Section 1

Introduction and Specifications


Instruction Manual

Overview
The SEL-700G Relay is designed to provide comprehensive protection,
integration and control features in a flexible, compact, and cost-effective
package. The SEL-700G0 and SEL-700G1 relays provide basic to full
generator protection for small to large machines. The SEL-700GT Relay
provides complete intertie and generator protection. The SEL-700GW Relay
provides dual feeder protection for a multimachine wind generator network
application, including overcurrent protection to feeders, transformers, etc. All
relays provide metering, monitoring, control and communications functions.
Flexible analog and digital input/output options and RTD based protection are
also included.
This manual contains the information necessary to install, set, test, operate,
and maintain any SEL-700G. You need not review the entire manual to
perform specific tasks.

Features
Protection Features The SEL-700G protection features depend on the model selected. The models
are configured with specific current/voltage input cards. The current/voltage
input cards are located in Slot Z and Slot E in the relay.
Slot Z cards are assigned a two-digit code beginning with the number 8 in the
SEL-700G Model Options Table (MOT, see Models on page 1.6). For
example, 81 in the MOT for Slot Z indicates a SELECT 4 ACI /3 AVI card with
3-phase ac current inputs (1 A nominal), neutral ac current input (1 A
nominal), and 3-phase ac voltage inputs (300 Vac).
Slot E cards are assigned a two-digit code beginning with the number 7 in the
SEL-700G Model Options Table (MOT). For example, 71 in the MOT for
Slot E indicates a SELECT 3 ACI /4 AVI card with the 3-phase ac current
inputs (1 A nominal), 3-phase ac voltage inputs (300 Vac), and VS (Vsysnc)
input (300 Vac).
Slot Z inputs, except for IN, are designated as X-side inputs. Slot E inputs,
except for VN and VS, are designated as Y-side inputs. The SEL-700G has
between 6 and 14 analog inputs, depending on the model and options selected.
Table 1.1 shows the current and voltage inputs for the different models
available. Current inputs are 1 A or 5 A nominal rating and voltage inputs are
300 V continuous rating.
When the VS or VN voltage inputs are unused in the SEL-700G0+,
SEL-700G1+, and SEL-700GT+ models and the setting
DELTAY_X := DELTA, then one of these voltage inputs could be used to

Date Code 20240329 Instruction Manual SEL-700G Relay


1.2 Introduction and Specifications
Features

connect an external zero-sequence voltage input. In such an application, the


setting EXT3V0_X must also be set accordingly. Refer to Section 4:
Protection and Logic Functions for more details.

Table 1.1 Current (ACI) and Voltage (AVI) Card Selection for SEL-700G Models

Slot Z Card Slot E Card


Model Description (MOT Digits) Slot Z Inputs (MOT Digits) Slot E Inputs

700G0 Basic generator protection 4 ACI/3 AVI IAX, IBX, ICX, IN, (OX)
(81, 82, 85, 86) VAX, VBX, VCX
700G0+ Basic generator protection plus 4 ACI/3 AVI IAX, IBX, ICX, IN, 2 AVI (74) VS, VN
(see Table 1.2 for additional (81, 82, 85, 86) VAX, VBX, VCX
protection elements)
700G1 Full generator protection 4 ACI/3 AVI IAX, IBX, ICX, IN, 3 ACIE IAY, IBY, ICY
(81, 82, 85, 86) VAX, VBX, VCX (73, 77)
700G1+ Full generator protection plus 4 ACI/3 AVI IAX, IBX, ICX, IN, 3 ACI/2 AVI IAY, IBY, ICY, VS, VN
(see Table 1.2 for additional (81, 82, 85, 86) VAX, VBX, VCX (72, 76)
protection elements)
700GT Intertie protection 1 ACI (84, 88) IN 3 ACI/4 AVI IAY, IBY, ICY,
(71, 75) VS, VAY, VBY, VCY
700GT+ Intertie and generator protection 4 ACI/3 AVI IAX, IBX, ICX, IN, 3 ACI/4 AVI IAY, IBY, ICY,
(81, 82, 85, 86) VAX, VBX, VCX (71, 75) VS, VAY, VBY, VCY
700GW Basic wind generator protection 3 ACIZ (83, 87) IAX, IBX, ICX 3 ACIE (73, 77) IAY, IBY, ICY

The SEL-700G offers an extensive variety of protection features, depending


on the model and options selected. Table 1.2 lists the protection features
available in different models. Elements using X-side inputs have an 'X' added
to them. For example, phase overcurrent elements using X-side CT inputs are
designated as 50PX while phase overcurrent elements using Y-side CT inputs
are designated as 50PY.

Table 1.2 SEL-700G Protection Elements (Sheet 1 of 3)


Basic With
Basic Intertie and Wind
Generator 21C, 25, 21C, 78, 21C, 25, Intertie Generator Generator
Protection Elements
Protection 64G, 78 87 64G, 78, 87 Protection Protection Protection
700G0 700G0+ 700G1 700G1+ 700GT 700GT+ 700GW
87 Phase Differential X X
87N Ground Differential X X X X X
REF Restricted Earth Fault X X X X X
64G 100% Stator Ground X X
64F Field Ground X X X X X X
40 Loss of Field X X X X X
49T Thermal Overload X X X X X
49RTD RTDs X X X X X X X
46 Current Unbalance X X X X X
24 Volts/Hz X X X X X
78 Out of Step X X X
78VS Vector Shift X X X X X X
INAD Inadvertent Energization X X X X X
21C Compensator Distance X X X
51C Voltage-Controlled TOC X X X X X

SEL-700G Relay Instruction Manual Date Code 20240329


Introduction and Specifications 1.3
Features

Table 1.2 SEL-700G Protection Elements (Sheet 2 of 3)


Basic With
Basic Intertie and Wind
Generator 21C, 25, 21C, 78, 21C, 25, Intertie Generator Generator
Protection Elements
Protection 64G, 78 87 64G, 78, 87 Protection Protection Protection
700G0 700G0+ 700G1 700G1+ 700GT 700GT+ 700GW
51V Voltage-Restrained TOC X X X X X
51PX Phase Time-Overcurrent X
51PY Phase Time-Overcurrent Xa Xa X
51QX Neg.-Seq. Time-Overcurrent X
51QY Neg.-Seq. Time-Overcurrent Xa Xa X
51GX Ground Time-Overcurrent Xa Xa Xa Xa Xa X
51GY Ground Time-Overcurrent Xa Xa X
51N Neutral Time-Overcurrent Xa Xa Xa Xa X Xa
50PX Phase Overcurrent X X X X X X
50PY Phase Overcurrent X X X X X
67PY Directional Phase X X
Overcurrent
50QX Neg.-Seq. Overcurrent X X X X X X
50QY Neg.-Seq. Overcurrent X X X X X
67QY Directional Neg.-Seq. X X
Overcurrent
50GX Ground Overcurrent X X X X X X
67GX Directional Ground X X X X X
Overcurrent
50GY Ground Overcurrent X X X X X
67GY Directional Ground X X
Overcurrent
50N Neutral Overcurrent Xb Xb Xb Xb X Xb
67N Directional Neutral X X X X X
Overcurrent
27X Undervoltage X X X X X
27Y Undervoltage X X
27S Synchronism Undervoltage X X X X
27I Inverse-Time Undervoltagec X X X X X X
59X Overvoltage (P, Q, G) X X X X X
59Y Overvoltage (P, Q, G) X X
59S Synchronism Overvoltage X X X X
59I Inverse-Time Overvoltaged X X X X X X
32X Directional Power X X X X X
32Y Directional Power X X
81X Over/Underfrequency X X X X X
81Y Over/Underfrequency X X
81RX Rate-of-Change of X X X X X
Frequency
81RY Rate-of-Change of X X
Frequency
BFX Breaker Failure X X X X X X
BFY Breaker Failure X X X
60LOPX Loss of Potential X X X X X

Date Code 20240329 Instruction Manual SEL-700G Relay


1.4 Introduction and Specifications
Features

Table 1.2 SEL-700G Protection Elements (Sheet 3 of 3)


Basic With
Basic Intertie and Wind
Generator 21C, 25, 21C, 78, 21C, 25, Intertie Generator Generator
Protection Elements
Protection 64G, 78 87 64G, 78, 87 Protection Protection Protection
700G0 700G0+ 700G1 700G1+ 700GT 700GT+ 700GW
60LOPY Loss of Potential X X
25 X Synchronism Check X X X
25 Y Synchronism Check X X
Autosynchronizer X X X
Off-Frequency X X X X X
Accumulators
a These inverse time-overcurrent elements have directional control.
b The 50N element uses the 67NnP and 67NnT Relay Word bits for the SEL-700G0, SEL-700G0+, SEL-700G1, SEL-700G1+, and SEL-700GT+
models.
c Two elements are available (select X- and/or Y-side phase, phase-to-phase, positive sequence, or synchronism voltage VS, depending on
the part number).
d Two elements are available (select X- and/or Y-side phase, phase-to-phase, residual, positive sequence, negative sequence, neutral voltage
VN, or synchronism voltage VS, depending on the part number).

Generator Protection The SEL-700G provides protection elements suitable for applications
protecting many different generators. Use Table 1.3 to select the protection
Element Selection elements to enable for specific applications.

Table 1.3 Recommended Protection Elements by Generator Grounding Method (Sheet 1 of 2)

High-Impedance Resistance Solidly


Element/Function Grounded Grounded Grounded
21 Backup Element Compensator Distance (DC) Availablea Availablea Availablea
24 Volts/Hertz Element Recommended Recommended Recommended
27 Undervoltage Optional Optional Optional
32 Reverse/Low-Forward Power Recommended Recommended Recommended
40 Loss-of-Field Recommended Recommended Recommended
46 Negative-Sequence Overcurrent Recommended Recommended Recommended
50N/51N Neutral Overcurrent Suggestedb Suggestedb Recommended
50P Phase Overcurrent Not Recommended Not Recommended Recommended
51C/51V Voltage-Controlled and Voltage-Restrained Availablea Availablea Availablea
Time-Overcurrent
59 Overvoltage Optional Optional Optional
64G 100% Stator Ground Elements Recommended Suggestedc Not Recommended
78 Out-of-Step Recommended Recommended Recommended
81 Over- and Underfrequency Elements Recommended Recommended Recommended
81 AC Abnormal Frequency Scheme Available Available Available

SEL-700G Relay Instruction Manual Date Code 20240329


Introduction and Specifications 1.5
Features

Table 1.3 Recommended Protection Elements by Generator Grounding Method (Sheet 2 of 2)

High-Impedance Resistance Solidly


Element/Function Grounded Grounded Grounded
87 Current Differential Elements Suggested for Large Optional Optional
Machines
87N Ground Differential Element Not Recommended Suggestedb Suggestedb
a Select no more than one of 21DC, 51C, or 51V elements for backup protection.
b If neutral CT is available.
c If neutral PT is available.

Front-Panel Options The SEL-700G offers two front-panel HMI layouts that are model and option
dependent. Table 1.4 lists the HMI options for the SEL-700G front panel. For
ordering options, refer to the SEL-700G MOT.

Table 1.4 SEL-700G Front-Panel Options

Front-Panel Option (MOT


Model/Display Description String Digit Number 17) Number of Pushbuttons LED Type

SEL-700G With Two-Line Display 0/1 8 Tricolor


(2 x 16 characters)

SEL-700G With Touchscreen Display A/B 8 Tricolor


(5-inch, color, 800 x 480 pixels)

Monitoring Features ➤ Event summaries that contain relay ID, date and time, trip cause,
and current/voltage magnitudes
➤ Event reports including filtered and raw analog data
➤ Sequential Events Recorder (SER)
➤ Compatibility with SEL-3010 Event Messenger
➤ A complete suite of accurate metering functions
➤ Generator operating statistics monitoring
➤ Breaker wear monitoring
➤ Load profile report
➤ Generator automatic synchronization report

Communications and ➤ EIA-232, front-panel port

Control Features ➤ EIA-232, EIA-485, single or dual, copper or fiber-optic


Ethernet, and fiber-optic rear panel EIA-232 ports
➤ Built-in Web Server
➤ IRIG-B time-code input
➤ Modbus RTU slave, Modbus TCP/IP, DNP3 serial, DNP3 LAN/
WAN, Ethernet FTP, Telnet, Simple Network Time
Protocol (SNTP), IEEE-1588-2008 firmware-based Precision
Time Protocol (PTP), MIRRORED BITS, IEC 61850 Edition 2,
IEC 60870-5-103, DeviceNet, EtherNet/IP, Synchrophasors with
C37.118 Protocol, Parallel Redundancy Protocol (PRP), and
Rapid Spanning Tree Protocol (RSTP)
➤ SEL ASCII, Compressed ASCII, Fast Meter, Fast Operate, Fast
SER, and Fast Message Protocols
➤ Programmable Boolean and math operators, logic functions, and
analog compare

Date Code 20240329 Instruction Manual SEL-700G Relay