Relay Setting Calculation
Base MVA=100
Fault MVA=1200
Source impedance=0.083
Cable impedance=.015*4=0.06 ohm
Transformer impedance=11 % at 20 MVA base
=0.11*100/20=0.55 ohm
Total fault impedance at 6 kV Bus=0.083+.06+.55=0.693 ohm
PSM=14000/800=17.5
PSM=14000/160=87.5=20(max)
PSM= 14000/2300=6.086
Relay operating time based on std formula=0.14/(6.086)0.02-1=3.806
Actual operating time=3.806*0.25=950 ms
PSM=14000/400=35=20 (max)
Relay operating time based on std formula=2.26
B/Z CTR=800/1
Vk (Min) =242 V
CTR=400/5
Rct (max) =0.55 ohm
Vk (min) =133 volt
Vk/2=65 volt
CTR=2000/5