633 8 8 223.9 231.4 350 350 300 300 223.9 231.4 350 350 300 300
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
275
460 60 414 506 8 8 296.2 305.6 450 450 350 400 314.8 305.6 450 450 400 400
575 60 518 633 8 8 237.7 245.2 350 350 300 300 252.5 245.2 400 350 300 300
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
300
460 60 414 506 9 9 309.7 319.0 500 500 400 400 328.3 319.0 500 500 400 400
575 60 518 633 9 9 247.7 255.2 400 400 300 300 262.6 255.2 400 400 350 300
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
325
460 60 414 506 10 10 338.0 347.3 500 500 400 400 356.6 347.3 500 500 450 400
575 60 518 633 10 10 270.3 277.8 400 400 350 350 285.1 277.8 450 400 350 350
380 60 342 418 11 9 — — — — — — — — — — — —
400 60 360 440 11 9 — — — — — — — — — — — —
350
460 60 414 506 11 9 — — — — — — — — — — — —
575 60 518 633 11 9 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
400
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
450
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

142
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
STANDARD CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 7.5 HP Pump, N+1, Low Static 10 HP Pump, N+1, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 5 5 — — — — — — — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
140 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — — — — — — —
575 60 518 633 5 5 — — — — — — — — — — — —
208/230 60 187 253 6 6 397.6 410.4 600 600 500 500 — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
160 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 180.0 186.3 250 250 225 225 — — — — — —
575 60 518 633 6 6 144.5 149.6 225 225 175 175 — — — — — —
208/230 60 187 253 6 6 512.6 525.4 800 800 600 700 — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
180 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 201.2 207.5 300 300 250 250 — — — — — —
575 60 518 633 6 6 160.8 165.8 250 250 200 200 — — — — — —
208/230 60 187 253 7 7 — — — — — — 529.1 508.7 800 700 700 600
380 60 342 418 7 7 — — — — — — — — — — — —
200 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — 243.5 234.3 350 350 300 300
575 60 518 633 7 7 — — — — — — 195.0 187.6 250 250 225 225
380 60 342 418 8 6 — — — — — — — — — — — —
400 60 360 440 8 6 — — — — — — — — — — — —
225
460 60 414 506 8 6 — — — — — — 308.8 209.3 450 300 400 250
575 60 518 633 8 6 — — — — — — 247.5 167.6 350 250 300 200
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
250
460 60 414 506 8 8 — — — — — — 298.2 289.0 450 450 350 350
575 60 518 633 8 8 — — — — — — 238.8 231.4 350 350 300 300
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
275
460 60 414 506 8 8 — — — — — — 314.8 305.6 450 450 400 400
575 60 518 633 8 8 — — — — — — 252.5 245.2 400 350 300 300
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
300
460 60 414 506 9 9 — — — — — — 328.3 319.0 500 500 400 400
575 60 518 633 9 9 — — — — — — 262.6 255.2 400 400 350 300
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
325
460 60 414 506 10 10 — — — — — — 356.6 347.3 500 500 450 400
575 60 518 633 10 10 — — — — — — 285.1 277.8 450 400 350 350
380 60 342 418 11 9 — — — — — — — — — — — —
400 60 360 440 11 9 — — — — — — — — — — — —
350
460 60 414 506 11 9 — — — — — — — — — — — —
575 60 518 633 11 9 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
400
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
450
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

143
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+1, High Static NO HYDRONIC PACKAGE
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 5 5 — — — — — — 323.6 310.8 500 500 400 400
380 60 342 418 5 5 — — — — — — 177.0 170.0 250 250 225 200
140 400 60 360 440 5 5 — — — — — — 169.3 162.3 250 250 200 200
460 60 414 506 5 5 — — — — — — 146.2 140.4 225 225 175 175
575 60 518 633 5 5 — — — — — — 117.4 112.8 175 175 150 150
208/230 60 187 253 6 6 404.6 424.4 600 600 500 500 373.0 360.2 600 500 450 450
380 60 342 418 6 6 — — — — — — 204.8 197.8 300 300 250 250
160 400 60 360 440 6 6 — — — — — — 194.2 187.2 300 300 225 225
460 60 414 506 6 6 185.0 196.3 250 300 225 225 168.5 162.7 250 250 200 200
575 60 518 633 6 6 148.5 157.6 225 225 175 200 135.5 130.8 200 200 175 175
208/230 60 187 253 6 6 519.6 539.4 800 800 600 700 488.0 475.2 800 800 600 600
380 60 342 418 6 6 — — — — — — 267.3 260.3 400 400 350 350
180 400 60 360 440 6 6 — — — — — — 219.2 212.2 350 350 300 250
460 60 414 506 6 6 206.2 217.5 300 300 250 250 189.7 183.9 300 300 225 225
575 60 518 633 6 6 164.8 173.8 250 250 200 200 151.7 147.1 225 225 200 175
208/230 60 187 253 7 7 529.1 508.7 800 700 700 600 462.9 445.8 700 700 600 600
380 60 342 418 7 7 — — — — — — 253.6 244.3 400 400 300 300
200 400 60 360 440 7 7 — — — — — — 241.5 232.2 350 350 300 300
460 60 414 506 7 7 243.5 234.3 350 350 300 300 209.0 201.3 300 300 250 250
575 60 518 633 7 7 195.0 187.6 250 250 225 225 167.5 161.4 250 250 200 200
380 60 342 418 8 6 — — — — — — 332.6 212.8 500 350 400 250
400 60 360 440 8 6 — — — — — — 317.7 202.2 500 300 400 250
225
460 60 414 506 8 6 308.8 209.3 450 300 400 250 274.9 175.7 450 250 350 225
575 60 518 633 8 6 247.5 167.6 350 250 300 200 220.6 140.8 350 225 300 175
380 60 342 418 8 8 — — — — — — 320.1 310.8 500 500 400 400
400 60 360 440 8 8 — — — — — — 305.2 295.9 500 450 400 350
250
460 60 414 506 8 8 298.2 289.0 450 450 350 350 264.3 256.6 400 400 350 300
575 60 518 633 8 8 238.8 231.4 350 350 300 300 211.8 205.7 300 300 250 250
380 60 342 418 8 8 — — — — — — 340.1 330.8 500 500 400 400
400 60 360 440 8 8 — — — — — — 323.9 314.6 500 500 400 400
275
460 60 414 506 8 8 — — — — — — 280.9 273.2 450 450 350 350
575 60 518 633 8 8 — — — — — — 225.6 219.4 350 350 300 300
380 60 342 418 9 9 — — — — — — 357.8 348.5 500 500 450 450
400 60 360 440 9 9 — — — — — — 340.1 330.8 500 500 400 400
300
460 60 414 506 9 9 — — — — — — 294.9 287.2 450 450 350 350
575 60 518 633 9 9 — — — — — — 236.1 230.0 350 350 300 300
380 60 342 418 10 10 — — — — — — 391.8 382.5 600 600 500 450
400 60 360 440 10 10 — — — — — — 373.8 364.5 600 600 450 450
325
460 60 414 506 10 10 — — — — — — 323.8 316.1 500 500 400 400
575 60 518 633 10 10 — — — — — — 259.2 253.0 400 400 350 300
380 60 342 418 11 9 — — — — — — 514.6 352.3 800 500 700 450
400 60 360 440 11 9 — — — — — — 488.8 334.6 800 500 600 400
350
460 60 414 506 11 9 — — — — — — 424.6 290.9 700 450 500 350
575 60 518 633 11 9 — — — — — — 339.7 233.7 500 350 400 300
380 60 342 418 11 11 — — — — — — 506.5 496.5 800 800 600 600
400 60 360 440 11 11 — — — — — — 481.9 472.0 800 700 600 600
400
460 60 414 506 11 11 — — — — — — 418.4 410.2 600 600 500 500
575 60 518 633 11 11 — — — — — — 335.1 328.6 500 500 400 400
380 60 342 418 12 12 — — — — — — 548.0 538.0 800 800 700 700
400 60 360 440 12 12 — — — — — — 521.9 511.9 800 800 700 600
450
460 60 414 506 12 12 — — — — — — 453.0 444.8 700 700 600 600
575 60 518 633 12 12 — — — — — — 363.2 356.6 600 600 450 450
See Legend and Notes on page 115.

144
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 7.5 HP Pump, N+0, Low Static 10 HP Pump, N+0, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 5 5 356.0 339.8 500 500 450 400 — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
140 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 161.3 154.0 250 225 200 200 — — — — — —
575 60 518 633 5 5 129.5 123.6 200 175 150 150 — — — — — —
208/230 60 187 253 6 6 405.4 389.2 600 600 500 450 — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
160 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 183.6 176.3 250 250 225 225 — — — — — —
575 60 518 633 6 6 147.5 141.7 225 225 175 175 — — — — — —
208/230 60 187 253 6 6 520.4 504.2 800 800 700 600 — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
180 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 204.8 197.5 300 300 250 250 — — — — — —
575 60 518 633 6 6 163.8 157.9 250 250 200 200 — — — — — —
208/230 60 187 253 7 7 — — — — — — 502.2 517.8 700 800 600 600
380 60 342 418 7 7 — — — — — — — — — — — —
200 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — 229.1 238.5 350 350 300 300
575 60 518 633 7 7 — — — — — — 183.6 191.1 250 250 225 225
380 60 342 418 8 6 — — — — — — — — — — — —
400 60 360 440 8 6 — — — — — — — — — — — —
225
460 60 414 506 8 6 — — — — — — 295.0 212.9 450 300 350 250
575 60 518 633 8 6 — — — — — — 236.7 170.6 350 250 300 200
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
250
460 60 414 506 8 8 — — — — — — 284.4 293.8 450 450 350 350
575 60 518 633 8 8 — — — — — — 227.9 235.4 350 350 300 300
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
275
460 60 414 506 8 8 — — — — — — 301.0 310.4 450 450 350 400
575 60 518 633 8 8 — — — — — — 241.7 249.2 350 350 300 300
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
300
460 60 414 506 9 9 — — — — — — 315.1 324.4 500 500 400 400
575 60 518 633 9 9 — — — — — — 252.2 259.7 400 400 300 300
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
325
460 60 414 506 10 10 — — — — — — 344.0 353.3 500 500 400 450
575 60 518 633 10 10 — — — — — — 275.3 282.8 400 450 350 350
380 60 342 418 11 9 — — — — — — — — — — — —
400 60 360 440 11 9 — — — — — — — — — — — —
350
460 60 414 506 11 9 — — — — — — — — — — — —
575 60 518 633 11 9 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
400
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
450
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

145
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+0, High Static 7.5 HP Pump, N+1, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
208/230 60 187 253 5 5 363.0 346.8 500 500 450 400 — — — — — —
380 60 342 418 5 5 — — — — — — — — — — — —
140 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 166.3 159.0 250 225 200 200 — — — — — —
575 60 518 633 5 5 133.5 127.6 200 200 175 150 — — — — — —
208/230 60 187 253 6 6 412.4 396.2 600 600 500 500 405.4 418.2 600 600 500 500
380 60 342 418 6 6 — — — — — — — — — — — —
160 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 188.6 181.3 250 250 225 225 183.6 189.9 250 250 225 225
575 60 518 633 6 6 151.5 145.7 225 225 175 175 147.5 152.6 225 225 175 175
208/230 60 187 253 6 6 527.4 511.2 800 800 700 600 520.4 533.2 800 800 700 700
380 60 342 418 6 6 — — — — — — — — — — — —
180 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 209.8 202.5 300 300 250 250 204.8 211.1 300 300 250 250
575 60 518 633 6 6 167.8 161.9 250 250 200 200 163.8 168.8 250 250 200 200
208/230 60 187 253 7 7 502.2 517.8 700 800 600 600 — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
200 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 229.1 238.5 350 350 300 300 — — — — — —
575 60 518 633 7 7 183.6 191.1 250 250 225 225 — — — — — —
380 60 342 418 8 6 — — — — — — — — — — — —
400 60 360 440 8 6 — — — — — — — — — — — —
225
460 60 414 506 8 6 295.0 212.9 450 300 350 250 — — — — — —
575 60 518 633 8 6 236.7 170.6 350 250 300 200 — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
250
460 60 414 506 8 8 284.4 293.8 450 450 350 350 — — — — — —
575 60 518 633 8 8 227.9 235.4 350 350 300 300 — — — — — —
380 60 342 418 8 8 — — — — — — — — — — — —
400 60 360 440 8 8 — — — — — — — — — — — —
275
460 60 414 506 8 8 319.6 310.4 500 450 400 400 — — — — — —
575 60 518 633 8 8 256.5 249.2 400 350 300 300 — — — — — —
380 60 342 418 9 9 — — — — — — — — — — — —
400 60 360 440 9 9 — — — — — — — — — — — —
300
460 60 414 506 9 9 333.7 324.4 500 500 400 400 — — — — — —
575 60 518 633 9 9 267.1 259.7 400 400 350 300 — — — — — —
380 60 342 418 10 10 — — — — — — — — — — — —
400 60 360 440 10 10 — — — — — — — — — — — —
325
460 60 414 506 10 10 362.6 353.3 500 500 450 450 — — — — — —
575 60 518 633 10 10 290.1 282.8 450 450 350 350 — — — — — —
380 60 342 418 11 9 — — — — — — — — — — — —
400 60 360 440 11 9 — — — — — — — — — — — —
350
460 60 414 506 11 9 — — — — — — — — — — — —
575 60 518 633 11 9 — — — — — — — — — — — —
380 60 342 418 11 11 — — — — — — — — — — — —
400 60 360 440 11 11 — — — — — — — — — — — —
400
460 60 414 506 11 11 — — — — — — — — — — — —
575 60 518 633 11 11 — — — — — — — — — — — —
380 60 342 418 12 12 — — — — — — — — — — — —
400 60 360 440 12 12 — — — — — — — — — — — —
450
460 60 414 506 12 12 — — — — — — — — — — — —
575 60 518 633 12 12 — — — — — — — — — — — —
See Legend and Notes on page 115.

146
Table 22 — 60 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer (cont)
CONTROL
HIGH STATIC CONDENSER FANS
UNIT VOLTAGE NUMBER OF CIRCUIT
UNIT COND FANS 10 HP Pump, N+1, Low Static 10 HP Pump, N+1, High Static
30XV Voltage MCA
Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE 1 Ph, and
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
208/230 60 187 253 5 5 — — — — — — — — — — — — 115 60
380 60 342 418 5 5 — — — — — — — — — — — — 115 60
140 400 60 360 440 5 5 — — — — — — — — — — — — 115 60
460 60 414 506 5 5 — — — — — — — — — — — — 115 60
575 60 518 633 5 5 — — — — — — — — — — — — 115 60
208/230 60 187 253 6 6 — — — — — — 412.4 432.2 600 600 500 500 115 60
380 60 342 418 6 6 — — — — — — — — — — — — 115 60
160 400 60 360 440 6 6 — — — — — — — — — — — — 115 60
460 60 414 506 6 6 — — — — — — 188.6 199.9 250 300 225 250 115 60
575 60 518 633 6 6 — — — — — — 151.5 160.6 225 225 175 200 115 60
208/230 60 187 253 6 6 — — — — — — 527.4 547.2 800 800 700 700 115 60
380 60 342 418 6 6 — — — — — — — — — — — — 115 60
180 400 60 360 440 6 6 — — — — — — — — — — — — 115 60
460 60 414 506 6 6 — — — — — — 209.8 221.1 300 300 250 300 115 60
575 60 518 633 6 6 — — — — — — 167.8 176.8 250 250 200 225 115 60
208/230 60 187 253 7 7 538.2 517.8 800 800 700 600 538.2 517.8 800 800 700 600 115 60
380 60 342 418 7 7 — — — — — — — — — — — — 115 60
200 400 60 360 440 7 7 — — — — — — — — — — — — 115 60
460 60 414 506 7 7 247.7 238.5 350 350 300 300 247.7 238.5 350 350 300 300 115 60
575 60 518 633 7 7 198.5 191.1 300 250 225 225 198.5 191.1 300 250 225 225 115 60
380 60 342 418 8 6 — — — — — — — — — — — — 115 60
400 60 360 440 8 6 — — — — — — — — — — — — 115 60
225
460 60 414 506 8 6 313.6 212.9 450 300 400 250 313.6 212.9 450 300 400 250 115 60
575 60 518 633 8 6 251.5 170.6 350 250 300 200 251.5 170.6 350 250 300 200 115 60
380 60 342 418 8 8 — — — — — — — — — — — — 115 60
400 60 360 440 8 8 — — — — — — — — — — — — 115 60
250
460 60 414 506 8 8 303.0 293.8 450 450 350 350 303.0 293.8 450 450 350 350 115 60
575 60 518 633 8 8 242.8 235.4 350 350 300 300 242.8 235.4 350 350 300 300 115 60
380 60 342 418 8 8 — — — — — — — — — — — — 115 60
400 60 360 440 8 8 — — — — — — — — — — — — 115 60
275
460 60 414 506 8 8 319.6 310.4 500 450 400 400 — — — — — — 115 60
575 60 518 633 8 8 256.5 249.2 400 350 300 300 — — — — — — 115 60
380 60 342 418 9 9 — — — — — — — — — — — — 115 60
400 60 360 440 9 9 — — — — — — — — — — — — 115 60
300
460 60 414 506 9 9 333.7 324.4 500 500 400 400 — — — — — — 115 60
575 60 518 633 9 9 267.1 259.7 400 400 350 300 — — — — — — 115 60
380 60 342 418 10 10 — — — — — — — — — — — — 115 60
400 60 360 440 10 10 — — — — — — — — — — — — 115 60
325
460 60 414 506 10 10 362.6 353.3 500 500 450 450 — — — — — — 115 60
575 60 518 633 10 10 290.1 282.8 450 450 350 350 — — — — — — 115 60
380 60 342 418 11 9 — — — — — — — — — — — — 115 60
400 60 360 440 11 9 — — — — — — — — — — — — 115 60
350
460 60 414 506 11 9 — — — — — — — — — — — — 115 60
575 60 518 633 11 9 — — — — — — — — — — — — 115 60
380 60 342 418 11 11 — — — — — — — — — — — — 115 60
400 60 360 440 11 11 — — — — — — — — — — — — 115 60
400
460 60 414 506 11 11 — — — — — — — — — — — — 115 60
575 60 518 633 11 11 — — — — — — — — — — — — 115 60
380 60 342 418 12 12 — — — — — — — — — — — — 115 60
400 60 360 440 12 12 — — — — — — — — — — — — 115 60
450
460 60 414 506 12 12 — — — — — — — — — — — — 115 60
575 60 518 633 12 12 — — — — — — — — — — — — 115 60
See Legend and Notes on page 115.

147
Table 23 — 60 Hz Dual Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
ECM FANS
UNIT VOLTAGE NUMBER OF
UNIT NO HYDRONIC PACKAGE 7.5 HP Pump, N+0, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 5 5 166.7 159.6 250 250 200 200 — — — — — —
140 400 60 360 440 5 5 159.3 152.2 250 250 200 200 — — — — — —
460 60 414 506 5 5 137.5 131.7 200 200 175 175 152.6 145.3 225 225 175 175
380 60 342 418 6 6 192.6 185.6 300 300 225 225 — — — — — —
160 400 60 360 440 6 6 182.6 175.6 250 250 225 225 — — — — — —
460 60 414 506 6 6 158.4 152.5 250 250 200 200 173.5 166.1 250 250 200 200
380 60 342 418 6 6 252.0 245.0 400 400 300 300 — — — — — —
180 400 60 360 440 6 6 206.3 199.3 300 300 250 250 — — — — — —
460 60 414 506 6 6 178.5 172.7 250 250 225 225 193.7 186.3 300 300 225 225
380 60 342 418 7 7 238.8 229.4 350 350 300 300 — — — — — —
200 400 60 360 440 7 7 227.2 217.9 350 350 300 300 — — — — — —
460 60 414 506 7 7 196.6 188.9 300 300 250 225 — — — — — —
380 60 342 418 8 6 313.4 199.9 500 300 400 250 — — — — — —
225 400 60 360 440 8 6 299.2 189.8 450 300 350 225 — — — — — —
460 60 414 506 8 6 258.9 164.9 400 250 350 200 — — — — — —
380 60 342 418 8 8 301.6 292.2 450 450 400 350 — — — — — —
250 400 60 360 440 8 8 287.4 278.0 450 450 350 350 — — — — — —
460 60 414 506 8 8 248.8 241.1 400 400 300 300 — — — — — —
380 60 342 418 8 8 320.6 311.2 500 500 400 400 — — — — — —
275 400 60 360 440 8 8 305.2 295.8 500 450 400 350 — — — — — —
460 60 414 506 8 8 264.6 256.9 400 400 350 350 — — — — — —
380 60 342 418 9 9 337.0 327.7 500 500 400 400 — — — — — —
300 400 60 360 440 9 9 320.2 310.8 500 500 400 400 — — — — — —
460 60 414 506 9 9 277.6 269.9 450 450 350 350 — — — — — —
380 60 342 418 10 10 369.0 359.6 600 600 450 450 — — — — — —
325 400 60 360 440 10 10 351.8 342.5 500 500 450 400 — — — — — —
460 60 414 506 10 10 304.7 297.0 500 450 400 350 — — — — — —

Table 23 — 60 Hz Dual Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
ECM FANS
UNIT VOLTAGE NUMBER OF
UNIT 10 HP Pump, N+0, Low Static 10 HP Pump, N+0, High Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSE SIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 5 5 — — — — — — — — — — — —
140 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — 157.6 150.3 225 225 200 175
380 60 342 418 6 6 — — — — — — — — — — — —
160 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 178.5 171.1 250 250 225 200
380 60 342 418 6 6 — — — — — — — — — — — —
180 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 — — — — — — 198.7 191.3 300 300 250 225
380 60 342 418 7 7 — — — — — — — — — — — —
200 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 216.8 226.1 300 350 250 300 216.8 226.1 300 350 250 300
380 60 342 418 8 6 — — — — — — — — — — — —
225 400 60 360 440 8 6 — — — — — — — — — — — —
460 60 414 506 8 6 279.0 202.1 400 300 350 250 279.0 202.1 400 300 350 250
380 60 342 418 8 8 — — — — — — — — — — — —
250 400 60 360 440 8 8 — — — — — — — — — — — —
460 60 414 506 8 8 268.9 278.3 400 400 350 350 268.9 278.3 400 400 350 350
380 60 342 418 8 8 — — — — — — — — — — — —
275 400 60 360 440 8 8 — — — — — — — — — — — —
460 60 414 506 8 8 284.7 294.1 450 450 350 350 303.3 294.1 450 450 350 350
380 60 342 418 9 9 — — — — — — — — — — — —
300 400 60 360 440 9 9 — — — — — — — — — — — —
460 60 414 506 9 9 297.7 307.1 450 450 350 400 316.3 307.1 450 450 400 400
380 60 342 418 10 10 — — — — — — — — — — — —
325 400 60 360 440 10 10 — — — — — — — — — — — —
460 60 414 506 10 10 324.9 334.2 500 500 400 400 343.5 334.2 500 500 400 400
See Legend and Notes on page 115.

148
Table 23 — 60 Hz Dual Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
ECM FANS
UNIT VOLTAGE NUMBER OF
UNIT 7.5 HP Pump, N+1, Low Static 10 HP Pump, N+1, Low Static
COND FANS
30XV Supplied MCA MOCP FUSE SIZE MCA MOCP FUSESIZE
V(3 Ph) Hz
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 5 5 — — — — — — — — — — — —
140 400 60 360 440 5 5 — — — — — — — — — — — —
460 60 414 506 5 5 — — — — — — — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
160 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 173.5 179.7 250 250 200 225 — — — — — —
380 60 342 418 6 6 — — — — — — — — — — — —
180 400 60 360 440 6 6 — — — — — — — — — — — —
460 60 414 506 6 6 193.7 199.9 300 300 225 250 — — — — — —
380 60 342 418 7 7 — — — — — — — — — — — —
200 400 60 360 440 7 7 — — — — — — — — — — — —
460 60 414 506 7 7 — — — — — — 235.4 226.1 350 350 300 300
380 60 342 418 8 6 — — — — — — — — — — — —
225 400 60 360 440 8 6 — — — — — — — — — — — —
460 60 414 506 8 6 — — — — — — 297.6 202.1 450 300 350 250
380 60 342 418 8 8 — — — — — — — — — — — —
250 400 60 360 440 8 8 — — — — — — — — — — — —
460 60 414 506 8 8 — — — — — — 287.5 278.3 400 400 350 350
380 60 342 418 8 8 — — — — — — — — — — — —
275 400 60 360 440 8 8 — — — — — — — — — — — —
460 60 414 506 8 8 — — — — — — 303.3 294.1 450 450 350 350
380 60 342 418 9 9 — — — — — — — — — — — —
300 400 60 360 440 9 9 — — — — — — — — — — — —
460 60 414 506 9 9 — — — — — — 316.3 307.1 450 450 400 400
380 60 342 418 10 10 — — — — — — — — — — — —
325 400 60 360 440 10 10 — — — — — — — — — — — —
460 60 414 506 10 10 — — — — — — 343.5 334.2 500 500 400 400

Table 23 — 60 Hz Dual Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options (cont)
CONTROL
ECM FANS
UNIT VOLTAGE NUMBER OF COND CIRCUIT
UNIT FANS 7.5 HP Pump, N+1, Low Static
30XV Voltage MCA
Supplied MCA MOCP FUSE SIZE 1 PH, and
V(3 Ph) Hz 60 Hz MOCP
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
380 60 342 418 5 5 — — — — — — 115 60
140 400 60 360 440 5 5 — — — — — — 115 60
460 60 414 506 5 5 — — — — — — 115 60
380 60 342 418 6 6 — — — — — — 115 60
160 400 60 360 440 6 6 — — — — — — 115 60
460 60 414 506 6 6 178.5 189.7 250 250 225 225 115 60
380 60 342 418 6 6 — — — — — — 115 60
180 400 60 360 440 6 6 — — — — — — 115 60
460 60 414 506 6 6 198.7 209.9 300 300 250 250 115 60
380 60 342 418 7 7 — — — — — — 115 60
200 400 60 360 440 7 7 — — — — — — 115 60
460 60 414 506 7 7 235.4 226.1 350 350 300 300 115 60
380 60 342 418 8 6 — — — — — — 115 60
225 400 60 360 440 8 6 — — — — — — 115 60
460 60 414 506 8 6 297.6 202.1 450 300 350 250 115 60
380 60 342 418 8 8 — — — — — — 115 60
250 400 60 360 440 8 8 — — — — — — 115 60
460 60 414 506 8 8 287.5 278.3 400 400 350 350 115 60
380 60 342 418 8 8 — — — — — — 115 60
275 400 60 360 440 8 8 — — — — — — 115 60
460 60 414 506 8 8 — — — — — — 115 60
380 60 342 418 9 9 — — — — — — 115 60
300 400 60 360 440 9 9 — — — — — — 115 60
460 60 414 506 9 9 — — — — — — 115 60
380 60 342 418 10 10 — — — — — — 115 60
325 400 60 360 440 10 10 — — — — — — 115 60
460 60 414 506 10 10 — — — — — — 115 60
See Legend and Notes on page 115.

149
Table 24 — 50 Hz Single Point Power Standard Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS CONTROL CIRCUIT
NUMBER
UNIT Supplied Voltage MCA
OF COND FUSE FUSE
30XV V(3 Ph) Hz MCA MOCP MCA MOCP 1 Ph, and
Min Max FANS SIZE SIZE
60 Hz MOCP
380 50 342 418 8 385.1 500 450 390.6 500 450 115 60
400 50 360 440 8 367.0 500 450 372.4 500 450 115 60
160
415 50 374 457 8 354.1 450 400 359.6 450 400 115 60
440 50 396 484 8 333.7 450 400 339.2 450 400 115 60
380 50 342 418 8 443.6 600 500 449.1 600 500 115 60
400 50 360 440 8 423.2 500 500 428.7 500 500 115 60
180
415 50 374 457 8 408.1 500 450 413.6 500 500 115 60
440 50 396 484 8 385.4 500 450 390.9 500 450 115 60
380 50 342 418 10 462.2 600 600 469.0 600 600 115 60
400 50 360 440 10 441.2 600 500 448.0 600 500 115 60
200
415 50 374 457 10 425.7 500 500 432.5 500 500 115 60
440 50 396 484 10 400.1 500 450 407.0 500 450 115 60
380 50 342 418 10 530.5 700 600 537.3 700 600 115 60
400 50 360 440 10 505.5 700 600 512.3 700 600 115 60
225
415 50 374 457 10 487.5 700 600 494.3 700 600 115 60
440 50 396 484 10 460.2 600 600 467.1 600 600 115 60
380 50 342 418 12 611.3 800 700 619.5 800 700 115 60
400 50 360 440 12 583.0 800 700 591.2 800 700 115 60
250
415 50 374 457 12 562.6 700 700 570.8 700 700 115 60
440 50 396 484 12 529.7 700 600 537.9 700 600 115 60
380 50 342 418 12 631.6 800 700 639.8 800 800 115 60
400 50 360 440 12 601.0 800 700 609.2 800 700 115 60
275
415 50 374 457 12 580.6 800 700 588.8 800 700 115 60
440 50 396 484 12 547.7 700 700 555.9 700 700 115 60
380 50 342 418 14 674.9 800 800 684.5 800 800 115 60
400 50 360 440 14 643.8 800 800 653.3 800 800 115 60
300
415 50 374 457 14 620.7 800 700 630.2 800 700 115 60
440 50 396 484 14 584.9 800 700 594.5 800 700 115 60
380 50 342 418 16 743.0 1000 1000 753.9 1000 1000 115 60
400 50 360 440 16 706.8 800 800 717.6 800 800 115 60
325
415 50 374 457 16 683.3 800 800 694.2 800 800 115 60
440 50 396 484 16 644.6 800 800 655.6 800 800 115 60
380 50 342 418 16 864.2 1200 1000 875.2 1200 1000 115 60
400 50 360 440 16 822.8 1000 1000 833.6 1000 1000 115 60
350
415 50 374 457 16 793.3 1000 1000 804.2 1000 1000 115 60
440 50 396 484 16 748.3 1000 1000 759.4 1000 1000 115 60
380 50 342 418 18 915.2 1200 1200 927.5 1200 1200 115 60
400 50 360 440 18 871.6 1200 1000 883.9 1200 1000 115 60
400
415 50 374 457 18 841.0 1000 1000 853.3 1000 1000 115 60
440 50 396 484 18 792.7 1000 1000 805.1 1000 1000 115 60
380 50 342 418 20 1089.0 1200 1200 1102.7 1200 1200 115 60
400 50 360 440 20 1035.9 1200 1200 1049.5 1200 1200 115 60
450
415 50 374 457 20 998.1 1200 1200 1011.7 1200 1200 115 60
440 50 396 484 20 942.4 1200 1200 956.2 1200 1200 115 60
380 50 342 418 22 1172.9 1600 1600 1187.9 1600 1600 115 60
400 50 360 440 22 1116.9 1200 1200 1131.8 1200 1200 115 60
500
415 50 374 457 22 1076.4 1200 1200 1091.4 1200 1200 115 60
440 50 396 484 22 1015.6 1200 1200 1030.8 1200 1200 115 60
See Legend and Notes on page 115.

150
Table 25 — 50 Hz Single Point Power Standard Tier Fan Motors with Control Power Transformer, with
Electrically Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM Condenser Fans CONTROL CIRCUIT
UNIT Supplied NUMBER OF Voltage MCA
30XV COND FANS FUSE
V(3 Ph) Hz MCA MOCP 1 Ph, and
Min Max SIZE
60 Hz MOCP
380 50 342 418 8 368.6 500 450 115 60
400 50 360 440 8 351.2 450 400 115 60
160
415 50 374 457 8 337.7 450 400 115 60
440 50 396 484 8 317.0 400 350 115 60
380 50 342 418 8 424.2 500 500 115 60
400 50 360 440 8 404.7 500 450 115 60
180
415 50 374 457 8 390.2 500 450 115 60
440 50 396 484 8 368.5 500 450 115 60
380 50 342 418 10 442.4 600 500 115 60
400 50 360 440 10 422.3 500 500 115 60
200
415 50 374 457 10 407.5 500 450 115 60
440 50 396 484 10 383.0 500 450 115 60
380 50 342 418 10 507.4 700 600 115 60
400 50 360 440 10 483.5 700 600 115 60
225
415 50 374 457 10 466.3 600 600 115 60
440 50 396 484 10 440.2 600 500 115 60
380 50 342 418 12 584.8 800 700 115 60
400 50 360 440 12 557.7 700 700 115 60
250
415 50 374 457 12 538.2 700 600 115 60
440 50 396 484 12 506.7 700 600 115 60
380 50 342 418 12 604.0 800 700 115 60
400 50 360 440 12 574.8 700 700 115 60
275
415 50 374 457 12 555.3 700 700 115 60
440 50 396 484 12 523.8 700 600 115 60
380 50 342 418 14 645.8 800 800 115 60
400 50 360 440 14 616.0 800 700 115 60
300
415 50 374 457 14 593.9 800 700 115 60
440 50 396 484 14 559.7 700 700 115 60
380 50 342 418 16 711.0 800 800 115 60
400 50 360 440 16 676.4 800 800 115 60
325
415 50 374 457 16 653.9 800 800 115 60
440 50 396 484 16 616.9 800 700 115 60
See Legend and Notes on page 115.

151
Table 26 — 50 Hz Single Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS CONTROL CIRCUIT
NUMBER
UNIT Supplied Voltage MCA
OF COND FUSE FUSE
30XV V(3 Ph) Hz MCA MOCP MCA MOCP 1 Ph, and
Min Max FANS SIZE SIZE
60 Hz MOCP
380 50 342 418 8 333.4 450 400 338.8 450 400 115 60
400 50 360 440 8 317.5 400 350 322.9 400 400 115 60
140
415 50 374 457 8 309.9 400 350 312.3 400 350 115 60
440 50 396 484 8 290.9 350 350 296.4 400 350 115 60
380 50 342 418 10 365.4 450 400 372.3 500 450 115 60
400 50 360 440 10 349.0 450 400 355.8 450 400 115 60
160
415 50 374 457 10 341.1 450 400 342.5 450 400 115 60
440 50 396 484 10 316.9 400 350 323.8 400 400 115 60
380 50 342 418 10 414.9 500 500 421.8 500 500 115 60
400 50 360 440 10 396.2 500 450 403.0 500 450 115 60
180
415 50 374 457 10 380.7 500 450 387.5 500 450 115 60
440 50 396 484 10 359.6 450 400 366.5 500 450 115 60
380 50 342 418 12 462.8 600 600 471.0 600 600 115 60
400 50 360 440 12 441.3 600 500 449.4 600 500 115 60
200
415 50 374 457 12 425.3 500 500 433.5 500 500 115 60
440 50 396 484 12 401.4 500 450 409.7 500 450 115 60
380 50 342 418 12 517.1 700 600 525.3 700 600 115 60
400 50 360 440 12 492.8 700 600 500.9 700 600 115 60
225
415 50 374 457 12 475.3 600 600 483.5 600 600 115 60
440 50 396 484 12 448.7 600 500 456.9 600 600 115 60
380 50 342 418 14 584.9 800 700 594.5 800 700 115 60
400 50 360 440 14 558.3 700 700 567.8 700 700 115 60
250
415 50 374 457 14 537.4 700 600 547.0 700 600 115 60
440 50 396 484 14 508.4 600 600 518.0 600 600 115 60
380 50 342 418 14 625.4 800 700 635.0 800 700 115 60
400 50 360 440 14 596.5 800 700 606.0 800 700 115 60
275
415 50 374 457 14 575.7 700 700 585.2 800 700 115 60
440 50 396 484 14 542.1 700 600 551.8 700 700 115 60
380 50 342 418 16 653.0 800 800 663.9 800 800 115 60
400 50 360 440 16 621.3 800 700 632.1 800 700 115 60
300
415 50 374 457 16 600.0 800 700 610.9 800 700 115 60
440 50 396 484 16 565.8 700 700 576.9 700 700 115 60
380 50 342 418 18 712.1 800 800 724.4 800 800 115 60
400 50 360 440 18 677.5 800 800 689.7 800 800 115 60
325
415 50 374 457 18 653.6 800 800 665.9 800 800 115 60
440 50 396 484 18 616.6 800 700 629.0 800 700 115 60
380 50 342 418 18 802.8 1000 1000 815.1 1000 1000 115 60
400 50 360 440 18 764.3 1000 1000 776.5 1000 1000 115 60
350
415 50 374 457 18 736.6 1000 1000 748.9 1000 1000 115 60
440 50 396 484 18 695.6 800 800 708.0 1000 800 115 60
380 50 342 418 20 909.0 1200 1000 922.7 1200 1200 115 60
400 50 360 440 20 864.9 1000 1000 878.5 1200 1000 115 60
400
415 50 374 457 20 833.8 1000 1000 847.5 1000 1000 115 60
440 50 396 484 20 787.2 1000 1000 801.0 1000 1000 115 60
380 50 342 418 22 1085.1 1200 1200 1100.2 1200 1200 115 60
400 50 360 440 22 1031.4 1200 1200 1046.3 1200 1200 115 60
450
415 50 374 457 22 995.4 1200 1200 1010.4 1200 1200 115 60
440 50 396 484 22 939.1 1200 1200 954.3 1200 1200 115 60
380 50 342 418 24 1142.0 1200 1200 1158.4 1200 1200 115 60
400 50 360 440 24 1085.4 1200 1200 1101.7 1200 1200 115 60
500
415 50 374 457 24 1046.7 1200 1200 1063.1 1200 1200 115 60
440 50 396 484 24 987.6 1200 1200 1004.2 1200 1200 115 60
See Legend and Notes on page 115.

152
Table 27 — 50 Hz Single Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM Condenser Fans CONTROL CIRCUIT
UNIT Supplied NUMBER OF Voltage MCA
30XV COND FANS FUSE
V(3 Ph) Hz MCA MOCP 1 Ph, and
Min Max SIZE
60 Hz MOCP
380 50 342 418 8 319.4 400 350 115 60
400 50 360 440 8 304.2 400 350 115 60
140
415 50 374 457 8 294.0 400 350 115 60
440 50 396 484 8 278.8 350 350 115 60
380 50 342 418 10 350.5 450 400 115 60
400 50 360 440 10 334.7 450 400 115 60
160
415 50 374 457 10 322.0 400 400 115 60
440 50 396 484 10 303.9 400 350 115 60
380 50 342 418 10 397.5 500 450 115 60
400 50 360 440 10 379.6 500 450 115 60
180
415 50 374 457 10 364.7 450 400 115 60
440 50 396 484 10 344.6 450 400 115 60
380 50 342 418 12 443.7 600 600 115 60
400 50 360 440 12 423.1 500 500 115 60
200
415 50 374 457 12 407.8 500 450 115 60
440 50 396 484 12 384.9 500 450 115 60
380 50 342 418 12 495.2 700 600 115 60
400 50 360 440 12 472.0 600 600 115 60
225
415 50 374 457 12 455.3 600 600 115 60
440 50 396 484 12 429.8 600 500 115 60
380 50 342 418 14 560.3 700 700 115 60
400 50 360 440 14 534.8 700 600 115 60
250
415 50 374 457 14 514.8 700 600 115 60
440 50 396 484 14 487.0 600 600 115 60
380 50 342 418 14 598.8 800 700 115 60
400 50 360 440 14 571.1 700 700 115 60
275
415 50 374 457 14 551.2 700 700 115 60
440 50 396 484 14 519.1 700 600 115 60
380 50 342 418 16 625.5 800 700 115 60
400 50 360 440 16 595.2 800 700 115 60
300
415 50 374 457 16 574.8 700 700 115 60
440 50 396 484 16 542.1 700 600 115 60
380 50 342 418 18 682.3 800 800 115 60
400 50 360 440 18 649.2 800 800 115 60
325
415 50 374 457 18 626.3 800 700 115 60
440 50 396 484 18 590.8 800 700 115 60
See Legend and Notes on page 115.

153
Table 28 — 50 Hz Single Point Power High Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS CONTROL CIRCUIT
NUMBER
UNIT Supplied Voltage MCA
OF COND FUSE FUSE
30XV V(3 Ph) Hz MCA MOCP MCA MOCP 1 Ph, and
Min Max FANS SIZE SIZE
60 Hz MOCP
380 50 342 418 10 320.4 400 350 327.3 400 400 115 60
400 50 360 440 10 306.2 400 350 313.0 400 350 115 60
140
415 50 374 457 10 295.2 350 350 300.8 400 350 115 60
440 50 396 484 10 278.6 350 350 283.2 350 350 115 60
380 50 342 418 12 370.5 500 450 378.7 500 450 115 60
400 50 360 440 12 353.5 450 400 361.6 450 400 115 60
160
415 50 374 457 12 342.0 450 400 349.0 450 400 115 60
440 50 396 484 12 322.6 400 400 328.5 400 400 115 60
380 50 342 418 12 485.3 600 600 493.5 600 600 115 60
400 50 360 440 12 461.5 600 600 469.6 600 600 115 60
180
415 50 374 457 12 445.5 600 500 453.7 600 500 115 60
440 50 396 484 12 421.6 500 500 429.9 500 500 115 60
380 50 342 418 14 458.9 600 500 468.5 600 600 115 60
400 50 360 440 14 436.8 500 500 446.3 600 500 115 60
200
415 50 374 457 14 422.7 500 500 432.2 500 500 115 60
440 50 396 484 14 398.1 500 450 407.8 500 450 115 60
380 50 342 418 14 511.7 700 600 521.2 700 600 115 60
400 50 360 440 14 486.8 600 600 496.3 700 600 115 60
225
415 50 374 457 14 471.2 600 600 480.7 600 600 115 60
440 50 396 484 14 443.9 600 500 453.5 600 600 115 60
380 50 342 418 16 581.0 700 700 591.9 800 700 115 60
400 50 360 440 16 553.8 700 700 564.6 700 700 115 60
250
415 50 374 457 16 534.8 700 600 545.7 700 600 115 60
440 50 396 484 16 505.1 600 600 516.1 700 600 115 60
380 50 342 418 16 617.0 800 700 627.9 800 700 115 60
400 50 360 440 16 587.5 800 700 598.4 800 700 115 60
275
415 50 374 457 16 566.3 700 700 577.2 700 700 115 60
440 50 396 484 16 534.3 700 600 545.4 700 600 115 60
380 50 342 418 18 649.1 800 800 661.4 800 800 115 60
400 50 360 440 18 619.0 800 700 631.2 800 700 115 60
300
415 50 374 457 18 597.3 800 700 609.6 800 700 115 60
440 50 396 484 18 562.6 700 700 575.0 700 700 115 60
380 50 342 418 20 712.7 800 800 726.3 800 800 115 60
400 50 360 440 20 677.5 800 800 691.1 800 800 115 60
325
415 50 374 457 20 655.4 800 800 669.1 800 800 115 60
440 50 396 484 20 617.8 800 700 631.6 800 700 115 60
380 50 342 418 20 810.2 1000 1000 823.8 1000 1000 115 60
400 50 360 440 20 771.0 1000 1000 784.6 1000 1000 115 60
350
415 50 374 457 20 743.9 1000 1000 757.6 1000 1000 115 60
440 50 396 484 20 702.0 1000 800 715.8 1000 800 115 60
380 50 342 418 22 920.9 1200 1200 935.9 1200 1200 115 60
400 50 360 440 22 876.1 1200 1000 891.1 1200 1000 115 60
400
415 50 374 457 22 844.6 1000 1000 859.7 1000 1000 115 60
440 50 396 484 22 797.4 1000 1000 812.6 1000 1000 115 60
380 50 342 418 24 998.0 1200 1200 1014.4 1200 1200 115 60
400 50 360 440 24 950.4 1200 1200 966.7 1200 1200 115 60
450
415 50 374 457 24 916.2 1200 1200 932.6 1200 1200 115 60
440 50 396 484 24 863.8 1000 1000 880.4 1200 1000 115 60
See Legend and Notes on page 115.

154
Table 29 — 50 Hz Single Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM Condenser Fans CONTROL CIRCUIT
UNIT Supplied NUMBER OF Voltage MCA
30XV COND FANS FUSE
V(3 Ph) Hz MCA MOCP 1 Ph, and
Min Max SIZE
60 Hz MOCP
380 50 342 418 10 307.7 400 350 115 60
400 50 360 440 10 294.1 350 350 115 60
140
415 50 374 457 10 282.3 350 350 115 60
440 50 396 484 10 265.2 350 300 115 60
380 50 342 418 12 355.9 450 400 115 60
400 50 360 440 12 339.5 450 400 115 60
160
415 50 374 457 12 327.3 400 400 115 60
440 50 396 484 12 307.5 400 350 115 60
380 50 342 418 12 464.9 600 600 115 60
400 50 360 440 12 442.1 600 500 115 60
180
415 50 374 457 12 426.9 500 500 115 60
440 50 396 484 12 403.9 500 450 115 60
380 50 342 418 14 440.6 500 500 115 60
400 50 360 440 14 419.3 500 500 115 60
200
415 50 374 457 14 405.8 500 450 115 60
440 50 396 484 14 382.3 500 450 115 60
380 50 342 418 14 490.7 700 600 115 60
400 50 360 440 14 466.8 600 600 115 60
225
415 50 374 457 14 451.9 600 600 115 60
440 50 396 484 14 425.7 600 500 115 60
380 50 342 418 16 557.1 700 700 115 60
400 50 360 440 16 531.0 700 600 115 60
250
415 50 374 457 16 512.8 600 600 115 60
440 50 396 484 16 484.4 600 600 115 60
380 50 342 418 16 591.3 800 700 115 60
400 50 360 440 16 563.1 700 700 115 60
275
415 50 374 457 16 542.7 700 600 115 60
440 50 396 484 16 512.2 600 600 115 60
380 50 342 418 18 622.4 800 700 115 60
400 50 360 440 18 593.6 800 700 115 60
300
415 50 374 457 18 572.8 700 700 115 60
440 50 396 484 18 539.5 700 600 115 60
380 50 342 418 20 683.4 800 800 115 60
400 50 360 440 20 649.7 800 800 115 60
325
415 50 374 457 20 628.5 800 700 115 60
440 50 396 484 20 592.5 800 700 115 60
See Legend and Notes on page 115.

155
Table 30 — 50 Hz Dual Point Power Standard Tier Variable Speed Fan Motors
with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS CONTROL CIRCUIT
NUMBER OF
UNIT FUSE FUSE Voltage MCA
Supplied COND FANS MCA MOCP MCA MOCP
30XV V(3 Ph) Hz SIZE SIZE 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 50 342 418 4 4 214.5 207.4 350 350 300 250 217.2 210.2 350 350 300 250 115 60
400 50 360 440 4 4 204.5 197.5 300 300 250 250 207.2 200.2 300 300 250 250 115 60
160
415 50 374 457 4 4 197.5 190.4 300 300 250 225 200.2 193.2 300 300 250 250 115 60
440 50 396 484 4 4 186.2 179.2 300 300 225 225 189.0 182.0 300 300 225 225 115 60
380 50 342 418 4 4 247.0 239.9 400 400 300 300 249.7 242.7 400 400 300 300 115 60
400 50 360 440 4 4 235.8 228.7 400 350 300 300 238.5 231.5 400 350 300 300 115 60
180
415 50 374 457 4 4 227.5 220.4 350 350 300 300 230.2 223.2 350 350 300 300 115 60
440 50 396 484 4 4 215.0 207.9 350 350 300 250 217.7 210.7 350 350 300 250 115 60
380 50 342 418 5 5 256.6 249.6 400 400 350 300 260.0 253.0 400 400 350 300 115 60
400 50 360 440 5 5 245.1 238.1 400 400 300 300 248.5 241.5 400 400 300 300 115 60
200
415 50 374 457 5 5 236.6 229.6 350 350 300 300 240.0 233.0 400 350 300 300 115 60
440 50 396 484 5 5 222.6 215.5 350 350 300 300 226.0 219.0 350 350 300 300 115 60
380 50 342 418 6 4 349.8 219.9 500 350 450 300 353.9 222.7 500 350 450 300 115 60
400 50 360 440 6 4 333.1 210.0 500 350 400 250 337.1 212.7 500 350 400 300 115 60
225
415 50 374 457 6 4 321.8 201.7 500 300 400 250 325.9 204.4 500 300 400 250 115 60
440 50 396 484 6 4 303.7 190.4 500 300 400 225 307.9 193.2 500 300 400 250 115 60
380 50 342 418 6 6 339.8 330.5 500 500 400 400 343.9 334.6 500 500 450 400 115 60
400 50 360 440 6 6 324.3 315.0 500 500 400 400 328.4 319.1 500 500 400 400 115 60
250
415 50 374 457 6 6 313.1 303.8 500 500 400 400 317.2 307.9 500 500 400 400 115 60
440 50 396 484 6 6 295.0 285.7 450 450 350 350 299.1 289.8 500 450 400 350 115 60
380 50 342 418 6 6 351.1 341.7 500 500 450 450 355.2 345.9 600 500 450 450 115 60
400 50 360 440 6 6 334.3 325.0 500 500 400 400 338.4 329.1 500 500 400 400 115 60
275
415 50 374 457 6 6 323.1 313.8 500 500 400 400 327.2 317.9 500 500 400 400 115 60
440 50 396 484 6 6 305.0 295.7 500 500 400 350 309.1 299.8 500 500 400 400 115 60
380 50 342 418 7 7 374.5 365.2 600 600 450 450 379.3 370.0 600 600 450 450 115 60
400 50 360 440 7 7 357.4 348.1 600 500 450 450 362.2 352.9 600 500 450 450 115 60
300
415 50 374 457 7 7 344.8 335.4 500 500 450 400 349.5 340.2 500 500 450 400 115 60
440 50 396 484 7 7 325.1 315.8 500 500 400 400 329.9 320.6 500 500 400 400 115 60
380 50 342 418 8 8 411.7 402.3 600 600 500 500 417.1 407.8 700 600 500 500 115 60
400 50 360 440 8 8 391.8 382.5 600 600 500 450 397.2 387.9 600 600 500 500 115 60
325
415 50 374 457 8 8 378.9 369.6 600 600 450 450 384.4 375.1 600 600 450 450 115 60
440 50 396 484 8 8 357.7 348.4 600 500 450 450 363.2 353.9 600 500 450 450 115 60
380 50 342 418 9 7 543.8 390.2 800 600 700 500 550.0 395.0 800 600 700 500 115 60
400 50 360 440 9 7 517.4 371.8 800 600 700 450 523.5 376.6 800 600 700 450 115 60
350
415 50 374 457 9 7 499.3 357.9 800 600 600 450 505.5 362.7 800 600 600 450 115 60
440 50 396 484 9 7 471.6 337.0 700 500 600 400 477.8 341.9 800 500 600 450 115 60
380 50 342 418 9 9 507.0 497.0 800 800 600 600 513.1 503.2 800 800 700 600 115 60
400 50 360 440 9 9 483.1 473.1 800 800 600 600 489.2 479.2 800 800 600 600 115 60
400
415 50 374 457 9 9 466.2 456.3 700 700 600 600 472.4 462.4 700 700 600 600 115 60
440 50 396 484 9 9 439.7 429.7 700 700 600 600 445.9 436.0 700 700 600 600 115 60
380 50 342 418 10 10 602.9 592.9 1000 1000 800 700 609.7 599.8 1000 1000 800 800 115 60
400 50 360 440 10 10 573.7 563.7 800 800 700 700 580.5 570.5 800 800 700 700 115 60
450
415 50 374 457 10 10 552.9 542.9 800 800 700 700 559.7 549.8 800 800 700 700 115 60
440 50 396 484 10 10 522.3 512.3 800 800 700 700 529.2 519.3 800 800 700 700 115 60
380 50 342 418 11 11 648.8 638.8 1000 1000 800 800 656.3 646.4 1000 1000 800 800 115 60
400 50 360 440 11 11 618.0 608.1 1000 1000 800 800 625.5 615.6 1000 1000 800 800 115 60
500
415 50 374 457 11 11 595.8 585.8 1000 1000 800 700 603.3 593.4 1000 1000 800 700 115 60
440 50 396 484 11 11 562.4 552.5 800 800 700 700 570.0 560.1 800 800 700 700 115 60
See Legend and Notes on page 115.

156
Table 31 — 50 Hz Dual Point Power Standard Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM Condenser Fans CONTROL CIRCUIT
NUMBER OF COND
UNIT FANS FUSE Voltage MCA
Supplied MCA MOCP
30XV V(3 Ph) Hz SIZE 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 50 342 418 4 4 205.3 198.2 300 300 250 250 115 60
400 50 360 440 4 4 195.8 188.7 300 300 250 225 115 60
160
415 50 374 457 4 4 189.0 182.0 300 300 225 225 115 60
440 50 396 484 4 4 178.3 171.2 250 250 225 225 115 60
380 50 342 418 4 4 236.1 229.1 400 350 300 300 115 60
400 50 360 440 4 4 225.5 218.4 350 350 300 300 115 60
180
415 50 374 457 4 4 217.5 210.5 350 350 300 250 115 60
440 50 396 484 4 4 205.6 198.6 300 300 250 250 115 60
380 50 342 418 5 5 245.6 238.6 400 400 300 300 115 60
400 50 360 440 5 5 234.6 227.6 350 350 300 300 115 60
200
415 50 374 457 5 5 226.5 219.5 350 350 300 300 115 60
440 50 396 484 5 5 213.1 206.0 350 350 250 250 115 60
380 50 342 418 6 4 334.6 210.1 500 350 400 250 115 60
400 50 360 440 6 4 318.6 200.6 500 300 400 250 115 60
225
415 50 374 457 6 4 307.8 192.7 500 300 400 250 115 60
440 50 396 484 6 4 290.6 181.9 450 300 350 225 115 60
380 50 342 418 6 6 325.1 315.7 500 500 400 400 115 60
400 50 360 440 6 6 310.2 300.9 500 500 400 400 115 60
250
415 50 374 457 6 6 299.5 290.2 500 450 400 350 115 60
440 50 396 484 6 6 282.2 272.9 450 450 350 350 115 60
380 50 342 418 6 6 335.8 326.4 500 500 400 400 115 60
400 50 360 440 6 6 319.7 310.4 500 500 400 400 115 60
275
415 50 374 457 6 6 309.0 299.7 500 500 400 400 115 60
440 50 396 484 6 6 291.7 282.4 450 450 350 350 115 60
380 50 342 418 7 7 358.3 349.0 600 500 450 450 115 60
400 50 360 440 7 7 342.0 332.7 500 500 450 400 115 60
300
415 50 374 457 7 7 329.9 320.5 500 500 400 400 115 60
440 50 396 484 7 7 311.1 301.8 500 500 400 400 115 60
380 50 342 418 8 8 393.9 384.6 600 600 500 500 115 60
400 50 360 440 8 8 374.9 365.6 600 600 450 450 115 60
325
415 50 374 457 8 8 362.6 353.3 600 600 450 450 115 60
440 50 396 484 8 8 342.3 333.0 500 500 450 400 115 60
See Legend and Notes on page 115.

157
Table 32 — 50 Hz Dual Point Power Mid Tier Variable Speed Fan Motors with Control Power Transformer
UNIT VOLTAGE STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS CONTROL CIRCUIT
NUMBER O
UNIT FUSE FUSE Voltage MCA
Supplied COND FANS MCA MOCP MCA MOCP
30XV V(3 Ph) Hz SIZE SIZE 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 50 342 418 4 4 185.7 178.7 300 300 225 225 188.4 181.4 300 300 225 225 115 60
400 50 360 440 4 4 177.0 170.0 250 250 225 200 179.7 172.7 250 250 225 225 115 60
140
415 50 374 457 4 4 171.2 164.2 250 250 200 200 173.9 166.9 250 250 225 200 115 60
440 50 396 484 4 4 162.5 155.4 250 250 200 200 165.2 158.2 250 250 200 200 115 60
380 50 342 418 5 5 202.9 195.8 300 300 250 250 206.3 199.3 300 300 250 250 115 60
400 50 360 440 5 5 193.9 186.9 300 300 250 225 197.3 190.3 300 300 250 225 115 60
160
415 50 374 457 5 5 186.6 179.6 300 300 225 225 190.0 183.0 300 300 225 225 115 60
440 50 396 484 5 5 176.3 169.3 250 250 225 200 179.8 172.8 250 250 225 225 115 60
380 50 342 418 5 5 230.4 223.3 350 350 300 300 233.8 226.8 350 350 300 300 115 60
400 50 360 440 5 5 220.1 213.1 350 350 300 300 223.5 216.5 350 350 300 300 115 60
180
415 50 374 457 5 5 211.6 204.6 350 300 250 250 215.0 208.0 350 350 300 250 115 60
440 50 396 484 5 5 200.1 193.0 300 300 250 250 203.5 196.5 300 300 250 250 115 60
380 50 342 418 6 6 257.3 248.0 400 400 300 300 261.4 252.1 400 400 300 300 115 60
400 50 360 440 6 6 245.6 236.2 400 350 300 300 249.6 240.3 400 400 300 300 115 60
200
415 50 374 457 6 6 236.8 227.5 350 350 300 300 240.9 231.6 350 350 300 300 115 60
440 50 396 484 6 6 223.7 214.4 350 350 300 300 227.9 218.6 350 350 300 300 115 60
380 50 342 418 7 5 339.5 214.6 500 350 400 300 344.3 218.0 500 350 450 300 115 60
400 50 360 440 7 5 323.7 204.4 500 300 400 250 328.4 207.8 500 300 400 250 115 60
225
415 50 374 457 7 5 312.3 197.1 500 300 400 250 317.0 200.5 500 300 400 250 115 60
440 50 396 484 7 5 295.1 185.5 450 300 350 225 299.9 189.0 450 300 350 225 115 60
380 50 342 418 7 7 324.5 315.2 500 500 400 400 329.3 320.0 500 500 400 400 115 60
400 50 360 440 7 7 309.9 300.6 500 500 400 400 314.7 305.4 500 500 400 400 115 60
250
415 50 374 457 7 7 298.5 289.2 450 450 350 350 303.3 294.0 500 450 400 350 115 60
440 50 396 484 7 7 282.6 273.3 450 450 350 350 287.4 278.1 450 450 350 350 115 60
380 50 342 418 7 7 347.0 337.7 500 500 450 400 351.8 342.5 500 500 450 450 115 60
400 50 360 440 7 7 331.2 321.8 500 500 400 400 335.9 326.6 500 500 400 400 115 60
275
415 50 374 457 7 7 319.8 310.4 500 500 400 400 324.5 315.2 500 500 400 400 115 60
440 50 396 484 7 7 301.4 292.0 500 450 400 350 306.2 296.9 500 500 400 350 115 60
380 50 342 418 8 8 361.7 352.3 600 500 450 450 367.1 357.8 600 600 450 450 115 60
400 50 360 440 8 8 344.3 335.0 500 500 450 400 349.7 340.4 500 500 450 400 115 60
300
415 50 374 457 8 8 332.7 323.3 500 500 400 400 338.1 328.8 500 500 400 400 115 60
440 50 396 484 8 8 314.0 304.6 500 500 400 400 319.5 310.2 500 500 400 400 115 60
380 50 342 418 9 9 393.8 384.5 600 600 500 500 400.0 390.7 600 600 500 500 115 60
400 50 360 440 9 9 374.9 365.6 600 600 450 450 381.0 371.7 600 600 450 450 115 60
325
415 50 374 457 9 9 361.8 352.5 600 500 450 450 368.0 358.7 600 600 450 450 115 60
440 50 396 484 9 9 341.6 332.2 500 500 400 400 347.8 338.5 500 500 450 400 115 60
380 50 342 418 10 8 503.5 362.3 800 600 600 450 510.3 367.8 800 600 600 450 115 60
400 50 360 440 10 8 479.3 345.0 800 500 600 450 486.1 350.4 800 500 600 450 115 60
350
415 50 374 457 10 8 462.3 332.1 700 500 600 400 469.1 337.6 700 500 600 400 115 60
440 50 396 484 10 8 436.7 313.4 700 500 600 400 443.6 318.9 700 500 600 400 115 60
380 50 342 418 10 10 502.9 492.9 800 800 600 600 509.7 499.8 800 800 600 600 115 60
400 50 360 440 10 10 478.7 468.7 800 700 600 600 485.5 475.5 800 800 600 600 115 60
400
415 50 374 457 10 10 461.6 451.7 700 700 600 600 468.5 458.5 700 700 600 600 115 60
440 50 396 484 10 10 436.1 426.1 700 700 600 600 443.0 433.0 700 700 600 600 115 60
380 50 342 418 11 11 600.0 590.1 1000 1000 800 700 607.6 597.6 1000 1000 800 800 115 60
400 50 360 440 11 11 570.5 560.6 800 800 700 700 578.0 568.1 800 800 700 700 115 60
450
415 50 374 457 11 11 550.8 540.8 800 800 700 700 558.3 548.4 800 800 700 700 115 60
440 50 396 484 11 11 519.9 510.0 800 800 700 700 527.5 517.6 800 800 700 700 115 60
380 50 342 418 12 12 631.0 621.0 1000 1000 800 800 639.2 629.2 1000 1000 800 800 115 60
400 50 360 440 12 12 599.9 589.9 1000 1000 800 700 608.1 598.1 1000 1000 800 800 115 60
500
415 50 374 457 12 12 578.7 568.8 800 800 700 700 586.9 577.0 800 800 700 700 115 60
440 50 396 484 12 12 546.3 536.3 800 800 700 700 554.6 544.6 800 800 700 700 115 60
See Legend and Notes on page 115.

158
Table 33 — 50 Hz Dual Point Power Mid Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM Condenser Fans CONTROL CIRCUIT
NUMBER OF
UNIT COND FANS FUSE Voltage MCA
Supplied MCA MOCP
30XV V(3 Ph) Hz SIZE 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 50 342 418 4 4 178.0 170.9 250 250 225 225 115 60
400 50 360 440 4 4 169.6 162.6 250 250 200 200 115 60
140
415 50 374 457 4 4 164.1 157.0 250 250 200 200 115 60
440 50 396 484 4 4 155.7 148.7 250 250 200 175 115 60
380 50 342 418 5 5 194.6 187.5 300 300 250 225 115 60
400 50 360 440 5 5 186.0 178.9 300 250 225 225 115 60
160
415 50 374 457 5 5 179.0 172.0 250 250 225 225 115 60
440 50 396 484 5 5 169.1 162.1 250 250 200 200 115 60
380 50 342 418 5 5 220.7 213.6 350 350 300 300 115 60
400 50 360 440 5 5 210.9 203.9 350 300 250 250 115 60
180
415 50 374 457 5 5 202.7 195.7 300 300 250 250 115 60
440 50 396 484 5 5 191.7 184.7 300 300 225 225 115 60
380 50 342 418 6 6 246.7 237.4 400 350 300 300 115 60
400 50 360 440 6 6 235.4 226.1 350 350 300 300 115 60
200
415 50 374 457 6 6 227.1 217.8 350 350 300 300 115 60
440 50 396 484 6 6 214.6 205.2 350 300 250 250 115 60
380 50 342 418 7 5 325.1 205.3 500 300 400 250 115 60
400 50 360 440 7 5 309.9 195.5 500 300 400 250 115 60
225
415 50 374 457 7 5 299.0 188.6 500 300 350 225 115 60
440 50 396 484 7 5 282.6 177.5 450 250 350 225 115 60
380 50 342 418 7 7 310.8 301.5 500 500 400 400 115 60
400 50 360 440 7 7 296.9 287.5 450 450 350 350 115 60
250
415 50 374 457 7 7 285.9 276.6 450 450 350 350 115 60
440 50 396 484 7 7 270.7 261.4 450 400 350 350 115 60
380 50 342 418 7 7 332.2 322.8 500 500 400 400 115 60
400 50 360 440 7 7 317.1 307.7 500 500 400 400 115 60
275
415 50 374 457 7 7 306.1 296.8 500 500 400 350 115 60
440 50 396 484 7 7 288.5 279.2 450 450 350 350 115 60
380 50 342 418 8 8 346.4 337.1 500 500 450 400 115 60
400 50 360 440 8 8 329.8 320.5 500 500 400 400 115 60
300
415 50 374 457 8 8 318.7 309.3 500 500 400 400 115 60
440 50 396 484 8 8 300.8 291.4 500 450 400 350 115 60
380 50 342 418 9 9 377.3 367.9 600 600 450 450 115 60
400 50 360 440 9 9 359.2 349.8 500 500 450 450 115 60
325
415 50 374 457 9 9 346.7 337.3 500 500 450 400 115 60
440 50 396 484 9 9 327.3 317.9 500 500 400 400 115 60
See Legend and Notes on page 115.

159
Table 34 — 50 Hz Dual Point Power High Tier Variable Speed Fan Motors with Control Power Transformer
CONTROL
UNIT VOLTAGE STANDARD CONDENSER FANS HIGH STATIC CONDENSER FANS
NUMBER OF CIRCUIT
UNIT COND FANS FUSE FUSE Voltage MCA
30XV Supplied MCA MOCP MCA MOCP
V(3 Ph) Hz SIZE SIZE 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 50 342 418 5 5 177.9 170.8 250 250 225 200 181.3 174.3 250 250 225 225 115 60
400 50 360 440 5 5 170.1 163.1 250 250 200 200 173.5 166.5 250 250 225 200 115 60
140
415 50 374 457 5 5 164.1 157.1 250 250 200 200 167.5 160.5 250 250 200 200 115 60
440 50 396 484 5 5 155.1 148.0 250 225 200 175 158.5 151.5 250 225 200 200 115 60
380 50 342 418 6 6 205.0 198.0 300 300 250 250 209.1 202.1 300 300 250 250 115 60
400 50 360 440 6 6 195.8 188.7 300 300 250 225 199.8 192.8 300 300 250 225 115 60
160
415 50 374 457 6 6 189.5 182.5 300 300 225 225 193.6 186.6 300 300 225 225 115 60
440 50 396 484 6 6 178.9 171.9 250 250 225 225 183.1 176.1 250 250 225 225 115 60
380 50 342 418 6 6 268.8 261.7 400 400 350 350 272.9 265.9 450 400 350 350 115 60
400 50 360 440 6 6 255.8 248.7 400 400 300 300 259.8 252.8 400 400 350 300 115 60
180
415 50 374 457 6 6 247.0 240.0 400 400 300 300 251.1 244.1 400 400 300 300 115 60
440 50 396 484 6 6 233.9 226.9 350 350 300 300 238.1 231.1 350 350 300 300 115 60
380 50 342 418 7 7 254.5 245.2 400 400 300 300 259.3 250.0 400 400 350 300 115 60
400 50 360 440 7 7 242.4 233.1 350 350 300 300 247.2 237.9 400 350 300 300 115 60
200
415 50 374 457 7 7 234.8 225.4 350 350 300 300 239.5 230.2 350 350 300 300 115 60
440 50 396 484 7 7 221.4 212.0 350 350 300 250 226.2 216.9 350 350 300 300 115 60
380 50 342 418 8 6 334.2 213.0 500 350 400 250 339.6 217.1 500 350 400 300 115 60
400 50 360 440 8 6 318.1 202.5 500 300 400 250 323.5 206.6 500 300 400 250 115 60
225
415 50 374 457 8 6 307.7 196.3 500 300 400 250 313.1 200.4 500 300 400 250 115 60
440 50 396 484 8 6 290.2 184.4 450 300 350 225 295.7 188.6 450 300 350 225 115 60
380 50 342 418 8 8 321.7 312.3 500 500 400 400 327.1 317.8 500 500 400 400 115 60
400 50 360 440 8 8 306.8 297.5 500 450 400 350 312.2 302.9 500 500 400 400 115 60
250
415 50 374 457 8 8 296.4 287.1 450 450 350 350 301.9 292.6 450 450 400 350 115 60
440 50 396 484 8 8 280.2 270.9 450 450 350 350 285.7 276.4 450 450 350 350 115 60
380 50 342 418 8 8 341.7 332.3 500 500 400 400 347.1 337.8 500 500 450 400 115 60
400 50 360 440 8 8 325.6 316.2 500 500 400 400 331.0 321.7 500 500 400 400 115 60
275
415 50 374 457 8 8 313.9 304.6 500 500 400 400 319.4 310.1 500 500 400 400 115 60
440 50 396 484 8 8 296.5 287.1 450 450 350 350 302.0 292.7 450 450 400 350 115 60
380 50 342 418 9 9 358.8 349.5 500 500 450 450 365.0 355.7 600 500 450 450 115 60
400 50 360 440 9 9 342.4 333.1 500 500 400 400 348.5 339.2 500 500 450 400 115 60
300
415 50 374 457 9 9 330.6 321.3 500 500 400 400 336.7 327.4 500 500 400 400 115 60
440 50 396 484 9 9 311.6 302.2 500 500 400 400 317.8 308.5 500 500 400 400 115 60
380 50 342 418 10 10 393.5 384.2 600 600 500 450 400.3 391.0 600 600 500 500 115 60
400 50 360 440 10 10 374.3 365.0 600 600 450 450 381.1 371.8 600 600 450 450 115 60
325
415 50 374 457 10 10 362.3 352.9 600 500 450 450 369.1 359.8 600 500 450 450 115 60
440 50 396 484 10 10 341.7 332.3 500 500 400 400 348.6 339.3 500 500 450 400 115 60
380 50 342 418 11 9 516.9 353.2 800 500 700 450 524.4 359.4 800 500 700 450 115 60
400 50 360 440 11 9 492.4 335.6 800 500 600 400 499.9 341.7 800 500 600 400 115 60
350
415 50 374 457 11 9 475.2 323.8 800 500 600 400 482.7 329.9 800 500 600 400 115 60
440 50 396 484 11 9 448.0 306.0 700 500 600 400 455.6 312.2 700 500 600 400 115 60
380 50 342 418 11 11 508.8 498.8 800 800 600 600 516.3 506.4 800 800 700 600 115 60
400 50 360 440 11 11 484.3 474.3 800 800 600 600 491.8 481.8 800 800 600 600 115 60
400
415 50 374 457 11 11 467.1 457.1 700 700 600 600 474.6 464.6 700 700 600 600 115 60
440 50 396 484 11 11 441.2 431.2 700 700 600 600 448.8 438.8 700 700 600 600 115 60
380 50 342 418 12 12 551.0 541.0 800 800 700 700 559.2 549.2 800 800 700 700 115 60
400 50 360 440 12 12 524.9 514.9 800 800 700 700 533.1 523.1 800 800 700 700 115 60
450
415 50 374 457 12 12 506.2 496.3 800 800 600 600 514.4 504.5 800 800 700 600 115 60
440 50 396 484 12 12 477.5 467.6 800 700 600 600 485.8 475.9 800 800 600 600 115 60
See Legend and Notes on page 115.

160
Table 35 — 50 Hz Dual Point Power High Tier Fan Motors with Control Power Transformer, with Electrically
Commutated Variable Speed Fan Motor and Permanent Magnet Compressor Options
UNIT VOLTAGE ECM Condenser Fans CONTROL CIRCUIT
NUMBER OF
UNIT COND FANS FUSE Voltage MCA
Supplied MCA MOCP
30XV V(3 Ph) Hz SIZE 1 Ph, and
Min Max CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 60 Hz MOCP
380 50 342 418 5 5 170.8 163.8 250 250 200 200 115 60
400 50 360 440 5 5 163.4 156.4 250 250 200 200 115 60
140
415 50 374 457 5 5 157.6 150.6 250 225 200 200 115 60
440 50 396 484 5 5 149.0 141.9 225 225 175 175 115 60
380 50 342 418 6 6 196.9 189.9 300 300 250 225 115 60
400 50 360 440 6 6 188.0 181.0 300 250 225 225 115 60
160
415 50 374 457 6 6 182.0 175.0 250 250 225 225 115 60
440 50 396 484 6 6 171.9 164.8 250 250 200 200 115 60
380 50 342 418 6 6 257.5 250.4 400 400 350 300 115 60
400 50 360 440 6 6 245.0 238.0 400 400 300 300 115 60
180
415 50 374 457 6 6 236.7 229.6 350 350 300 300 115 60
440 50 396 484 6 6 224.1 217.1 350 350 300 300 115 60
380 50 342 418 7 7 244.3 235.0 350 350 300 300 115 60
400 50 360 440 7 7 232.7 223.4 350 350 300 300 115 60
200
415 50 374 457 7 7 225.4 216.0 350 350 300 300 115 60
440 50 396 484 7 7 212.5 203.2 300 300 250 250 115 60
380 50 342 418 8 6 320.3 204.1 500 300 400 250 115 60
400 50 360 440 8 6 304.9 194.0 500 300 400 250 115 60
225
415 50 374 457 8 6 294.9 188.1 450 300 350 225 115 60
440 50 396 484 8 6 278.2 176.7 450 250 350 225 115 60
380 50 342 418 8 8 308.4 299.1 500 500 400 350 115 60
400 50 360 440 8 8 294.2 284.8 450 450 350 350 115 60
250
415 50 374 457 8 8 284.2 274.9 450 450 350 350 115 60
440 50 396 484 8 8 268.7 259.4 400 400 350 350 115 60
380 50 342 418 8 8 327.4 318.1 500 500 400 400 115 60
400 50 360 440 8 8 312.0 302.6 500 500 400 400 115 60
275
415 50 374 457 8 8 300.9 291.5 450 450 400 350 115 60
440 50 396 484 8 8 284.2 274.8 450 450 350 350 115 60
380 50 342 418 9 9 344.0 334.7 500 500 450 400 115 60
400 50 360 440 9 9 328.3 319.0 500 500 400 400 115 60
300
415 50 374 457 9 9 317.0 307.6 500 500 400 400 115 60
440 50 396 484 9 9 298.8 289.4 450 450 350 350 115 60
380 50 342 418 10 10 377.2 367.9 600 600 450 450 115 60
400 50 360 440 10 10 358.9 349.5 500 500 450 450 115 60
325
415 50 374 457 10 10 347.3 338.0 500 500 450 400 115 60
440 50 396 484 10 10 327.6 318.3 500 500 400 400 115 60
See Legend and Notes on page 115.

161
Table 36 — 60 Hz Compressor and Fan Data
High Static ECM
UNIT Standard
NUMBER OF COND FANS Condenser Fans Condenser Fans Compressor RLA PM Compressor RLA
VOLTAGE Condenser Fans FLA
UNIT FLA FLA
30XV Single Point Dual Point Tier Tier Tier A B A B
V
Hz STD STD
(3 Ph) STD MID HIGH STD MID HIGH STD MID HIGH MID HIGH MID HIGH STD HIGH MID STD+ STD HIGH MID STD+ STD STD+ MID HIGH STD+ MID HIGH
+ +
208/230 60 8 8 10 4/4 4/4 5/5 6.6 10.6 10.6 — 11.9 11.9 11.9 — — — 201 221 212 228 201 221 212 228 — — — — — —
380 60 8 8 10 4/4 4/4 5/5 3.6 5.8 5.8 — 6.5 6.5 6.5 5.8 5.8 — 110 121 116 125 110 121 116 125 105 115 110 105 115 110
140 400 60 8 8 10 4/4 4/4 5/5 3.5 5.5 5.5 — 6.2 6.2 6.2 5.5 5.5 — 105 115 111 119 105 115 111 119 100 109 105 100 109 105
460 60 8 8 10 4/4 4/4 5/5 3.0 4.8 4.8 — 5.4 5.4 5.4 4.8 4.8 — 91 100 96 103 91 100 96 103 86 95 91 86 95 91
575 60 8 8 10 4/4 4/4 5/5 2.4 3.8 3.8 — 4.3 4.3 4.3 — — — 73 80 77 83 73 80 77 83 — — — — — —
208/230 60 8 10 12 4/4 5/5 6/6 6.6 10.6 10.6 10.6 11.9 11.9 11.9 — — — 231 238 263 273 231 238 263 273 — — — — — —
380 60 8 10 12 4/4 5/5 6/6 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 127 130 144 149 127 130 144 149 121 124 137 121 124 137
160 400 60 8 10 12 4/4 5/5 6/6 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 120 124 137 142 120 124 137 142 114 118 130 114 118 130
460 60 8 10 12 4/4 5/5 6/6 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 104 107 119 123 104 107 119 123 99 102 113 99 102 113
575 60 8 10 12 4/4 5/5 6/6 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 84 86 96 99 84 86 96 99 — — — — — —
208/230 60 8 10 12 4/4 5/5 6/6 6.6 10.6 10.6 10.6 11.9 11.9 11.9 — — — 323 275 308 318 323 275 308 318 — — — — — —
380 60 8 10 12 4/4 5/5 6/6 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 177 151 169 174 177 151 169 174 168 143 161 168 143 161
180 400 60 8 10 12 4/4 5/5 6/6 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 140 143 160 166 140 143 160 166 133 136 152 133 136 152
460 60 8 10 12 4/4 5/5 6/6 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 121 124 139 144 121 124 139 144 115 118 132 115 118 132
575 60 8 10 12 4/4 5/5 6/6 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 97 100 112 115 97 100 112 115 — — — — — —
208/230 60 10 12 14 5/5 6/6 7/7 6.6 10.6 10.6 10.6 11.9 11.9 11.9 — — — 290 303 313 325 290 303 313 325 — — — — — —
380 60 10 12 14 5/5 6/6 7/7 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 159 166 172 178 159 166 172 178 151 158 163 151 158 163
200 400 60 10 12 14 5/5 6/6 7/7 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 151 158 163 169 151 158 163 169 143 150 155 143 150 155
162

460 60 10 12 14 5/5 6/6 7/7 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 131 137 141 147 131 137 141 147 124 130 134 124 130 134
575 60 10 12 14 5/5 6/6 7/7 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 105 110 114 118 105 110 114 118 — — — — — —
380 60 10 12 14 6/4 7/5 8/6 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 217 226 239 250 139 145 153 160 206 215 227 132 138 145
400 60 10 12 14 6/4 7/5 8/6 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 207 215 227 237 132 137 146 152 197 204 216 125 130 139
225
460 60 10 12 14 6/4 7/5 8/6 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 179 186 197 206 115 119 126 132 170 177 187 109 113 120
575 60 10 12 14 6/4 7/5 8/6 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 144 149 158 165 92 96 101 106 — — — — — —
380 60 12 14 16 6/6 7/7 8/8 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 207 214 231 235 207 214 231 235 197 203 219 197 203 219
400 60 12 14 16 6/6 7/7 8/8 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 197 204 219 223 197 204 219 223 187 194 208 187 194 208
250
460 60 12 14 16 6/6 7/7 8/8 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 171 177 190 193 171 177 190 193 162 168 181 162 168 181
575 60 12 14 16 6/6 7/7 8/8 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 137 142 153 155 137 142 153 155 — — — — — —
380 60 12 14 16 6/6 7/7 8/8 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 223 232 240 254 223 232 240 254 212 220 228 212 220 228
400 60 12 14 16 6/6 7/7 8/8 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 212 220 228 241 212 220 228 241 201 209 217 201 209 217
275
460 60 12 14 16 6/6 7/7 8/8 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 184 191 198 209 184 191 198 209 175 182 188 175 182 188
575 60 12 14 16 6/6 7/7 8/8 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 148 153 159 168 148 153 159 168 — — — — — —
380 60 14 16 18 7/7 8/8 9/9 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 232 239 253 258 232 239 253 258 220 227 240 220 227 240
400 60 14 16 18 7/7 8/8 9/9 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 220 227 241 245 220 227 241 245 209 216 229 209 216 229
300
460 60 14 16 18 7/7 8/8 9/9 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 191 197 209 213 191 197 209 213 181 187 198 181 187 198
575 60 14 16 18 7/7 8/8 9/9 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 153 158 168 171 153 158 168 171 — — — — — —
380 60 16 18 20 8/8 9/9 10/10 3.6 5.8 5.8 5.8 6.5 6.5 6.5 5.8 5.8 5.8 254 259 278 282 254 259 278 282 241 246 264 241 246 264
400 60 16 18 20 8/8 9/9 10/10 3.5 5.5 5.5 5.5 6.2 6.2 6.2 5.5 5.5 5.5 242 246 264 268 242 246 264 268 230 234 251 230 234 251
325
460 60 16 18 20 8/8 9/9 10/10 3.0 4.8 4.8 4.8 5.4 5.4 5.4 4.8 4.8 4.8 210 214 229 233 210 214 229 233 199 203 218 199 203 218
575 60 16 18 20 8/8 9/9 10/10 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 168 172 184 187 168 172 184 187 — — — — — —
380 60 16 18 20 9/7 10/8 11/9 3.6 5.8 5.8 5.8 6.5 6.5 6.5 — — — 347 341 377 387 235 247 273 280 — — — — — —
400 60 16 18 20 9/7 10/8 11/9 3.5 5.5 5.5 5.5 6.2 6.2 6.2 — — — 329 324 358 367 223 235 260 266 — — — — — —
350
460 60 16 18 20 9/7 10/8 11/9 3.0 4.8 4.8 4.8 5.4 5.4 5.4 — — — 286 281 311 319 194 204 225 231 — — — — — —
575 60 16 18 20 9/7 10/8 11/9 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 229 225 249 256 156 163 181 185 — — — — — —
Table 36 — 60 Hz Compressor and Fan Data (cont)
High Static ECM
UNIT Standard
NUMBER OF COND FANS Condenser Fans Condenser Fans Compressor RLA PM Compressor RLA
VOLTAGE Condenser Fans FLA
UNIT FLA FLA
30XV Single Point Dual Point Tier Tier Tier A B A B
V
Hz STD STD
(3 Ph) STD MID HIGH STD MID HIGH STD MID HIGH MID HIGH MID HIGH STD HIGH MID STD+ STD HIGH MID STD+ STD STD+ MID HIGH STD+ MID HIGH
+ +
380 60 18 20 22 9/9 10/10 11/11 3.6 5.8 5.8 5.8 6.5 6.5 6.5 — — — 340 340 348 364 340 340 348 364 — — — — — —
400 60 18 20 22 9/9 10/10 11/11 3.5 5.5 5.5 5.5 6.2 6.2 6.2 — — — 323 323 331 346 323 323 331 346 — — — — — —
400
460 60 18 20 22 9/9 10/10 11/11 3.0 4.8 4.8 4.8 5.4 5.4 5.4 — — — 281 280 287 300 281 280 287 300 — — — — — —
575 60 18 20 22 9/9 10/10 11/11 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 225 225 230 241 225 225 230 241 — — — — — —
380 60 20 22 24 10/10 11/11 12/12 3.6 5.8 5.8 5.8 6.5 6.5 6.5 — — — 368 411 418 423 368 411 418 423 — — — — — —
400 60 20 22 24 10/10 11/11 12/12 3.5 5.5 5.5 5.5 6.2 6.2 6.2 — — — 350 390 397 402 350 390 397 402 — — — — — —
450
460 60 20 22 24 10/10 11/11 12/12 3.0 4.8 4.8 4.8 5.4 5.4 5.4 — — — 304 339 345 349 304 339 345 349 — — — — — —
575 60 20 22 24 10/10 11/11 12/12 2.4 3.8 3.8 3.8 4.3 4.3 4.3 — — — 244 271 277 280 244 271 277 280 — — — — — —
380 60 22 24 — 11/11 12/12 — 3.6 5.8 — 5.8 6.5 — 6.5 — — — — 431 450 444 — 431 450 444 — — — — — —
500 400 60 22 24 — 11/11 12/12 — 3.5 5.5 — 5.5 6.2 — 6.2 — — — — 410 427 422 — 410 427 422 — — — — — —
460 60 22 24 — 11/11 12/12 — 3.0 4.8 — 4.8 5.4 — 5.4 — — — — 356 371 366 — 356 371 366 — — — — — —
575 60 22 24 — 11/11 12/12 — 2.4 3.8 — 3.8 4.3 — 4.3 — — — — 285 298 293 — 285 298 293 — — — — — —
See Legend and Notes on page 115.

Table 37 — 50 Hz Compressor and Fan Data


High Static ECM
UNIT Standard
NUMBER OF COND FANS Condenser Fans Condenser Fans Compressor RLA PM Compressor RLA
VOLTAGE Condenser Fans FLA
UNIT FLA FLA
163

30XV Single Point Dual Point Tier Tier Tier A B A B


V
Hz STD STD
(3 Ph) STD MID HIGH STD MID HIGH STD MID HIGH MID HIGH MID HIGH STD HIGH MID STD+ STD HIGH MID STD+ STD STD+ MID HIGH STD+ MID HIGH
+ +
380 50 8 8 10 4/4 4/4 5/5 3.7 5.9 5.9 — 6.6 6.6 6.6 5.9 5.9 — 113 124 119 128 113 124 119 128 107 118 113 107 118 113
400 50 8 8 10 4/4 4/4 5/5 3.5 5.6 5.6 — 6.3 6.3 6.3 5.6 5.6 — 108 118 114 122 108 118 114 122 103 112 108 103 112 108
140
415 50 8 8 10 4/4 4/4 5/5 3.4 5.4 5.4 — 6.1 6.1 6.1 5.4 5.4 — 104 114 109 118 104 114 109 118 99 108 104 99 108 104
440 50 8 8 10 4/4 4/4 5/5 3.2 5.1 5.1 — 5.8 5.8 5.8 5.1 5.1 — 98 108 103 111 98 108 103 111 93 103 98 93 103 98
380 50 8 10 12 4/4 5/5 6/6 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 130 133 147 152 130 133 147 152 124 126 140 124 126 140
400 50 8 10 12 4/4 5/5 6/6 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 124 127 140 145 124 127 140 145 118 121 133 118 121 133
160
415 50 8 10 12 4/4 5/5 6/6 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 120 122 135 140 120 122 135 140 114 116 128 114 116 128
440 50 8 10 12 4/4 5/5 6/6 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 113 115 127 132 113 115 127 132 107 109 121 107 109 121
380 50 8 10 12 4/4 5/5 6/6 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 181 155 173 178 181 155 173 178 172 147 164 172 147 164
400 50 8 10 12 4/4 5/5 6/6 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 172 148 165 170 172 148 165 170 163 141 157 163 141 157
180
415 50 8 10 12 4/4 5/5 6/6 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 166 142 159 163 166 142 159 163 158 135 151 158 135 151
440 50 8 10 12 4/4 5/5 6/6 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 157 134 150 154 157 134 150 154 149 127 143 149 127 143
380 50 10 12 14 5/5 6/6 7/7 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 163 170 176 182 163 170 176 182 155 162 167 155 162 167
400 50 10 12 14 5/5 6/6 7/7 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 155 162 168 173 155 162 168 173 147 154 160 147 154 160
200
415 50 10 12 14 5/5 6/6 7/7 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 150 156 162 167 150 156 162 167 143 148 154 143 148 154
440 50 10 12 14 5/5 6/6 7/7 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 141 147 152 158 141 147 152 158 134 140 144 134 140 144
380 50 10 12 14 6/4 7/5 8/6 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 222 231 244 255 142 148 157 164 211 219 232 135 141 149
400 50 10 12 14 6/4 7/5 8/6 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 211 220 232 243 135 141 150 156 200 209 220 128 134 143
225
415 50 10 12 14 6/4 7/5 8/6 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 204 212 224 234 131 136 144 151 194 201 213 124 129 137
440 50 10 12 14 6/4 7/5 8/6 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 192 200 211 221 123 128 136 142 182 190 200 117 122 129
380 50 12 14 16 6/6 7/7 8/8 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 212 219 236 240 212 219 236 240 201 208 224 201 208 224
400 50 12 14 16 6/6 7/7 8/8 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 202 209 225 228 202 209 225 228 192 199 214 192 199 214
250
415 50 12 14 16 6/6 7/7 8/8 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 195 201 217 220 195 201 217 220 185 191 206 185 191 206
440 50 12 14 16 6/6 7/7 8/8 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 184 190 204 208 184 190 204 208 175 181 194 175 181 194
Table 37 — 50 Hz Compressor and Fan Data (cont)
High Static ECM
UNIT Standard
NUMBER OF COND FANS Condenser Fans Condenser Fans Compressor RLA PM Compressor RLA
VOLTAGE Condenser Fans FLA
UNIT FLA FLA
30XV Single Point Dual Point Tier Tier Tier A B A B
V
Hz STD STD
(3 Ph) STD MID HIGH STD MID HIGH STD MID HIGH MID HIGH MID HIGH STD HIGH MID STD+ STD HIGH MID STD+ STD STD+ MID HIGH STD+ MID HIGH
+ +
380 50 12 14 16 6/6 7/7 8/8 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 228 237 245 260 228 237 245 260 217 225 233 217 225 233
400 50 12 14 16 6/6 7/7 8/8 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 217 226 233 247 217 226 233 247 206 215 221 206 215 221
275
415 50 12 14 16 6/6 7/7 8/8 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 209 218 225 239 209 218 225 239 199 207 214 199 207 214
440 50 12 14 16 6/6 7/7 8/8 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 197 205 212 225 197 205 212 225 187 195 201 187 195 201
380 50 14 16 18 7/7 8/8 9/9 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 237 244 259 264 237 244 259 264 225 232 246 225 232 246
400 50 14 16 18 7/7 8/8 9/9 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 226 232 247 251 226 232 247 251 215 220 235 215 220 235
300
415 50 14 16 18 7/7 8/8 9/9 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 218 224 238 242 218 224 238 242 207 213 226 207 213 226
440 50 14 16 18 7/7 8/8 9/9 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 205 211 224 228 205 211 224 228 195 200 213 195 200 213
380 50 16 18 20 8/8 9/9 10/10 3.7 5.9 5.9 5.9 6.6 6.6 6.6 5.9 5.9 5.9 260 265 284 288 260 265 284 288 247 252 270 247 252 270
400 50 16 18 20 8/8 9/9 10/10 3.5 5.6 5.6 5.6 6.3 6.3 6.3 5.6 5.6 5.6 247 252 270 274 247 252 270 274 235 239 257 235 239 257
325
415 50 16 18 20 8/8 9/9 10/10 3.4 5.4 5.4 5.4 6.1 6.1 6.1 5.4 5.4 5.4 239 243 261 264 239 243 261 264 227 231 248 227 231 248
440 50 16 18 20 8/8 9/9 10/10 3.2 5.1 5.1 5.1 5.8 5.8 5.8 5.1 5.1 5.1 225 229 246 249 225 229 246 249 214 218 234 214 218 234
380 50 16 18 20 9/7 10/8 11/9 3.7 5.9 5.9 5.9 6.6 6.6 6.6 — — — 354 348 385 395 240 252 279 286 — — — — — —
400 50 16 18 20 9/7 10/8 11/9 3.5 5.6 5.6 5.6 6.3 6.3 6.3 — — — 337 331 366 376 228 240 266 272 — — — — — —
350
415 50 16 18 20 9/7 10/8 11/9 3.4 5.4 5.4 5.4 6.1 6.1 6.1 — — — 325 319 353 362 220 231 256 262 — — — — — —
440 50 16 18 20 9/7 10/8 11/9 3.2 5.1 5.1 5.1 5.8 5.8 5.8 — — — 306 301 333 342 208 218 241 247 — — — — — —
380 50 18 20 22 9/9 10/10 11/11 3.7 5.9 5.9 5.9 6.6 6.6 6.6 — — — 347 347 355 372 347 347 355 372 — — — — — —
400 50 18 20 22 9/9 10/10 11/11 3.5 5.6 5.6 5.6 6.3 6.3 6.3 — — — 330 330 338 354 330 330 338 354 — — — — — —
400
415 50 18 20 22 9/9 10/10 11/11 3.4 5.4 5.4 5.4 6.1 6.1 6.1 — — — 318 318 326 341 318 318 326 341 — — — — — —
164

440 50 18 20 22 9/9 10/10 11/11 3.2 5.1 5.1 5.1 5.8 5.8 5.8 — — — 300 300 307 322 300 300 307 322 — — — — — —
380 50 20 22 24 10/10 11/11 12/12 3.7 5.9 5.9 5.9 6.6 6.6 6.6 — — — 376 420 427 432 376 420 427 432 — — — — — —
400 50 20 22 24 10/10 11/11 12/12 3.5 5.6 5.6 5.6 6.3 6.3 6.3 — — — 358 399 406 411 358 399 406 411 — — — — — —
450
415 50 20 22 24 10/10 11/11 12/12 3.4 5.4 5.4 5.4 6.1 6.1 6.1 — — — 345 385 391 396 345 385 391 396 — — — — — —
440 50 20 22 24 10/10 11/11 12/12 3.2 5.1 5.1 5.1 5.8 5.8 5.8 — — — 325 363 369 374 325 363 369 374 — — — — — —
380 50 22 24 — 11/11 12/12 — 3.7 5.9 — 5.9 6.6 — 6.6 — — — — 440 459 453 — 440 459 453 — — — — — —
400 50 22 24 — 11/11 12/12 — 3.5 5.6 — 5.6 6.3 — 6.3 — — — — 418 437 431 — 418 437 431 — — — — — —
500
415 50 22 24 — 11/11 12/12 — 3.4 5.4 — 5.4 6.1 — 6.1 — — — — 403 421 415 — 403 421 415 — — — — — —
440 50 22 24 — 11/11 12/12 — 3.2 5.1 — 5.1 5.8 — 5.8 — — — — 380 397 392 — 380 397 392 — — — — — —
See Legend and Notes on page 115.
CCN COMMUNICATION BUS WIRING Table 38 — CCN Communication Bus Wiring
The communication bus wiring is a shielded, 3-conductor cable PART NUMBER
with drain wire and is field supplied and installed in the field. (See MANUFACTURER
Regular Wiring Plenum Wiring
Fig. 49.) Alpha 1895 —
The system elements are connected to the communication bus in a American A21451 A48301
daisy chain arrangement. The positive pin of each system element Belden 8205 884421
communication connector must be wired to the positive pins of the Columbia D6451 —
system elements on either side of it. This is also required for the Manhatten M13402 M64430
negative and signal ground pins of each system element. Wiring Quabik 6130 —
connections for CCN (Carrier Comfort Network) should be made
at TB (terminal block) 3. Consult the CCN Contractor’s Manual
for further information. (See Fig. 49.) IMPORTANT: A shorted CCN bus cable will prevent some rou-
tines from running and may prevent the unit from starting. If
NOTE: Conductors and drain wire must be 20 AWG (American abnormal conditions occur, disconnect the machine from the
Wire Gage) minimum stranded, tinned copper. Individual conduc- CCN. If conditions return to normal, check the CCN connector
tors must be insulated with PVC, PVC/nylon, vinyl, Teflon1, or and cable. Run new cable if necessary. A short in one section of
polyethylene. An aluminum/polyester 100% foil shield and an the bus can cause problems with all system elements on the bus.
outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a
minimum operating temperature range of –4F (–20C) to 140F BACNET IP OR ETHERNET COMMUNICATION
(60C) is required. See Table 38 for a list of manufacturers that
produce CCN bus wiring that meet these requirements. The 30XV units with Greenspeed® Intelligence come standard
with BACnet IP and Ethernet communications. The cabling for
It is important when connecting to a CCN communication bus that this is standard CAT 5 (minimum) with RJ45 connector.
a color coding scheme be used for the entire network to simplify
the installation. It is recommended that red be used for the signal NON-CCN COMMUNICATION WIRING
positive, black for the signal negative, and white for the signal The 30XV units with Greenspeed® intelligence offer several
ground. Use a similar scheme for cables containing different col- non-CCN translators. Refer to the separate installation instructions
ored wires. At each system element, the shields of its communica- for additional wiring steps.
tion bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield must FIELD CONTROL OPTION WIRING
be connected to a ground at one point only. If the communication Install field control wiring options. Some options, such as 4 to
bus cable exits from one building and enters another, the shields 20 mA demand limit that requires the energy management mod-
must be connected to grounds at the lightning suppressor in each ule, may require that accessories be installed first (if not factory in-
building where the cable enters or exits the building (one point per stalled) for terminal connections.
building only).
To connect the unit to the network: DUAL CHILLER LEAVING WATER SENSOR
1. Turn off power to the control box. If the dual chiller algorithm is used and the machines are installed
2. Cut the CCN wire and strip the ends of the red (+), white in parallel, an additional chilled water sensor must be installed for
(ground), and black (–) conductors. Substitute appropriate each chiller. Install the wells in the common leaving water header.
colors for different colored cables. (See Fig 50.) DO NOT relocate the chiller’s leaving water therm-
3. Connect the red wire to (+) terminal on TB3 of the plug, istors. They must remain in place for the unit to operate properly.
the white wire to COM terminal, and the black wire to the The thermistor well is a 1/4 in. NPT fitting for securing the well in
(–) terminal. the piping. The piping must be drilled and tapped for the well. Se-
4. The RJ14 CCN connector on TB3 can also be used, but is lect a location that will allow for removal of the thermistor without
any restrictions.
only intended for temporary connection (for example, a
laptop computer running service tool). Once the well is inserted, install the thermistors. Insert the therm-
istor into the well until the O-ring reaches the well body. Use the
nut on the thermistor to secure the thermistor in place. Once the
thermistor is in place, it is recommended that a thermistor wire
loop be made and secured with a wire tie to the chilled water pipe.
(See Fig. 50.)
For dual chiller control a CCN bus must be connected between the
two modules. (See Fig. 49). See the Carrier Comfort Network
Communication Bus Wiring section for additional information.
1. Teflon is a registered trademark of DuPont.

165
(+) (COM) (-) SHIELD (+) (COM) (-) SHIELD (+) (COM) (-) SHIELD

LEN CCN CCN LEN CCN CCN LEN CCN CCN

WHT

WHT
WHT

RED

RED
BLK
RED

BLK
BLK
SHIELD

TO NEXT
DEVICE

LEGEND
CCN — Carrier Comfort Network®
LEN — Local Equipment Network

Fig. 49 — TB3 — CCN Wiring

INSERT THERMISTOR UNTIL


O-RING MEETS THE
THERMISTOR WELL BODY.

5/8 in. HEX 1/4-18 NPT

WIRE TIE

6 in. MINIMUM
1.188 in.
CLEARANCE FOR
THERMISTOR 2.315 in.
REMOVAL

LOOP
THERMISTOR WIRE
AND SECURE
TO CHILLED WATER PIPE

Fig. 50 — Dual Chiller Accessory Kit Leaving Water Thermistor and Well (Part No. 00EFN900044000A)

Step 6 — Install Accessories COMMUNICATION ACCESSORIES


A number of accessories are available to provide the following op- A number of communication options are available to meet any re-
tional features (for details, refer to the Controls, Start-Up, Opera- quirement. Contact your local Carrier representative for more de-
tion, Service and Troubleshooting guide shipped with the unit). tails. For installation details, refer to separate installation instruc-
tions supplied with the accessory package.
ENERGY MANAGEMENT MODULE
The energy management module (EMM) is used for any of the SERVICE OPTIONS
following types of temperature reset, demand limit and ice A ground fault convenience outlet (GFI-CO) accessory is avail-
features: able to aid in servicing 30XV units with Greenspeed intelligence.
• 4 to 20 mA inputs for cooling set point reset and capacity The GFI-CO is a convenience outlet with a 5-amp GFI receptacle.
limit (requires field-supplied 4 to 20 mA generator) Contact your local Carrier representative for more details. For
• 0 to 10-v output for percentage total capacity running installation details, refer to separate installation instructions sup-
plied with the accessory package.
• 24-v discrete outputs for shutdown and running relays
• 10k space temperature input
The EMM provides discrete inputs for occupancy override,
demand limit switch 2 (step 1 demand limit is wired to the base
board, requires field-supplied dry contacts), remote lockout
switch, and ice done switch (requires field-supplied dry contacts).
UNIT SECURITY/PROTECTION ACCESSORIES
For applications with unique security and/or protection require-
ments, several options are available for unit protection. Security
grilles and hail guards are available. Contact your local Carrier
representative for more details. For installation details, refer to
separate installation instructions supplied with the accessory
package.

166
Step 7 — Leak Test Unit REFRIGERANT CHARGE
The 30XV chiller with Greenspeed® intelligence is shipped with a The 30XV chiller with Greenspeed intelligence is shipped from
complete operating charge of R-134a and should be under suffi- the factory with a full charge of R-134a. The unit should not need
cient pressure to conduct a leak test. to be charged at installation unless a leak was detected in Leak
Perform a leak test to ensure that leaks have not developed Test Unit section. If dehydration and recharging is necessary, use
during unit shipment. Dehydration of the system is not required industry standard practices or refer to Carrier Standard Service
unless the entire refrigerant charge has been lost. There are sev- Techniques Manual as required.
eral O-ring face seal fittings utilized in the oil line piping. If a
leak is detected at any of these fittings, open the system and in- IMPORTANT: These units are designed for use with R-134a
spect the O-ring surface for foreign matter or damage. Do not re- only. DO NOT USE ANY OTHER refrigerant in these units.
use O-rings. Repair any leak found following good refrigeration
practices.
CAUTION
CAUTION When evacuating or charging, circulate water through the
DO NOT OVERTIGHTEN THESE O-RING FACE SEAL evaporator at all times to prevent freezing and a potential re-
FITTINGS. Over-tightening will result in O-ring damage and frigerant leak. Failure to follow this procedure will impact or
a potential refrigerant leak. otherwise negatively affect the warranty should damage result
from freezing.
Refer to the Controls, Start-Up, Operation, Service and Trouble-
shooting manual for additional information.
CAUTION
DEHYDRATION
Refer to Carrier Standard Service Techniques Manual, Chapter 1, DO NOT OVERCHARGE system. Overcharging results in
Refrigerants, Sections 6 and 7 for details. Do not use compressor higher discharge pressure with higher power consumption and
to evacuate system. possible compressor damage.

167
© 2021 Carrier

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300224-01 Printed in U.S.A. Form 30XV-17SI Pg 168 12-21 Replaces: 30XV-11SI