Differential Protection
Differential Protection
Differential Relay
87
Fault
I1
I2
87
I 1 I 2 = I Diff
I Diff > Basic Sensitivity + K % (I restraint ) + (depending on Algorithm)
5
Fault
87
I 1 I 2 = I Diff
I Diff > Basic Sensitivity + K % (I restraint ) + (depending on Algorithm)
6
Fault
87
Vector Corrected
Ratio Corrected
Main CT
Differential Relay
Tool 1
Conventional CT Connections
Dy11(+30)
Yd1(-30)
Differential Relay
Interposing CT provides
Vector correction
Ratio correction
Zero sequence compensation
10
Yd1(-30)
Differential Relay
11
Dy11(+30)
Yd1(-30)
12
Transformer Information
CT Ratio Information
CT Connection Information
13
Purpose
Protect from undesired
tripping due to
CT ratio Mismatch
CT saturation
Operate
2
I diff
%
2
K
1
Basic Sensitivity
e
p
o
l
S
Restrain
lope
K1% S
I through
14
e = voltage
= magnetic flux
i = current
Because inrush is dependant on where on the waveform the transformer is switched, it will be
different every time. As previously stated, highest if you switch in at voltage peak.
15
Instant
Instantinintime
timewhen
whentransformer
transformer
isisconnected
to
AC
voltage
connected to AC voltage
source
= emax
sourcee(t)
at e(t)
= e(0) = 0
t
In a continuously
operating
transformer
In a continuously
operating
transformer
when when
e(t)=e
(t)=0
i(t)=0
max
e(t)=0
(t)=
i(t)=imin
min
16
Inrush current
17
Inrush
Undesired
current
e
Tripping
No Load
I1
I2
87
18
Solution
To avoid the system from undesired tripping due to inrush current
We have two solutions
1. Blocking
2. Restraining
19
Blocking Scheme
i
Inrush
current
No Load
I1
I2
Fundamental
87
Harmonic
Filter
No Trip
Inrush
(harmonic)
20
Blocking Scheme -
Disadvantages
The relay will not issue trip signal when the fault occurs
during transformer energization
The relay will not issue trip signal when the fault occurs
during continuous operation and there are harmonics more than
its threshold level
21
Restraining Scheme
i
Inrush
current
No Load
I1
I2
Fundamental
87
Harmonic
Filter
Ip
Is
Load
In ideal condition
Magnetizing current = 0
So
Ip is a true replica of Is
No Saturation
Practically Impossible
23
Practical CT
Ip
Is
Is
Im
Load
Is = Is + Im
Where
Im = magnetizing current
Is = load Current
24
When a CT saturates
Ip
Load
Is Is
Im >
<<<
Is I s
IIm >>
I
m >>> sIs
So,
Is = Im + Is
The dip is due to the current drawn
by magnetizing impedance
25
26
P2
P1
S2
P1, P2 CT Primary terminals
S1, S2 CT Secondary terminals
S1
Similarly
Current entering in P1 leaves
from
its corresponding
secondary
Current
entering in P2 leaves
terminal
S1.
from its corresponding
secondary
terminal S2.
27
P2
P1
S2
S1
28
P2
P1
S2
S1
Push button
DC ammeter
-
+
DC battery
29