Overview
The SEL-700G Relay is designed to provide comprehensive protection,
integration and control features in a flexible, compact, and cost-effective
package. The SEL-700G0 and SEL-700G1 relays provide basic to full
generator protection for small to large machines. The SEL-700GT Relay
provides complete intertie and generator protection. The SEL-700GW Relay
provides dual feeder protection for a multimachine wind generator network
application, including overcurrent protection to feeders, transformers, etc. All
relays provide metering, monitoring, control and communications functions.
Flexible analog and digital input/output options and RTD based protection are
also included.
This manual contains the information necessary to install, set, test, operate,
and maintain any SEL-700G. You need not review the entire manual to
perform specific tasks.
Features
Protection Features The SEL-700G protection features depend on the model selected. The models
are configured with specific current/voltage input cards. The current/voltage
input cards are located in Slot Z and Slot E in the relay.
Slot Z cards are assigned a two-digit code beginning with the number 8 in the
SEL-700G Model Options Table (MOT, see Models on page 1.6). For
example, 81 in the MOT for Slot Z indicates a SELECT 4 ACI /3 AVI card with
3-phase ac current inputs (1 A nominal), neutral ac current input (1 A
nominal), and 3-phase ac voltage inputs (300 Vac).
Slot E cards are assigned a two-digit code beginning with the number 7 in the
SEL-700G Model Options Table (MOT). For example, 71 in the MOT for
Slot E indicates a SELECT 3 ACI /4 AVI card with the 3-phase ac current
inputs (1 A nominal), 3-phase ac voltage inputs (300 Vac), and VS (Vsysnc)
input (300 Vac).
Slot Z inputs, except for IN, are designated as X-side inputs. Slot E inputs,
except for VN and VS, are designated as Y-side inputs. The SEL-700G has
between 6 and 14 analog inputs, depending on the model and options selected.
Table 1.1 shows the current and voltage inputs for the different models
available. Current inputs are 1 A or 5 A nominal rating and voltage inputs are
300 V continuous rating.
When the VS or VN voltage inputs are unused in the SEL-700G0+,
SEL-700G1+, and SEL-700GT+ models and the setting
DELTAY_X := DELTA, then one of these voltage inputs could be used to
Table 1.1 Current (ACI) and Voltage (AVI) Card Selection for SEL-700G Models
700G0 Basic generator protection 4 ACI/3 AVI IAX, IBX, ICX, IN, (OX)
(81, 82, 85, 86) VAX, VBX, VCX
700G0+ Basic generator protection plus 4 ACI/3 AVI IAX, IBX, ICX, IN, 2 AVI (74) VS, VN
(see Table 1.2 for additional (81, 82, 85, 86) VAX, VBX, VCX
protection elements)
700G1 Full generator protection 4 ACI/3 AVI IAX, IBX, ICX, IN, 3 ACIE IAY, IBY, ICY
(81, 82, 85, 86) VAX, VBX, VCX (73, 77)
700G1+ Full generator protection plus 4 ACI/3 AVI IAX, IBX, ICX, IN, 3 ACI/2 AVI IAY, IBY, ICY, VS, VN
(see Table 1.2 for additional (81, 82, 85, 86) VAX, VBX, VCX (72, 76)
protection elements)
700GT Intertie protection 1 ACI (84, 88) IN 3 ACI/4 AVI IAY, IBY, ICY,
(71, 75) VS, VAY, VBY, VCY
700GT+ Intertie and generator protection 4 ACI/3 AVI IAX, IBX, ICX, IN, 3 ACI/4 AVI IAY, IBY, ICY,
(81, 82, 85, 86) VAX, VBX, VCX (71, 75) VS, VAY, VBY, VCY
700GW Basic wind generator protection 3 ACIZ (83, 87) IAX, IBX, ICX 3 ACIE (73, 77) IAY, IBY, ICY
Generator Protection The SEL-700G provides protection elements suitable for applications
protecting many different generators. Use Table 1.3 to select the protection
Element Selection elements to enable for specific applications.
Front-Panel Options The SEL-700G offers two front-panel HMI layouts that are model and option
dependent. Table 1.4 lists the HMI options for the SEL-700G front panel. For
ordering options, refer to the SEL-700G MOT.
Monitoring Features ➤ Event summaries that contain relay ID, date and time, trip cause,
and current/voltage magnitudes
➤ Event reports including filtered and raw analog data
➤ Sequential Events Recorder (SER)
➤ Compatibility with SEL-3010 Event Messenger
➤ A complete suite of accurate metering functions
➤ Generator operating statistics monitoring
➤ Breaker wear monitoring
➤ Load profile report
➤ Generator automatic synchronization report