Machine Foundation Design
Machine Foundation Design
MACHINE FOUNDATION
ANALYSIS-ONLY PRACTICAL VIEW
A.PAVAN KUMAR
AGENDA :-
DESIGN OVERVIEW
Design Criteria:
The basic goal in
the design of a
machine
foundation is to
limit its motion to
amplitudes that
neither endanger
the satisfactory
operation of the
machine nor
disturb people
working in the
immediate vicinity.
(Gazetas 1983)
Performance Criteria
STRUCTURAL DRAWING OF TG
BUILDING
10
11
12
13
14
15
SCOPE
The objective is to study the dynamic behavior of Turbine Generator
(TG) pedestal under normal operating conditions and also emergency
conditions for 2X150 MW Nagai Thermal Power Plant located at
Nagapattinam (Dist), Near Okku & Venkidanathangal Villages,
Tamilnadu State, India.
The following checks with relevant structural analysis have been carried
out to accomplish the above object.
Natural Frequency check Modal analysis is carried out in ANSYS
software to elicit the natural frequencies of machine-foundation system
for all significant modes of vibration. The natural frequencies are
checked with relevant provisions of DIN 4024 Part1.
Vibration amplitude check The absolute maximum amplitudes are
obtained by performing steady state harmonic analysis of STG
foundation in ANSYS and checked according to VDI-guideline 2056,
Machine group T
16
2165-T-1-VVG-C-501
2165-T-1-VVG-C-502
2165-T-1-UMP-C-501
2165-T-1-VVB-M-501
IS 2974 (Part 3)
Design and Construction of Machine Foundations Foundations For Rotary Type Machines (Medium and
High Frequency)
17
MATERIAL DETAILS
Material
Concrete, C40
Property
Value
Units
Density
25
kN/ cum
Characteristic
Strength
40
N/ Sq mm
Modulus of Elasticity
32500 (Dynamic)
Remarks
IS-456 (2000)
N/ sq mm
IS-2974 (Part 3)
18
19
20
SOLID MODEL-ANSYS
21
22
SUPPORT CONDITIONS
23
24
1.
f1 = 2.8586 Hz
0.8*50 = 40 Hz
Hence condition 1 is o.k.
fn
0.9*fm
and
fn+1 1.1*fm
If condition 2a) is not met, it shall suffice that fn is less than fm where n
is equal to 10 or 6.
f10 = 27.3487
50 Hz
From the above frequency table, it can be seen that the fundamental
structural frequencies are within 30 Hz where the predominant portion
25
of applied mass is participated..
26
FREQUENCY SEPARATION
CRITERIA
MODE
MODE
NATURAL
FREQ. (Hz)
MACHIN
E FREQ.
(Hz)
FREQ.
SAPARATION
(%)
XTRANS
YTRANS
ZTRANS
ROT-X
ROT-Y
ROT-Z
2.85863
50
94.28274
17.6915
50
64.617
3.58554
50
92.82892
4
1
4
17.6915
2.85863
17.6915
50
50
50
64.617
94.28274
64.617
27
MODE 1
28
MODE 2
29
MODE 3
30
MODE 4
31
33
BEARING
#1
#2
#3
#4
36.3
36.3
36.6
36.6
LOCATION
TURBINE
TURBINE
GENERATOR
GENERATOR
VIBRATION AMPLITUDES
The maximum displacement amplitudes obtained from the harmonic
analysis for 2% damping are tabulated below.The same results are
presented graphically.The vibration amplitudes are listed on top of deck
at corresponding bearing locations.
NODE
UX
(m)
UY
(m)
UZ
(m)
1750
2.2283
59
2.1000
78
1.4559
65
2.1000
78
0.4765
84
0.9830
78
1.0681
2.0949
875
1.8002
342
0.6442
127
1.8002
342
0.7991
964
2.4001
657
1.4327
693
0.5894
506
-
0.7163
144
0.8717
515
1.5667
955
0.8717
515
0.7032
227
0.5480
38
0.7475
793
1.0218
484
-
2.4001
1793
2
1560
1524
4459
4468
4607
4760
UX,
MAX
UY, MAX
1750
4468
1.2016
05
2.2283
59
-
35
From the above table it can be seen that the vibration amplitudes in both
directions are very less and well within the manufacturers specified limits and
also VDI guideline. This is also obvious from the natural frequency table in Sec
3.0 that the contribution of vibration modes to amplitude response in
concentrated around lower modes only and its effect is tapered off towards
higher modes.
Rating according to VDI-guideline 2056, Machine group T (Refer to chart in
next page)
At 50 Hz: Amplitudes < 12.5 m Rating: Good
(2% Damping)
Hence, the foundation system adopted is classified as Good for normal
operating conditions.
36
37
38
DYNAMIC PROPERTIES
Dynamic Equilibrium Equation:
M X C X K X F (t )
In Veletsos Model, the Dynamic Impedance
Expressed as:
Mode
Vertical
Static Spring
4Gv Rv
Kv
Constants
1
Dynamic
Impedance
Horizontal
Rocking
8Gh Rh
Kh
2
8Gr Rr
Kr
31
K v k v ia 0 cv K h k h ia 0 ch
K r k r ia 0 c r
Torsion
16Gt Rt
Kt
3
K t k t ia 0 ct
DYNAMIC PROPERTIES
The classic single lumped mass machinefoundation-soil system with circular foundation on
elastic half-space summarized by Richart, Woods,
HallMotion
(1970): Spring Constant
Reference
Vertical
Horizontal
Rocking
Torsion
Ky
4G R
1
32(1 )GR
7 8
8GR 3
K rz
31
16
K ry
G R3
3
Kx
a : Dimensionless frequency.
DYNAMIC PROPERTIES
Dimensionless frequency, a0
R
a0
Vs
Where:
: machine speed equipment;
R: foundation radius foundation;
Vs: shear wave speed soil.
DYNAMIC PROPERTIES
Veletsos Model Dynamic Stiffness and
Damping Coefficients:
DYNAMIC PROPERTIES
Veletsos Model, kx &
cx to Frequency
Relation in Horizontal
Mode:
cx is independent of
a , or the frequency.
0
kx in sandy soil is
kind of sensitive to
a , or the frequency.
0
THANQ
44