EPRI Accelerating Commercial Engagement (ACE)
EPRI Accelerating Commercial Engagement (ACE)
EPRI Accelerating Commercial Engagement (ACE)
Engagement (ACE)
Technology Transfer Session
Inverter-based Supplemental Grounding Tool (ISGT)
Mute Chat
2 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Presentations and Recordings
Webcast being recorded for re-listen and review. Please end your
participation if you do not consent to being recorded.
3 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Agenda
Overview of ACE
Technical background
Developed tool and data requirements
Results verification
Q&A
4 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Accelerating Commercial Engagement (ACE)
Industry Research
EPRI Research Results
Need
Industry Technical
ACE Goals: Share research Transfer
Commercial
Application
5 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Related Activities
6 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
The Ground Fault Overvoltage (GFOV) Concern
I1
L-G Fault
Grid +
I2
Load
+
Grounding 3Zfault
Transformer
INV.Z2 V2 GT.Z2 LD.Z2
Inverter -
I0
Applicable to 4-wire multi-grounded distribution systems
Grounding is a system issue! +
Grid following inverter DER have insignificant impact on INV.Z0 GT.Z0
V0 LD.Z0
system grounding from when breaker closed
Primary system ground source is lost when breaker opens -
Effective Grounding and Inverter-based Generation: A “New” Look at an “Old” Subject. EPRI, Palo Alto, CA. August 2019. 3002015945.
7 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Inverter Representation Inverter Sequence Models
0 Sequence
Current source or current-limited power
Open circuit for typical
source model is adequate for fundamental inverters
Z2
source during unbalanced Some inverters designed to
VDE standards have defined
(e.g., ground fault) conditions Z2 settable from 0.17 – 0.5 p.u.
8 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Does a Grounded Neutral Connection Make an Inverter a Grounded Source?
9 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
The Role of Loads in Inverter-Sourced Systems
10 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Research Results
A ground connection on an inverter ground
source
If more than 33% of loads are grounded,
supplemental ground source is unnecessary
Adding a ground source can have adverse
consequences
– Reduced ground fault detection sensitivity
– Increased arc flash risk
– Maintains energization of open phases
– Can increase ground fault overvoltage in some cases
If > 2/3 of loads are L-to-L connected, a ground
source is necessary to ensure effective grounding
Widely used guidelines for supplemental grounds
are not appropriate for inverter sources
Effective Grounding and Inverter-based Generation: A “New” Look at an “Old” Subject. EPRI, Palo Alto, CA. August 2019. 3002015945
11 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Software Objectives
Develop an easy-to-use, single purpose tool
for evaluation
Allows for quick screening and sensitivity
analysis
Allow for sufficient user customization to
address most common situations
Perform optimization in selection of
important parameters
Graphically display information where
appropriate
12 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Background/Limitations/Assumptions
Based upon symmetrical component analysis (C62.92.6)
Assumes 3-phase grid following inverters
Where multiple 3-phase inverters exist on an islanded system, those can be aggregated in the calculation sheet
to choose a system ground source
Assumed inverter characteristics
– Inverter modeled with an inner current regulation loop with the current reference set, up to a limit, by an outer power
regulation loop
– Reference current adjusted to meet P = 1.0 p.u. within limits of current reference range
– Assumptions may not be accurate under extreme voltage conditions
– Application purpose is to define grounding to remove extreme voltages
Load composition and amount of minimum concurrent load is important
– Line-to-ground load provides system grounding
– Line-to-line load doesn’t provide grounding
Negative sequence impedance is an entry and tool can determine a worst-case value within constraints
– Negative sequence is determined by control characteristics, not physics
– This parameter is typically undocumented; no OEMs publish a value
Does not include protection considerations in sizing of supplemental ground source
13 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Unique Data Requirements
Negative sequence impedance
– Not readily available from manufacturers
– Software performs parametric sweep to find worst case
Load
– Estimation of L-G load composition
– Allow for customization
Current reference limit
– Typically, between 1.0 p.u. and 1.2 p.u.
– May be available from inverter vendors
Zero sequence impedance
– Represents ground transformer
14 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Software Implementation
15 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Calculations
Classic symmetrical component analysis
Use Excel “solver” optimization to choose…
– Worst-case negative sequence impedance
– Zero sequence impedance
– Adjusted current reference
Plots
– Uses core symmetrical component analysis for sweeps
– GFOV vs. negative sequence impedance
– Bullet curve
16 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Comparison to EMT Analysis = ISGT
Peak = EMT
2.5
2.3
2.3
2.1 2.1
1.9 1.9
Voltage (pu)
1.7 1.7
Voltage (pu)
1.5
1.5
1.3
1.3 1.1
1.1 0.9 Analysis Peak
Analysis Peak 0.7
0.9
0.7 0.5
0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
Gen/Load Gen/Load
1.3
1.2
1.1
1
0.9 Peak Analysis
0.8
0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8
Gen/Load
GT = 0.6 pu, X/R = 4 & 100% L-G Load
17 www.epri.com © 2020 Electric Power Research Institute, Inc. All rights reserved.
Together…Shaping the Future of Electricity
18 www.epri.com © 2021 Electric Power Research Institute, Inc. All rights reserved.