Transformer Testing
Transformer Testing
System
Transformer Testing
TRANSFORMER TEST
For confirming the specifications and
performances of an electrical transformer it has
to go through numbers of testing procedures.
Some tests are done at manufacturer premises
before delivering the transformer. Mainly two
types of transformer testing are done at
manufacturer premises - type test of transformer
and routine test of transformer. In addition to
that some transformer tests are also carried out
at the consumer site before commissioning and
also periodically in regular & emergency basis
through out its service life.
2
TRANSFORMER TEST
For confirming the specifications and
performances of an electrical transformer it has
to go through numbers of testing procedures.
Some tests are done at manufacturer premises
before delivering the transformer. Mainly two
types of transformer testing are done at
manufacturer premises - type test of transformer
and routine test of transformer. In addition to
that some transformer tests are also carried out
at the consumer site before commissioning and
also periodically in regular & emergency basis
through out its service life.
3
Type of transformer testing
1. Routine Test
2. Type Test
Insulation resistance test of transformer is essential type test. This test is carried
out to ensure the healthiness of over all insulation system of an electrical power
transformer.
HV-LV
Insulation Resistance Test of
transformer
HV-EARTH
LV-EARTH
Transformer Ratio Test
MAGNETIZING CURRENT
RN YN BN
Voltage applied at
left side phase 230 180 50
Voltage applied at
central phase 115 230 115
Voltage applied at
right phase
50 180 230
Seperate source voltage withstand test (High Voltage tests on HV & LV)-
This test checks the insulation property between Primary to earth,
Secondary to earth and between Primary & Secondary.
Procedure
The values of test voltage for different fully insulated winding are furnished below in
the table.
Nominal system Highest system Rated short duration
voltage rating voltage rating power frequency
for equipment for equipment withstand voltage
415V 1.1 KV 3 KV
11 KV 12 KV 28 KV
33 KV 36 KV 70 KV
Slowly rising voltage is applied between the electrodes. The rate of rising
voltage is controlled at 2 KV/s and observe the voltage at which sparking
starts between the electrodes. That means at which voltage dielectric
strength of transformer oil between the electrodes has been broken down.
This measurement is taken 3 to 6 times in the same sample of oil and the
average value of these reading is taken. BDV is an important and popular test
of transformer oil, as it is the primary indicator of the health of oil and it can
be easily carried out at the site.
Dry and clean oil gives BDV results, better than the oil with moisture content
and other conducting impurities. Minimum breakdown voltage of transformer
oil or dielectric strength of transformer oil at which this oil can safely be
used in transformer, is considered as 30 KV.
The water content in oil is measured as ppm (parts per million unit).
The water content in oil is allowed up to 50 ppm as recommended
Dd0
Delta connected HV winding, delta connected LV winding, no phase shift
between HV and LV.
Dyn11
Delta connected HV winding, star connected LV winding with neutral
brought out, LV is leading HV with 30¦
YNd5
Star connected HV winding with neutral brought out, delta connected LV
winding, LV lags HV with 150¦
Measured voltage:-
1U2N + 1V2N =1U1V
1V2V = 1V2W
1W2W < 1W2V
Montag, 7. Dezember 2015 Fußzeilentext 31
Vector Group Test of Transformer