SV 3 Safety Valve
SV 3 Safety Valve
SV 3 Safety Valve
IM-P310-07
CH Issue 4
SV 3 Safety Valve
Installation and Maintenance Instructions
1. General specification 2. Supply 3. Setting the valve 4. Installation 5. Prevention of seat damage 6. Commissioning 7. Testing during use 8. Guidelines for setting a SV3 safety valve
Printed in the UK Copyright 1997
1. General specification
Steam supply
Condensate
Fig 1. Typical installation of safety valve, downstream of pressure reducing valve station
Description
The SV3 is a high lift, Pop Type Safety Valve approved to BS6759 parts 1 and 2 for use on compressed air and steam.
Limiting conditions
Steel body valves Max. upstream conditions 13 bar at 245C Max. body design conditions 16 bar at 350C 20 bar at 250C 25 bar at 120C Cold hydraulic test 38 bar Gunmetal body valves Maximum upstream conditions (DN1520) 21 bar at 240C (DN2540) 17 bar at 224C (DN50) 13 bar at 245C Max. body design conditions (DN15 and 20) 17 bar at 260C 24 bar at 230C 40 bar at 120C Cold hydraulic test 60 bar Max. body design conditions (DN25 to 50) 10.5 bar at 260C 16 bar at 230C 25 bar at 120C Cold hydraulic test 38 bar Soft seal insert (not suitable for use on steam) Nitrile -10 to + 90C EPDM -20 to +125C Viton -20 to +200C
Available types
Gunmetal body, screwed DN 15 to 50 Steel body screwed DN 65 and 80 Steel body Flanged DN 50 to 100 Each of the above are available with 3 optional soft seal inserts: Nitrile, EPDM or Viton.
Materials
No 1 2 3 4 5 6 7 8 9 10 11 Part Body Screwed DN 15 to 50 Screwed DN65 and 80, Flanged DN 50 to 100 Spring Plate Spring Easing Lever Disc Seat Adjustment Screw Lever Housing (DN15 to 50 Gunmetal Body) (DN50 to 100 Steel Body) Spring Housing (DN15 to 50 Gunmetal Body) (DN50 to 100 Steel Body) Stem (DN15 to 50 Gunmetal Body) (DN50 to 100 Steel Body) 'O' Ring Material Gunmetal BS 1400 LG2 Steel DIN 17245 GS C25 Brass BS 2872 CZ 121 Steel BS 970 Pt 5 735 A 50 SG Iron DIN 1693 GGG 40 Stainless Steel BS 3146 Pt2 Gr ANC2 Stainless Steel BS 3146 Pt2 Gr ANC2 Brass BS 2874 CZ 121 Gunmetal BS 1400 LG2 Cast Iron DIN 1691 GG 20 Gunmetal BS 1400 LG2 Cast Iron DIN 1691 GG 20 Brass BS 2874 CZ 121 Stainless Steel BS 970 431 S29 According to service
Screwed DN15 to 80
5 6
Dimensions
Screwed DN A 15 151 20 160 25 199 32 224 40 263 50 301 65 385 80 419 Flanged DN 50 65 80 100 A 301 385 419 604
(approximate) in mm B 50 54 65 74 86 92 110 120 C 38 46 56 65 73 80 100 110 Weight 1.1 kg 1.6 kg 2.7 kg 4.1 kg 6.1 kg 8.2 kg 15.9 kg 22.3 kg
Spring ranges
The spring ranges are colour coded according to their pressure range and are listed below. Gold DN 15 to 40 0.3 0.7 bar Pink 0.7 1.0 bar Green 1.0 1.7 bar Brown 1.7 3.1 bar Red 3.1 5.2 bar White 5.2 7.9 bar Black DN 15 to 80 7.9 11.4 bar DN 100 7.9 10.3 bar Blue DN 15 to 40 11.4 15.5 bar Blue DN 50 to 80 11.4 13.0 bar Blue DN 100 10.3 13.0 bar Light DN 25 to 40 15.5 17.2 bar Grey Dark DN 15 & 20 15.5 20.7 bar Grey C
Seat tightness
Tested to the general standard laid down in API 527.
How to specify
1 DN 40 Spirax Sarco SV 3 seat N=Nitrile E=EPDM V=Viton C Pop Type Safety valve set at 1.0 bar g. Having a gunmetal body with screwed BSP connections and incorporating an easing lever and locking device.
2 Supply
Normally, the valve will be supplied set at the required pressure and sealed. B.S. 6759 and local regulations requires that the setting of the valve should only be carried outby an authorised/competent person. Spirax Sarco accepts no responsibility for valves which have been reset by unauthorised persons.
4 Installation
4.1 The valve should always be mounted vertically upwards with its main axis vertical. 4.2 The valve should be fitted to the pipework or vessel by means of the shortest possible length of pipe or fitting. 4.3 There should be no intervening valve or fitting i.e. it should not be possible to isolate safety valve. (Fig. 2) 4.4 The inlet pipe connection should not be smaller than the valve. 4.5 The outlet pipe should be equal to or larger than the valve outlet to keep back pressure below 12% of set pressure. 4.6 Direct the outlet pipework to a safe point of discharge where there is no risk of injury to persons or damage to property in the event of the valve operating. 4.7 The outlet pipework should be adequately supported such that it does not place undue stress on the safety valve. 4.8 Where the outlet pipework is directed upwards a small bore drain should be provided at the lowest point. (Fig. 3) This drain should be taken to a place where any discharge will not create a hazard or inconvenience. 4.9 Each safety valve should have its own unrestricted discharge pipe. 4.10 Safety valve should not be lagged. 4.11 Safety valves can operate very suddenly and will be too hot to touch without protection when installed on steam systems.
Fig 2 Fig 3
a Inlet area 'A' approximately twice that of area 'a'. r Radius 'r' not less than inlet diameter Fig 5 A
Fig 6
6 Commissioning
6.1 Once the valve has been fitted check that there are no leaks from either the inlet or the outlet connections. 6.2 Test the valve by raising the system pressure. Check that the valve operates at the correct pressure and that the overpressure is limited to 10% of the safety valve setting. 6.3 Reduce the system pressure to the normal operating pressure and check that the safety valve reseats.
8 Guidelines for setting a SV3 safety valve (By Authorised Persons Only)
8.1 Choice of Set Pressure A decision must be made regarding the pressure at which the safety valve should be set. The maximum set pressure, in accordance with B.S.5500, is the safe working pressure of the plant it protects and the valve must achieve its rated capacity with an overpressure of no more than 10%. If the valve is set too close to the operating pressure of the system the valve may operate prematurely. It will also fail to close satisfactorily when normal operating pressure is restored. Fig. 7 outlines the way a safety valve operates under abnormal pressure conditions. It can be seen that the safety valve does not re-seat when the pressure falls to the safety valve set pressure. There must be adequate differential between the maximum system operating pressure and the safety valve set pressure if the valve is to reseat. The maximum system operating pressure will occur during no-load conditions. Fig. 8 shows the range within which the valve must be set. Note: The operating pressure of a system will vary and it is important that the safety valve is set high enough to accommodate such fluctuations. 8.2 Setting the Valve British Standard 6759 requires that a safety valve should only be set by an Authorised Person. Spirax Sarco cannot be held responsible for unauthorised alteration of the set pressure. Full lift position Reseat differential Set pressure
Maintenance
All safety valves should receive planned maintenance. It is recommended that the Spirax Sarco SV3 safety valves are returned to Spirax Sarco for a thorough overhaul periodically. The valve will be returned having been overhauled, tested re-set and sealed in accordance with B.S.6759.
Reseat pressure
Fig 7
Max. setting of safety valve Safety valve may be set within this range Min. setting of safety valve
Reseat differential
Normal system pressure variation Operating pressure Flow rate = max. rating of PRV Fig 8