Samsung Air
Samsung Air
Samsung Air
INDOOR UNIT
SH12VCD SH09VCD
OUTDOOR UNIT
SH12VCDX SH09VCDX
SERVICE
AIR CONDITIONER
Manual
CONTENTS 1. Precautions 2. Product Specifications 3. Operating Instructions and Installation 4. Disassembly and Reassembly 5. Troubleshooting 6. Exploded Views and Parts List 7. PCB Diagrams 8. Wiring Diagrams
1. Precautions
1. Warning: Prior to repair, disconnect the power cord from the circuit breaker. 2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.) 3. Use the proper tools: Use the proper tools and test equipment, and know how to use them. Using defective tools or test equipment may cause problems later-intermittent contact, for example. 4. Power Cord: Prior to repair, check the power cord and replace it if necessary. 5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire. 6. After completing repairs and reassembly, check the insulation resistance. Procedure: Prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megaohms. 7. Make sure that the grounds are adequate. 8. Make sure that the installation conditions are satisfactory. Relocate the unit if necessary. 9. Keep children away from the unit while it is being repaired. 10. Be sure to clean the unit and its surrounding area.
Fig. 1-3 No Kids Nearby!
Samsung Electronics
1-1
MEMO
1-2
Samsung Electronics
2. Product Specifications
2-1 Table
Model(Indoor/Outdoor) Item Power Source Capacity Energy efficiency ratio Air Flow Moisture removal Noise level Indoor(Hi/Mid/Low) Noise level Outdoor Capacity Energy efficiency ratio Air Flow Noise level Indoor(Hi/Mid/Low) Noise level Outdoor Available voltage range Running amperes Cooling Power input Power factor Running amperes Electrical Heating Power input Rating Power factor Starting current Fuse capacity Power cord Cable-connector Type Com- Model name pressor Oil/Quantity Safety devices Model name Indoor Running capacitor Fan motor Model name Outdoor Running capacitor Narrow tube : Liquid Refrigerant tube Wide tube : Gas Cooling Capillary tube Heating Refrigerant to charge (R22) Additional Refrigerant (R22) Indoor unit : W x H x D Dimension Outdoor unit : W x H x D Indoor unit Weight Outdoor unit Heating Remark : Test condition Cooling test Heating test -V-Hz W Btu/h Btu/wh m3/min \/h dBA W Btu/h Btu/wh m3/min dBA V A W % A W % A AxV AxV mm3 x G CC F x VAC F x VAC mmxMT mmxMT mm mm gr gr/m mm mm Kg Kg SH12VCD/SH12VCDX 1-220 / 240-50 3510(2340~4100) 12000(8000~14000) 9.0(11~7.7) 7.8 1.9 39 / 37 / 35 52 3800(2550~4980) 13000(8700~17000) 9.3(11.9~7.5) 8.3 39 / 37 / 35 53 187~264 5.9(3.2~8.2), MAX12A 1330(720~1820) 97.1(96.3~96.5) 6.1(3.3~10.0), MAX12 1400(730~2260) 99.8(96.2~98.3) 12 3.15 x 250 / 20 x 250 15 x 250 1.5 x 4 Single Rotary 48A135RV2EL SUN ISO4GSD-T / 410 204CT AMPFS-022WTVA 1.2 x 450 AMASS-020WTVB 1.7 x 450 OD 6.35 x 5 OD 12.7 x 5 1.7 x 800 780 30 790 x 245 x 165 750 x 530 x 245 8 42 SH09VCD/SH09VCDX 1-220 / 240-50 2630(1640~3010) 9000(5600~10300) 8.6(10.8~7.8) 6.5 1.5 38 / 36 / 34 52 3310(1900~4100) 11300(6500~14000) 9.8(12.0~9.1) 7.1 38 / 36 / 34 53 187~264 4.6(2.5~5.8), MAX12 1040(520~1315) 98.3(90.4~98.6) 5.2(2.6~6.7), MAX12 1152(545~1530) 94.5(90.4~99.3) 12 3.15 x 250 / 20 x 250 15 x 250 1.5 x 4 Single Rotary 44B092QV2EL SUN ISO4GSD-T / 360 204CT AMPFS-022WTVA 1.2 x 450 AMASS-020WTVB 1.7 x 450 OD 6.35 x 5 OD 9.52 x 5 ID1.5 x 1000 670 20 790 x 245 x 165 750 x 530 x 245 8 39 Outdoor room DB35C / WB24C DB7C / WB6C Remark
Cooling
Performance
More 5m
Samsung Electronics
2-1
2-2 Dimensions
2-2-1 Indoor Unit
(Front view)
Air in
790
245
165
Air out
(Remote control)
45
115
22
Installation plate
2-2
Samsung Electronics
P roduct Specifications
10 10
600
(Front view)
256
(Rear view)
532
145 55 245
Samsung Electronics
2-3
INDOOR UNIT
Capillary tube T1 2-way valve Liquid side
OUTDOOR UNIT
T2 Gas side 3-way valve 4-way valve Cooling Compressor Heating Gas leak check point
2-4
Samsung Electronics
Propeller fan
Cross fan
The ON Timer enables you to switch on the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To cancel, press the (Set/Cancel) button.
The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours. To cancel, press the (Set/Cancel) button.
To select the 5 way function with the remote control, press the (5 way) button one or more times until the desired mode is selected. Each time you press the (5 way) button, each 5 way indicator on the indoor unit lights up in order.
Samsung Electronics
3-1
Outdoor temperature
Indoor temperature
31C over 29C over 31C less 21C over 27C over 29C less Cooling 25C over 27C less 21C over 18C over 21C less 18C less 18C less 25C less All area 27C over
Outdoor temperature
Indoor temperature
Operation type
Set temperature
Wind volume
31C over 29C over 31C less 21C over 27C over 29C less Cooling 25C over 27C less 21C over 18C over 21C less 18C less 18C over 21C less 18C less 25C less 23C over 27C over 23C less 27C less
28C 27C Automatic 26C 25C to be set automatically by controller Dehumid- according to the fying indoor temperature at the operation start. to be set automatically by controller according to the indoor temperaHeating ture at the operation start. 23C 21C
2. COOL MODE : The unit operates according to the difference between the setting and room temperature.(setting Temp.: 18C~30C) 3. HEAT MODE : The unit operates according to the difference between the setting and room temperature.(setting Temp.: 16C~30C) *Prevention against cold wind : For about 3~5 minutes after initial operation (thermo control or de-ice), the indoor fan will either not operate or operate very slowly, then switch to the selected fan speed. This period is to allow the indoor unit's heatexchanger to prewarm until emitting warm air.
3-2
Samsung Electronics
*High temperature release function : The outdoor unit and compressor ON/OFF is controlled for safety operation when heat exchanger of indoor unit is over heated. *De-ice : Deicing operation is controlled by outdoor unit's heat exchanger temperature and accumulating time of compressor's operation. De-ice ends by sensing of the processing time by de-ice Condition. 4. DRY MODE : *According to the difference between the set temperature (Ts) and indoor temperature (Tr), the operation frequency of compressor is controlled as each area. (Cooling area/COMPor ON/OFF area/Monitoring area) Cooling area : same as the cool mode COMPor ON/OFF area : repeat of COMPor frequency 36[Hz] for 4 minutes operation/0[Hz](off) for 6 minutes Monitoring area : COMPor off. 5. TURBO MODE : This mode is available in AUTO, COOL, HEAT, DRY, FAN MODE. When this button is pressed at first, the air conditioner is operated in powerful state for 30 minutes regardless of the set temperature, room temperature. When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode. *But, if you press the TURBO button in DRY or FAN mode, it is changed into AUTO mode automatically. 6. SLEEP MODE : Sleep mode is available only in COOL or HEAT mode. The operation will stop after 6 hours. *In COOL mode : The setting temperature is automatically raised by 1C each 1hour When the temperature has been raised by total of 2C, that temperature is maintained.
*In HEAT mode : The setting temperature is automatically droped by 1C each 1hour. When the temperature has been droped by total of 2C, that temperature is maintained. 7. FAN SPEED : Manual (3 step), Auto (4 step) Fan speed automatically varies depending on the difference between setting and the room temperature. 8. COMPULSORY OPERATION : For operating the air conditioner without the remote controller, the tact key in indoor unit can be used. When started with this key, the mode is set on AUTO. The operating is the same function as AUTO MODE in the remote controller. Each time you press this key, 5WAY function is changed in the following order; STD(standard) NATURE POWER(High-speed) Saving(PowerSaving) SILENCE STD(standard)( ) : General operation Mode NATURE( ) : The unit is operated according to health pattern control POWER( ) : The unit is operated in powerful state SAVING( ) : The unit is operated in power saving state SILENCE( ) : The unit is operated quitely Each mode has Auto(Cool or Heat) operation designed in advance. 9. SWING : BLADE-H is rotated vertically by the stepping motor. *Memory louver : When ON/OFF button is pressed at stop state, the BLADE-H returns to its original location which is operating state before stop.
Samsung Electronics
3-3
*Swing Set : Press the button under the remote control is displayed on LCD the and the blades move up and down. If the one more time press the button, blade location is stop. 10. 24-Hour ON/OFF Real Setting Timer. : The air conditioner is turned ON at a specified time using . OFF TIMER : The air Conditioner is turned OFF at a specified time using . *ON TIMER : Only timer LED lights on. *OFF TIMER : Both timer and operation LED lights on. 11. SELF Diagnosis
Indoor unit
Outdoor unit
Description
: Lamp on : Lamp flickering X : Lamp off Indoor unit room temperature sensor error(open or short) Indoor unit heat exchanger temperature sensor error(open or short) Indoor fan motor mal function EEPROM error option error Outdoor unit temperature sensor error (open or short) - outdoor temp-sensor - deice temp-sensor - OLP temp-sensor - discharge temp-sensor - heatsink temp-sensor Abnormal communication (Indoor - Outdoor unit) Abnormal increase of operation current Abnormal increase of discharge and OLP temperature Over current of IPM circuit Trouble of the PTC circuit of the outdoor Trouble of AC current sensor(open/short) and Leakage of refrigerant (R-22)
X X X X
X X X X X X X X X
X X X X X X
X X X X X X
12. BUZZER SOUND : Whenever the ON/OFF button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep".
3-4
Samsung Electronics
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable to the customer's needs. (Fix the unit firmly if it is mounted in a high place.) 3. Make sure that you install the outdoor unit in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet. 4. Make sure that you install the outdoor unit in area free from animals or plants. 5. Make sure that you install the outdoor unit in area not blocking the traffic. 6. Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit. 7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(15 meters). Note 1. Add 20 grams of refrigerant (R-22) for every 1 meter if the pipe length exceeds the standard pipe length of 5 meters. 2. Maintain a height between the indoor and outdoor units. 8. Make sure that you install the outdoor unit in an area which is large enough to accommodate the measurements.
Caution
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
Samsung Electronics
3-5
2. Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
Press this ON/OFF Switch for 5sec. And then the Airconditioner operating on rating speed.
4. Set the unit to Low pressure checking mode. * Press the ON/OFF switch for 5 second. *All lamps blink on the indoor unit.
Suspension hook
5. Check the pressure indicated by the pressure gauge(low pressure side). * Refer to Low pressure graph.
Compound gauge
6. Open the refrigerant tank and fill with refrigerant until the rated pressure is reached. * It is recommended not to pour the refrigerant in too quickly, but gradually while operating a pressure valve.
8. Close the 3-way valve, disconnect the pressure gauge, and open the 3-way valve again.
3-6
Samsung Electronics
R-22
6~15m
300
350
500
550
Samsung Electronics
3-7
3) Contract the second finger to the left, and right handle and pull to open the inlet grille. 4) Take the left and right filter out. *Taking off the deodorizing filter. 5) Loosen one of the right fixing screw and seperate the terminal cover. 6) Loosen three fixing screws of front grille.
7) Pull the upper left and right of discharge softly for the outside cover to be pulled out.
8) Pull softly the lower part of discharge and push it up. Caution; Assemble the front panel and fix the hooks of left and right.
4-1
Samsung Electronics
No 2
Procedure 1) Do 1above 2) Take all the connector of PCB upper side out. (Inclusion Power cord) 3) Separate the outdoor unit connection wire from the terminal block. 4) If pulling the Main PCB up. it will be taken out. 1) Do 1, 2 above Separate the drain hose from the extension drain hose. 2) Pull tray drain out from the back body.
Remark
Heat Exchanger
1) Do 1 and 2, 3 above 2) Loosen two fixing earth screws of right side. 3) Separate the connection pipe. 4) Separate the holder pipe at the rearside. 5) Loosen the three fixing screws of right and left side. 6) Lifting the heat exchanger up a little to push the up side for separation from the indoor unit.
1) Do 1, 2, 3, 4 above. 2) Loosen the fixing two screws and separate the motor holder. 3) Loosen the fixing screw of fan motor. (By use of M3 wrench) 4) Separate the fan motor from the fan. 5) Separate the fan from the left holder bearing.
Samsung Electronics
4-2
Common Work 1) Loosen the fixing screw and separate the & Cover-Valve. Assy-control Out 2) Separate the Cable-Connector Wire from the Terminal-Block.
3) Loosen five fixing screws and separate the Cabi-Upper. 4) Loosen five fixing screws from the Assy-Control Out.
5) Separate the Terminal-Housing from the Assy-Control Out. 6) Separate the Assy-Control Out from the outdoor unit.
4-3
Samsung Electronics
No 2
Parts Fan-Motor
Remark
2) Remove the nut flange (Turn to the right to remove, as it is a left hand screw) 3) Separate the fan.
Heat Exchanger
1) Do 1 above. 2) Loosen three fixing screws of Assy-Frame and Partition. 3) Disassemble the inlet and outlet pipe by welding. 4) Separate the heat exchanger.
Samsung Electronics
4-4
No 4
Parts Compressor
Procedure 1) Do 1 above. 2) Open the terminal cover of compressor and unscrew the connection terminal. 3) Disassemble the inlet and outlet pipe of compressor by welding. 4) Disassemble the inlet and outlet pipe of condenser by welding.
Remark
5) Loosen the three bolts of the lower part. 6) Separate the compressor.
4-5
Samsung Electronics
5. Troubleshooting
Since the inverter air conditioner is equipped with Electrical control circuits at both Indoor & outdoor unit, the trouble shooting shall be performed according to the error mode. Inside the controller of the outdoor unit (inverter), the large capacity of electrolytic condenser so that it takes the time to discharge after the power off since the electrical charge remains (the charging voltage DC 340V). Take care of the electrical shock by contact on the charging part before the discharge after the power off. (It takes approximately 2 minutes to discharge).
Cause and reason Is the power off or the power unplugged? Does it stop because it is the completion time? Unplug and plug again the power source for 2 minutes. Is the filter clogged with dust or dirty? Is there any direct light on the outdoor unit or any obstacle against it? Is the selected temperature too high? Lower the selected temperature lower than the current one (during cooling). Is the selected temperature too low? Raise the desired temperature than the current one (during heating). Is the Fan only Mode operation?
Is the battery run out? Is the battery inserted in the wrong way(+, -)? Is the detection part of the indoor unit blocked? Does it interfered with the radio of neon sign?
Is the operation selected among one of Auto / Dry / Turbo / Sleeping? The temperature setting is not required since the wind volume set automatically. Check again at the state of Cooling / Fan only / Heating.
Is the operation selected among the Dry / Turbo / Sleeping / Fan only Mode. Since the temperature is automatically set, the temperature setting is not required. Check again at the cooling/heating state. The standard temperature 2C during the automatic operation.
6 The operation lamp continues to be flickering. 7 The immediate operation starts without control of remote controller when plugged
Push the Operation / Stop button. Unplug and plug the power source.
It is the case that the auto restart function works. # Auto restart function is the convenient function where the operation state is memorized in the Memory IC during the blackout and the operation restarts when the power comes back.
Samsung Electronics
5-1
POWER indicator NATURE indicator STANDARD indicator Remote Control Sensor On/Off & 5 Way Selection button
Description
: LAMP ON : LAMP FLICKERING X : LAMP OFF Indoor unit room temperature sensor error(open or short) Indoor unit heat exchanger temperature sensor error (open or short) Indoor fan motor mal function EEPROM error Option error Outdoor unit temperature sensor error(open or short) - outdoor temp-sensor - deice temp-sensor - OLP temp- sensor - discharge temp-sensor - heatsink temp-sensor
TIMER
STD X
NATURE X X
POWER X X X X
SAVING X X X X
SILENCE X X X
X X X X X X X X X X
X X X X X X
X X X X X X
Abnormal communication (Indoor - Outdoor unit) \Abnormal increase of operation current Abnormal increase of discharge and OLP temperature Over current of IPM circuit Trouble of the PTC circuit of the outdoor Trouble of AC current sensor (open/short) and Leakage of refrigerant(R-22)
5-2
Samsung Electronics
Troubleshooting
RED
GREEN
YELLOW
LED3
LED2
LED1
Description
: LAMP ON : LAMP FLICKERING X : LAMP OFF Normal operation and communication (Indoor-Outdoor unit) Abnormal communication(Indoor-Outdoor unit) Trouble of the control power of the outdoor Abnormal communication (Sub-Main micom) No zero-crossing signal
GREEN
RED
X X
Trouble of option setting Abnormal increase of discharge temperature Abnormal increase of OLP temperature X Abnormal increase of operation current Over current of IPM circuit Over voltage of IPM circuit Over voltage and current of PFC circuit Trouble of DC link voltage circuit X Trouble of discharge temp-sensor(open/short) Trouble of outdoor temp-sensor(open/short) Trouble of deice temp-sensor(open/short) Trouble of OLP temp-sensor(open/short) Trouble of AC current sensor(open/short) and Leakage of refrigerant(R-22)
X X
Samsung Electronics
5-3
OPERATION START
The indoor unit does not work even though the power is plugged. There is no sound DING The lamp is not on the display. The indoor unit does not work when operated by the remocon.
Checking the Remocon. (5-3-2) Check the control board and the display board of indoor unit.(5-3-2)
The lamp of the indoor display is flickering and the indoor unit stops several minutes after the indoor unit starts.
Check the error mode by confirming the lamp flickering of indoor unit display.
Timer lamp( ) flickering Standard( ), Timer( ) lamp flickering Nature( ) lamp flickering
Check of the indoor temperature sensor (5-3-3) Check of the indoor heat exchanger (5-3-3) Check of indoor unit fan motor (5-3-4) Check the lines of the indoor and outdoor communication (5-3-5)
Timer(
), Nature(
) lamp flickering
) lamp flickering Check of the outdoor unit temperature sensor : Discharge temperature sensor (5-3-6) : Comp top OLP temperature sensor (5-3-6) : Deice temperature sensor (5-3-7) : Outdoor temperature sensor (5-3-7) POWER( ) flickering Check of the abnormal increase protection of the operation Current (5-3-8) Timer( ), POWER( ) lamp Check of the instantaneous over-current protection flickering mode of IPM circuit (5-3-9) Nature( ), POWER lamp( ) Check the abnormal increase of the comp flickering discharge gas temperature and OLP protection mode.(5-3-10) Standard( ), Nature (
5-4
Samsung Electronics
Troubleshooting
N L 1 2
SKY-BLU
(N1)
Step 3 : Check whether the fuse (F701)(F702) on the control board is normal. (5 [A]/250[V]:F701) (1[A]/250[V] : F702) If the fuse is broken, replace it with the new one. Step 4 : check the output of SMPS on the control board. Input power AC187~AC264V-IC 02 Input: DC 12V IC 02 Output : DC 5V
5-3-3 Check the indoor temperature sensor and indoor heat exchanger temperature sensor.
Take out the thermistor connected to the connector (CN41) of control board of indoor unit and measure the resistance between two wires and if it is same as follows: it is normal but if not, replace it. Ambient temperature (C) Resistance of thermistor [K] 15C 14.68 20C 12.09 25C 10 30C 8.31 35C 6.94 40C 5.83
Samsung Electronics
5-5
Troubleshooting
5-3-5 Check of communication line between the indoor unit and outdoor unit
(Communication error mode)
1) Check of connection Check whether the cable wire connecting the indoor unit with outdoor unit is correctly connected to the (N1), 1, 2 terminal. (If the wire is connected reversely, the communication error occurs) If the cable connecting the indoor unit and outdoor unit is longer than 20m, error mode occurs (shorten the cable length).
(Terminal block)
SKY-BLU
N L 1 2
SKY-BLU
(N1)
2) Check of power supply to the outdoor unit After operation of aircon, select the turbo mode and approximately 3minutes later, check whether the red color lamp of control board (to be seen if the top cover of outdoor unit) is on. If the red lamp (LED 3) is not on, check the power part of control board of outdoor unit. Check the connection of reactor. If the red lamp (LED3) is on and green lamp is flickering, it is normal.
5-6
Samsung Electronics
Troubleshooting
5-3-6 Check of discharge temperature sensor and comp top OLP temperature sensor.
Connector of outdoor unit control board (PIN#3,4 of CN51 - discharge temperature sensor), (PIN#1,2 of CN52-OLP Temperature sensor) Measure the resistance between two wires and if it is same as follows, it is normal but if not, replace. Ambient temperature (C) Resistance of thermistor [K] 0C 553 10C 362 20C 242 30C 166 40C 165 50C 82
5-3-7 Check the deice temperature sensor and outdoor temperature sensor
Connector of outdoor unit control board (PIN#1,2 of CN51 - outdoor temperature sensor),(PIN#3,4 of CN52-deice Temperature sensor) Measure the resistance between two wires and if it is same as follows, it is normal but if not, replace it. Ambient temperature (C) Resistance of thermistor [K] 15C 14.68 20C 12.09 25C 10 30C 8.31 35C 6.94 40C 5.83
Samsung Electronics
5-7
Troubleshooting
(Condition of installation)
The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (C) ) Reinstall the outdoor unit so that the good ventilation can be made. In case that the operation is made with the cover bent of the outdoor unit. Take out the cover. If two outdoor units are operating face to face, (the bad ventilation is made) Reinstall the outdoor unit for the good ventilation. The air circulation is bad due to the attachment of falling leaves. Take away the leaves for the good ventilation. If the Refrigerant is overcharged. Check the amount of Refrigerant.
(Unit defect)
If the comp is locked. Replace the comp. If the comp is operating without the revolution of fan motor. Check the fan motor connector and replace the fan motor. In case the parts of the control board is damaged. Replace simultaneously the inverter control board.
5-3-10 Check of the comp discharge gas temperature and OLP temperature abnormal rise.
If the comp discharge gas temperature and OLP temperature rises higher than a certain level, it protects the circuit. If the comp discharge gas temperature and OLP temperature rises abnormally, check the following items.
(Condition of installation)
The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (C) ) Reinstall the outdoor unit so that the good ventilation can be made. In case that the operation is made with the cover bent of the outdoor unit. Take out the cover. If two outdoor units are operating face to face, (the bad ventilation is made) Reinstall the outdoor unit for the good ventilation. The air circulation is bad due to the attachment of falling leaves Take away the leaves for the good ventilation. If the refrigerant is insufficient. Fill up the amount of refrigerant.
(Unit defect)
If the comp is locked. Replace the comp. If the comp is operating without the revolution of fan motor Take out the protection cover. Check the fan motor connector and replace the fan motor.
5-8
Samsung Electronics
Measure resistance between terminals (CN72) with a tester Normal At ambient temperature (10C ~ 30C) between Red, Blue Red, Yellow Abnormal , O open or short Voltage 41010% 32510%
Main Sub
Measure the voltage between ground and signal wire of the fan motor Normal between Gray, Orange Yellow, Orange Voltage 0.5V~4.5V 5V
Abnormal if voltage does not change from 0V to 5V. At ambient temperature (10C ~ 30C) between Black, Red Black, White Resistance 27510% 35010%
Main Sub
, O open or short
Measure resistance between red wire and each terminal. Normal Abnormal Approx. 380 at ambient temperature (20C ~30C) , O open or short
Samsung Electronics
5-9
Applicable key
Display status
2nd step Method) If the first digit of LCD is 0 on the remocon screen, go to the 3rd step.
If it is 1, press the mode key once to change to 0 and go to the 3rd step.
3rd step Method) Press the marked key to input the option number. example) 021E31 Result) Go to 4th step if it displays as shown in the right (The number increases from 1~9, and A, b, C, d, E, F whenever pressing the key.)
5-10
Samsung Electronics
Troubleshooting
Remote controller operation method as per the step 4th step Method) After completion of 3rd step, and if the MODE KEY is pressed once, ! 1~3 steps are saved internally @ If the first number at the time is 1, it is correct and so go to 5th step If pressing mode key and the first digit becomes 0, the screen of 1~3 steps can be seen.
Applicable key
Display status
5th step Method) Pressing the marked key to input the option number. example) 142285 Result) If it displays as shown in the right go to the 6th step
6th step Method) When pressing the operation ON/OFF key with the direction of remote controller for set, the sound Ding, or Diriring is heard and then the input of option is completed. Refer to the right side if the error appears.
ERROR MODE 1. When the lamps of (STANDARD( ), NATURE( ), TIMER( ) is flickering failute of option input After removing the set power cord and insert it again, pressing the operation on/off key to retry and if the condition is same, EPROM is deffcective or misinsertted. So replace the PCB.
2. When all lamps of indoor unit ( ) are flickering with the sound of Dididiring, The current option input is different from that of already input one: Check the option number correctly and if it is correct, press the key once more to input the option. (check correctly) If the option is not input at the time and all lamps are continuously flickering ; since it is the case that the option number is out of the input range, check the option number again and do again the steps from 1 - 6steps
Samsung Electronics
5-11
Troubleshooting
SH12VCD
007315-10123F
SH09VCD
007d08-1010Fb
5-12
Samsung Electronics
MEMO
Samsung Electronics
5-13
16 19
20-2
13
13-2 13-3 13-4
14 15 10
13-1
17 11 12
18
8 22 24 9 6 21 25
5 7
4 23 3 2
You can search for the updated part code number through the ITSELF.
URL : http://itself.sec.samsung.co.kr
6-1
Samsung Electronics
Parts List
QTY No.
1 2 3 4 5 6 7 8 9 10 11 12 13 13-1 13-2 13-3 13-4 14 15 16 17 18 19 20 20-1 20-2 20-3 20-4 20-5 20-6
CODE NO
DB64-00354A DB63-00064A DB95-00287G DB63-00067A DB92-00248G DB67-00051A DB67-00032A DB63-00083A DB94-00040F DB60-20011A DB31-00033A DB32-00020A DB93-00960D DB93-00951A DB65-00076A DB61-00219A DB93-01601A DB94-00056G DB94-00104A DB61-00165A DB39-00146A DB39-00147A DB70-00036A DB94-00058N DB94-00062E DB66-00127A DB66-00128A DB66-00128B DB63-00082A DB95-20138A DB31-10129A DB93-01558A DB61-40251A DB67-60030A DB96-01248A DB96-01247C
Description SH12VCD
GRILLE-AIR INLET GUARD-AIR FILTER ASSY-CLEANER FILTER COVERTER-TERMINAL ASSY PANEL-FRONT SPACER-EVAP LOW SPACER-EVAP UP COVER U-BEND ASSY-CROSS FAN BOLT-SPECIAL MOTOR-FAN-IN THERMISTOR-WIRE ASSY ASSY CONTROL IN ASSY PCB MAIN TERMINAL BLOCK HOLDER-CLAMP IN ASSY DISPLAY ASSY BACK BODY ASSY-HOLDER MOTOR HOLDER-PIPE CONNECT WIRE- DISPLAY CONNECT WIRE-PCB PLATE-HANGER ASSY TRAY DRAIN ASSY DRAIN-HOSE BLADE-H BLADE-V,A BLADE-V,B SCREEN-SAFETY WIRE ASSY-MOTOR STEPPING MOTOR-STEPPING ASSY DISPLAY-CENTER HOLDER-SENSOR SPRING-SENSOR ASSY CYCLE IN ASSY CYCLE IN RUBBER BEARING ASSY REMOCON 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 6 1 1 1 1 1 1 1 1 1
SH09VCD
1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 6 1 1 1 1 1 1 1 1 1
20-6-1 20-7 21 22 23
24 25
DB94-40003A DB93-00251L
Samsung Electronics
6-2
6-3
7
8-1
8 22 23 11
6 21
1
21-1
18 16 17 10 15 20
12 14 13 5 9
19
Samsung Electronics
Parts List
No.
1 2 3 4 5
CODE NO
DB63-00104B DB60-30004A DB67-50063A DB31-10058E DB90-00241P DB90-00241N
Description
GUARD-FAN NUT-FLANGE PROPELLER-FAN MOTOR-FAN OUT ASSY-FRAME ASSY-FRAME ASSY-PARTITION ASSY-PARTITION REACTOR CABI-UPPER ASSY-CONTROL OUT ASSY-CONTROL OUT ASSY-MAIN PCB ASSY-MAIN PCB FELT COMP BOTTOM FELT COMP BOTTOM CLOTH COMP SIDE CLOTH COMP SIDE CLOTH COMP UPPER COMPRESSOR COMPRESSOR GROMMET-ISOLATOR GROMMET-ISOLATOR NUT-WASHER GASKET COVER-TERMINAL THERMISTOR-OLP NUT-FLANGE ASSY-4WAY VALVE ASSY-4WAY VALVE ASSY-CAPI TUBE ASSY-CAPI TUBE ASSY-CONDENSER ASSY-CONDENSER THERMISTOR-OUT CABI-SIDE HANDLE-CABI RH
Specification SH12VCDX
HSWR 2C SM20C M6 NTR AS+G/F,405 AMASS-020WTVB ASSY ASSY ASSY ASSY 12A,21mH SECC-P ASSY ASSY ASSY ASSY FELT FELT FELT FELT FELT 48A135RV2EL 44B092QV2EL NR NR HEX 2C MB ZPC EPDM NYLON 204CT/103AT M5,SM20C ASSY ASSY ASSY ASSY ASSY ASSY ASSY SECC-P PP 1 1 1 1 1 0 1 0 1 1 1 0 1 0 1 0 1 0 1 1 0 3 0 3 1 1 1 1 1 0 1 0 1 0 1 1 1
QTY SH09VCDX
1 1 1 1 0 1 0 1 1 1 0 1 0 1 0 1 0 1 1 0 1 0 3 3 1 1 1 1 0 1 0 1 0 1 1 1 1
DB94-00160B DB94-00160A
6-1 7 8
8-1
DB93-00953B DB93-00953A
DB63-00380B DB63-00380A
10
DB72-00211A DB72-00162A
11 12
13
DB73-00070A DB73-00067A
14 15 16 17 18 19
20
DB99-00186A DB99-00169A
21
DB96-01588A DB96-10502A
21-1 22 23
Samsung Electronics
6-4
4 5 1 2
Parts List
No
1 2 3 4 5 6 7
Description
INLAY LCD CASE TOP LCD KEY RUBBER ASSY PCB REMOCON CASE LOW BATTERY COVER
QTY
1 1 1 1 1 1 1
Remark
6-5
Samsung Electronics
Parts List
No
1 2 3
Description
HOLDER CONTROL ASSY MAIN PCB ASSY TERMINAL BLOCK
Specification
ABS, UL94-V0 UL1015 AWG#16, ORG/SKY-BLUE/BRN ASTRO1010 P.B.T+CF30%(BLK) C2680-1/2H SMP250-05(1), SMT-250(5) SMP200-05(1), YMT-200(5) SGCC-M UL1015 AWG#16, GRN+YEL WP, TH, +, M4, L8, ZPC(WHT), T.C PH, +, M3, L22, ZPC(YEL), SWRCH10A SGCC-M
QTY
1 1 2 4 1 5
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
CONNECTOR WIRE FAN MOTOR BRACKET EARTH CONNECTOR WIRE EARTH SCREW CREW HOLDER CLAMP IN SEAL-PANEL FRONT RH SEAL-H/CONTROL FRONT MF CAPAITOR CONNECTOR WIRE MF CAPACITOR CONNECTOR WIRE EARTH LEAD WIRE(N) LEAD WIRE(L) LEAD WIRE(C) ASSY DISPLAY PC
1200nF, 450V, 39.6 x 16 x 27 ST730619 UL1015 AW#22, WHT UL1015 AWG#20, GRN+YEL UL1015 ASG#16, ORG UL1015 AWG#16, SKY=BLUE UL1015 AWG#16, BLK
2 2 1 1 1 1 1 1 2 2 1 1 1 1 1
Samsung Electronics
6-6
ISOMETRIC VIEW
6-7
Samsung Electronics
Parts List
QTY No.
1
Description
CASE CONTROL BASE
Specification DB93-00962A
RESIN-ABS DB62-00774A 1 1 2 1 2 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1
DB93-00962B
1 1 2 1 2 2 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1
SCREW-MACHINE
PCB-ASSY DB93-00953B
5 6 7 8 9 10 11 12 13 14
SCREW-MACHINE SCREW-MACHINE SCREW-TAPPING SCREW-TAPPING ASSY TERMINAL BLOCK SCREW-MACHINE RUBBER CLAMP HOLDER WIRE SCREW-MACHINE COVER
M3 x 16 WSP PH+ M4 x 16 WSP PH+ M3 x 8 2S PH+ M3 x 14 SWP PH+ CBF-HARNESS M4 x 25 WSP PH+ NBR RESIN-ABS M4 x 16 WSP PH+ RESIN-ABS UL1015 AWG#16/RED
15
16
17
18
19
20 21 *
Samsung Electronics
6-8
7. PCB Diagrams
7-1 ASSY PCB IN : DB93-00951A
s TOP
s BOTTOM
7-1
Samsung Electronics
PCB Diagrams
Parts List
No
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63
Design Location
D701,702,703 D101 BD71 ZD11 ZD12 ZD71 CD11 Q201,401,602 Q603 Q301,302,601 Q901 ~ 904 IC05,06 IC04 IC51 IC03 IC01 IC02 VA71,72,73 R606 R202 ~ R205 R206,601,602,902 R201,207,208,301,401,403,607,905 R102 ~ 104 R106,107 R503,504 R101,303,603,703,901 R105,302,604,605 R501,502 R510,511 R701,706,707 R704,705 R702 R402 XC71 C106 C702 C703 C301,510,511,903 C203,204,401,705 C103,107,109,110,112,201,202,302,500,501,502, 901 XC72 C111 C601,701 C101,102 X301 SS71 F702 F701 F701 CN72 CN71 CN42 CN41 CN91 CN61 ST11 DSA1 PC01 PC31,32 PC02 BZ61 FT72 RY71
Description
DIODE-RECTIFIER DIODE-RECTIFIER DIODE-BRIDGE DIODE-ZENER DIODE-ZENER DIODE-ZENER DIODE-TVS TR-SMALL SIGNAL TR-SMALL SIGNAL TR-SMALL SIGNL TR-DIGITAL TR-ARRAY IC-MCU IC-EEPROM IC-VOLTAGE COMP IC-PWM CONTROLLLER REGULATER VARISTOR R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CARBORN R-CARBORN R-CARBORN R-CHIP C-CERAMIC C-AL C-CERAMIC C-CERAMIC C-CHIP C-CHIP C-CHIP C-FILM C-AL C-AL C-AL RESONATOR-CERAMIC SSR FUSE FUSE-HOLDER FUSE CONNECTOR-HEADER CONNECTOR-HEADER CONNECTOR-HEADER CONNECTOR-HEADER CONNECTOR-HEADER CONNECTOR-HEADER TRANS SWITCHING POSISTOR PHOTO-COUPLER PHOTO-COUPLER PHOTO-COUPLER BUZZER FILTER RELAY-POWER
Specification
MRA4005,600V,1A,SMA,TP UG2B, 100V, 2A, DO-204AC,TP DF06S, 600V, 1A, SMD-4,TP BZX84C3V/6, 350mW,SOT-23,T BZX84-C11, 6V, 35MW, S INR4749,24V/1W ST02D-200,200W,DO 2SC2412K,NPN,200mW,SOT-2 MMST2907,PNP,200mW,SOTDTC114EKA,PNP DTA114EKA,PNP,200MW,10K/10K ULN2003AFW,NPN,1W,SOP-16 uPD780034 93LC56,128*16Bit,SOP KA7533,TO-92,30,SINGLE TNY255P,DIP,8P,300MIL KA78L05 470V,4500A,17*12mm,BK 560OHM,5%,1/10W,DA,TP,2012 100KOHM,5%,1/8W,DA,TP,3216 10KOHM,5%,1/10W,DA,TP,2012 1KOHM,5%,1/10W,DA,TP,2012 220KOHM,5%,1/8W,DA,TP,3216 220OHM,5%,1/10W,DA,TP,2012 330OHM,5%, 1/10W,DA,TP,2012 4.7KOHM,5%,1/10W,DA,TP,2012 470OHM, 55,1/10W,DA,TP,2012 6.8KOHM,1%,1/10W,DA,TP,2012 47KoHM,5%,1/10W,TP,2012 82KOHM,2W 10KOHM,2W 100KoHM,1/10W 6.8KOHM,5%,1/10W,DA,TP,2012 DISC,2.2nF,20%,400V,Y5V,TP,12 1000uF,10%,25V 10nF,+820%,50V,Y5V,TP1 4.7nF,275V CL21B102KBNC CL21B103KBNC CL21B104KBNC 100nF,10%,275V,BK,18*6*12,15 470uF,20%,16V,GP,TP,10*12.5,5 47uF,20%,50V,GP,TP,6.3*11,5 6.8uF,20%,450V,GP,TP,10*16,T 10MHz,0.5%,TP,10*5 12VDC,2A,1mS 250V,1A,TIME-LAG FUSE-HOLDER 250,5A YW396-03AV,WHT YW396-05AV,WHT SMW250-03,BLU SMW200-04,WHT SMW200-12,WHT SMW200-05,WHT DC12V DSA-332M,2pF,MAX,100MOHM TLP181GB TLP181 TLP620GR CBE2220BA LS403110 UKH-12S
QTY
3 1 1 1 1 1 1 2 1 3 4 2 1 1 1 3 1 4 4 8 3 2 5 5 2 1 2 3 2 1 1 1 1
2 4 11 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1
Samsung Electronics
7-2
7-3
Samsung Electronics
PCB Diagrams
s BOTTOM
Samsung Electronics
7-4
PCB Diagrams
Parts List
No
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59
Design Location
C101,C102,C103(7k,9k) C101,C102,C103(12k) C115 C408,C409,C410 C110,C201,C415 C107,C108,C109,C112 CABLE(JU;JV;JW=RED;BLU;YEL) CABLE(REACTOR01;02=YEL;WHT) CABLE(DCN01/DCN02) CABLE(PC01;PC02) C303 C302,C506 C401,C402,C403,C404,C405,C406, C407 C701,C702 C202,C501,C502,C503,C504,C505, C507,C508,C509,C703,C704,C706 C203 C305,C306 C106,C111,C116,C204,C705,C802 C414 C412 C113,C114,C411,C803 C104,C105,C304 C005,C006,C007 C001,C002 C301 C413 C004 C003 Running capacitor(Main case+ screw) CABLE (L;N=BRN;BLU) FT00 FT01 L101 L001 CN51 CN52 CN02,CN31 CN01 X501 X701 D301,D103,D104,D105,D106 D101 D201 BD01 ZD21 ZD31 D102,D401,D402,D403 ZD22 FUSE FUSE CLIP H/S(PFC) IC51 IC83 IC41 IC81 MICOM IC15,IC21,IC31,IC32,IC54 IC11 IC16
Description
C-AL C-AL C-AL C-AL C-AL C-AL CBF-HARNESS CBF-HARNESS CBF-HARNESS CBF-HARNESS C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,CHIP C-CERAMIC,DISC C-CERAMIC,DISC C-CERAMIC,DISC C-FILM,MPET C-FILM,MPP C-FILM,MPPF C-FILM,MPPF C-FILM,MPPF COIL CHOKE ASSY COIL CHOKE COIL CHOKE COIL CHOKE COIL-CHIP CONNECTOR-HEADER CONNECTOR-HEADER CONNECTOR-HEADER CONNECTOR-HEADER CRYSTAL-RESONATOR CRYSTAL-RESONATOR DIODE DIODE DIODE DIODE-BRIGE DIODE-ZENER DIODE-ZENER DIODE-ZENER DIODE-ZENER FUSE FUSE-CLIP HEAT SINK IC-MASK IC-LOGIC IC-LOGIC IC-LOGIC IC-MICOM IC-PHOTO-COUPLER IC-PWM CONTROLLER IC-REG
Specification
RADIAL,560UF,105,20%,400V,2PIN,BK,35x50mm RADIAL,680uF,105,20%,400V,2PIN,BK,35x50mm RADIAL,RG 450V 10UF 12.5*20 TP RADIAL,RZ 35V 22uF 6.3x11 TP RADIAL,RZ 35V 47uF 6.3x11 TP RADIAL,WD 25V 220uF 8x11.5 TP HA01, #16, 270,280,290mm,RED,BLU,YEL(COMP)(CORE #1) HA02, #16, 270,270mm,WHT,YEL(REACTOR) HA04, #16, 140mm,BLU(DC-) HA05, #20, 140mm,WHT(CON) CL10B102KBNC CL10B103KBNC CL10C101JBNC CL10C220JBNC CL10F104ZANC CL21B102KBNC CL21B103KBNC CL21B104KBNC CL21B222KBNC CL21B223KBNC CL31F105ZANC RADIAL,SC E 222M 10FF7 RADIAL,SCE 103Z 14FF7 RADIAL,SCE 472M 14FF7 RADIAL,5TY2ARB103KAN TP RADIAL,PC2J104K 630V TP RADIAL,330nF,10%,275V,TP,26x8.5x18m RADIAL,680nF,10%,275V,BK,31x11x21 RMES-45H015UA (LSA15009 ASSY, mH,43X32X28mm,18Turn,CABLE)+C54 LS615014,mH,38.5x38x30mm, 20Turn, 4PIN LS615014S,mH, 38.5X38X30mm,15Turn ,6PIN RADIAL,10mH(DR6.5*7.5) FCI 3216 R47K (0.47uH) SMAW250A-04,RED,YENHO SMAW250A-04,WHT,YENHO YAW396A-03AV,WHT,YENHO YAW396A-05AV,WHT,YENHO CST 4MHZ HC-49/S,12.288MHz ES1D,D0-214AC, 200V FEP30JP,FORMING US1G,D0-214AC, 400V GS1B2560,FORMING AXIAL,1N4749A AXIAL,1N4751A AXIAL,1N4937 MMBZ5232B 65TL 250V,20A FC61B 27X17.5X40 S3C9434XZ0-SKB4 74HCT00D,SOP-14 LM324D ULN2003ADR TMP88PH47F(MASK),QFP TLP181(GRH-TLP),SOP,TP TOP222P KA78L05AZTA(0.1A Positive Vol Reg)
QTY
3 3 1 3 3 4 1 1 1 2 1 2 7 2 12 1 2 6 1 1 4 3 3 2 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 5 1 1 1 1 1 4 1 1 2 1 1 1 1 1 1 5 1 1
7-5
Samsung Electronics
PCB Diagrams
Parts List
No
60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83
Design Location
IC17 Q801 Q002 Q001 Q201,Q202,Q301,Q302,Q802 Q803 IC14 IC52,IC71 IPM(7k,9k) IPM(12k) LED2 LED3 LED1 PCB R801 R003 R411 R501,R504 R502,R503 R205,R904,R905,R906 R204 R505 R303, R304 R305,R401,R402,R403,R404,R405 R406,R407,R506,R508,R702 R306 R101,R102 R803 R810 R113 R109 R805 R108 R106 R207,R806,R807 R507,R701 R414 R413 R802 R412 R408,R409,R410 R107 R203,R302,R804 R415 R105 R110,R111,R112 R001, R002 R004 RV01,RV02 RV03 R005 R202 R201 R301 R104 DSS DSA PT01 PT02 VA02,VA05,VA06,VA07 VA01,VA04
Description
IC-REG IC-TR IC-TR IC-TR IC-TR-DIGITAL IC-TR-IGBT IC-VOL REF IC-VOL IPM IPM LED_GRN LED_RED LED_YEL PCB R-CEMENT(S) R-CEMENT(S) R-CEMENT(S) R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP R-CHIP RELAY RELAY-POWER R-METAL OXIDE(S) R-METAL OXIDE(S) R-METAL OXIDE(S) R-METAL OXIDE(S) R-METAL OXIDE(S) SURGE-ABSORBER SURGE-ABSORBER THERMISTER-PTC TRANS-PULSE VARISTER VARISTER
Specification
KA78M05TU(0.1A Positive Vol Reg) BC847B,NPN, SOT-23 KTA1715 KTC2814 KRC102S,NPN,200mW,10K-10K,SOT IRG4BC30F(004).TO-220AB, IR KA431DTF(3-Terminal Adjustable Reg) RN5VT45(46)CA,SOT-23-5 PS21244-E, MIT,600V,15A PS21245, MIT,600V,20A SM4433(FORMING) SA4433(FORMING) SY4433(FORMING) FR4,GREEN, 220X140mm, 15/20A-MISTU 3RJ 0.045ohm(10%,3W,CB,BK,12x8x25mm) 5RJ 200ohm(5%,5W,CB,BK,13x9x25.5mm) 7RJ 0.015ohm(10%,7W,CA,BK,35x9.5xmm) MCR03EZH F1802, 18Kohm, 1/10W, 1%, 1608 MCR03EZH F2402, 24Kohm, 1/10W, 1%, 1608 MCR03EZH J102, 1.0Kohm, 1/8W, 5%, 1608 MCR03EZH J203, 20Kohm, 1/10W, 5%, 1608 MCR03EZH J331, 330ohm, 1/10W, 5%, 1608 MCR03EZH J471, 470ohm, 1/8W, 5%, 1608 MCR03EZH J472, 4.7Kohm, 1/10W, 5%, 1608 MCR03EZH J561, 560ohm, 1/10W, 5%, 1608 MCR100EZH J184, 180kohm, 1W, 5%, 6432 MCR100EZH J222, 2.2Kohm, 1W, 5%, 6432 MCR10EZH F1002, 10Kohm, 1/8W, 1%, 2012 MCR10EZH F1502, 15Kohm, 1/8W, 1%, 2012 MCR10EZH F1801, 1.8Kohm, 1/8W, 1%, 2012 MCR10EZH F2201, 2.2Kohm, 1/8W, 1%, 2012 MCR10EZH F6801, 6.8Kohm, 1/8W, 1%, 2012 MCR10EZH J102, 1.0Kohm, 1/8W, 5%, 2012 MCR10EZH J103, 10Kohm, 1/8W, 5%, 2012 MCR10EZH J105, 1.0Mohm, 1/8W, 5%, 2012 MCR10EZH J202, 2.0Kohm, 1/8W, 5%, 2012 MCR10EZH J203, 20Kohm, 1/8W, 5%, 2012 MCR10EZH J221, 220ohm, 1/8W, 5%, 2012 MCR10EZH J222, 2.2Kohm, 1/8W, 5%, 2012 MCR10EZH J330, 33ohm, 1/8W, 5%, 2012 MCR10EZH J332, 3.3Kohm, 1/8W, 5%, 2012 MCR10EZH J472, 4.7Kohm, 1/8W, 5%, 2012 MCR10EZH J473, 47Kohm, 1/8W, 5%, 2012 MCR10EZH J6R8, 6.8ohm, 1/8W, 5%, 2012 MCR18EZH F4703, 470Kohm, 1/4W, 1%, 3216 MCR50EZH F4703, 470Kohm, 1/2W, 1%, 5025 MCR50EZH J101, 100ohm, 1/2W, 5%, 5025 F3AA012E UKH-12S,12VDC AXIAL,MOR 1/4TSJ 100ohm, 5%, 1/4W, AA TP AXIAL,MOR 2TSJ 100Kohm ,5%,2W,AA,TP AXIAL,MOR 2TSJ 47Kohm,,5%,2W,AA,TP) AXIAL,MOR 2TSJ 5.6Kohm,5%,2W,AA,TP) MOR 3TSJ 47Kohm,5%,3W,AA,TP) AXIAL,300V,DSS-301 AXIAL,500V,DSA-501 J512Q24E270M265 PT_20A , 1.4mH 470V,0.6W,50A,14MM,INR14D471K 470V,0.6W,50A,14MM,INR20D471K
QTY
1 1 1 1 5 1 1 2 1 1 1 1 1 1 1 1 1 2 2 4 1 1 2 11 1 2 1 1 1 1 1 1 1 3 2 1 1 1 1 3 1 3 1 1 3 2 1 2 1 1 1 1 1 1 1 1 1 1 4 2
84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119
Samsung Electronics
7-6
PCB Diagrams
s PART LIST
No
1 2 3 4 5 6 7 8 9 10
Description
PCB-DISPLAY MODULE REMOCON TACT SWITCH C-CERAMIC C-CERAMIC DIODE SWITCHING R-CARBON CONNECTOR WAFER C/W DIS & MODULE HOLDER-LED
Specification
FR-1, T1.6 KSM-713TH5 KPT-1105A CA 0A 50V 102K CA 0A 50V 104Z 1N4148 470 1/2W 5% SMAW200-05(WHT) UL1007 AWG/26/11 HIPS
QTY
1 1 1 1 1 1 3 1 1 1
7-7
Samsung Electronics
8. Wiring Diagrams
8-1 Indoor Unit
Samsung Electronics
8-1
8-2
Samsung Electronics
Wiring Diagrams
X X X X X X X X
Normal operation and communication(Indoor - Outdoor unit) Abnormal communication(Indoor - Outdoor unit) Trouble of the control power of the outdoor Abnormal communication(Sub-Main micom) No zero-crossing signal X X Trouble of option setting Abnormal increase of discharge temperature Abnormal increase of OLP temperature X Abnormal increase of operation current Over current of IPM circuit Over voltage of IPM circuit Over voltage and current of PFC circuit Trouble of DC link voltage circuit X X Tourble fo discharge temp-sensor(open/short) Trouble of outdoor temp-sensor(open/short) Trouble of deice temp-sensor(Open/short) Trouble of OLP temp-sensor(open/short) Trouble of AC current sensor(open/short) and Leakage of refrigerant (R-22)
X X
X : LAMP OFF
Samsung Electronics
8-3
MEMO
8-4
Samsung Electronics
MEMO
Samsung Electronics
8-5
MEMO
8-6
Samsung Electronics
Use this page to keep any special servicing information. (Service Bulletin, etc.) If only parts number changes, Just change parts number directly on parts list. And if you need more information, please see the service website. Itself Solution
Integrated technology supporting electronic library
http://itself.sec.samsung.co.kr
Copyright 2002
By Samsung Electronics Co., Ltd. All rights reserved. This manual may not, in whole or in part, be copied, photocopied, reproduced, translated, or converted to any electronic or machine readable from without prior written permission of Samsung Electronics Co., Ltd. Printed in Korea.
ELECTRONICS
Samsung Electronics Co., Ltd. Dec. 2002. Printed in Korea. Code No. DB98-08728A(1)