GRILLES

Ajustable Blade Grilles Fixed Blade Grilles Door Grilles Floor Grilles Aircell Polymer Range

Contents

Adjustable Blade Grilles


1H,1V, 2H, 2V Single and Double Deflection Grilles . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1RV, 2RV Adjustable Duct Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 (R)RTC, 2(R)RTC Reversible Core Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

Fixed Blade Grilles


3HG, 3HJ, 3HF, GC5, PER Exhaust Grilles . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 ALN, ALM, ALF, ALG, ALJ Airline Linear Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 SG1, SG2, SG3 Security Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

Door / Sidewall Grilles


NS, DV, NSNL Air Transfer Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .22 WFV,WFVG Fire Rated Transfer Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 DSRX Acoustic Transfer Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . .26 WPT Sidewall Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

Floor Grilles
AFG Light Duty Floor Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 HDFG Heavy Duty Floor Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

Aircell Polymer Grilles


Aircell S, D, G, A, T, E Aircell Polymer Grilles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Aircell N Neck Reducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . .39 Aircell GO Opposed Blade Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 OBSS Aluminium Opposed Blade Damper for E600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

Technical Information
PBG Grille Plenum Chambers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 FDC, FDQ, OBCO, OBSS Plenum Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 Fixing Options Various . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 R16, R25, R32 Border Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 RC, AF, PF Sub Frame Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 OBSS, ED Volume Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 DT-2M Air Turn Volume Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .42 Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .43

Waterloo 1.0

Adjustable Blade Grilles


1H 1V 2H 2V
Introduction
The Waterloo adjustable, single and double deflection grilles are suitable for duct, ceiling and sidewall applications in most commercial projects. The grille vanes are individually adjustable to allow jet spread or deflection to be set within 45 of the duct axis.

19

1H 1V 2H 2V OBSS ED DT-2M

Single set of horizontal blades Single set of vertical blades Double set of blades with front set horizontal Double set of blades with front set vertical Allen key operated opposed blade damper Equalising deflector Adjustable duct turn (Installed in duct)

Nom. - 25

Features
Single or double deflection for complete air pattern control Teardrop blade for quiet operation but maximum induction
70 (Open) 86 (Open)

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours or anodised finish available on request

1H + OBSS

Nom. - 25

19

Product Description

2H + OBSS

Weights
1H /1V 8.5 kg/m2 face area 2H/2V 12.0 kg/m2 face area OBSS/ED 9.5 kg/m2 face area DT2M 9.0 kg/m2 face area

Nom. - 25

Nom. - 25

Nom.

Sizes
Minimum Size - 100 x 100 Maximum Size - 1200 x 1200

Fixing Options
SF PFVS BSSBD CF RCHS CRB AFHS VS AFCF AFVS RCCF
27 43

1V

2V

BSSBP (NOT for 2H or 2V) Free Area

Order Example
1H/300x300/PPM9010/R25/SF/OBSS
Type Nominal Width Nominal Height Finish Border Fixing Options

1H/1V 74%

2H/2V 66%

Please refer to pages 40 - 43 for full details of: Fixing Options Control Options Sub Frames Sizing Implications Border Options

Waterloo 1.0

Nom.

Adjustable Blade Grilles


Selection Criteria
Performance data is based on grilles situated within 0.6m of ceiling with supply air at an 11C cooling differential. Throw is the horizontal distance from the grille face to the point at which the velocity of the airstream has retarded to 0.4 m/s. For grilles situated 0.6m or more below ceiling level reduce throw by 1 3 . NC is sound pressure / level/Noise Criteria Curve based on a room absorption of 8 dB for sound power (Lw) ref 10-12 W.

1H 1V 2H 2V
Selection Example 2H/500x150/25T/SF
Air Volume 300 I/s Grille @ 0 deflection Throw 16m Velocity 6.1m/s Grille @ 45 deflection Throw 8.5m Velocity 6.1m/s NC 22 NC 30 Ps 10 Ps 32 Ps 16 Ps 51

Grille with damper @ 0 deflection Throw 16m Velocity 6.1m/s NC 27 Grille with damper @ 45 deflection Throw 8.5m Velocity 6.1m/s NC 35

NR(Lp) and Static Pressure (Ps) Correction Factors for Grilles With an Open Damper
Grille Width Lp Addition (CL) Ps Multiplier (CP) 100+ 12 2.5 125+ 11 2.4 150+ 10 2.2 200+ 9 2.0 250+ 8 1.9 300+ 7 1.8 350+ 6 1.7 450+ 5 1.6 550+ 5 1.5 600+ 4 1.5 700+ 4 1.4 850+ >1000 4 1.3 3 1.2

Performance Nomogram
throw

AIR FLOW RATE (l/s)


5000 4000

NOMINAL WIDTH (mm)

NOMINAL HEIGHT (mm)


100

3000

Throw (m)
2000 (Vt = 0.4 m/s)

NC Level

Velocity (m/s) on grille face

Static Pressure Ps (Pa)

200 150

45 Deflection

45 Deflection

1000 900 800 700 600 500

45 Deflection

0 Deflection

0 Deflection

0 Deflection

0 Deflection

PIVOT LINE

600mm max

Nomogram based on ceiling effect jet as shown. For free jet correction factor see notes above.

150

200

50 40 30 300 20 45 40 30 20 10 9 8 7 6 10 9 8 7 6 5 4 3 700 5 4 3 20 30 20 45 40 10 8 6 5 4 3 2 1 5 4 3 2 1 500 400

20 10 5

50 40 30 20 10 400 300

400

300

200

Pivot Line
2

1 600 500

100 90 80 70 60 50

Terminal Velocity Correction Factors


Vt (m/s) Throw multiplier

600 800 700

0.6 0.65

0.5 0.8

0.4 1.0

0.3
1000

800

1.3
1200 1000

25

Please refer to page 2 for used definitions.

1200

Waterloo 1.0

Adjustable Duct Grilles


1RV 2RV
Introduction
The Waterloo 1RV & 2RV are designed to fit directly onto the side of an exposed circular duct without the need for a stub duct or transition piece. The flange is supplied complete with a foam sealing gasket on all 4 sides. These units can be provided with either a single row of vertical blades, or a set of vertical blades at the front and a set of horizontal blades at the rear. There are a range of sizes for each grille to suit ducts from 125 - 1500. Each grille can be supplied with an aluminium opposed blade damper if required.
30

Nom. - 25
D

Product Description
1RV 2RV OBSS DT-2MG Single vertical set of blades One set vertical, one set of horizontal blades Allen key operated opposed blade damper Adjustable duct turns E F
30

Features
Supply and exhaust applications for warm or cooled air Adjustable blades Suitable for large range of duct sizes

1RV

Nom.

PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Free Area 1RV 74% 2RV 66%


D

Weights
1RV 2RV OBSS DT-2MG 8.5 kg/m2 face area 12.0 kg/m2 face area 9.5 kg/m2 face area 9.0 kg/m2 face area E F

2RV

Sizes
Nom. W 225mm - 1225mm in 100 mm increments Nom. H 75mm - 225mm in 50 mm increments Please refer to page 42 for full details of: Control Options (OBSS / DT-2MG)

Fixing
SF Only - Screw through face flange W 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225 225-1225

Sizes Dimensions and Angles H 75 75 75 75 125 125 125 125 175 175 175 225 225 225
D

min

max

E 45 35 30 25 35 30 25 15 25 20 30 25 15

A 53 53 53 53 66 80 80 80 101 101 135 135 135

Advantages
Large size range High air handling capacity Fully adjustable throws No need for transition piece on ducts

125 151 201 301 200 301 401 551 450 551 901 500 601 901

150 200 300 400 300 400 550 900 550 900 1250 600 900 1500

Order Example
1RV-250/325x75/PPM9010/SF/OBSS
Type Duct Diameter Duct Opening Width Duct Opening Height Finish Fixing Option

12.5 101

Waterloo 1.0

Nom.

Finishes

Nom. - 25

F 55 55 55 55 69 63 61 59 68 65 61 76 72 65

Adjustable Duct Grilles


1RV 2RV
Selection Criteria
Temperature Differential -11K NC is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB Throw is based on a free jet application

Selection Example 1RV/925x225 at 0 deflection


Air Volume 900 I/s Throw 18.5 m Pressure Drop 9 Pa Noise Level NC 26 Face Velocity 6 m/s Jet Terminal Velocity Correction Factors

Please refer to page 2 for used symbols, definitions and criteria.

Performance Nomogram

0.6 m/s x 0.65

0.5 m/s x 0.80

0.4 m/s x 1.0

0.3 m/s x 1.3

THROW (m) Vt = 0.4 m/s TOTAL AIR FLOW RATE (l/s) 0 45 VELOCITY (m/s) on grille face 50 0 40 NC LEVEL 20 0 45 0 45 STATIC PRESSURE LOSS Ps (Pa)

NOMINAL WIDTH (mm) 325

NOMINAL HEIGHT (mm)

1000 900 800 700 30 600 500

75

425

20

50 10 9 8 7 6 30 40 45 40 10 8 30 6 5 20 4 3 3 5 4 3 2 825 1 1 PIVOT LINE 925 725 175 5 20 10 50 40 30 20 10 625 125 525

400

300

10 9 8 7 6

5 4

20

200 5

2 4 2 3

100 90 80 70 60 50 1125 PIVOT LINE 1025

225

1225

Waterloo 1.0

Reversible Core Grilles


(R)RTC 2(R)RTC
6
5
o

Introduction
The Waterloo reversible core grilles have been designed for commercial projects requiring aesthetically attractive grilles but with a superior performance. The specially designed, close pitch vanes, produce high levels of induction and mixing with ambient air resulting in more even air diffusion in the occupied zone. The core is removable and may be rotated or reversed to provide either 5 or 15 deflection upwards or downwards; in addition the core can easily be cleaned before replacing in the frame. Alternatively any of the Exhaust grille or airline linear grilles cores may be specified.

12 22

22 3.2

15 Nom.

3.2

15 Nom.

RTC(C)-6

RTC(C)-12

Product Description
Nom. - 25

RTC 2RTC RRTC

Reversible core grille Reversible core grille with rear vertical blades Same as RTC grille with frame suitable for round ducts (See Page 6) 2RRTC Same as 2RTC grille with frame suitable for round ducts (See page 6) RTC(C) Reversible core only (no frame) OBSS Allen key operated opposed blade damper DT-2MG Adjustable Air Turn (fixed on grille) DT-2M Adjustable Air Turn (Fixed in duct)

30

Nom. - 6

Nom.

Features
Turbulator vanes provide high induction and mixing with room air Core removable for access and cleaning One core provides 5 or 15 deflection, up or down Rear set of vanes available as an option for horizontal spread/deflection control 48.5 30 54

2RTC-6

2RRTC-6

For sizes E and F see 1RV/2RV

Border Types
5 5 16 16 24.5 5

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours or anodised finish available on request (Anodised finish unavailable on (2)RRTC)

R5

35

R16

R16-24

Sizes Weights
R(R)TC 2R(R)TC OBSS / ED DT2M(G) 14 kg/m2 face area 18 kg/m2 face area 9.5 kg/m2 face area 9.0 kg/m2 face area Minimum Size - 325 x 125 mm Maximum Size - 1500 x 450mm

Fixings
ST For (2)RRTC RCCF SF ONLY

Order Example
RTC-6/500x250/PPM9010/R16/CF/OBSS
Type Nominal Width Nominal Height Finish Border Fixing Options

R16 + ST

R5 + ST

R16-24 + ST
Free Area

R16 + RCCF

RTC-6 RRTC-6 RTCC-6 74%

2RTC-6 2RRTC-6 66%

RTC-12 2RTC-12 RRTC-12 2RRTC-12 RTCC-12 87% 79%

Waterloo 1.0

Nom.

Reversible Core Grilles


(R)RTC 2(R)RTC
Please refer to page 2 for symbols used, definitions and criteria.

Selection Example RTC-6/425x125


Spread 0 Air Volume 83 I/s Throw 4.7 m Pressure Drop 5 Pa Noise Level NR 13

Note!
Maximum Throws in the following tables are for an a terminal air velocity of 0.15m/s within the comfort zone.

Performance Table RTC-6 2RTC-6


m3/h 100 l/s 28 T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp T Ps Lp

Supply
325x125 425x125 525x125 625x125 425x225 525x225 625x225 825x225 625x325 825x325

0 30 0 30 0 30 0 30 0 30 0 30 0 30 0 30 0 30 0 30
2.9 2.3 1 2 3.4 2.6 2 3 4.5 3.4 4 6 5.5 4.3 10 15 19 24 8.2 6.9 17 25 25 31 3.1 2.1 1 2 3.9 2.9 2 3 4.7 3.6 5 8 13 17 7.3 5.7 10 15 20 25 8.2 6.7 16 25 25 30 3.5 2.7 1 3 4.2 3.2 3 4 6.3 5.0 5 8 15 20 7.4 6.1 10 14 21 25 9.4 7.8 15 23 26 31 3.2 2.4 1 2 3.8 3.0 2 3 5.6 4.3 4 6 12 16 6.8 5.5 7 10 17 22 8.6 6.8 11 19 22 27 11.1 9.1 18 26 28 33 3.5 2.8 1 2 5.0 4.1 2 4 6.3 5.0 3 6 16 7.4 5.8 6 8 15 20 9.8 7.6 8 13 21 25 4.6 3.6 1 2 5.5 4.3 2 3 6.4 5.4 3 5 14 8.2 6.6 5 8 17 22 4.8 3.8 1 2 5.9 4.8 2 3 7.5 6.0 3 5 13 17 5.5 4.5 1 2 6.7 5.3 2 3 8.9 7.1 3 5 12 17 6.0 5.0 1 2 7.9 6.3 2 3 14 6.7 5.3 1 2 8.9 7.3 2 3 -

150

42

200

56

300

83

400

111

500

139

600

167

750

208

1000

278

13.4 10.6 11.3 9.2 10.1 8.0 16 25 10 15 7 10 28 33 23 28 19 24

1250

347

14.8 12.0 12.9 10.2 11.3 9.4 10.5 8.1 16 24 10 15 4 7 3 5 29 34 24 29 18 22 15 20

1500

417

17.0 13.5 14.4 12.0 13.0 10.4 11.4 9.1 17 25 9 10 12 6 4 6 30 35 23 28 21 26 13 19 18.0 15.1 17.1 13.4 14.5 11.7 16 24 11 16 6 10 31 35 28 33 22 27 20.5 16.9 17.4 14.1 14 22 10 15 35 40 28 32 20.5 16.8 16 25 34 39

2000

556

2500

694

3000

833

Waterloo 1.0

Reversible Core Grilles


(R)RTC 2(R)RTC
Selection Example 2RRTC-6/825x75
Spread 0 Ceiling Height Throw Correction Factors Ceiling Height (m) Maximum Throw (m) 2.5 2.5 2.7 3.3 3.0 4.5 3.5 6.3 Air Volume 83 l/s Throw 4.7 m Pressure Drop 5 Pa Noise Level NR 13

Performance Table Nom. H =75mm Suitable for round ducts 150 up to 400

RRTC-6 2RRTC-6
m3/h l/s 100 28 T Ps Lp 150 42 T Ps Lp 200 56 T Ps Lp 300 83 T Ps Lp 400 111 T Ps Lp 500 139 T Ps Lp 600 167 T Ps Lp 750 208 T Ps Lp

Supply / Exhaust
325 x 75 425 x 75 525 x 75 625 x 75 825 x 75 1025 x 75 1225 x 75

0 30
3.6 4 4.1 11 19 6.0 19 26 2.8 6 3.3 16 24 4.7 27 32

0 30
3.4 2 3.9 6 11 5.3 11 19 6.5 24 32 2.7 3 3.1 9 14 4.2 16 24 5.1 32 38

0 30
3.2 1 3.7 3 4.9 7 13 5.9 15 23 2.5 3 2.9 5 3.9 10 16 4.6 21 29

0 30
2.9 1 3.4 2 4.5 4 5.5 10 19 8.2 17 25 2.3 2 2.6 3 3.4 6 4.3 15 24 6.9 25 31

0 30

0 30

0 30

3.1 1 3.9 2 4.7 5 13 7.3 10 20 8.2 16 25

2.1 2 2.9 3 3.6 8 17 5.7 15 25 6.7 25 30 3.5 1 4.2 3 6.3 5 15 7.4 10 21 9.4 15 26 2.7 3 3.2 4 5.0 8 20 6.1 14 25 7.8 23 31 3.2 1 3.8 2 5.6 4 12 6.8 7 17 8.6 11 22 18 28 2.4 2 3.0 3 4.3 6 16 5.5 10 22 6.8 19 27 26 33

11.1 9.1

Waterloo 1.0

10

Reversible Core Grilles


(R)RTC 2(R)RTC
Selection Example 2RRTC-6/425x125
Spread 0 Air Volume 83 l/s Throw 4.7 m Pressure Drop 5 Pa Noise Level NR 13

Ceiling Height Throw Correction Factors Ceiling Height (m) Maximum Throw (m) 2.5 2.5 2.7 3.3 3.0 4.5 3.5 6.3

Performance Table Nom. H =125mm Suitable for round ducts 300 up to 900

RRTC-6 2RRTC-6
m3/h l/s T 100 28 Ps Lp T 150 42 Ps Lp T 200 56 Ps Lp T 300 83 Ps Lp T 400 111 Ps Lp T 500 139 Ps Lp T 600 167 Ps Lp T 750 208 Ps Lp T 1000 278 Ps Lp T 1250 347 Ps Lp T 1500 417 Ps Lp

Supply / Exhaust
325 x 125 425 x 125 525 x 125 625 x 125 825 x 125 1025 x 125 1225 x 125

0 30
2.9 1 3.4 2 4.5 4 5.5 10 19 8.2 17 25 2.3 2 2.6 3 3.4 6 4.3 15 24 6.9 25 31

0 30

0 30

0 30

0 30

0 30

0 30

3.1 1 3.9 2 4.7 5 13 7.3 10 20 8.2 16 25

2.1 2 2.9 3 3.6 8 17 5.7 15 25 6.7 25 30 3.5 1 4.2 3 6.3 5 15 7.4 10 21 9.4 15 26 2.7 3 3.2 4 5.0 8 20 6.1 14 25 7.8 23 31 3.2 1 3.8 2 5.6 4 12 6.8 7 17 8.6 11 22 18 28 2.4 2 3.0 3 4.3 6 16 5.5 10 22 6.8 19 27 26 33 3.5 1 5.0 2 6.3 3 7.4 6 15 9.8 8 21 16 28 2.8 2 4.1 4 5.0 6 16 5.8 8 20 7.6 13 25 25 33 4.6 1 5.5 2 6.4 3 8.2 5 17 10 23 16 29 3.6 2 4.3 3 5.4 5 14 6.6 8 22 15 28 24 34 4.8 1 5.9 2 7.5 3 13 7 19 10 24 17 30 3.8 2 4.8 3 6.0 5 17 10 24 15 29 25 35

11.1 9.1

13.4 10.6 11.3 9.2 10.1 8.0

14.8 12.0 12.9 10.2

17.0 13.5

Waterloo 1.0

11

Reversible Core Grilles


(R)RTC 2(R)RTC
Selection Example 2RRTC-6/425x175
Spread 0 Ceiling Height Throw Correction Factors Ceiling Height (m) Maximum Throw (m) 2.5 2.5 2.7 3.3 3.0 4.5 3.5 6.3 Air Volume 111 l/s Throw 5.6 m Pressure Drop 4 Pa Noise Level NR 12

Performance Table Nom. H =175mm Suitable for round ducts 450 up to 1250

RRTC-6 2RRTC-6
m3/h l/s T 200 56 Ps Lp T 300 83 Ps Lp T 400 111 Ps Lp T 500 139 Ps Lp T 600 167 Ps Lp T 750 208 Ps Lp T 1000 278 Ps Lp T 1250 347 Ps Lp T 1500 417 Ps Lp T 2000 556 Ps Lp T 2500 694 Ps Lp

Supply / Exhaust
325 x 175 425 x 175 525 x 175 625 x 175 825 x 175 1025 x 175 1225 x 175

0 30
3.5 1 4.5 3 6.1 8 17 7.8 13 22 9.9 21 32 2.7 3 3.3 5 5.0 12 21 6.1 20 27 7.9 34 36

0 30
3.1 1 3.8 1 5.6 4 12 6.8 7 17 8.6 11 22 18 28 2.3 2 3.0 3 4.4 6 16 5.5 10 22 6.8 19 30 26 33

0 30

0 30

0 30

0 30

0 30

3.5 1 5.1 2 6.3 4 12 7.7 7 17 10 23 19 31

2.7 2 4.1 3 5.1 6 16 6.2 9 21 15 27 29 36 4.9 1 5.8 2 7.1 4 13 9.1 7 19 13 25 23 33 3.8 2 4.5 4 13 5.4 7 18 7.0 11 24 19 30 35 38 4.8 1 5.9 2 7.5 3 13 7 19 10 24 17 30 3.8 2 4.8 3 6.0 5 17 10 24 15 29 25 35 5.2 1 6.6 2 8.9 3 14 6 20 11 25 18 30 4.0 2 5.4 3 7.1 5 18 9 24 15 29 27 37 6.0 1 7.9 2 3 15 6 21 11 28 14 35 5.0 2 6.3 3 14 5 20 10 26 16 33 22 40

11.1 9.2 10.1 8.2

14.1 11.5 12.6 9.7 10.1 8.0

16.1 12.5 12.9 10.2 11.3 9.3 10.5 8.1

17.0 13.5 14.7 11.9 13.0 10.4

19.6 16.1 17.1 13.4

20.5 16.9

Waterloo 1.0

12

Reversible Core Grilles


(R)RTC 2(R)RTC
Ceiling Height Throw Correction Factors Ceiling Height (m) Maximum Throw (m) 2.5 2.5 2.7 3.3 3.0 4.5 3.5 6.3

Selection Example 2RRTC-6/425x225


Spread 30 Air Volume 139 l/s Throw 5.0 m Pressure Drop 6 Pa Noise Level NR 16

Performance Table Nom. H =225mm Suitable for round ducts 600 up to 1500

RRTC-6 2RRTC-6
m3/h l/s T 200 56 Ps Lp T 300 83 Ps Lp T 400 111 Ps Lp T 500 139 Ps Lp T 600 167 Ps Lp T 750 208 Ps Lp T 1000 278 Ps Lp T 1250 347 Ps Lp T 1500 417 Ps Lp T 2000 556 Ps Lp T 2500 694 Ps Lp T 3000 833 Ps Lp

Supply / Exhaust
325 x 225 425 x 225 525 x 225 625 x 225 825 x 225 1025 x 225 1225 x 225

0 30
3.1 1 3.8 2 5.6 4 12 6.8 7 17 8.6 11 22 18 28 2.3 2 3.0 3 4.4 6 16 5.5 10 22 6.8 19 27 26 33

0 30

0 30

0 30

0 30

0 30

0 30

3.5 1 5.0 2 6.3 3 7.4 6 15 9.8 8 21 16 28

2.8 2 4.1 4 5.0 6 16 5.8 8 20 7.6 13 25 25 33 4.6 1 5.5 2 6.4 3 8.2 5 17 10 23 16 29 3.6 2 4.3 3 5.4 5 14 6.6 8 22 15 28 24 34 4.8 1 5.9 2 7.5 3 13 7 19 10 24 17 30 3.8 2 4.8 3 6.0 5 17 10 24 15 29 25 35 5.5 1 6.7 2 8.9 3 12 4 18 9 23 16 31 4.5 2 5.3 3 7.1 5 17 7 22 12 28 24 35 6.0 1 8.0 2 3 11 5 18 10 25 16 31 4.7 2 5.9 3 5 17 8 23 16 30 24 36 6.7 1 8.9 2 4 13 6 22 10 28 16 34 5.3 2 7.3 3 6 19 10 27 15 32 25 39

11.1 9.1

13.4 10.6 11.3 9.2 10.1 8.0

14.8 12.0 12.9 10.2 11.3 9.4 10.1 8.1

17.0 13.5 14.4 12.0 12.9 10.5 11.4 9.1

18.0 15.1 16.3 13.4 14.5 11.7

19.4 16.1 17.4 14.1

20.5 16.8

Waterloo 1.0

13

Exhaust Grilles
3HG 3HJ 3HF GC5 PER
Introduction
The Waterloo 3 Series vane grilles, GC5 eggcrate and PER mesh grilles have been designed to satisfy all exhaust applications in H & V systems. The various cores may be selected to satisfy both engineering and architectural requirements. The frames are constructed from aluminium extrusions which are mitred and welded or cleated. Cores are constructed from aluminium extrusions supported on integral aluminium tubes; Mesh cores are perforated aluminium sheet.

Nom. - 25

Nom. - 25

Nom. - 25

Nom.

Nom.

Product Description
3HG 3HJ 3HF GC5 GC5(C) PER OBSS ED 0 fixed blade grille 15 fixed blade grille 45 fixed blade grille 12.5 x 12.5 x 12.5 eggcrate grille Eggcrate grille (core only) Perforated plate grille Allen key operated opposed blade damper Equalising deflector

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours or anodised finish available on request GC5/(C) Core is mill finished as standard

3HG

3HJ

3HF

Weights
Series 3 GC5 PER OBSS/ED 7.0 5.0 6.0 9.5 kg/m2 kg/m2 kg/m2 kg/m2 face face face face area area area area
Nom.

Nom. - 25

Nom. - 25

Sizes
Minimum Size - 100 x 100 Maximum Size - 1500 x 1200 (Maximum GC5 1200 x 1200)

Fixing Options
SF PFVS BSSBD CF RCHS BSSBP CRB AFHS VS AFCF AFVS RCCF

GC5(C) GC5 PER

Order Example
3HG/300x300/PPM9010/R25/SF/OBSS Type Nominal Width Nominal Height Finish Border Fixing Options 3HG 84%

Free Area for Series 3 Grilles 3HJ 84% 3HF 54% GC5 91% PER 51%

Please refer to pages 40-43 for full details of: Fixing Options Control Options Sub Frames Sizing Implications Border Options

Waterloo 1.0

14

Nom.

Nom.

Nom.

Exhaust Grilles
3HG 3HJ 3HF GC5 PER
Selection Example 400 x 300 Grille Handling 400 l/s
3HJ grille NC 24 Ps 15 PER grille NC 28 Ps 25 3HJ with open damper NC 30 Ps 25 PER with open damper NC 34 Ps 42

NR(Lp) and Static Pressure (Ps) Correction Factors for Grilles With an Open Damper
Grille Width Lp Addition (CL) Ps Multiplier (CP) 100+ 12 2.5 125+ 11 2.4 150+ 10 2.2 200+ 9 2.0 250+ 8 1.9 300+ 7 1.8 350+ 6 1.7 450+ 5 1.6 550+ 5 1.5 600+ 4 1.5 700+ 4 1.4 850+ >1000 4 1.3 3 1.2

Performance Nomogram
AIR FLOW RATE (l/s) NOMINAL WIDTH (mm) NOMINAL HEIGHT (mm)

Please refer to page 2 for used symbols, definitions and criteria.


200

100

5000 4000

3000 250
Velocity (m/s) 25mm from grille face NC Level 3HG 3HJ PER GC5 3HF 3HF Pressure Loss Ps (Pa) PER 3HG 3HJ GC5

PIVOT LINE

150

2000

300

200

1000 900 800 700 600

50 50 40 40 30 30 20 20 30 20
Pivot Line

10 100 50 40 5 4 3 2 10 1 5 2
Pivot Line

100 50 400 250

100 50

50 300 10 10 5 2 2 600 400 500 5

500 400

300

200

700 500 800

100

600 900

1000

50 1200 1000

25

1500

1200

Waterloo 1.0

15

Airline Linear Grilles


ALN ALM ALF ALG ALJ
Introduction
Waterloo airline linear grilles have been designed to satisfy air diffusion and engineering requirements as well as architectural specifications. Airline grilles may be used in modular or continuous situations for ceiling, sidewall, cill or bulkhead applications. The range is available with a wide variety of special options and fabrications to suit most project requirements. Grilles may be supplied with or without frames and borders - cores are represented with a suffix (C).

12.5

Product Description
ALN ALM ALF ALG ALJ ALG10 ALJ10 ALG2 ALJ2 ALN2 ALM2 2ALF 0 6mm thick blade, 12.5mm pitch 15 6mm thick blade, 12.5mm pitch 45 5mm thick blade, 12.5mm pitch 0 3mm thick blade, 12.5mm pitch 15 3mm thick blade, 12.5mm pitch 0 3mm thick blade, 10mm pitch 15 3mm thick blade, 10mm pitch As above with a rear set of adjustable blades As above with a rear set of adjustable blades As above with a rear set of adjustable blades As above with a rear set of adjustable blades 2 way cores are available on angled blade designs (Suffix M, F or J) OBSS Allen Key operated opposed blade damper ED Equalising deflector DT-2M Adjustable duct turn (Installed in duct) ALF-RB Reverse Border (Any blade can be specified)

12.5

Nom. - 3 12.5

Nom. - 25

Nom.

Nom.

Nom.

ALF

ALF-RB

ALF(C)

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours or anodised finish available on request Special 2 way cores are available for all angled blade configurations, i.e. 2ALF as shown below.

Weights
ALG Others OBSS/ED DT2M(G) 14 kg/m2 face area 10 kg/m2 face area 9.5 kg/m2 face area 9.0 kg/m2 face area

2ALF

ALF(2)

Sizes
Minimum size - 150 x 50mm Maximum single section of cores - 1500 x 800mm Refer to head office for borders upto 4 meters in one piece Continuous grilles are supplied in sections for butt jointing on site.

Fixing Options
SF ARCF BSSBD CF RCCF BSSBP VS CRB AFVS RCHS PFVS AFHS

Order Example ALG/1000x150/PPM9010/R25/SF/OBSS


Type Nominal Width Nominal Height Finish Border Fixing Option

The following fixings are not compatible with the ALF blade CRB RCHS AFHS BSSBD BSSBP - Not suitable for grilles with a rear blade or ALF blade. Please refer to pages 40-43 for full details of: Fixing Options Control Options. Sub Frames Sizing Implications Border Options

Waterloo 1.0

16

Airline Linear Grilles


ALN ALM ALF ALG ALJ
Free Area
Type Pitch
12.5 12.5 12.5
Nom. - 25

12.5

ALG 10mm 12.5mm 68% 74%

ALJ 68% 74%

ALF

ALM

ALN

Nom.

44%

49%

49%

ALG

ALM

ALN

ALJ
86 (Open)

ALG(2)

ALM(2)

ALN(2)

ALJ(2)

ALF(2) + OBSS

ALG Blade Blade Angle 0 Blade Thickness 3mm

ALM Blade Blade Angle 15 Blade Thickness 6mm

ALN Blade Blade Angle 0 Blade Thickness 6mm

ALJ Blade Blade Angle 15 Blade Thickness 3mm

ALF Blade Blade Angle 45 Blade Thickness 4mm

Curved ALG Grille

Example of Waterloos Bespoke Manufacturing Capability:


We at Waterloo pride ourselves on our ability to meet tough design requirements for bespoke products. If you dont see what you are looking for in the brochure, please call our head office on the phone number at the bottom of the page.

Waterloo 1.0

17

Airline Linear Grilles


ALN ALM ALF ALG ALJ
Correction Factors
Terminal Velocity Correction Factors
V t (m/s) Throw Multiplier

Notes:
0.3 x1.66 Where AL2 grilles are used multiply Ps x 3.0 and add 6dB to NC level. 2.5 +3 3 +5 Grille selections for sidewall and cill applications should be based on a minimum discharge velocity of 2m/s. For sidewall grilles that are to be mounted more than 0.2m from the ceiling, it is preferable to use a 15 blade format. For sidewall grilles mounted 0.5m or more below ceiling level the throw is reduced by 1/3. For grilles with OBSS opposed blade damper (open), multiply the pressure loss by 1.5 and add 3dB to the NC level.

0.6 x0.8

0.5 x1.0

0.4 x1.3

Grille Length Correction Factors


Length (m) Lp T 0.25 -6 x 0.9 0.5 -3 x 0.9 1.25 0 2 +2

x 1.0 x 1.0 x 1.1 x 1.1

Non-isothermal Jet Correction Factors


Differential Sidewall Throw Cill Throw 10C Cooling x 0.9 x 0.9 0C x 1.0 x 1.0 10C Warming x 1.1 x 1.1

Performance Nomogram (Supply)

AIR FLOW RATE (l/s/m)


1500

KEY THROW (m) VELOCITY (m/s) 25mm from grille face 40 30 NC LEVEL
13 10 40 8 7 6 5 4 100 50

ALN ALM ALG10 ALJ10 ALG ALJ

NOMINAL DUCT HEIGHT (mm)


50

1000 900 800 700 600 500 400

STATIC PRESSURE LOSS (Pa)

20

75

10
30 300 250 200 20

100

10 5

5 4

10 2 pivot line

150

150

100 90 80 70 60 50

throw

throw
200

500mm max CILL SIDEWALL

300

Waterloo 1.0

18

Airline Linear Grilles


ALN ALM ALF ALG ALJ
Selection Criteria
Performance data is derived from tests carried out in accordance with BS 4773 Pt I & Pt II and is based on isothermal conditions for a 1.25m long grille mounted 0.2m below a ceiling surface. Throw is the horizontal distance to where the envelope velocity equals 0.5m/s.

Selection Example 1250mm Long by 50mm Wide Grille Supplying 100 l/s/m
ALF PS = 65Pa ALN PS = 22Pa ALG 10 PS = 18Pa ALG PS = 16Pa NC35 NC24 NC27 NC24 ALF/OBSS PS = 98Pa ALN/OBSS PS = 33Pa NC43 NC32

ALG 10/OBSS PS = 27Pa NC35 ALG/OBSS PS = 24Pa NC32

Please refer to page 2 for used symbols, definitions and criteria.

Performance Nomogram (Exhaust)


AIR FLOW RATE (l/s/m)
1500

1000 900 800 700 600 500 400 300 250 200 150 ALG ALJ ALN ALM 50 40 30 20 10 100 90 80 70 60 50 40 30 25 20 15

VELOCITY (m/s) 25mm from grille face NC LEVEL


ALG 10 ALJ 10 50 40 30 20 10 50 40 30 20 10 Pivot line 1 10 5 1 1
200

STATIC PRESSURE LOSS (Pa)


ALF 10 8 7 6 5 4 3 2 ALF ALN ALM 200 100 200 100 50 10 5 10 5 10 5 50 ALG10 ALJ10 ALG ALJ 200 200 100 50 100 50

NOMINAL DUCT HEIGHT (mm)


50

75

100

1
150

0.5 Pivot line

300

10

Waterloo 1.0

19

Security Grilles
SG1 SG2 SG3
Introduction
The Waterloo SG series security grilles have been designed in conjunction with the prison service for supply and extract of air in places where security is a priority - from prison institutions, courts and police stations to secure buildings. Manufactured from 3mm thick mild steel plate, SG series grilles are available in three versions - SG1, SG2 and SG3 - able to meet ventilation needs in high, medium or low security applications. The series o ers rectangular or square size options from 100mm up to 600mm. Nom.W + 100 K

Nom.H + 100

Nom.W

K + 80

Product Description
SG1 SG2 High Security Grille With Rear Fixing Medium Security Grille With Face and Rear Fixing SG3 Low Security Grille With Face Fixing OBSS Allen Key Operated Opposed Blade Damper PB Plenum Box

SG1 + OBSS

Nom.W + 100 15

15

Nom. H + 100

Features
Low, Medium or High Security Applications Side or Top Entry Connections Available 3mm Perforated Faceplates

Nom.W K + 80

Finishes
Zintec coating as standard. PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request.

SG2 + OBSS

Nom.W + 50 12.5

90

Nom.H + 50 12.5

Perforations are 3mm diameter at a 5mm pitch Please note that security grilles with face x are not supplied with screws.

Nom.W

Nom. + 12

Speci cation of Perforations in Front Face

Nom.H

50

SG3 + OBSS

Order Example
SG1/300x300x150/PPM9006/OBSS
Type Nominal Width Nominal Height Depth Finish Control

Free Area
35%

Waterloo 1.0

20

Nom. + 156

Nom. + 16

Nom. + 8

Nom.H

Nom. + 156

Nom. + 82

Nom. + 8

Nom.H

Security Grilles
SG1 SG2 SG3
Selection Criteria
Throw data is based on a free jet under isothermal conditions and is presented for a terminal velocity of 0.5m/s. Jet throws to a terminal velocity of 0.25m/s can be obtained by applying a factor of 1.5. Noise data is presented in terms of sound power based NR levels and is valid for supply and exhaust applications

Selection Example SG1/300x300 for an Exhaust application


Air flow rate 200 l/s Jet throw 4.8m Pressure loss 18 Pa Noise level NR 20

Performance Nomogram
Nominal Grille Size
Width (mm) Height (mm)
100

Air flow rate l/s

800 700 600 500 450 400 Vt=0.5m/s 350 300 250 200 10
ple

Duct Air Velocity (m/s) Jet throw (m)


Pivot Line

Pivot Line 0.005

Static Pressure Loss (Pa)


EXHAUST

100 0.006 150

0.008 SUPPLY 0.01 200 150 0.015

Noise Level NRlw


50 40 30 20 2.0 4.0

Exam

8.0 6.0 5.0 4.0 3.0

150

70 50 30 20 10

70 50 30 20 10 5 250 0.04 0.03 0.02 200

250

300

100 90 80 70 60 50 45 40 35 30 25 20

2.0

1.0

1.0

0.5

400 300 0.05

0.5 500 400 0.08 0.1 600

500 0.15

15 600

10

Free Area (m2)

Waterloo 1.0

21

Air Transfer Grilles


NS DV NSNL
NSA

Introduction
Waterloo transfer grilles are suitable for mounting in doors, partitions and walls to allow ventilation air to pass between adjacent rooms. The NS series are small format grilles with a no-sight feature, the DV series are large format grilles for door ventilator applications. The range is available with a wide variety of frame and fixing options to suit various design needs.

NS
20

NSC

Nom. - 2 9.8

Nom. - 25

Nom. - 19

Nom. - 25

Nom.

Nom.

Product Description
NS NSA Core only grille for beading in place Framed no-sight grille with matching reverse frame NSC Framed no-sight grille without a matching reverse frame DV Core only door ventilator for bead fixing DVA Framed door ventilator with matching reverse frame DVC Framed door ventilator without a matching reverse frame NSNL Core only No Sight No Light grille for beading in place. NSNLA Framed NSNL grille with matching reverse frame. NSNLC Framed NSNL grille without matching reverse frame.

30 - 50

DVA DV
27.5

DVC

Nom. - 2 16.3

Nom. - 25

Nom. - 19

Nom. - 25

Features
Small, large or dark room formats to suit design requirements No sight (NS) option for room to room privacy Small, or large formats to suit design requirements Narrow core only for modern door systems (NS) Flange screw fixing provided Two border styles available

Nom.

30 - 50

Nom.

Finishes
NS/DV PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) NSNL PPG9005 (RAL 9005 Matt Black) Other colours or anodised finish available on request

NSNL
41

NSNLA

NSNLC

9.8

Nom. - 25

Nom. - 19

Nom. - 25

Nom.

NS DV
NSNL

16 kg/m2 face area 19 kg/m2 face area 29 kg/m2 face area

Sizes
Minimum size - 100 x 100mm Maximum single section - 1200 x 550mm
40 - 50

Order Example
NSA/300x300/PPM9010/R25/SF
Type Nominal Width Nominal Height Finish Border Fixing

Fixings
See page 41 for details
Suffix C Suffix A SF only PSF SF All others have no fixing (NF)

Nom.

Weights

Nom. - 2

Free Area
NS NSA NSC 41% DV DVA DVC 41% NSNL NSNLA NSNLC 34%

Waterloo 1.0

22

Nom.

Nom.

Nom.

Air Transfer Grilles


NS DV NSNL
Selection Criteria
NC LEVEL is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB for sound power Lw ref 1012W.

Selection Example 300 x 250 Grille Supplying 200 l/s


NS PS = 10Pa DV PS = 13Pa NSNL PS = 23Pa NC27 NC23 NC23

Performance Nomogram

AIR FLOW RATE (l/s)

NOMINAL DUCT WIDTH (mm)

NOMINAL DUCT HEIGHT (mm)


100

3000 200 2000 PIVOT LINE

1500

1000

150

500 400

NC LEVEL
NSNL NS DV 50 NS 5 4 3 40 40 2 30 30 20 20 1 Pivot line

STATIC PRESSURE LOSS Ps (Pa)


DV 150 100 50 150 100 50 NSNL

300

200

300

50

150 100 50

400

250

200

10 5

10 5 2 10 5 2 600 500

300

100

2 0.5 Pivot line

400

700 800 900 1000

500

50

600

20

Waterloo 1.0

23

Fire rated transfer grilles


WFV WFVG
Introduction
The Waterloo fire rated ventilators are suitable for 1 hour rated doors and partitions. The units, which satisfy BS 476 Part 8, incorporate intumescent elements which expand and carbonise when exposed to temperatures in excess of 150C, thereby sealing off the ventilation opening. The ventilators may be beaded directly into the door/partition opening or covered by optional steel grilles to suit aesthetic requirements. Tested and rated in accordance with BS 476 Part 8. Certificate number TRADA IT 245 WRCSI 37354. WFV units are constructed from hollow PVC extrusions enclosing PALUSOL 210 wire reinforced intumescent media. The extrusions are retained in a horizontal louvre pattern by reinforced vertical members and an enclosing frame system. W - 2 o/a 40

H - 2 o/a

Product Description
WFV Core only fire rated ventilator WFVG Fire rated ventilator complete with 2 matching steel grilles Note: Special assemblies using standard Waterloo aluminium grilles are available for partition arrangements

Beading

Features
1 hour fire rating to BS 476 Part 8 Available in 5 standard sizes Easy to install Attractive appearance Available as core only Available with covering steel grilles Suitable for door and partition mounting Special assemblies available for partitions incorporating standard Waterloo grilles Nominal size = Opening size

6mm Louvre

20 Pitch (Approx)

Finishes
WFV - Silver PVC Grilles - Stove enamel gloss white

Sizes
Width (W) and height (H) are nominal opening sizes

Type WFV

Type WFVG

Authority
Tested and Rated in accordance with BS 476 Part 8. Certificate Numbers TRADA IT 245 WRCSI 37354.

Installation
WFV cores should be fitted into a cleanly cut aperture with a maximum gap of 5mm around the frames; gaps larger than this should be filled with intumescent paste. The cores may be retained by screwing through the stack holes provided, or by using a bead frame. If supplied, the pressed steel cover grilles should be screw fixed through the frame holes provided.

Order Example WFVG/300/300/Gloss White


Type Nominal width Nominal height Finish (If applicable)

Nominal Size mm W x H 150 x 150 200 x 200 300 x 300 600 x 300 600 x 600

Overall Size mm 185 x 185 235 x 235 340 x 340 645 x 340 645 x 645

Weight kg 0.45 0.80 1.80 3.60 7.20

Free Area Measured W FV 56% 58% 59% 60% 61%

Waterloo 1.0

24

Overall Size

Fire rated transfer grilles


WFV WFVG
Selection Criteria
Performance is based on a room to room application with the WFV mounted in a partition or door. Q = Air flow rate through the ventilator at the stated differential pressure. P (Differential pressure) = static pressure difference across the assembly. NR Level = Noise Rating Peak level on NR curves based on sound power level ref. 10 -12 W less 8dB room absorption.

Selection Example
Select a WFV unit to handle 300 l/s with a maximum pressure loss of 25 Pa and Noise level of NR 30. Enter graph at Q = 300 l/s and extend upwards until a standard size may be selected which satisfies pressure and noise level specified. Size 300 x 300 WFV selected: Pressure Drop 22 Pa NR Level = NR 24

Performance graph
100 150 x 150 200 x 200 300 x 300

WFV
NR25 NR20

NR35 NR30

WFV
600 x 300

P = Differential Pressure (Pa)

(Ventilator only)

50 40 30 20

600 x 600 10

50

100

200

300

400

500

1000

Q = Air Flow Rate (l/s)

100

150 x 150

200 x 200

300 x 300

WFVG
NR40

WFVG
(Ventilator plus cover grilles)
600 x 300

P = Differential Pressure (Pa)

50 40

NR35 NR30

30 NR25 20 NR20 10 600 x 600

10

20

30

40 50

100

200

300 400 500

Q = Air Flow Rate (l/s)

Waterloo 1.0

25

Acoustic transfer grilles


DSRX
Introduction
The Waterloo series DSRX have been developed for use in partitions and doors where a reduction in noise transfer or cross-talk from one space to another is required, as well as ventilation air transfer. The DSRX are manufactured from high quality aluminium extrusions with channel section cores forming a labyrinth airway lined internally with acoustic damping media. The cores are retained within a flanged frame which is fitted with a sealing gasket. Units are supplied with fixed border and matching adjustable rear border frame. DSRX units will only provide acoustic isolation improvements over that of a clear aperture. DSRX units may be used in series to increase transmission loss.

38

Nominal W x H + 51

Nominal W x H - 25

60 4.5 75 142 Minimum 38 20 60

20

40

Product Description
DSRX Acoustic transfer grille with rear matching frame

Features
Suitable for partition, wall or door mounting Easy to install Fits most standard doors and partitions Easy to clean Modular sizes

DSRX

Nominal W x H

20

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 Matt White) PPG9010 (RAL 9010 Gloss White) Other colours available on request
Min 40 * Variable

DSRX back-to-back (2 No. required)

Max 100

Sizes
Width 325 minimum to 1025 maximum in 100mm increments. Height 125 minimum to 1005 maximum in 80mm increments.

75

Door / Partition mounting 40 - 100mm thick

Order Example
* Note: 30mm protrusion with minimum depth of door

DSRX/425/285/PPM9010
Nominal width Nominal height Finish

Waterloo 1.0

26

Acoustic Transfer Grilles


DSRX
Spectrum Correction (Add to LwNR)
Frequency (Hz) 125 250 500 +1 +4 +3 1K 0 2K 4K -10 -16

Selection Example
Select a DSRX grille to handle 70 l/s when mounted within a 100mm partition and a maximum permitted pressure loss of 20 Pa.

From Nomogram Select Size 425 x 365


Pressure loss = 16Pa (DSRX) LwNR 26 Sound Power Spectrum is 1K 29 2K 26 4K 16 10

Freq (Hz)125 250 500

Performance Nomogram TRANSMISSION LOSS


TRANSMISSION LOSS (dB) 30 25 20 15 10 5 63 125 250 500 1K 2K

SWL (dB) 27

30

NOMINAL DUCT HEIGHT (mm)

125

AIR FLOW RATE (l/s)

2x

DS

RX

DSRX

800 700 600 500 400 300


REGENERATED NOISE L W NR

FREQUENCY (Hz)
NOMINAL DUCT WIDTH (mm)

Pivot Line

1000 900

4K

8K

205

325 285

PRESSURE LOSS Ps (Pa)

200

2 x DSRX DSRX 50 80 40 40 30 40 20
Pivot Line

425 365 525 445

20 10

100 90 80 70 60 50 40 30

20 10

625 525 725 605 825 685 925 1025 765 845 925 1005

Waterloo 1.0

27

Sidewall Grilles
WPT
Introduction
The Waterloo WPT grille is a sidewall grille made with an aluminium frame and a steel perforated plate. The perforations on the plate are angled to supply air in a fixed direction. The standard plenum box wall mounting that comes with a supply grille, is angled in order that the air stream is trained vertically down the wall and along the floor. This floods the floor with fresh cool air. As the air heats up it rises and is extracted from the top of the room (This system is sometimes refered to as displacement ventilation). When used for extract the grille should be mounted high in the room and flush with the wall. This grille provides a good air distribution with low velocities and low sound levels. With minimal air mixing.
Nom. W - 25 Nom. W + 25 Nom. W + 35

75

Product Description
WPT-T WPT-R Supply Grill (including plenum)
125 175

Extract Grill (including AF-subframe)


125 100

Features
High levels of comfort due to low velocities No plenum assembly in the duct is necessary Low noise levels Minimal mixing of the air

WPT-T

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Other colours available on request

Weights
WPT-T WPT-R 15.0 kg/m2 face area 14.5 kg/m2 face area

Sizes
Nom. W 225 to 925 mm in 100mm increments Nom. H = 125 mm
Nom. W - 25 Nom. W + 25

Fixings
WPT-T WPT-R Fixing plate AFCF (AF-subframe + clipfixing)

Order Example WPT-T/425x125/PPM9010


Type Supply/Exhaust Nominal Width Nominal Height Finish

150

28

Free Area 35%

34

WPT-R

Waterloo 1.0

28

125

Sidewall Grilles
WPT
Selection Criteria
NC LEVEL is sound pressure level /Noise Criteria Curve based on a room absorption of 8dB for sound power Lw ref 1012W.

Selection Example WPT-T/425x125


Air Volume 21 l/s Throw on floor 2.6 m Pressure Drop 6 Pa Noise Level < NR 20

Performance Table
WPT
m3/h 50 l/s I 14 Ps Lp I 75 21 Ps Lp I 100 28 Ps Lp I 125 35 Ps Lp I 150 42 Ps Lp I 200 56 Ps Lp I 250 69 Ps Lp I 300 83 Ps Lp 3.0 14 4.0 26 26 3.0 12 3.5 20 35 2.6 6 3.2 12 3.5 18 4.0 26 27 2.4 4 3.0 9 3.2 14 4.0 20 2.2 3 2.4 6 2.6 9 3.0 13 4.0 22 31 2.0 3 2.2 5 2.4 8 3.0 12 3.5 19 4.0 31 34 1.6 2 2.0 4 2.2 6 2.6 8 3.2 14 4.0 22 33 1.6 4 2.0 5 2.2 7 3.0 12 3.5 18 29 4.0 26 35

Supply
225x125 325x125 425x125 525x125 625x125 725x125 825x125 925x125

Ceiling height

Waterloo 1.0

29

2.4m

Comfort Area vr = .... m/s

Light Duty Floor Grilles


AFG
Introduction
The Waterloo light duty floor grille has been specifically designed for cill and floor applications where light foot traffic will be experienced. In addition, the AFG is available with any of the airline cores which then makes the product ideal for sidewall applications where reinforced recessed frames are necessary. The AFG is constructed from aluminium alloy extrusions with tube type cores and fully welded frames. The core is supported by rear reinforcing bars. Nom. H + 12 3 12.5 3 19 OBSS Nom. H - 7 Nom. H Nom. W + 12 3 3 Nom. W - 7 Nom. W

44.5 35

Product Description
AFG OBSS ED PB Light duty floor grille Allen key operated opposed blade damper Equalising deflector Plenum box

Features
Removable cores for easy access and cleaning Core retaining clips for security/safety Various core styles Recessed frame detail Robust enough for light foot traffic on floors or cills Suitable for low level sidewall applications Solid extruded blades

Finishes
PPM9006 (RAL 9006 Matt Silver) PPM9010 (RAL 9010 20% Gloss White) PPG9010 (RAL 9010 Gloss White) Nylon Decanol Other colours available on request

Weights
12.0kg/m2 face area

Sizes
Minimum size - 150 x 50 Maximum size - 1500 x 200 Height and Width increments: 50mm

Order Example AFG/1500x150/PPM9010


Type Nominal Width Nominal Height Finish

Free Area
49%

Waterloo 1.0

30

87.5 (OBSS open)

Light Duty Floor Grilles


AFG
Selection Criteria
Performance data is based on isothermal conditions for a 1.25m long grille mounted adjacent to a wall surface. NC values are equal to the peak sound power level on NC curves less 8dB allowance for room absorption (SWL re 10-12W). Throw is the distance to where the envelope velocity equals 0.5m/s. For grilles mounted more than 500mm from a wall reduce the throw by 1/3. Exhaust Air Correction Factors
Static pressure loss = supply pressure x 1.2 NC level = supply NC + 4dB Terminal Velocity Correction Factors Vt (m/s) 0.6 Throw multiplier 0.8 0.5 1.0 0.4 1.3 0.3 1.66

Selection Example AFG/2000/50


Air Volume 150 I/s/m Throw = 11.2m NC level = NC30 +2dB length correction = NC32 PS = 42 Pa

Non-isothermal Jet Correction Factors


Differential Sidewall throw Cill throw 10C cooling 0.9 0.9 0C 1.0 1.0 10C heating 1.0 1.1

Distributed load (typically foot traffic)


Grille height (mm) Max. static load (kg) Max. shock load (kg) 100 960 384 200 480 192

Safety factors: Static load = 2, Shock load = 5

Grille Length Correction Factors


Length (m) NC addition Throw x 0.25 0.5 1.25 2 -6 -3 0 +2 0.9 0.9 2.5 +3 3 +5

Point load
(25x25mm point load over any 2 blades)

Grille height (mm) Max. static load (kg) Max. shock load (kg)

up to 200 105 42

1.0 1.0 1.1 1.1

Performance Nomogram
AIR FLOW RATE (l/s/m) 1000 900 800 700 600 500 20 400 NC LEVEL 40 10 30 20 5 4 100 90 80 70 60 50 1 40 3
Pivot Line

NOMINAL DUCT HEIGHT (mm) THROW (m)


(Vt = 0.5 m/s)

40 30

VELOCITY (m/s) 25mm from grille face STATIC PRESSURE LOSS (Pa) 13 10 8 7 6 5 4 3 10 5 150 250 200 150 100 50 100 75 50

300 250 200

150

10 5

200

Throw

30

20

Waterloo 1.0

31

Heavy Duty Floor Grilles


HDFG
Introduction
The Waterloo HDFG heavy duty oor grille has been designed for commercial and industrial applications where heavy foot tra c is experienced. The S type is a 600mm tile replacement and L type is for linear applications; both are available with a recessed border style. This improved design is suitable for use with most types of raised oor pedestal system.

HDFG/L
Nom. L

Product description
HDFG-XS HDFG-S HDFG-L OBSS BL

Extra heavy duty tile replacement with steel subframe Standard tile replacement Linear Opposed blade damper Blanking plate

Single unit Nom. L

Features
HDFG-XS tested to PSA MOB PF2 PS/SPU speci cation dated March 1992 Reversible core (0 or 15 discharge) Suitable for most pedestal ooring systems Facility for on site blanking of linear version Recessed border style Border alignment facility on linear version End section Nom. L

Finish
Mill nish as standard, powder or nylonic coating options available on request.

Advantages
Integrated design features - enabling tile and linear grille combinations for aesthetic continuity Improved additional strength design Easy Drop in installation Convenient damper adjustment Intermediate section Nom. W

Weights
28 18.0 kg/m
2

face area 100

Sizes
HDFG-S & XS 600 x 600mm HDFG-L Length - maximum single section 1000mm Width - maximum 600mm minimum 100mm

Nom.W - 40

Order Example
HDFG-L/1000x300/MILL/OBSS/BL Type Section Length Section Width Finish Damper Blanking Plate

HDFG-L + OBSS / / HDFG-L + BL


2 alignment strips supplied with each section for site xing .

Free Area
47%

Wa te rlo o 1 . 0

32

59

66

Nom. W

Heavy Duty Floor Grilles


HDFG
Selection Example HDFG-L/1200x200
Air Volume 250 I/s/m Throw 3.6 m Pressure Drop 7 Pa Noise Level NR 22

Please refer to page 2 for used symbols, definitions and criteria.

Spectrum Corrections
Frequency (Hz) 125 250 500 Supply +9 +13 +12 Exhaust +9 +11 +12 Extract Nom.Grille Width (mm) HDFG-S
m3/h 1080 6 2 <20 <20 1440 13 4 2 27 <20 <20 1800 20 6 3 34 <20 <20 2160 28 39 37 43 50 47 1 9 4 2 23 <20 <20 13 6 3 600 1 500 400 1 l/s T 300 Ps Lp T Ps Lp T Ps Lp T Ps Lp

Performance Tables
HDFG-L
m3/h/m l/s/m T 180 50 Ps Lp T 270 75 Ps Lp T 360 100 Ps Lp T 450 125 Ps Lp T 540 150 Ps Lp T 630 175 Ps Lp T 720 200 Ps Lp T 900 250 Ps Lp T 1080 300 Ps Lp T 1440 400 Ps Lp T 2160 600 Ps Lp T 2880 800 Ps Lp T 3600 1000 Ps Lp

1k +6 +0

2k +2 -5

4k -2 -11

Supply Nom.Grille Width (mm)

100 150 200 300 450 600 100 150 200 300 450 600 1.8 2 <20 2.7 1.5 4 1 <20 <20 3.6 2.3 1.3 7 3 22 <20 <20 4.4 2.7 1.8 12 5 16 32 22 35 6 29 39 4 2 29 <20 <20 3.2 2.3 1.3 6 3 20 <20 <20 7 4.2 10 4 3 6 2 2 3 17 32 28 38 1 2 2 39 45 17 6 3 31 <20 <20 30 43 13 6 37 43 9 4 21 <20 13 5 2 3 <20

600x600 Tile Replacement


Supply 2.3 3 <20 3 6 <20 3.6 8 22 4.3 11 28 18 35 12 27 8 <20 5 <20 Return

5.5 3.6 2.7 1.7 22 <20 <20 27 <20 <20

Load Deflection Characteristics


HDFG-XS Floor Grille 600 x 600 Tested to PSA MOB PF2 PS/SPU specification dated March 1992 HDFG-S Floor Grille 600 x 600 Load applied on grille centre line distributed over 25mm x 25mm point between subframe supports. Maximum recommended point load 400kg.
2

26 <20 <20 4.9 3.6 2.5 1.3 16 32 22 36 32 45 7 4 22 <20 <20 11 4 4 10 5 17 32 30 39 47 44 2 2.7 4

27 <20 <20 18 6 3

5.5 4.3 2.7 1.8 1.2 27 <20 <20 <20 22 36 7 44 43 32 <20 <20 <20

7.3 5.7

26 <20 <20 3.6 2.7 7 4 22 <20 13 30 21 37 7 20 11 28

HDFG-L Floor Grille 300mm Wide Load applied on grille centre line distributed over 25mm x 25mm point between blade supports. Maximum recommended point load 360kg. HDFG-S Floor Grille 600mm Wide Load applied on grille centre line distributed over 25mm x 25mm point between blade supports. Maximum recommended point load 180kg.

27 <20 22 37 36 45 10 25 18 35

6.2 4.5 3.4

7.2 5.5 4.3

Waterloo 1.0

33

Heavy Duty Floor Grilles


HDFG
HDFG-S - 600x600
599 x 599

97 64

505
OBSS (Optional)

Pedestal Head

Steel Subframe

595 x 595

595

Order Example
HDFG-S/600x600/MILL/OBSS
Type Nominal Width Nominal Height Finish Option

Where possible, full details of pedestal system & finished tile thickness should be provided with order Steel Subframe Pedestal Head

Waterloo 1.0

34

599 x 599

Min. 30

Heavy Duty Floor Grilles


HDFG
HDFG-L - Linear Corner Sections

ng

le

300
15 0

Note:
Orders for corner sections will be made to the configuration shown with a 90 angle. Requirements for angles other than 90 should be identified with a customer drawing or site template. Orders for installations which include corner sections should clearly identify any preference for core discharge angle relative to the layout (0 or 15). Unless specified otherwise, corners will be manufactured for 0 deflection.

Order Example
HDFG-L/300/90/300/100/MILL Type Length 1 Corner Angle Length 2 Section Width (W) Finish

Waterloo 1.0

35

300

Aircell Polymer Grilles


S, D, G, A, T, E
Introduction
The Aircell range of supply & exhaust grilles are injection moulded in self coloured white, Class 0 fire rated engineering polymer. Aircell S (Single deflection) and Aircell D (Double deflection) have individually adjustable vanes on a 19mm pitch to allow jet spread or deflection to be set within 45 of the duct axis. Aircell G (0 fixed blade) has horizontal 0 fixed blades on a 20mm pitch. Aircell A (45 fixed blade) can be used as a wall or ceiling mounted grille, or alternatively they can be supplied with a reduced stack for use as a door mounted transfer grille. (see Aircell T ) Aircell T (45 fixed blade) are supplied as a pair of reduced stack Aircell A grilles for door mounting. Aircell E (Eggcrate) has a lattice core with a 13mm pitch and is suitable for all exhaust applications. All types are available in 5 standard sizes, plus an E600 which has been specifically designed for full ceiling tile replacement. The E600 has an overall size of 596mm x 596mm and for the North American market 603mm x 603mm overall ( E603 ) and for the German Market, 621mm x 621mm overall ( E621 ). Waterloos Aircell products can be used in any air distribution system where temperatures do not exceed 50C. 33 5 46.5 5 33 49

Nom. + 41 Nom. - 25 19

Nom. + 41 Nom. - 25 19

Aircell S

Nom.

Aircell D
46.5 30

5 33

46.5 30 33

Product Description
Aircell S Aircell D Aircell G Aircell A Aircell T Aircell E GO N OBSS NR Single deflection grille Double deflection grille 0 fixed blade grille 45 fixed blade grille 45 fixed blade grilles for door transfer 13mm Eggcrate grille Opposed blade damper in black engineering polymer Neck reducer in black engineering polymer Aluminium opposed blade damper for E600 Steel neck reducer for E600 Nom. + 41 Nom. - 25 20 Nom. + 41 Nom. - 25 19

Features
Class 0 fire rating Consistent high quality Moulded in easy to clean engineering polymer

Nom.

Aircell G
Weights S D G A T E GO 7.0 Kg/m 7.2 Kg/m 7.7 Kg/m 10.2 Kg/m 7.7 Kg/m 10.9 Kg/m 7.6 Kg/m 6.4 Kg/m
2 2 2 2

Aircell A

Fixing
Screw through face flange

min.40 5 33 33 5

46.5 30

Finishes
Self coloured white

Advantages
Good size range Standard size neck reducers No visible mitres Available off the shelf

Nom. + 41 Nom. - 25 19

Nom. + 41 Nom. - 25 12.5

2 2 2 2

Nom.

Order Example
Aircell A/300x300/GO/N Grille Type Nominal Width Nominal Height Option 1 Option 2

WxH
150 x 150 200 x 200 250 x 250 300 x 150 300 x 300

Aircell T

Aircell E

Waterloo 1.0

36

Nom.

Nom.

Nom.

Aircell Polymer Grilles


S, D, G, A, T, E
Selection Example Aircell D-250x250
with straight blades
Air Volume 250 I/s Throw 13.0 m Pressure Drop 15 Pa Noise Level NR 24

Please refer to page 2 for used symbols, definitions and criteria.

Aircell D

Aircell G

45 Blade Angle Correction Factors For S & D Throw multiplier 0.55 NR addition +8dB Pa multiplier 3.1

Performance Tables
Aircell G
150 x 150 Ps Lp 180 50 Ps Lp 360 100 Ps Lp 540 150 Ps Lp 720 200 Ps Lp 900 250 Ps Lp 1080 300 Ps Lp 1440 400 Ps Lp

Extract
200 x 200 250 x 250 300 x 150 300 x 300

Aircell S Aircell D
m3/h l/s T 150 x 150 2.1 1 <20 4.7 3 <20 8.5 14 29 14 29 41 18 52 49 3.4 2

Supply
200 x 200 250 x 250 300 x 150 300 x 300

m3/h

l/s

90

25

2 <20 10 <20 39 28 90 37

1 <20 3 <20 13 23 30 33 53 40 85 46 1 <20 5 <20 10 14 18 21 29 27 42 31 72 39 3 <20 10 <20 23 25 40 31 63 36 90 40 2 <20 5 13 9 20 15 24 22 28 40 34

90

25

Ps Lp T

2.6 1 <20 5.1 3 <20 7.7 6 <20 10 10 17 13 15 24 15 21 29 20 36 38

2.9 1 <20 6.0 6 <20 9.4 12 20 12 21 28 15 32 35 18 45 40 4.3 1 <20 6.4 2 <20 9 3 <20 10 5 <20 13 7 18 17 12 25

180

50

Ps Lp T

<20 6.4 8 <20 9.4 18 21 12 31 30 16 48 37 20 66 42

360

100

Ps Lp T

540

150

Ps Lp T

720

200

Ps Lp T

900

250

Ps Lp T

1080

300

Ps Lp T

1440

400

Ps Lp

Please note that when using the N series neck reducer, air volumes must not exceed the following guidelines. Grille WxH 150 x 150 200 x 200 250 x 250 300 x 150 300 x 300
Spigot D

Free Area
150 200 250 300 300 x x x x x 150 200 250 150 300 S D G 49% 53% 58% 53% 59% 49% 53% 58% 53% 59% 58% 60% 64% 62% 67%

97 147 197 97 247

Maximum Volume l/s m3/h 126 35 252 468 126 684 70 130 35 190

Waterloo 1.0

37

Aircell Polymer Grilles


S, D, G, A, T, E
Selection Criteria
Ceiling height 2.7m L pNR is sound pressure level/Noise Criteria Curve based on a room absorption of 8dB

Selection Example Aircell A-200x200


Air Volume 50 I/s Pressure Drop 15 Pa Noise Level NR 28

Aircell A

Aircell E

Performance Tables
Aircell A
m3/h l/s 150 x 150 Ps Lp 180 50 Ps Lp 360 100 Ps Lp 540 150 Ps Lp 720 200 Ps Lp 900 250 Ps Lp 10 21 40 35

Return
200 x 200 4 15 15 28 57 42 250 300 300 x x x 250 150 300 2 2 m3/h

Aircell E
l/s 150 x 150 Ps Lp 3 <20 11 20 25 31 45 39 70 45 180 50 Ps Lp 360 100 Ps Lp 540 150 Ps Lp 720 200 Ps Lp 900 250 Ps Lp 2 <20 10 <20 40 33 3 <20 11 <20 26 27 45 36 72 44 200 x 200

Return
250 300 300 x x x 250 150 300 600 x 600

90

25

90

25

<20 <20 6 <20 24 28 50 39 10 25 39 38 88 46

2 <20 5 10 2

<20 <20 <20 11 <20 19 23 30 31 22 27 39 36 62 43 5 <20 9 <20 14 16

For performance of the Aircell T series, please multiply the above pressure loss by 2 and add 3db to the NR level.

1080

300

Ps Lp

42 38 74 48

88 49

20 23 35 35 55 44 4
<20

1440

400

Ps Lp

1800

500

Ps Lp

Free Area
150 200 250 300 300 600 x x x x x x 150 200 250 150 300 600 A T E 32% 30% 37% 33% 36% 32% 30% 37% 33% 36% -

2700

750

Ps Lp

8
<20

3600

1000

Ps Lp

14 22 21 31 30 39

4500

1250

Ps Lp

44% 50% 51% 49% 53% 56% 5400 1500


Ps Lp

Waterloo 1.0

38

Aircell Polymer Grilles


S, D, G, A, T, E
Accessories
80

Aircell GO Opposed Blade Damper Aircell GO series opposed blade dampers are manufactured from injection moulded components in self coloured black engineering polymer. Adjustable through the grille face, the damper can be clipped directly onto the grille without fixings.
Nom. - 16 Nom.

Aircell N Neck Reducer Aircell N series neck reducers are injection moulded in self coloured black engineering polymer. The units are available in five sizes to suit the grille range and are designed to snap fit over the opposed blade damper or directly onto the grille stack. All reducers have standard size circular spigots related to the grille height (see dimensional details below). Please note that when using the N series neck reducer, air volumes must not exceed the following guidelines. Grille WxH 150 x 150 200 x 200 250 x 250 300 x 150 300 x 300
Spigot D

Aircell A + GO

147 197 97 247

252 468 126 684

70 130 35 190

OBSS damper and NR neck reducer for E600 series The OBSS aluminium opposed blade damper and NR steel neck reducer are available for the E600 series to allow volume control and circular duct connection directly onto the E600 grille. Please state spigot size required when ordering.
D (315

50 162.5

Aircell G + GO + N

/ 400)

102

50

13

578 x 578 587 x 587 595 x 595

E600 + OBSS + NR

Waterloo 1.0

39

97

Nom. - 8

Maximum Volume l/s m3/h 126 35

Grille Plenum Chambers


Introduction
Correct selection and sizing of distribution plenum chambers is critical because grille air resistance is very low relative to the distribution ductwork resistance. It is therefore recommended that whenever possible grilles are served by low velocity stub ducts from branch ducting systems fitted with correct balancing controls. Where it is necessary to specify and use grille plenums a generous allowance for commissioned noise generation should be made.

Product Description
PBG PBG/LL PBLG PBLG/LL PBSG Individual grille plenum Low line grille plenum Linear grille plenum Low line linear grille plenum Security grille plenum PBLG/LL - Top entry Low-line linear grille plenum box.

Spigot Options
SE TE 1CC 1RC 1FO Side entry Top entry 1- circular connection 1- rectangular/square connection 1- flat oval connection

PBLG - Side entry Linear grille plenum box.

Features
Plated steel with stiched seam joints. Standard circular connection diameters :97, 122, 157, 197, 247, 312 and 397 Available with circular, square,rectangular or flat oval spigots in either top or side entry applications Standard or Lo-line configurations Optional 6mm internal thermal/acoustic lining PBG - Side entry grille plenum box.

FDC
Cord operated flap damper for mounting within circular spigots to plenum chambers. The cord should be fed through the air terminal device ready for commissioning.

FDQ
Flap damper with external quadrant control for mounting within circular spigots to plenum chambers. The quadrant is accessible from outside the duct and the damper can be locked in any position.

OBCO
Cord operated opposed blade damper for installation within square or rectangular spigots to plenum chambers. The cord should be fed through the air terminal device ready for commissioning.

OBSS / ED
Standard opposed blade damper for diffuser or duct mounting. Adjustable by screwdriver inside the duct or through the face of the air terminal device. The ED is an individually adjustable blade device for equalising airflow across the diffuser.

Waterloo 1.0

40

Controls and Fixing Options


Fixing Options
7.5

RCCF
15 Min. (T32) 30 Min. (T48)

SF

AFCF

CF RCHS AFHS

OBSS

50 (T32) 65 (T48)

CRB

13 (T32) 29 (T48)

AFVS

PFVS

23 (T32) 39 (T48)

VS

20 (T32) 35 (T48)

10 5 Min. 40 Max.

BSSBD

BSSBP

Overall Grille Sizes


Grille Grille Grille Grille Grille with with with with with R16 R25 R32 RC PF = = = = = Nominal Nominal Nominal Nominal Nominal W/H W/H W/H W/H W/H + + + + + 7mm 25mm 39mm 39mm 21mm Note: AF en RC subframes can be made to a maximum size of 800mm in any direction in one piece, for sizes above that we supply in parts for assembly on site by others.

Standard Frames
RC
16 32/48 25 32/48 32 32/48

Sub Frames
PF AF

R16

R25

R32
RCCF RCHS PFVS AFCF AFHS AFVS

Waterloo 1.0

41

Controls and Fixing Options


Control Options - Grille Mounted

OBSS - Opposed Blade Damper (Volume Control Damper- Capable of Shut Off)

Correction for Grille + Damper


Supply 0 spread Supply 45 spread Exhaust NR + 2 NR + 2 NR + 2 Ps x 1.3 Ps x 1.1 Ps x 1.2

ED - Equalising Deflector (Directional Blades Incapable of Shut Off)

DT-2M - Duct Fitted The hinged strip is used to calibrate the amount of air desired, by altering the angle of the blades and therefore altering the amount of dissruption to the airflow.

Waterloo 1.0

42

Technical Information
Basis of Throw
Unless noted differently on the individual supply grille performance information all Throw performance data is based on isothermal supply air conditions, to a terminal velocity (vt), in the center of the jet, of 0.5 m/s. See tables below for other conditions. Throw Throw vr vr

Remark:

Cill

300mm max

Sidewall

If the distance between grille and ceiling is more than 300 mm, the throw will be reduced by 30%.

Jet Temperature Decay Characteristics


The following graph indicates the jet residual temperature at various throw distances. Given throw = x (m) and supply air differential = Dto Calculate Ac = Grille Area (m2) Calculate x/ Ac Enter graph at required value x/ Ac Exit graph at value Dtx/Dto Calculate D tx = D to x (D tx/D to) D tx = Residual temperature differential (C) 1.0 0.8 0.6
TY P

Working Example for Temperature Decay Calculations 1H/300x150/R25/SF


Supply Air Temp = 18 C Room Temp DT0 Air Volume = 20 C = 2 C = 200 l/s

From Performance data (Page 5) Throw = 8.32 m x/ Ac = 8.32/ (0.3x0.15) = 39.22


IC AL GR TC ILLE G RIL LE

D tx D to eg. 0.1875

Therefore DTx = 0.375 C and the air temperature at maximum throw (8.32 m) is = 19.6 (19.625) C

0.4 0.2 0

10

20 30 x/ Ac

40 50 eg. 39.22

Throttled Damper Factors


PR = Ps (Grille) / Ps (Duct) 4 3 2 1 0 5 10 15 20 25 PR = Ps (Grille) / Ps (Duct) SUPPLY

Example of Throtled Damper Factor Handling


Consider a Supply Grille with Damper PS (Grille) = 50 Pa PS (Duct) PR = 2.5 Therefore addition is = 13.5 Assume that we are using the same grille as in the Temperature Decay Calculation (above); From the Performance data on page 5, NR = 25 + 13.5 = NR 38.5 = 20 Pa

NR addition EXHAUST

5 4 3 2

5 10 NR addition

Waterloo 1.0

43

Waterloo Product Range


G R ILL E S
A complete range of products suitable for all wall, ceiling and made from aluminium, and have a range of applications. Most grilles are ed or moveable blades designed to give

performance whilst remaining aesthetically pleasing to the eye. Grilles are made to customer sizes and colours (PPM/G); standard colour is PPM9010 (20% Gloss White). This range is complemented by the Aircell range of polymer Grilles and Di users.

DI FFUS E RS
A complete range of products designed to be installed in various ceiling systems. Most di users are made from aluminium, and can be ordered with or without plenum chambers for easy connection to duct work. Di users can be ordered in customer range of polymer Grilles and Di users. (PPM/G) colours; standard colour is PPM 9010 (20% Gloss White). This range is complemented by the Aircell

ACT IVE A N D PASS IVE CHILLED BEAM S


The quality range of high output active beams, used for ventilated heating and cooling applications. These units have 4 pipe coils to allow heating and cooling circuits to run simultaneously, giving constant and responsive control. The design allows a large optimum capacity, and also allows the customer to specify the nozzle type and pitch for individual circumstances. Active beams are made from steel to a large range of customer are suitable for various di erent ceiling systems. Standard (PPM/G) colours are available on request. sizes and as such is PPM 9010, however other

AIR VOLUME CONTR O L DAM P ERS


A complete range of pressure independent Variable Air Volume and Constant air Volume dampers. Most volume dampers are regulated with an electronic motor and sensors, and are calibrated to customer before delivery. The constant air volume damper requires no power source as it is controlled via a mechanical device it is also calibrated before delivery. All volume dampers are made from Zintec plate and all units can be ordered with a single or double (with insulation) skin.

EXTE RNAL LOUV RES


A quality range of products for external wall applications. Made from aluminium, with birdscreen or insect screen options. All louvres are made to customer spe colours; standard colour is PPM 9006 ed sizes and (PPM/G)

DISPLACEMENT

design.

Waterloo Group Limited Waterloo Air Products plc


Mills Road, Aylesford Maidstone, Kent ME20 7NB Tel: +44 (0)1622 717861 Fax: +44 (0)1622 710648 email: mail@waterloo.co.uk internet: www.waterloo.co.uk Hyde Park House, Cartright Street, Newton Hyde. SK14 4EH Tel: +44 (0)161 367 1264 Fax: +44 (0)161 367 1262 email: mail@waterloo.co.uk internet: www.waterloo.co.uk

Waterloo BV
Postbus 28, 7450 AA HOLTEN Ondernemersweg 2, 7451 PK HOLTEN Tel: +31 (0) 548 374 374 Fax: +31 (0) 548 364 165 email: verkoop@waterloo.nl internet: www.waterloo.nl

Waterloo Klimatechnik
Kaiserwerther Strae 115 D-40880 Ratingen Tel: +49 (0) 21 04 - 50 70 86 Fax: +49 (0) 21 04 - 50 70 87 Mobil: +49 (0) 173 - 2 15 64 59 email: info@waterloo-klimatechnik.de internet: www.waterloo-klimatechnik.de

Waterloo Araulique
La Grande Arche Paroi Nord F-92044 Paris La Dfense cedex Tel: +33 (0)140 90 30 44 Fax: +33 (0)140 90 31 01 email: ventes@waterloo-aeraulique.eu internet: www.waterloo-aeraulique.eu

Waterloo Switzerland
Zugerstrasse 162 CH-8820 Wdenswil Tel: +41 (0) 43 833 20 20 Fax: +41 (0) 43 833 20 21 email: waterloo@comfosystems.ch internet: www.waterloo-klimatechnik.ch

NOVEMBER 2009

You might also like