GRL100 D - Model 0.0
GRL100 D - Model 0.0
GRL100 D - Model 0.0
FEATURES
Fully numerical line protection for use with digital telecommunication systems Operating time typically 1 cycle Master/master design Automatic transmission delay compensation CT ratio correction Applicable to various lines such as two-terminal or three-terminal lines, overhead lines or underground cables, etc. Phase-segregated differential protection Zero-sequence current differential protection for high resistance earth faults Charging current compensation Distance protection with independent three forward and one reverse zone Backup directional earth fault command protection with forward and reverse looking element Overcurrent backup protection Overvoltage and undervoltage protection Thermal overload protection Stub fault protection for one-and-a-half busbar system Transfer tripping Out-of-step protection Broken conductor detection Breaker failure protection Fail-safe overcurrent scheme Autoreclose function Power swing blocking function VT fail detection CT fail detection Accurate fault location using all terminal currents and voltages Configurable binary inputs and outputs Programmable logic for I/O configuration, alarms, indications, recording, etc. Automatic monitoring Metering and recording functions Menu-driven user interfaces Front-mounted RS232C port for communication to a local PC and rear-mounted RS485 for communication to a remote PC, and fibre optic or Ethernet LAN serial port for communication to a Substation Automation System. Data communication with substation control and automation systems is supported according to the IEC 61850 and IEC 60870-5-103 standards. IRIG-B port for external clock
APPLICATION
GRL100 provides high-speed and phase-segregated line differential protection for use with telecommunication systems. For telecommunication systems, dedicated optical fibre, 64 kbps multiplexed communication channels or microwave links are employed. GRL100 system is a master/master design. Each terminal has a differential calculation function and performs arithmetical operation independently and simultaneously. GRL100 measures the transmission delay automatically and compensates the delay time continuously to perform correct differential calculation. The relay can be applied in various EHV/HV network configurations. Overhead lines or underground cables Two-terminal or three-terminal lines Lines with weak or no-infeed Single or parallel lines Lines with heavy load current Short or long distance lines GRL100 provides the following protection schemes: Phase-segregated current differential protection (DIF) provides high reliability and security for diverse faults including single-phase and multi-phase faults and double-faults on double-circuit lines and developing faults. Zero-sequence current differential protection (DIFG) enables sensitive protection for high impedance earth faults. Distance protection provides three forward and one reverse protection zones for phase and earth faults. Directional earth fault protection provides protection for earth fault with carrier scheme protection. Non-directional overcurrent backup protection provides both inverse time overcurrent and definite time overcurrent protection for phase faults and earth faults. Thermal overload protection provides protection for cables and other plants Stub fault protection for one-and-a-half breaker scheme Out-of-step protection performs phase comparison of the local and remote voltages and operates only when the out-of-step loci cross the protected line. Breaker failure protection provides a re-tripping and/or backup tripping function for circuit breaker failure. For current differential protection, a charging current compensation function is provided. GRL100 can provide high-speed single-shot autoreclose or multi-shot autoreclose. GRL100 provides the following metering and recording
GRL100
functions: Metering Fault recording Event recording Fault location Disturbance recording GRL100 provides the following user interfaces for relay setting or viewing stored data: Relay front panel: LEDs, LCD display and operation keys Local PC Remote PC The relay can be accessed from a local PC or a remote PC through communication ports. A local PC can be connected to the relay via the RS232C port on the front fascia of the relay. Rear port (RS485 or Fibre optic) is provided for connection to a remote PC and for IEC 60870-5-103 communication with a substation control and automation system. Further, an Ethernet LAN port can be provided and communication according to the IEC 61850 standard is also supported. Table 1 shows the functions that can be incorporated in GRL100 models applied to two-terminal line and three-terminal line or two-terminal line with dual communication.
1CB x x x x x x x
1CB/2CB x x x x x x x
Model x0xD: For two-terminal end application Model x1xD: For three-terminal end application or two-terminal end application with dual communication Legend DIF: DIST: DEF ARC: DIFG: CCC: BF: OST: FL: OC/EF THM BCD OV: UV: Phase-segregated current differential protection Backup distance protection Directional earth fault protection Autoreclose Zero-phase current differential protection Charging current compensation Breaker failure protection Out-of-step protection Fault locator Overcurrent backup protection Thermal overload protection Broken conductor detection Overvoltage protection Undervoltage protection
GRL100
RELAY FUNCTIONS
Phase-segregated Current Differential Protection
GRL100 provides high-speed phase-segregated current differential protection for both phase-to-phase faults and phase-to-earth faults. The phase-segregated current differential protection exhibits high selectivity and sensitivity for various types of faults. It has the percentage ratio differential characteristic as shown in Figure 1.
A Id IA C IC IB
Operating zone
A Id IA C IB
IC
Operating zone
5/6DIFGI 0
Slope=1/6 Ir
Id: Differential current (|IA + IB + IC|) Ir: Restraining current (|IA| + |IB| + |IC|) DIFGI: Setting value
5/6DIFI1
Ir
-2DIFI2 Id: Differential current (|IA + IB + IC|) Ir: Restraining current (|IA| + |IB| + |IC|) DIFI1: Setting of small current region DIFI2: Setting of large current region
Dual Communication
Three-terminal application models have dual communication mode. By connecting the remote terminal with dual communication routes, even if one of the routes fails, it is possible to continue sampling synchronization and protection by the current differential relay.
CH1
CH1
GRL100
CH2
GRL100
CH2
GRL100
Stub Protection
Stub protection operates for a fault in a stub zone on one-and-a-half busbar system. With the auxiliary contact of the line disconnector open, only the local terminal current is used as the operating quantity by setting the remote terminal current data to zero.
Z3 BFRS Z2S BFR2S
BFR1S Z1S1
75
BRLS
Out-of-Step Protection
By transmitting the phase information of the local voltage to the remote terminal, the out-of-step protection can measure the phase difference between the terminals of a transmission line. It detects an out-of-step condition when the difference in the phase angle exceeds 180and trips both terminals. The out-of-step protection can detect an out-of-step condition even with a high rate of slip.
zone
Z2G BFR2G
Z1G BRRG
BFR1G Z1G1
75
BRLG
zone
Z2S BFR2S
BFR1S
Z2G
BFR2G
ZRG Z4G
BRLG
GRL100
Directional Earth Fault Protection (Model 7x1D and 7x2D)
The GRL100 provides directional earth fault protection. Both forward and reverse looking elements are available for inverse time or definite time operation. The system residual voltage is used as the polarizing signal. The residual voltage is obtained by direct measurement or derived internally from the three phase-to-neutral voltages. The directional earth fault elements have a user selectable minimum voltage threshold. DEF protection using telecommunication is provided with forward and reverse looking DEF element. The characteristics are shown in Figure 7.
Backward DEF
The IDMT element has a reset feature with definite time reset. If the reset time is set to instantaneous, then no intentional delay is added. As soon as the energising current falls below the reset threshold, the element returns to its reset condition. If the reset time is set to some value in seconds, then an intentional delay is added to the reset period. If the energising current exceeds the setting for a transient period without causing tripping, then resetting is delayed for a user-definable period. When the energising current falls below the reset threshold, the integral state (the point towards operation that it has travelled) of the timing function (IDMT) is held for that period. This does not apply following a trip operation, in which case resetting is always instantaneous. Definite time overcurrent protection is enabled by the instantaneous overcurrent element and pickup-delay timer. Tripping by each element can be disabled by the scheme switches, and overcurrent backup protection can be blocked by a binary input signal. The definite time earth fault element (EF) can be configured to issue either an alarm and/or trip signal.
-3V0 3I0
Forward DEF
GRL100
IEC60255-8 Thermal Characteristics
Thermal Curves (Cold Curve - no prior load)
1000
100
100
10
10
10
10
I2 t = .Ln 2 ; 2 I (k .I FLC )
IEC60255-8 Cold Curve
2 I 2 IP t = .Ln 2 2 I (k .I FLC )
t = time to trip for constant overload current I (seconds) I = overload current (largest phase current) (pu) IP = previous load current (pu) k.IFLC (or I) = thermal overload current setting (pu) = thermal time constant (seconds) Ln = natural logarithm
Autoreclose
Most faults on HV and EHV overhead transmission lines are transient faults, which are removed following line de-energization. After a short time, the hot gases disperse and the air de-ionizes. After clearing the fault and deionizing the fault arc, reclosing can be performed. GRL100 provides two autoreclose schemes, single-shot autoreclose and multi-shot autoreclose.
Single-shot autoreclose
Single-shot reclosing can provide any of four autoreclose modes; single-phase autoreclose, three-phase autoreclose, single-and three-phase autoreclose and multiphase autoreclose. In the single-phase autoreclose mode, only a faulted phase is tripped, and then reclosed if a single-phase earth fault occurs. In the three-phase autoreclose mode, all three phases are tripped, and then reclosed regardless of the fault mode, whether a single-phase fault or a multi-phase fault has occurred. In the single- and three-phase autoreclose mode, the single-phase is reclosed if a single-phase is tripped and the three phases are reclosed if three phases are tripped.
Multi-shot autoreclose
In a multi-shot autoreclose, two- to four-shot reclosing can be selected. The first shot is selected from any of the four autoreclose modes available in the single-shot autoreclose scheme.
GRL100
If reclosing by the first shot fails, three-phase tripping and reclosing is applied for the second to fourth shots.
Synchronism check
For the correct operation of three-phase autoreclose, voltage and synchronism check are necessary. The characteristics of the synchronism check element are shown in Figure 10.
VB 0 deg
OV Operating zone UV
GRL100 Opt. I/F Optical Fibre Bit rate: 64kbps a) Optical interface
Optical I/F Unit G1IF1 (Option)
f=
where,
180TSYN
Multiplexer
f: : TSYN:
slip cycle synchronism check angle setting synchronism check timer setting
Twisted pair wire with shield CCITT-G703. Bit rate: 64kbps b) Optical interface using multiplexer
GRL100 Elec. I/F Twisted pair wire with shield CCITT-G703. Bit rate: 64kbps
Multiplexer
GRL100
METERING AND RECORDING
Metering and Monitoring
The following power system data is measured continuously and can be displayed on the LCD on the relay fascia, at the local PC, and the remote PC. Local and remote terminal currents (phase, phase to phase, symmetrical components) Differential current and restraint current Voltages (phase, phase to phase, symmetrical components) Voltage phase differential between both terminals of the transmission line Active power and reactive power Frequency Data transmission delay time Currents, voltages and differential current can be indicated as primary or secondary values. Active power and reactive power are indicated as primary values. The user can monitor the following output and status on the LCD and at local/remote PCs - Relay element output - Binary input/output - CB status
Fault Location
Fault location is initiated by relay tripping signals excluding breaker failure, overcurrent backup and out-of-step tipping. It can also be started on receipt of a start signal from external relays. The fault locator measures the distance to fault on the protected line utilizing both the local and remote current & voltages when the current differential protection is applied. In principle, this method of measurement is free from the errors that are inherent with the standard impedance measuring method normally employed. Fault location is indicated in km and % for the whole length of the protected line. The result of fault location calculation is stored as fault record data.
Disturbance Record
The relay can record 19 analog signals and 32 binary signals. The disturbance recorder is initiated by operation of the overcurrent element, undervoltage element or relay tripping. In respect to analog data, the local phase current and voltage, remote phase current and the local and remote zero sequence current are recorded. The data can be transformed into the COMTRADE format. Pre-fault recording time is fixed at 300ms, post-fault recording time can be set from 100ms to 3s. The maximum number of stored records depends on the post-fault recording time. In the case of a post-fault recording time of 500ms, up to 20 disturbance records can be stored. The record number of the recorded data is displayed on the LCD.
Event Record
The most recent 1024 time-tagged events are stored with 1ms resolution. The event items can be assigned to a signal number in the signal list. The status change mode is set to On (only recording On transitions) or On/Off (recording both On and Off transitions) mode by setting. Event items are freely selectable by using PLC. Events recorded are as follows. Tripping and reclosing Alarms Change of binary input signal Change of relay setting Relay failure
USER INTERFACE
Relay Front Panel
The relay front panel incorporates the following user interfaces. Setting the relay and viewing stored data are possible using the Liquid Crystal Display (LCD) and operation keys. - 40 character, 4 line LCD with back light - 8 Light Emitting Diodes (LED) including 4 that are configurable - Operation keys - RS232C port - Monitoring jacks Figure 12 shows the relay front panel. The following items can be displayed on the LCD. - Setting - Metering
Fault Record
A relay trip initiates fault recording. Time-tagged fault data can be stored for the 8 most recent faults. Fault record items are as follows. - Date and time - Faulted phase - Phases tripped - Tripping mode - Fault location - Pre-fault and post-fault current and voltage data (phase, phase to phase, symmetrical components) - Autoreclose operation
GRL100
- Event records - Fault records - The number of disturbance records - Fault location - Any failure message detected by the automatic supervision A maximum of 32 x 8 relays can be connected to the remote PC in multi-drop mode, via the protocol converter. The RSM100 software is also used to communicate with the relay and to view or analyze disturbance records on the remote PC. The data transmission rate between relays and the protocol converter is 64kbps.
TMT&D Corporation
MADE IN JAPAN
G1PR2
DISTANCE PROTECTION
OVERCURRENT RELAY
Metering 1
Metering 1
Ia Ib Ic 0.50A 0.50A 0.50A Va Vb Vc 63.5V 63.5V 63.5V Ia Ib Ic 0.50A 0.50A 0.50A
Va Vb Vc
Ia
0.0 A
VIEW
IN SERVICE
VIEW
TRIP ALARM
VIEW
RS T EE
RS T EE RS T EE
Type Model In Vn fn Vdc
GRD110
400A-11-11 1A -50Hz 110/125V DC Made in Japan
Ty pe Model In Vn fn Vdc
GRL100
201A-11-10 1A 100/110/115/120V 50Hz 110/125V DC MADE IN J APAN
Type Model In
GRZ100
201A-11-10 1A 100/110/115/120V 50Hz 110/125V DC MADE IN JAPAN
7 4 1 0
8 5 2 .
9 6 3 END
CAN CEL
Vn fn Vdc
7 4 1 0
8 5 2 .
9 6 3
END CAN CEL ENTER
0V
0V
END
CAN CEL
ENTER
ENTER
32
IEC60870-5-103 Communication
The relay can support the IEC60870-5-103 communication protocol. This protocol is mainly used when the relay communicates with a control system and is used to transfer the measurand data, status data and general command from the relay to the control system.
Local PC
The user can communicate with the GRL100 from a local PC via the RS232C port on the relay fascia. The following data can be viewed or analysed on the local PC with RSM100 software. - Setting - Metering - Event & Fault records - Disturbance records - Fault location
10
GRL100
Relay Setting
The user can input or change settings using the operation keys on the relay fascia or via a local or remote PC with the RSM system. Password protection is provided to change settings. Eight active setting groups are provided. This allows the user to set one group for normal operating conditions while other groups may be set to cover alternative operating conditions.
PC DISPLAY
Fault record
PLC Function
GRL100 is provided with a PLC (Programmable Logic Control) function allowing user-configurable sequence logics on binary signals. Configurable binary inputs, binary outputs and LEDs are programmed by the PLC function.
Metering
AUTOMATIC SUPERVISION
Automatic Monitoring Function
The automatic monitoring function will detect failures, should they occur, that might cause unwanted operation. The items monitored include the following: - Analog input circuits - Differential current - Analog-to-digital converter - Watch Dog Timer - Binary output circuits - DC power supply circuits - CPU - Telecommunication circuit - Synchronisation control circuit - Relay address monitoring
Alarms
In the unlikely event that a relay failure should occur, this is detected by automatic monitoring and the LED ALARM on the relay fascia is illuminated. A binary RELAY FAILURE output is simultaneously operated and the date/time of any such failure would be stored in the event record. Vector diagram
11
GRL100
TECHNICAL DATA
Ratings
AC current In: AC voltage Frequency: DC power supply: AC ripple on DC supply IEC60255-11 DC supply interruption IEC60255-11 Permissive duration of DC supply voltage interruption to maintain normal operation: Restart time: Binary input circuit DC voltage:
1A or 5A 100V, 110V, 115V, 120V 50Hz or 60Hz 110Vdc/125Vdc (Operative range: 88 - 150Vdc) 220Vdc/250Vdc (Operative range: 176 - 300Vdc) maximum 12%
AC voltage input
Burden AC current input
4 times rated continuous 100 times rated for 1s 2 times rated continuous 0.2VA per phase (at rated 5A) 0.4 VA at zero-sequence circuit (at rated 5A) 0.1VA per phase (at rated 1A) 0.3 VA at zero-sequence circuit (at rated 1A) 0.1VA (at rated voltage) less than16W (quiescent) less than 25W (operation)
0.5W per input at 110Vdc
0.10 to 2.00A in 0.01A steps (1A relay) 0.50 to 10.00A in 0.01A steps (5A relay) 0.6 to 24.0A in 0.1A steps (1A relay) 3.0 to 120.0A in 0.1A steps (5A relay) less than 1 cycle at 300% of DIFI1 less than 110ms (for tripping output) less than 40ms (for signal output)
Zero-sequence Current Differential Protection for high-resistance earth DIFGI 0.05 to 1.00A in 0.01A steps (1A relay) 0.25 to 5.00A in 0.01A steps (5A relay)
0.00 to 10.00s in 0.01s steps less than 45ms less than 100ms 0.00 to 1.00A in 0.01A steps (1A relay) 0.00 to 5.00A in 0.01A steps (5A relay) 0.05 to 2.00A in 0.01A steps (1A relay) 0.25 to 10.00A in 0.01A steps (5A relay) 0 to 60s in 1s steps OFF / TRIP / BO(separated from other trip signals)
Timer
Out-of-step protection
Out-of-step trip
12
GRL100
Telecommunication Interface for current differential protection
Bit rate Transmission format Electrical interface (Telecomm. equipment link) Applicable standard
64kbs IEC60870-5-1 CCITT-G703-1.2.1 CCITT-G703-1.2.2 or 1.2.3 X.21 NRZ (Non-Return to Zero) D-sub connector Graded-index multi-mode 50/125m or 62.5/125m ST type 820nm LED, more than 19dBm(50/125m), 16dBm(62.5/125m) PIN diode, less than 24dBm Single mode 10/125m Duplex LC 1310nm Laser, more than 13dBm PIN diode, less than 30dBm DSF 8/125m Duplex LC 1550nm Laser, more than 5dBm PIN diode, less than 34dBm 0.10 to 250.00 in 0.01 steps (1A relay) 0.01 to 50.00 in 0.01 steps (5A relay) 0.1 to 250.0 in 0.1 steps (1A relay) 0.01 to 50.00 in 0.01 steps (5A relay) 45 to 90 in 1 steps 7.5 fixed (1A relay) 1.5 fixed (5A relay) 0.1 to 250.0 in 0.1 steps (1A relay) 0.01 to 50.00 in 0.01 steps (5A relay) 75 fixed 90 to 135 0.10 to 250.00 in 0.01 steps (1A relay) 0.01 to 50.00 in 0.01 steps (5A relay) 0.1 to 500.0 in 0.1 steps (1A relay) 0.01 to 100.00 in 0.01 steps (5A relay) 45 to 90 in 1 steps 0.5 to 100.0 in 0.1 steps (1A relay) 0.10 to 20.00 in 0.01 steps (5A relay) 75 fixed 90 to 135
Type of code Connector type Optical interface (2 km class) Type of fibre Connector type Wave length Optical transmitter Optical receiver Optical interface (30 km class) Type of fibre Connector type Wave length Optical transmitter Optical receiver Optical interface (80 km class) Type of fibre Connector type Wave length Optical transmitter Optical receiver
Phase Fault Distance Measuring Element
Z1S, Z2S Z3S, ZRS and Z4S Characteristic angle ZRS and Z4S offset Blinder (BFR1S, BFR2S, BFRS, BRRS) BRLS: Linked with BRRS Characteristic angle (BFR1S,BFR2S,BFRS,BRRS) Characteristic angle (BFLS)
Earth Fault Distance Measuring Element
Z1G, Z2G Z3G, ZRG and Z4G Characteristic angle Blinder (BFR1G, BFR2G, BFRG, BRRG) BRLG: Linked with BRRG Characteristic angle (BFR1G,BFR2G,BFRG,BRRG) Characteristic angle (BFLG)
Time Setting for Zone Protection
Time setting of Z1S, Z2S, Z3S, ZRS, Z1G, Z2G, Z3G, ZRG
13
GRL100
Minimum Operating Current of Distance Protection
Current
Residual Current Compensation
0.08A (1A relay), 0.4A (5A relay) Adjustable as follows: 0 to 1000% in 1% steps 0 to 1000% in 1% steps 0 to 50ms in 1ms steps 20ms Less than 30ms (for tripping output) Less than 40ms (for signal output) 2.5 to 75.0 in 0.1 steps (1A relay) 0.50 to 15.00 in 0.01 steps (5A relay) 20 to 60ms in 1ms steps 10 to 60V in 1V steps 0.0 to 250.0 in 0.1 steps (1A relay) 0.0 to 50.0 in 0.1 steps (5A relay) 45 to 90 in 1 steps Automatically set according to residual current compensation setting of reactance element 50 to 100V in 1V steps 10 to 60V in 1V steps 0 to 90 in 1 steps (3I0 lags for 3V0) 1.7 to 21.0V in 0.1V steps 0.10 to 1.00A in 0.01A in 0.01A steps (1A relay) 0.5 to 5.0A in 0.1A steps (5A relay) 0.00 to 10.00s in 0.01s steps 0.00 to 0.30s in 0.01s steps 0 to 50ms in 1ms steps 0.10 to 5.00A in 0.01A steps (1A relay) 0.5 to 25.0A in 0.1A steps (5A relay) 0.05 to 1.00 in 0.01 steps Standard / Very / Extremely / Long-time inverse 0.0 to 10.0s in 0.1s steps 0.10 to 1.00A in 0.01A steps (1A relay) 0.5 to 5.0A in 0.1A steps (5A relay) 0.05 to 1.00 in 0.01 steps Standard / Very / Extremely / Long-time inverse 0.0 to 10.0s in 0.1s steps 0.1 to 20.0A in 0.1A steps (1A relay) 0.5 to 100.0A in 0.1A steps (5A relay) 0.00 to 10.00s in 0.01s steps 0.10 to 1.00A in 0.01A steps (1A relay) 0.5 to 5.0A in 0.1A steps (5A relay) 0.00 to 10.00s in 0.01s steps
Residual current compensation for reactance element of Z1G, Z2G, ZRG Earth return compensation Mutual coupling compensation (ZRG excluded) Command Protection Coordination time for BOP scheme Typical operating time Resetting time
Power Swing Blocking
Detection zone (PSBZS, PSBZG) Detection time Phase Selection Element Undervoltage Impedance Characteristic angle Residual current compensation
Weak Infeed and Echo Protection
Phase-to-phase undervoltage element Phase-to-earth undervoltage element Directional Earth Fault Protection Characteristic angle Polarising voltage (3V0) Zero-sequence current (3I0) Time for backup trip
Directional Earth Fault Command Protection
Time for delayed trip Coordination time Inverse Time Overcurrent Protection OCI (for phase fault protection) OCI time multiplier OCI characteristic Reset time delay EFI (for earth fault protection) EFI time multiplier EFI characteristic Reset time delay
Definite Time Overcurrent Protection OC (for phase fault protection)
14
GRL100
Overvoltage Protection
Phase-to-phase element (OVS) 1st, 2nd Overvoltage thresholds: Delay type (1st threshold only): IDMTL Time Multiplier Setting TMS: DTL delay: Dropout / Pickup ratio: Phase-to-earth element (OVG) 1st, 2nd Overvoltage thresholds: Delay type (1st threshold only): IDMTL Time Multiplier Setting TMS: DTL delay: Dropout / Pickup ratio: OFF, 5.0 150.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps 10 to 98% in 1% steps OFF, 5.0 150.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps 10 to 98% in 1% steps
Undervoltage Protection
Phase-to-phase element (UVS) 1st, 2nd Undervoltage thresholds: Delay type (1st threshold only): IDMTL Time Multiplier Setting TMS: DTL delay: Undervoltage block threshold: Phase-to-earth element (UVG) 1st, 2nd Undervoltage thresholds: Delay type (1st threshold only): IDMTL Time Multiplier Setting TMS: DTL delay: Undervoltage block threshold:
Thermal Overload Protection Thermal setting (THM = k.IFLC)
OFF, 5.0 150.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps 5.0 to 20.0V in 1V steps OFF, 5.0 150.0V in 0.1V steps DTL, IDMTL 0.05 - 100.00 in 0.01 steps Inst, 0.01 - 300.00s in 0.01s steps 5.0 to 20.0V in 1V steps OFF, 0.40 2.00A in 0.01A steps (1A rating) OFF, 2.0 10.0A in 0.1A steps (5A rating) 0.5 300.0mins in 0.1min steps OFF, 50% to 99% in 1% steps 0.00 1.00A in 0.01A steps (1A rating) 0.0 5.0A in 0.1A steps (5A rating) 0.4 to 3.0A in 0.1A steps (1A relay) 2.0 to 15.0A in 0.1A steps (5A relay) OFF, 0.10 - 1.00 in 0.01 steps 0.00 to 300.00s in 0.01s steps 0.1 to 2.0A in 0.1A steps (1A relay) 0.5 to 10.0A in 0.1A steps (5A relay) less than 80% of operating value 50 to 500ms in 1ms steps 50 to 500ms in 1ms steps less than 20ms at 50Hz or 17ms at 60Hz less than 15ms at 50Hz or 13ms at 60Hz
Overcurrent
Broken Conductor Detection
Reset BF timer for retry-trip of failed circuit breaker BF timer for adjacent circuit breaker tripping Operating time of overcurrent element Resetting time of overcurrent element
15
GRL100
Accuracy
Current differential protection: pick-up Distance measuring element Static accuracy Static angle accuracy Transient overreach Inverse time overcurrent characteristics Definite time overcurrent protection: pick-up Overcurrent element for BF: pick-up
Autoreclose function
5% (7% at I < 0.3In) 5% under SIR < 30, 5 +5% 5% 5% 10% under 30 < SIR < 50
Number of shots Timer settings Dead time for single-phase autoreclose Dead time for three-phase autoreclose Multi-shot dead line time Multi-shot reset time Reclaim time Pulse width of reclosing signal output Autoreclose reset time Reset time for developing fault One-and-a-half breaker system Follower breaker autoreclose delay time Voltage and synchronism check element Synchronism check angle UV element OV element Busbar or line dead check Busbar or line live check Synchronism check time Voltage check time
Voltage Transformer Failure Supervision
1 to 4 shots 0.01 to 10.00s in 0.01s steps 0.01 to 100.00s in 0.01s steps 5.0 to 300.0s in 0.1s steps 5.0 to 300.0s in 0.1s steps 5 to 300s in 1s steps 0.1 to 10.0s in 0.1s steps 0.01 to 100.00s in 0.01s steps 0.01 to 10.00s in 0.01s steps 0.1 to 10.0s in 0.1s steps 5 to 75 in 1 steps 60 to 150V in 1V steps 10 to 100V in 1V steps 10 to 100V in 1V steps 10 to 100V in 1V steps 0.01 to 10.00s in 0.01s steps 0.01 to 1.00s in 0.01s steps 50 to 100V in 1V steps 10 to 60V in 1V steps 0.1A fixed (1A relay) 0.5A fixed (5A relay) 20V fixed Common use with earth fault detection element 0.0 to 999.9 in 0.1 steps (1A relay) 0.00 to 199.99 in 0.01 steps (5A relay) 0.0 to 399.9km in 0.1km steps
1km (up to 100km) or 1% (up to 399.9km at DIFI=0.5In setting and Id=2In 2km (up to 100km) or 2% (up to 399.9km at DIFI=0.25In setting and Id=2In
Undervoltage element (phase-to-phase) Undervoltage element (phase-to-earth) Current change detection element Residual voltage element Residual current element
Fault Locator Line resistance and reactance settings
Line length Accuracy Two terminal Three terminal Minimum measuring cycles
Disturbance Record Initiation Overcurrent element
2 cycles 0.1 to 50.0A in 0.1A steps (1A relay) 0.5 to 250.0A in 0.1A steps (5A relay) 0 to 132V in 1V steps (for phase fault) 0 to 76V in 1V steps (for earth fault) 0.3s (fixed) 0.1 to 3.0 in 0.1s steps
16
GRL100
Communication Port Front communication port (local PC) Connection Cable type Cable length Connector Rear communication port (remote PC) RS485 I/F: Transmission data rate for RSM system Connection Connector Cable and length Isolation Fibre optic I/F:
Point to point Multi-core (straight) 15m (max.) RS232C 9-pin D-sub miniature connector female
64kbps Multidrop mode (max. 32 relays) Screw terminals Twisted pair cable, max. 1200m 2kVac for 1min. ST connector, graded-index multi-mode 50/125m or 62.5/125m type optical fibres 100BASE-TX: RJ-45 connector 100BASE-FX: SC connector BNC connector 50 ohm coaxial cable Typical 74Vdc(min.70Vdc) for 110V/125Vdc rating Typical 138Vdc(min.125Vdc) for 220V/250Vdc rating
Operating voltage
Contact Ratings Trip contacts Make and carry
Break Auxiliary contacts Make and carry Break Durability Make and carry Break
Mechanical design Weight Case colour Installation
5A continuously, 30A, 290Vdc for 0.5s (L/R=10ms) 0.15A, 290Vdc (L/R=40ms) 4A continuously, 10A, 220Vdc for 0.5s (L/R5ms) 0.1A, 220Vdc (L/R=40ms) 10,000 operations minimum 100,000 operations minimum 11kg (Type-A), 14kg (Type-B) 2.5Y7.5/1(approximation to Munsell value) Flush mounting or rack mounting
17
GRL100
ENVIRONMENTAL PERFORMANCE
Test Standards Details Atmospheric Environment Temperature IEC60068-2-1/2
Operating range: -10C to +55C. Storage / Transit: -25C to +70C. 56 days at 40C and 93% relative humidity. IP51 (Rear: IP20) Response - Class 1 Endurance - Class 1 Shock Response Class 1 Shock Withstand Class 1 Bump Class 1 Class 1 2kVrms for 1 minute between all terminals and earth. 2kVrms for 1 minute between independent circuits. 1kVrms for 1 minute across normally open contacts. Three positive and three negative impulses of 5kV(peak), 1.2/50s, 0.5J between all terminals and between all terminals and earth. 1MHz 2.5kV applied to all ports in common mode. 1MHz 1.0kV applied to all ports in differential mode.
IEC60068-2-78 IEC60529
IEC60255-21-2
Seismic
IEC60255-21-3
IEC60255-5
Electromagnetic Environment IEC60255-22-1 Class 3, High Frequency IEC61000-4-12 / Disturbance / EN61000-4-12 Damped Oscillatory Wave Electrostatic IEC60255-22-2 Class 3, Discharge IEC61000-4-2 / EN61000-4-2 Radiated RF IEC60255-22-3 Class 3, Electromagnetic IEC61000-4-3 / Disturbance EN61000-4-3 Fast Transient IEC60255-22-4, Disturbance IEC61000-4-4 / EN61000-4-4 Surge Immunity IEC60255-22-5, IEC61000-4-5 / EN61000-4-5
Field strength 10V/m for frequency sweeps of 80MHz to 1GHz and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450, 900 and 1890MHz. 4kV, 2.5kHz, 5/50ns applied to all inputs.
Conducted RF Electromagnetic Disturbance Power Frequency Disturbance Conducted and Radiated Emissions
IEC60255-22-6 Class 3, IEC61000-4-6 / EN61000-4-6 IEC60255-22-7, IEC61000-4-16 / EN61000-4-16 IEC60255-25, EN55022 Class A, IEC61000-6-4 / EN61000-6-4
1.2/50s surge in common/differential modes: HV ports: 2kV/1kV (peak) PSU and I/O ports: 2kV/1kV (peak) RS485 port: 1kV (peak) 10Vrms applied over frequency range 150kHz to 100MHz. Additional spot tests at 27 and 68MHz. 300V 50Hz for 10s applied to ports in common mode. 150V 50Hz for 10s applied to ports in differential mode. Not applicable to AC inputs. Conducted emissions: 0.15 to 0.50MHz: <79dB (peak) or <66dB (mean) 0.50 to 30MHz: <73dB (peak) or <60dB (mean) Radiated emissions (at 30m): 30 to 230MHz: <30dB 230 to 1000MHz: <37dB
18
GRL100
Optical Interface Unit G1IF1 (Option)
Ratings Power supply:
110Vdc/125Vdc (Operative range: 88 - 150Vdc) 220Vdc/250Vdc (Operative range: 170 - 300Vdc) 48Vdc/54Vdc/60Vdc (Operative range: 38.4 - 72Vdc) less than 8W CCITT-G703-1.2.1 CCITT-G703-1.2.2 or 1.2.3 X.21 less than 1.2km with 62.5/125m GI fibre (3dB/km) 820nm ST 62.5/125m GI fibre Operating range: -10C to +55C. Storage / Transit: -25C to +70C. 56 days at 40C and 93% relative humidity. IP40 (excluding terminal parts)
Burden:
Interface Communication interface:
IEC60068-2-78 IEC60529
110Vdc/100Vac (Operative range: 88 - 150Vdc of 110Vdc rated voltage, 80 - 120Vac of 100Vac rated voltage) 220Vdc/200Vdc (Operative range: 170 - 300Vdc of 220Vdc rated voltage, 200 - 240Vac of 200Vac rated voltage.) 48Vdc (Operative range: 38.4 - 72Vdc) less than 20W RS485 or Optical interface less than 1.2km with 62.5/125m GI fibre (3dB/km) 820nm ST 62.5/125m glass fibre
Burden:
Interface Interface: Optical interface Operative Range: Wavelength: Connector type: Fibre type: Contact Ratings Auxiliary contacts Make and carry
4A continuously, 10A, 220Vdc for 0.5s (L/R 5ms) 0.1A, 220Vdc (L/R=40ms) 10,000 operations minimum 100,000 operations minimum Operating range: -10C to +55C. Storage / Transit: -25C to +70C. 56 days at 40C and 93% relative humidity. IP20
IEC60068-2-78 IEC60529
19
GRL100
ORDERING
1. Line Differential Protection Relay a. Two-terminal application
Relay Type: Line differential protection relay Relay Model: -Model200: With autoreclose for single breaker scheme 25 BIs, 19 BOs, 6 trip BOs -Model300: With autoreclose for one and a half breaker scheme 31 BIs, 37 BOs, 6 trip BOs -Model700: With autoreclose for one-and-a-half breaker scheme / with distance protection scheme 25 BIs, 19 BOs, 6 trip BOs 31 BIs, 37 BOs, 6 trip BOs Ratings: 1A, 50Hz, 110V/125Vdc 1A, 60Hz, 110V/125Vdc 5A, 50Hz, 110V/125Vdc 5A, 60Hz, 110V/125Vdc 1A, 50Hz, 220V/250Vdc 1A, 60Hz, 220V/250Vdc 5A, 50Hz, 220V/250Vdc 5A, 60Hz, 220V/250Vdc Differential relay communication interface: Electrical interface (CCITT-G703-1.2.1) Electrical interface (CCITT-G703-1.2.2 or 1.2.3) Optical interface (Short wavelength light: GI: 2km class) Optical interface (Long wavelength light: SM: 30km class) Optical interface (Long wavelength light: DSF: 80km class) Communications: RS485 + 100BASE-TX RS485 + 100BASE-FX Fibre opt. + 100BASE-FX Miscellaneous None GRL100
GRL100
201 302
701 702 1 2 3 4 5 6 7 8
1 2 3 6 7
A B E
Note: Please inform us which is ordered panel surface mount type or 19-inch rack mount type. In 19 inch rack mount type, please order optional attachment kit. - for relay case Type-A attachment kit: EP101 - for relay case Type-B attachment kit: EP102
Terminal A Terminal B
GRL100
Communication route
GRL100
20
GRL100
b. Dual channel or Three-terminal application
Relay Type: Line differential protection relay Relay Model: -Model200: With autoreclose for single breaker scheme 25 BIs, 19 BOs, 6 trip BOs -Model300: With autoreclose for one and a half breaker scheme 31 BIs, 37 BOs, 6 trip BOs -Model700: With autoreclose for single breaker scheme / with distance protection scheme 25 BIs, 19 BOs, 6 trip BOs 31 BIs, 37 BOs, 6 trip BOs Ratings: 1A, 50Hz, 110V/125Vdc 1A, 60Hz, 110V/125Vdc 5A, 50Hz, 110V/125Vdc 5A, 60Hz, 110V/125Vdc 1A, 50Hz, 220V/250Vdc 1A, 60Hz, 220V/250Vdc 5A, 50Hz, 220V/250Vdc 5A, 60Hz, 220V/250Vdc Differential relay communication interface: Electrical interface (CCITT-G703-1.2.1) 2 Electrical interface (CCITT-G703-1.2.2 or 1.2.3) 2 Optical interface(Short wavelength light: GI: 2km class) 2 Optical interface(Long wavelength light: SM: 30km class) 2 Optical interface(Long wavelength light: DSF: 80km class) 2 Optical I/F (2km class) + Optical I/F (80km class) Communications: RS485 + 100BASE-TX RS485 + 100BASE-FX Fibre opt. + 100BASE-FX Miscellaneous None 1 2 3 6 7 H A B E 1 2 3 4 5 6 7 8 GRL100
GRL100
211 312
711 712
Note: Please inform us which is ordered panel surface mount type or 19-inch rack mount type. In 19 inch rack mount type, please order optional attachment kit. - for relay case Type-A attachment kit: EP101 - for relay case Type-B attachment kit: EP102
Terminal A
Terminal B
GRL100
Communication route
GRL100
21
GRL100
2. Optical Interface Unit (Option)
G1IF1 Type: Communication interface box Model: For X.21 For CCITT-G703-1.2.1 For CCITT-G703-1.2.2 or 1.2.3 Auxiliary power supply: DC 48V / 54V / 60V DC 110V / 125V DC 220V / 250V 01 02 03 01 02 03 G1IF1
22
GRL100
RELAY OUTLINE
28
65
23
GRL100
19-inch rack mount
(option)
(option)
24
GRL100
Outline of Optical interface unit
2- 5
130
195
156
RX 12
TX
CLK
SPARE
66
2-5x9
168 180
POWER
OFF ON
RS232C
P FG N
1 2
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3 TB2
TB1
RS485-1
RS485-2
RS485-3
RS485-4
RS485-5
RS485-6
RS485-7
RS485-8
SG
FG
200
TX 1 2 3 4 5 6 7 8 4-7.1 1 2 3 4 5 6 7 8 RX
PROTOCOL CONVERTER Type G1PR2 Model 180A-10- Power 110Vdc/100Vac Made in Japan
57.1 115
108.3
25
GRL100
EXTERNAL CONNECTION DIAGRAM
BUS BUS VT TB1 -1 2 3 4 5 6 7 8
BO1
B1 A2
CT
BO2
CB
B2 A3
BO3
B3 A4
BO5
B4 A5
BO4
B4 A5
VT
12 13 14
BO6
B5 A6
BO5
B5 A6
BO7
BUS VT (1) [Default setting] CB1 contacts (Closed when CB main contact closed.) (+)
52A (A-p h.) 52B (B-p h.) 52C (C-p h.) TB4-A4 B4 A5 B5 A6 B6
B6 A7
BO6
B6
15 16 20 (CASE EARTH)
BO8
B7 A8
IO#3
BO9
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25
IO#3 IO#2 IO#1
B8 A9
BO10
B9 A10
BO11
B10 A11 (HIGH SPEED RELAY) (HIGH SPEED RELAY) RELAY FAILURE
Disconnector N/O contact Disconnector N/C contact Dif. protection block (#43C) External CB close signal DC power supply Transfer trip command 1 Transfer trip command 2 Indication reset Backup protection block (#43BU)
A-ph B-ph C-ph A-ph
A7 B7 A8 B8 A9 B9 A10 B10 A11 (-) B11 TB3-A14 B14 A15 (-) B15 TB2-A7 B7 A8 B8 A9
BO12
B11 A13
BO13 FAIL
CN2
Interlink signals, Model 201 (Parallel line interlink signal for Term1) CB1 ARC ready (Bus CB)
B-ph. C-ph.
COM-A COM-B 0V
IO#1: IO1 module IO#2: IO2 module IO#3: IO6 module RS485 I/F (*1)
TB4 CN2
A1
TB3 TB2
B1
B1
CN1 (IRIG-B) E
ARC reset
(-)
B9 A10 B10
IO#3
A18 B18
B10 1
TB1
2
IO#1
IO#2
19
20
VCT
B1
B1
CN1 (IRIG-B) E
(*)
A1 A2 B2
B10 1
TB1
IO#3
A18 B18 19 20
TP-B1 TP-C1
IO#1
IO#2
VCT
Model GRL100-2x1D
Note GRL100-201: 2 terminal system, not provided with terminals marked with (*). GRL100-211: 3 terminal system
E (CASE EARTH)
GRL100
BUS BUS VT
TB2- A2
TB1 -1 2 3 4 5 6 7 8
TB3- A2 BO1 BO2 BO3 A1 B1 BO2 B2 A3 BO4 B3 A4 BO5 B4 A5 BO6 B5 A6 BO7 B6 A7 BO8 B7 A8 BO7 BO6 BO5 BO4 BO3 BO1
TB5-A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8
A1 B1 B2 A3 BO4 B3 A4
CT
CB
CB CT VT 11 12 13 14 CB 15 16 17 18 20 (CASE EARTH)
BO5
B4 A5
BO6
B5 A6
BO7
B6 A7
BUS
BO8
B7 A8
BO9
B8 A9
BO9
B8 A9
(1) [Default setting] CB1 contacts (Closed when CB main contact closed.) CB2 contacts (Closed when CB main contact closed.) Disconnector N/O contact Disconnector N/C contact Dif. protection block (#43C) External CB close signal DC power supply Transfer trip command 1 Transfer trip command 2 Indication reset Backup protection block(#43BU)
A-ph B-ph C-ph A-ph . B-ph . C-ph .
BO8
B8 A9
(+)
52A ( A-ph.) 52B ( B-ph.) 52C ( C-ph.) 52A ( A-ph.) 52B (B-ph.) 52C (C-ph.) TB4-A 4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 (-) B11 TB 2-A14 B14 A15 (-) B15 TB5-A12 B12 A13 B 13 A 14 B 14 A15 A-ph B15 A16 B 16 (-) A18 TB3-A1 4 B14 A15 B15
BO10
B9 A10
BO10
B9 A10
BO9
B9 A10
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28
I O#3 IO#2 I O#1
BO11
B10 A11 (HIGH SPEED B11 RELAY) A13 (HIGH SPEED B13 RELAY) A12 RELAY B12 FAILURE
BO11
B10
BO12
BO12
B11 A12
IO#3
BO13 FAIL
BO13
B12 A13
BO14
B13
IO#4
CN2
External trip signals (Reclose & CBF Initiation) Interlink signals (Parallel line interlink signal for terminal 1) CB1 ARC ready(Bus CB) CB2 ARC ready(Center CB) ARC reset
Communication Links
COM-A COM-B 0V
TB3 CN2
Interlink signals (Parallel line interlink signal for terminal 2, used for Model 312.)
B-ph C-ph
A18
B18
IO#2
19
20
VCT
A1
TB2
B1
IRIG-B TB4- A3 B3 TP-A1 A1 A2 B2 (+) TRIP-A TRIP-B TRIP-C (+) TRIP-A TRIP-B TRIP-C BUS CB
CH2 TX2
(*)
RX2
RELAY FAIL. DD FAIL. DC SUPPLY TB4 -A16 (+) B16 A17 (-) B17 A18 B18 A15 (1) B15 DC-DC
TP-B1 TP-C1
+5Vdc 0V
A18
B18
IO#3
IO#1
IO#4
IO#2
19
20
VCT
Model GRL100-3x2D
Note GRL100-302: 2 terminal system, not provided with terminals marked with (*). GRL100-312: 3 terminal system
E (CASE EARTH)
GRL100
TB3- A2
BUS BUS VT
BO1
TB1 -1 2 3 4 5 6 7 8 9 10
BO2 BO3
CT
CB
CB CT
11 VT 12 13 14 CB 15 16 17 18 20 (CASE EARTH)
TB4- A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 TB3- A14 B14 (-) A15 B15 TB2- A7 B7 A8 B8 A9 B9 A10 B10
BUS
BO8
B7 A8
IO#3
BO9
B8 A9
(1) [Default Setting] CB1 contacts (Closed when bus CB main contact closed.) CB2 contacts (Closed when center CB main contact closed.) Disconnector N/O contact Disconnector N/C contact Carrier from remote 1 Carrier from remote 2 DC power supply Transfer trip command 1 Transfer trip command 2 DEF carrier from remote 1 DEF carrier from remote 2
A-p h (-)
(+)
52A (A-ph.) 52B (B-ph.) 52C (C-ph.) 52A (A-ph.) 52B (A-ph.) 52C (A-ph.)
BO10
B9 A10
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25
RJ45 ST SC
IO#3 IO #2 IO#1
BO11
B10 A11 (HIGH SPEED RELAY) (HIGH SPEED RELAY) RELAY FAILURE
BO12
B11 A13
BO13 FAIL
TX1 CH1 RX1 CK1 TX2 (*)CH2 RX2 CK2 CH1 TX1 RX1 TX2 RX2
External trip signals (Reclose & CBF Initiation) Dif. protection block (#43C) External CB close Indication reset CB1 ARC ready (Bus CB) CB2 ARC ready (Center CB) ARC reset
(*) CH2
COM-A COM-B 0V
TB3 TB2
B1
B1 (IRIG-B)
CN1
CN2 E
B10 1
( -)
TB1
2
IO#3
A18 B18
IO#2
19
20
VCT
A1
TB3 TB2
B1
B1 (IRIG-B)
CN1
RELAY FAIL. DD FAIL. DC SUPPLY TB4 -A16 (+) B16 A17 (-) B17 A18 B18 A15 (1) B15 DC-DC
E
B10 1
TP-A1
+5Vdc 0V
A1 A2 B2
(*)
TB1
2
TP-B1 TP-C1
IO#3
A18 B18
IO#1
IO#2
19
20
VCT
E (CASE EARTH)
TP-B2 TP-C2
Model GRL100-7x1D
Note GRL100-701: 2 terminal system, not provided with terminals marked with (*). GRL100-711: 3 terminal system
GRL100
BUS BUS VT
TB2- A2
TB1 -1 2 3 4 5 6 7 8 9 10 11
TB3- A2 BO1 BO2 BO3 A1 B1 BO2 B2 A3 BO4 B3 A4 BO5 B4 A5 BO6 B5 A6 BO7 B6 A7 BO8 B7 A8 BO7 BO6 BO5 BO4 BO3 BO1
TB5-A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8
CT
CB
CB CT
VT
12 13 14
CB 15 16 17 18 (1) [Default setting] CB1 contacts (Closed when CB main contact closed.) CB2 contacts (Closed when CB main contact closed.) Disconnector N/O contact Disconnector N/C contact Carrier from remote 1 Carrier from remote 2 DC power supply Transfer trip command 1 Transfer trip command 2 DEF Carrier from remote 1 DEF carrier from remote 2
A-ph B-ph C-ph
BUS
20 (CASE EARTH)
BO9
B8 A9
BO8
B8 A9
(+)
52A ( A-ph.) 52B ( B-ph.) 52C ( C-ph.) 52A ( A-ph.) 52B (B-ph.) 52C (C-ph.) TB4-A 4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 (-) B11 TB 2-A14 B14 A15 (-) B15 TB5-A12 B12 A13 B 13 A 14 B 14 A15 B15 A16 B 16 (-) A18 TB3-A1 4 B14 A15 B15
BO10
B9 A10
BO9
B9 A10
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28
I O#3 IO#2 I O#1
BO11
B10 A11 (HIGH SPEED B11 RELAY) A13 (HIGH SPEED B13 RELAY) A12 RELAY B12 FAILURE
BO11
B10
BO12
BO12
B11 A12
IO#3
BO13 FAIL
BO13
B12 A13
BO14
B13
IO#4
CN2
External trip signals (Reclose & CBF Initiation) Dif. protection block (#43C) External CB close Indication reset CB1 ARC ready(Bus CB) CB2 ARC ready(Center CB) ARC reset
Communication Links
COM-A COM-B 0V
TB3
A18
B18
IO#2
19
20
VCT
A1
TB2
B1
CN1 (IRIG-B) E
IRIG-B TB4- A3 B3 TP-A1 A1 A2 B2 (+) TRIP-A TRIP-B TRIP-C (+) TRIP-A TRIP-B TRIP-C BUS CB
CH2 TX2
(*) TB1
1 2
RX2
RELAY FAIL. DD FAIL. DC SUPPLY TB4 -A16 (+) B16 A17 (-) B17 A18 B18 A15 (1) B15 DC-DC
TP-B1
1
A18
B18
IO#3
IO#1
IO#4
IO#2
19
20
VCT
TP-C1
+5Vdc 0V
Model GRL100-7x2D
Note GRL100-702: 2 terminal system, not provided with terminals marked with (*). GRL100-712: 3 terminal system
E (CASE EARTH)
GRL100
BUS BUS VT
TB2- A2 TB3- A2 BO1 BO2 BO3 B2 A3 BO4 B3 A4 BO4 A1 B1 BO2 B2 A3 B3 A4 BO5 B4 A5 BO6 B5 A6 BO7 B6 A7 BO8 B7 A8 A8 BO9 B8 A9 BO10 B9 A10 BO11 B10 A11 B11 A12 B12 A13 B13 BO10 BO9 BO8 B8 A9 B9 A10 B10 BO7 BO6 BO5 BO4 BO3 BO1 TB5-A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7
CT
CB
TB1 -1 2 3 4 5 6 7 8
A1 B1
CB CT VT 11 12 13 14 CB 15 16 17 18 20
BO6 BO5
B4 A5 B5 A6
BO7
B6 A7
BUS
BO8
B7 A8
BO9
B8 A9
[Default setting] CB1 contacts (Closed when CB main contact closed.) CB2 contacts (Closed when CB main contact closed.) Disconnector N/C contact Ditto for monitoring Dif. protection block (#43C) External CB close signal DC power supply Transfer trip command 1 Transfer trip command 2 Indication reset
(+)
52A (A-ph.) 52B (B-ph.) 52C (C-ph.) 52A (A-ph.) 52B (B-ph.) 52C (C-ph.) TB4-A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 (-) A11 B11 TB2-A14 B14 A15 (-) B15 TB5-A12 B12 A13 B13 A14 B14 A15 A-ph B15 A16 B16 (-) A18 TB3-A14 B14 A15 B15
BO10
B9 A10
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28
IO#3 IO#2 IO#1
BO11
B10 A11
BO12
BO13 FAIL
(HIGH SPEED BO12 B11 RELAY) A13 (HIGH SPEED BO13 B13 RELAY) A12 RELAY BO14 B12 FAILURE
IO#3
IO#4
CN2
TX CH1 RX CK TX (*)CH2 RX CK CH1 TX RX
TB2-A18 A17 A16 B18 B17 B16 Two ports RS485 I/F (option)
COM1-A COM1-B
Communication Links
COM1-0V
External trip signals (Reclose & CBF Initiation) Interlink signals (Parallel line interlink signal for terminal 1) CB1 ARC ready(Bus CB) CB2 ARC ready(Center CB) ARC block
TX (*) CH2 RX
COM-A COM-B 0V
TB3
TB2
B1
Interlink signals (Parallel line interlink signal for terminal 2, used for Model 312.)
B-ph C-ph
A18
B18
IO#2
19
20
VCT
A1
TB2
B1
(*)
RX2
RELAY FAIL. DD FAIL. DC SUPPLY TB4 -A16 (+) B16 A17 (-) B17 A18 B18 A15 (1) B15 DC-DC
A18
B18
TP-C1
IO#2
19
20
VCT
+5Vdc 0V
Model GRL100-3*2
Note GRL100-302: 2 terminal system, not provided with terminals marked with (*). GRL100-312: 3 terminal system
E (CASE EARTH)
GRL100
BUS BUS VT TB1 -1 2 3 4 5 6 7 8
BO1 BO2 BO3
TB2- A2 A1 B1 A2 B2 A3
BO4 BO2 BO2
TB3-A1
BO1
TB5-A1
BO1
CT CB
B1
B1 A2 B2 A3
B2 A3
BO3
B3 A4
BO3
11 VT 12 13 14
BO5
B3 A4
BO4
B3 A4 B4 A5
B4 A5
BO4
B4 A10
BO5
BO6
B5 A6
BO5
B5 A6
B10 A11
BO6
BUS VT
15 16 20
BO7
B6 A7
BO6
B6 A7
B11 A12
BO7
BO8
B7 A8
BO7
B7 A8
(+)
52A (A-ph.) 52B (B-ph.) 52C (C-ph.) TB4-A4 B4 A5 B5 A6 B6
B12 A13
BO8
BO9
B8 A9
BO8
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28 0V
IO#3 (*) CH2 IO#2 IO#1
B8 A9
BO10
B9 A10
B9 A10
BO11
B10 A11 (HIGH SPEED RELAY) (HIGH SPEED RELAY) RELAY FAILURE
FD2
(+)
BO10
Disconnector N/C contact Ditto for monitoring Dif. protection block (#43C) External CB close signal DC power supply Transfer trip command 1 Transfer trip command 2 Indication reset Backup protection block(#43BU)
A-ph (-)
A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 TB2-A14 B14 A15 (-) B15 TB5-A12 B12 A13 B13 A14
B10
BO12
B11 A13
BO13
(+)
IO#3
FAIL
IO#4
COM2-A COM2-B TB2-A18 A17 A16 B18 B17 B16 Two ports RS485 I/F (option)
CN2
External trip signals (Reclose & CBF Initiation) Interlink signals (Parallel line interlink signal for terminal 1) CB1 ARC ready(Bus CB) ARC block
Communication Links
COM-A COM-B
Interlink signals (Parallel line interlink signal for terminal 2, used for Model 411.)
TB3
TB2
B-ph C-ph
B1
CN1 (IRIG-B) E
TB1
A18
IO#2
B18 19
20
IRIG-B TB4- A3 B3 RELAY FAIL. DD FAIL. DC SUPPLY TB4 -A16 (+) B16 A17 (-) B17 A18 B18 A15 (1) B15
TP-B1
VCT
()Caution:
Connect FD output contact with A- to C-phase tripping output contacts in series.
TB5
A1
TB2
B1
CN1 (IRIG-B) E
TP-A1
A1 A2 B2
DC-DC
+5Vdc 0V
TP-C1
(*)
1
TB1
2
TB4-A14 B14
TP-A2 TP-B2
A18
B18
IO#3
IO#1
IO#4
IO#2
19
20
VCT
E (CASE EARTH)
TP-C2
Model GRL100-4*1
Note GRL100-401: 2 terminal system, not provided with terminals marked with (*). GRL100-411: 3 terminal system
32
GRL100
BUS
TB2- A2 BO1
BUS VT TB1 -1 2 3 4 5 6 7 8
TB5-A1 B1 A2 B2 A3 B3 A4 B4 A5
BO2 BO3
CT
CB
CB
BO5
CT VT 11 12 13 14 CB 15 16 17 18 20
B4 A5
BO6
B5 A6 BO5
A10 B10 A11 BO6 B11 A12 BO7 B12 A13 BO8 B13 A17 B17 A18 B18 FD1 A15 B15 A16 B16 (+)
BO5
B5 A6
BO7
B6 A7 BO6
B6 A7
BUS
BO8
B7 A8
BO7
B7 A8
BO9
B8 A9
BO8
B8 A9
BO10
[Default setting] CB1 contacts (Closed when CB main contact closed.) CB2 contacts (Closed when CB main contact closed.) Disconnector N/C contact Ditto for monitoring Dif. protection block (#43C) External CB close signal DC power supply Transfer trip command 1 Transfer trip command 2 Indication reset Backup protection block(#43BU)
A-ph
B9 A10
(+)
52A (A-ph.) 52B (B-ph.) 52C (C-ph.) 52A (A-ph.) 52B (B-ph.) 52C (C-ph.) TB4-A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 (-) TB2-A14 B14 A15 (-) B15 TB5-A12 B12 A13 B13 A14 B14 A15 A-ph B15 A16 B16 (-) A18
B9 A10 B10
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28
IO#3 IO#2 IO#1
BO11
B10 A11 (HIGH SPEED RELAY) (HIGH SPEED RELAY) RELAY FAILURE
FD2
BO12
B11 A13
BO13 FAIL
IO#3
IO#4
CN2
TX CH1 RX CK TX (*) CH2 RX CK TX CH1 RX (*) CH1 TX RX COM2-A COM2-B TB2-A18 A17 A16 B18 B17 B16 Two ports RS485 I/F (option)
COM2-0V
Communication Links
External trip signals (Reclose & CBF Initiation) Interlink signals (Parallel line interlink signal for terminal 1) CB1 ARC ready(Bus CB) CB2 ARC ready(Center CB) ARC block
COM-A COM-B 0V
TB3
TB2
B1
Interlink signals (Parallel line interlink signal for terminal 2, used for Model 511.)
B-ph C-ph
IO#3
IO#1
IO#4
B18 19
20
IO#2
VCT
TB4- A3 B3 TP-A1
RELAY FAIL. DD FAIL. TB4 -A16 (+) B16 DC A17 SUPPLY (-) B17 A18 B18 (1)These connections are connected A15 (1) B15 by short-bars before shipment. 1
()Caution:
Connect FD output contact with A- to C-phase tripping output contacts in series.
TB5
TB4
TB3
CN2
CH1 TX1 RX1 CH2 TX2
A1
TB2
B1
A1 A2 B2
(*)
RX2
TP-B1 TP-C1
A18
B18
DC-DC
+5Vdc 0V
IO#3
IO#1
IO#4
IO#2
19
20
VCT
Model GRL100-5*1
Note GRL100-501: 2 terminal system, not provided with terminals marked with (*). GRL100-511: 3 terminal system
E (CASE EARTH)
GRL100
BUS
TB2- A2 BO1
BUS VT TB1 -1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TB5-A1 B1 A2 B2 A3 B3 A4 B4 A5
BO2 BO3
CT
CB
CB CT
BO5
B4 A5
BO6
B5 A6 BO5
A10 B10 A11 BO6 B11 A12 BO7 B12 A13 BO8 B13 A17 B17 A18 B18 FD1 A15 B15 A16 B16 (+)
BO5
B5 A6
BO7
B6 A7 BO6
B6 A7
BO8
B7 A8
BO7
B7 A8
BO9
B8 A9
BO8
B8 A9
BO10
B9 A10
BUS
B9 A10 B10
BO11
B10 A11 (HIGH SPEED RELAY) (HIGH SPEED RELAY) RELAY FAILURE
FD2
BO12
[Default setting] CB1 contacts (Closed when CB main contact closed.) CB2 contacts (Closed when CB main contact closed.) Disconnector N/C contact Ditto for monitoring Dif. protection block (#43C) External CB close signal DC power supply Transfer trip command 1 Transfer trip command 2 Indication reset Backup protection block(#43BU)
A-ph (-)
B11 A13
(+)
52A (A-ph.) 52B (B-ph.) 52C (C-ph.) 52A (A-ph.) 52B (B-ph.) 52C (C-ph.) TB4-A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 TB2-A14 B14 A15 (-) B15 TB5-A12 B12 A13 B13 A14 B14 A15 A-ph B15 A16 B16 (-) A18
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24 BI25 BI26 BI27 BI28
IO#2 IO#1
BO13 FAIL
IO#3
IO#4
CN2
TX CH1 RX CK TX (*) CH2 RX CK CH1 TX RX TX RX COM2-A COM2-B TB2-A18 A17 A16 B18 B17 B16 Two ports RS485 I/F (option)
COM2-0V
Communication Links
(*) CH1
COM-A COM-B 0V
External trip signals (Reclose & CBF Initiation) Interlink signals (Parallel line interlink signal for terminal 1) CB1 ARC ready(Bus CB) CB2 ARC ready(Center CB) ARC block
TB3
TB2
B1
IO#3
RX1
IO#1
IO#4
IO#2
B18 29
30
VCT
Interlink signals (Parallel line interlink signal for terminal 2, used for Model 513.)
B-ph C-ph
()Caution:
Connect FD output contact with A- to C-phase tripping output contacts in series.
TB5
TB4
TB3
CN2
CH1 TX1 RX1 CH2 TX2
A1
TB2
B1
A1 A2 B2
(*)
1
RX2
RELAY FAIL. DD FAIL. TB4 -A16 DC (+) B16 A17 SUPPLY (-) B17 A18 B18 (1)These connections are connected A15 (1) B15 by short-bars before shipment. DC-DC
TP-C1
+5Vdc 0V
IO#3
IO#1
IO#4
A18
B18
IO#2
29
30
VCT
Model GRL100-5*3
Note GRL100-503: 2 terminal system, not provided with terminals marked with (*). GRL100-513: 3 terminal system
E (CASE EARTH)