Chapter 9:

9-1.

Transmission Lines

Calculate the dc resistance in ohms per kilometer for an aluminum conductor with a 3 cm diameter. SOLUTION The resistance per meter of aluminum conductor is given by Equation (9-2):

rDC =

r2

where = 2.83 10-8 -m. This value is

rDC =

( 2.83 10

-m
2

( 0.015 m )

) = 4.004 10

/m

Therefore the total DC resistance per kilometer would be

1000 m RDC = 4.004 105 /m = 0.040 /km 1 km


9-2. Calculate the dc resistance in ohms per mile for a hard-drawn copper conductor with a 1 inch diameter. (Note that 1 mile = 1.609 km). SOLUTION The resistance per meter of hard-drawn copper conductor is given by Equation (9-2):

rDC =

r2

where = 1.77 10-8 -m. Note that the radius in this equation must be in units of meters. This value is

rDC =

(1.77 10

-m

( 0.5 in )

0.0254 m 1 in

= 3.493 105 /m

Therefore the total DC resistance per mile would be 1000 rDC = 0.03367 .

1609 m = 0.0562 /mile RDC = 3.493 105 /m 1 mile


Problems 9-3 through 9-7 refer to a single phase, 8 kV, 50-Hz, 50 km-long transmission line consisting of two aluminum conductors with a 3 cm diameter separated by a spacing of 2 meters. 9-3. Calculate the inductive reactance of this line in ohms. SOLUTION The series inductance per meter of this transmission line is given by Equation (9-22).

l=

1 D + ln H/m r 4

(9-22)

where = 0 = 4 107 H/m .

l=

0 1 2.0 m 4 107 H/m 1 2.0 m 6 + = + ln ln = 2.057 10 H/m 4 4 0.015 m 0.015 m

Therefore the inductance of this transmission line will be

L = 2.057 106 H/m ( 50,000 m ) = 0.1029 H X = j L = j 2 fL = j 2 ( 50 Hz )( 0.1029 H ) = j 32.3


178

The inductive reactance of this transmission line is

9-4.

Assume that the 50 Hz ac resistance of the line is 5% greater than its dc resistance, and calculate the series impedance of the line in ohms per km. SOLUTION The DC resistance per meter of this transmission line is given by Equation (9-22).

rDC =

r2

where = 2.83 10-8 -m. This value is

rDC =

( 2.83 10

-m
2

( 0.015 m )

) = 4.004 10

/m

Therefore the total DC resistance of the line would be

RDC = 4.004 105 /m ( 50,000 m ) = 2.0

The AC resistance of the line would be

RAC = ( 2.0 )(1.05) = 2.1

The total series impedance of this line would be Z = 2.1 + j 30.5 , so the impedance per kilometer would be

Z = ( 2.1 + j 32.3 ) / ( 50 km ) = 0.042 + j 0.646 /km

9-5.

Calculate the shunt admittance of the line in siemens per km. SOLUTION The shunt capacitance per meter of this transmission line is given by Equation (9-41).

c=

c=

( 8.854 1012 F/m )


2.0 ln 0.015

D ln r

(9-41)

= 5.69 1012 F/m

Therefore the capacitance per kilometer will be

c = 5.69 109 F/km


The shunt admittance of this transmission line per kilometer will be

y sh = j 2 fc = j 2 ( 50 Hz ) 5.69 109 F/km = j1.79 106 S/km

Therefore the total shunt admittance will be

Ysh = j1.79 106 S/km ( 50 km ) = j8.95 105 S

9-6.

The single-phase transmission line is operating with the receiving side of the line open-circuited. The sending end voltage is 8 kV at 50 Hz. How much charging current is flowing in the line? SOLUTION Although this line is in the short range of lengths, we will treat it as a medium-length line, because we must include the capacitances if we wish to calculate charging currents. The appropriate transmission line model is shown below.

179

The charging current can be calculated by open-circuiting the output of the transmission line and calculating I S :

IS =

IS =

YVS VS + 1 2 Z+ Y /2 j8.95 105 S ( 80000 V )

80000 V

( 2.1

+ j 32.3 ) +

1 j8.95 105 S / 2

I S = 0.35890 A + 0.35890 A = 0.71690 A


9-7. The single-phase transmission line is now supplying 8 kV to an 800 kVA, 0.9 PF lagging single-phase load. (a) What is the sending end voltage and current of this transmission line? (b) What is the efficiency of the transmission line under these conditions? (c) What is the voltage regulation of the transmission line under these conditions? SOLUTION At 50 km length, we can treat this transmission line as a short line and ignore the effects of the shunt admittance. The corresponding equivalent circuit is shown below.

The transmission line is supplying a voltage of 8 kV at the load, so the magnitude of the current flowing to the load is

I=

S 800 kVA = = 100 A 8 kV V

(a) If we assume that the voltage at the load is arbitrarily assigned to be at 0 phase, and the power factor of the load is 0.9 lagging, the phasor current flowing to the load is I = 100 25.8 A . The voltage at the sending end of the transmission line is then

VS = VR + ZI VS = 80000 V + ( 2.1 + j 32.3 )(100 25.8 A ) VS = 1000016.4 V


(b) The complex output power from the transmission line is

SOUT = VR I* = ( 80000 V )(100 25.8 A ) = 800,00025.8 VA


*

Therefore the output power is

POUT = 800 cos 25.8 = 720 kW


The complex input power to the transmission line is

S IN = VS I* = (1000016.4 V )(100 25.8 A ) = 1,000,00042.2 VA


*

Therefore the input power is

PIN = 1000 cos 42.2 = 741 kW


The resulting efficiency is

POUT 720 kW 100% = 100% = 97.2% PIN 741 kW


180

(c)

The voltage regulation of the transmission line is

VR =

VS VR 10000 8000 100% = 100% = 25% VR 8000

Problems 9-8 through 9-10 refer to a single phase, 8 kV, 50-Hz, 50 km-long underground cable consisting of two aluminum conductors with a 3 cm diameter separated by a spacing of 15 cm. 9-8. The single-phase transmission line referred to in Problems 9-3 through 9-7 is to be replaced by an underground cable. The cable consists of two aluminum conductors with a 3 cm diameter, separated by a center-to-center spacing of 15 cm. As before, assume that the 50 Hz ac resistance of the line is 5% greater than its dc resistance, and calculate the series impedance and shunt admittance of the line in ohms per km and siemens per km. Also, calculate the total impedance and admittance for the entire line. SOLUTION The series inductance per meter of this transmission line is given by Equation (9-22).

l=

1 D + ln H/m 4 r

(9-22)

where = 0 = 4 107 H/m .

l=

0 1 0.15 m 4 107 H/m 1 0.15 m 6 ln + = + ln = 1.021 10 H/m 4 0.015 m 0.015 m 4

Therefore the inductance of this transmission line will be

L = 1.021 106 H/m ( 50,000 m ) = 0.0511 H X = j L = j 2 fL = j 2 ( 50 Hz )( 0.0511 H ) = j16.05

The inductive reactance of this transmission line is

The resistance of this transmission line is the same as for the overhead transmission line calculated previously: RAC = 2.1 . The total series impedance of this entire line would be Z = 2.1 + j16.05 , so the impedance per kilometer would be

Z = ( 2.1 + j16.05 ) / ( 50 km ) = 0.042 + j 0.321 /km c=

The shunt capacitance per meter of this transmission line is given by Equation (9-41).

c=

( 8.854 1012 F/m )


0.15 ln 0.015

D ln r

(9-41)

= 1.21 1011 F/m

Therefore the capacitance per kilometer will be

c = 1.21 108 F/km


The shunt admittance of this transmission line per kilometer will be

y sh = j 2 fc = j 2 ( 50 Hz ) 1.21 108 F/km = j 3.80 106 S/km

Therefore the total shunt admittance will be

Ysh = j 3.80 106 S/km ( 50 km ) = j1.90 104 S

9-9.

The underground cable is operating with the receiving side of the line open-circuited. The sending end voltage is 8 kV at 50 Hz. How much charging current is flowing in the line? How does this charging current in the cable compare to the charging current of the overhead transmission line? 181

SOLUTION Although this line is in the short range of lengths, we will treat it as a medium-length line, because we must include the capacitances if we wish to calculate charging currents. The appropriate transmission line model is shown below.

The charging current can be calculated by open-circuiting the output of the transmission line and calculating I S :

IS =

IS =

YVS VS + 1 2 Z+ Y /2 j1.90 104 S ( 80000 V )

80000 V

( 2.1

+ j 32.3 ) +

1 j1.90 104 S / 2

I S = 0.76090 A + 0.76290 A = 1.52290 A


Since the shunt admittance of the underground cable is more than twice as large as shunt admittance of the overhead transmission line, the charging current of the underground cable is more than twice as large. 9-10. The underground cable is now supplying 8 kV to an 800 kVA, 0.9 PF lagging single-phase load. (a) What is the sending end voltage and current of this transmission line? (b) What is the efficiency of the transmission line under these conditions? (c) What is the voltage regulation of the transmission line under these conditions? SOLUTION At 50 km length, we can treat this transmission line as a short line and ignore the effects of the shunt admittance. (Note, however, that this assumption is not as good as it was for the overhead transmission line. The higher shunt admittance makes its effects harder to ignore.) The transmission line is supplying a voltage of 8 kV at the load, so the magnitude of the current flowing to the load is

I=

S 800 kVA = = 100 A 8 kV V

(a) If we assume that the voltage at the load is arbitrarily assigned to be at 0 phase, and the power factor of the load is 0.9 lagging, the phasor current flowing to the load is I = 100 25.8 A . The voltage at the sending end of the transmission line is then

VS = VR + ZI VS = 80000 V + ( 2.1 + j16.05 )(100 25.8 A ) VS = 89908.7 V


(b) The complex output power from the transmission line is

SOUT = VR I* = ( 80000 V )(100 25.8 A ) = 800,00025.8 VA


*

Therefore the output power is

POUT = 800 cos 25.8 = 720 kW


The complex input power to the transmission line is 182

S IN = VS I* = ( 89908.7 V )(100 25.8 A ) = 899,00034.5 VA


*

Therefore the input power is

PIN = 899 cos 34.5 = 740.9 kW


The resulting efficiency is

=
(c)

720 kW POUT 100% = 100% = 97.2% PIN 740.9 kW VS VR 8990 8000 100% = 100% = 12.4% VR 8000

The voltage regulation of the transmission line is

VR =
9-11.

A 138 kV, 200 MVA, 60 Hz, three-phase, power transmission line is 100 km long, and has the following characteristics: r = 0.103 /km x = 0.525 /km (a) (b) (c) (d) (e) (f) (g) (a) y = 3.3 10-6 S/km What is per phase series impedance and shunt admittance of this transmission line? Should it be modeled as a short, medium, or long transmission line? Calculate the ABCD constants of this transmission line. Sketch the phasor diagram of this transmission line when the line is supplying rated voltage and apparent power at a 0.90 power factor lagging. Calculate the sending end voltage if the line is supplying rated voltage and apparent power at 0.90 PF lagging. What is the voltage regulation of the transmission line for the conditions in (e)? What is the efficiency of the transmission line for the conditions in (e)?

SOLUTION The per-phase series impedance of this transmission line is

Z = ( 0.103 + j 0.525 /km )(100 km ) = 10.3 + j 52.5


The per-phase shunt admittance of this transmission line is

Y = j 3.3 106 S/km (100 km ) = j 0.00033 S

(b) (c)

This transmission line should be modeled as a medium length transmission line. The ABCD constants for a medium length line are given by the following equations:

ZY +1 B=Z 2 ZY ZY C =Y + 1 D = +1 2 4 ZY (10.3 + j52.5 )( j0.00033 S) + 1 = 0.99130.1 A= +1 = 2 2 A= B = Z = 10.3 + j52.5 = 53.578.9

(9-73)

(10.3 + j52.5 )( j 0.00033 S) ZY C =Y + 1 = ( j 0.00033 S) + 1 4 4


183

C = 3.286 104 90 S ZY (10.3 + j52.5 )( j0.00033 S) + 1 = 0.99130.1 D= +1 = 2 2


(d) The phasor diagram is shown below:

(e) The rated line voltage is 138 kV, so the rated phase voltage is 138 kV / rated current is

3 = 79.67 kV, and the

IL =

Sout 200,000,000 VA = = 837 A 3VLL 3 (138,000 V )

If the phase voltage at the receiving end is assumed to be at a phase angle of 0, then the phase voltage at the receiving end will be VR = 79.670 kV , and the phase current at the receiving end will be

I R = 837 25.8 A . The current and voltage at the sending end of the transmission line are given by
the following equations:

VS = AVR + BI R VS = ( 0.99130.1)( 79.670 kV ) + ( 53.578.9 )( 837 25.8 A ) VS = 111.818.75 kV I S = CVR + DI R I S = 3.286 104 90 S ( 79.670 kV ) + ( 0.99130.1)( 837 25.8 A ) I S = 818.7 24.05 A
(f) The voltage regulation of the transmission line is

VR =
(g)

VS VR 111.8 kV 79.67 kV 100% = 100% = 40.3% VR 79.67 kV

The output power from the transmission line is

POUT = S PF = ( 200 MVA )( 0.9 ) = 180 MW


The input power to the transmission line is

PIN = 3V ,S I ,S cos = 3 (111.8 kV )( 818.7 A ) cos ( 42.8) = 201.5 MW


The resulting efficiency is

=
9-12.

PIN 180 kW 100% = 100% = 89.3% POUT 201.5 kW

If the series resistance and shunt admittance of the transmission line in Problem 9-11 are ignored, what would the value of the angle be at rated conditions and 0.90 PF lagging? SOLUTION If the series resistance and shunt admittance are ignored, then the sending end voltage of the transmission line would be 184

VS = VR + jXI R VS = 79.670 kV + ( j52.5 )( 837 25.8 A ) VS = 106.421.8 kV


Since is the angle between VS and VR , = 21.8 . 9-13. If the series resistance and shunt admittance of the transmission line in Problem 9-11 are not ignored, what would the value of the angle be at rated conditions and 0.90 PF lagging? SOLUTION From Problem 9-11, VS = 111.818.75 kV and VR = 79.670 kV , so the angle is 18.75 when the series resistance and shunt admittance are also considered. 9-14. Assume that the transmission line of Problem 9-11 is to supply a load at 0.90 PF lagging with no more than a 5% voltage drop and a torque angle 30. Treat the line as a medium-length transmission line. What is the maximum power that this transmission line can supply without violating one of these constraints? Which constraint is violated first? SOLUTION A MATLAB program to calculate the voltage regulation and angle as a function of the power supplied to a load an a power factor of 0.9 lagging is shown below.
% M-file: prob9_13.m % M-file to calculate the voltage drop and angle delta % for a transmission line as load is increased. % First, initialize the values needed in this program. v_r = p2r(79670,0); % Receiving end voltage v_s = 0; % Sending end voltage (will calculate) r = 0.103; % Resistance in ohms/km x = 0.525; % Reactance in ohms/km y = 3.3e-6; % Shunt admittance in S/km l = 100; % Line length (k) % Calculate series impedance and shunt admittance Z = (r + j*x) * l; Y = y * l; % A B C D Calculate ABCD constants = Y*Z/2 + 1; = Z; = Y*(Y*Z/4 + 1); = Y*Z/2 + 1;

% Calculate the transmitted power for various currents % assuming a power factor of 0.9 lagging (-25.8 degrees). % This calculation uses the equation for complex power % P = 3 * v_r * conj(i_r). i_r = (0:10:300) * p2r(1,-25.8); power = real( 3 * v_r * conj(i_r)); % Calculate sending end voltage and current for the % various loads v_s = A * v_r + B * i_r; i_s = C * v_r + D * i_r;

185

% Calculate VR for each current step VR = ( abs(v_s) - abs(v_r) ) ./ abs(v_r); % Calculate angle delta for each current step [v_r_mag, v_r_angle] = r2p(v_r); for ii = 1:length(i_r) [v_s_mag, v_s_angle] = r2p(v_s(ii)); delta(ii) = v_s_angle - v_r_angle; end % Which limit is reached first? for ii = 1:length(i_r) if VR(ii) > 0.05 % VR exceeded first--tell user str = ['VR exceeds 5% at ' num2str(power(ii)/1e6) ' MW']; disp(str); break; elseif abs(delta) > 30 % Delta exceeded first--tell user str = ['delta exceeds 30 deg at ' num2str(power(ii)/1e6) ' MW']; disp(str); break; end end % Plot the VR and delta vs power figure(1); plot(power/1e6,VR*100,'b-','LineWidth',2.0); xlabel('\bfPower (MW)'); ylabel('\bfVoltage Regulation (%)'); title ('\bfVoltage Regulation vs Power Supplied'); grid on; figure(2); plot(power/1e6,delta,'b-','LineWidth',2.0); xlabel('\bfPower (MW)'); ylabel('\bfAngle \delta (deg)'); title ('\bfAngle \delta vs Power Supplied'); grid on;

When this program is executed, the results are as shown below. Note that the voltage regulation is the first limit to be exceeded by this transmission line of the load is at 0.9 PF lagging. Try the same calculation with other power factors. How does the maximum power supplied vary?
>> prob9_13 VR exceeds 5% at 25.8222 MW

186

9-15.

The transmission line of Problem 9-11 is connected between two infinite busses, as shown in Figure P9-1. Answer the following questions about this transmission line.

Infinite Bus 1

Infinite Bus 2

Figure P9-1 A three-phase transmission line connecting two infinite busses together. (a) If the per-phase (line-to-neutral) voltage on the sending infinite bus is 8010 kV and the per-phase voltage on the receiving infinite bus is 760 kV, how much real and reactive power are being supplied by the transmission line to the receiving bus? (b) If the per-phase voltage on the sending infinite bus is changed to 8210 kV, how much real and reactive power are being supplied by the transmission line to the receiving bus? Which changed more, the real or the reactive power supplied to the load?

187

(c) If the per-phase voltage on the sending infinite bus is changed to 8015 kV, how much real and reactive power are being supplied by the transmission line to the receiving bus? Compared to the conditions in part (a), which changed more, the real or the reactive power supplied to the load? (d) From the above results, how could real power flow be controlled in a transmission line? How could reactive power flow be controlled in a transmission line? SOLUTION (a) If the shunt admittance of the transmission line is ignored, the relationship between the voltages and currents on this transmission line is

VS = VR + RI + jXI where I S = I R = I . Therefore we can calculate the current in the transmission line as V VR I= S R + jX 80,00010 76,0000 I= = 265 0.5 A 10.3 + j52.5
The real and reactive power supplied by this transmission line is

P = 3V ,R I cos = 3 ( 76 kV )( 265 A ) cos ( 0.5) = 60.4 MW Q = 3V ,R I sin = 3 ( 76 kV )( 265 A ) sin ( 0.5) = 0.53 MVAR
(b) If the sending end voltage is changed to 8210 kV, the current is

I=

82,00010 76,0000 = 280 7.7 A 10.3 + j52.5

The real and reactive power supplied by this transmission line is

P = 3V ,R I cos = 3 ( 76 kV )( 280 A ) cos ( 7.7) = 63.3 MW Q = 3V ,R I sin = 3 ( 76 kV )( 280 A ) sin ( 7.7) = 8.56 MVAR
In this case, there was a relatively small change in P (3 MW) and a relatively large change in Q (8 MVAR) supplied to the receiving bus. (c) If the sending end voltage is changed to 8210 kV, the current is

I=

80,00015 76,0000 = 3887.2 A 10.3 + j 52.5

The real and reactive power supplied by this transmission line is

P = 3V ,R I cos = 3 ( 76 kV )( 388 A ) cos ( 7.2) = 87.8 MW Q = 3V ,R I sin = 3 ( 76 kV )( 388 A ) sin ( 7.2) = 11 MVAR
In this case, there was a relatively large change in P (27.4 MW) and a relatively small change in Q (11.5 MVAR) supplied to the receiving bus. (d) From the above results, we can see that real power flow can be adjusted by changing the phase angle between the two voltages at the two ends of the transmission line, while reactive power flow can be changed by changing the relative magnitude of the two voltages on either side of the transmission line. 9-16. A 50 Hz three phase transmission line is 300 km long. It has a total series impedance of 23 + j 75 and a shunt admittance of j500 S . It delivers 150 MW at 220 kV, with a power factor of 0.88 lagging. Find the voltage at the sending end using (a) the short line approximation. (b) The medium-length line

188

approximation. (c) The long line equation. approximations for this case? SOLUTION

How accurate are the short and medium-length line

(a) In the short line approximation, the shunt admittance is ignored. The ABCD constants for this line are:

A =1 B = Z C = 0 D =1 A=1

(9-67)

B = Z = 23 + j 75 = 78.473
C=0S

D =1
The receiving end line voltage is 220 kV, so the rated phase voltage is 220 kV / current is

3 = 127 kV, and the

IL =

Sout 150,000,000 W = = 394 A 3VLL 3 ( 220, 000 V )

If the phase voltage at the receiving end is assumed to be at a phase angle of 0, then the phase voltage at the receiving end will be VR = 1270 kV , and the phase current at the receiving end will be

I R = 394 28.4 A . The current and voltage at the sending end of the transmission line are given by the following equations:

VS = AVR + BI R VS = (1)(1270 kV ) + ( 78.473 )( 394 28.4 A ) VS = 1518.2 kV I S = CVR + DI R I S = ( 0 S)(1330 kV ) + (1)( 394 28.4 A ) I S = 394 28.4 A
(b) In the medium length line approximation, the shunt admittance divided into two equal pieces at either end of the line. The ABCD constants for this line are:

ZY +1 B=Z 2 ZY ZY C =Y + 1 D = +1 2 4 ZY ( 23 + j 75 )( j0.0005 S) + 1 = 0.98130.34 A= +1 = 2 2 A=


( 23 + j 75 )( j 0.0005 S) ZY C =Y + 1 = ( j 0.0005 S) + 1 4 4
189

(9-73)

B = Z = 23 + j 75 = 78.473

C = 4.953 104 90.2 S ZY ( 23 + j75 )( j0.0005 S) + 1 = 0.98130.34 D= +1 = 2 2


The receiving end line voltage is 220 kV, so the rated phase voltage is 220 kV / current is

3 = 127 kV, and the

IL =

Sout 150,000,000 W = = 394 A 3VLL 3 ( 220, 000 V )

If the phase voltage at the receiving end is assumed to be at a phase angle of 0, then the phase voltage at the receiving end will be VR = 1270 kV , and the phase current at the receiving end will be

I R = 394 28.4 A . The current and voltage at the sending end of the transmission line are given by
the following equations:

VS = AVR + BI R VS = 148.48.7 kV I S = CVR + DI R I S = 361 19.2 A


(c) In the long transmission line, the ABCD constants are based on modified impedances and admittances:

sinh d d tanh ( d / 2 ) Y =Y d /2 Z = Z A=

(9-74) (9-75)

and the corresponding ABCD constants are

Z Y B = Z +1 2 Z Y Z Y C = Y + 1 D = +1 2 4
yz

(9-76)

The propagation constant of this transmission line is =

= yz =

j500 106 300 km

S 23 + j 75 = 0.0006681.5 300 km

d = ( 0.0006681.5)( 300 km ) = 0.19881.5


The modified parameters are

sinh ( 0.19881.5) sinh d = ( 23 + j 75 ) = 77.973 0.19881.5 d tanh ( d / 2 ) Y =Y = 5.01 104 89.9 S d /2 Z = Z

and the ABCD constants are

190

A=

Z Y + 1 = 0.9830.33 2

B = Z = 77.973 Z Y C = Y + 1 = 4.9790.1 S 4 Z Y D= + 1 = 0.9830.33 2


The receiving end line voltage is 220 kV, so the rated phase voltage is 220 kV / current is

3 = 127 kV, and the

IL =

Sout 150,000,000 W = = 394 A 3VLL 3 ( 220, 000 V )

If the phase voltage at the receiving end is assumed to be at a phase angle of 0, then the phase voltage at the receiving end will be VR = 1270 kV , and the phase current at the receiving end will be

I R = 394 28.4 A . The current and voltage at the sending end of the transmission line are given by
the following equations:

VS = AVR + BI R VS = 148.28.7 kV I S = CVR + DI R I S = 361.2 19.2 A


The short transmission line approximate was rather inaccurate, but the medium and long line models were both in good agreement with each other. 9-17. A 60 Hz, three phase, 110 kV transmission line has a length of 100 miles and a series impedance of 0.20 + j 0.85 /mile and a shunt admittance of 6 106 S/mile. The transmission line is supplying 60 MW at a power factor of 0.85 lagging, and the receiving end voltage is 110 kV. (a) What are the voltage, current, and power factor at the receiving end of this line? (b) What are the voltage, current, and power factor at the sending end of this line? (c) How much power is being lost in this transmission line? (d) What is the current angle of this transmission line? How close is the transmission line to its steady-state stability limit? SOLUTION This transmission line may be considered to be a medium-line line. The impedance Z and admittance Y of this line are:

Y = j 6 106 /mile (100 miles) = j 0.0006 S


The ABCD constants for this line are:

Z = ( 0.20 + j 0.85 /mile )(100 miles ) = 20 + j85

A=

ZY ( 20 + j85 )( j0.0006 S) + 1 = 0.97450.35 +1 = 2 2

( 20 + j85 )( j 0.0006 S) ZY + 1 = ( j 0.0006 S) + 1 = 0.0005990.2 S C =Y 4 4


191

B = Z = 20 + j85 = 87.376.8

D=
(a)

ZY ( 20 + j85 )( j0.0006 S) + 1 = 0.97450.35 +1 = 2 2

Assuming that the receiving end voltage is at 0, the receiving end phase voltage and current are.

VR = 1100 kV/ 3 = 63.50 kV P 60 MW IR = = = 370 A 3V cos 3 (110 kV )( 0.85)


I R = 370 31.7 A
The receiving end power factor is 0.85 lagging. The receiving end line voltage and current are 110 kV and 370 A, respectively. (b) The sending end voltage and current are given by

VS = AVR + BI R = A ( 63.50 kV ) + B ( 370 31.7 A ) VS = 87.815.35 kV I S = CVR + DI R = C ( 63.50 kV ) + D ( 370 31.7 A ) I S = 342.4 26 A
The sending end power factor is cos = cos ( 41.4) = 0.751 lagging . The sending end line 15.35 ( 26) voltage and current are 3 ( 87.8 kV ) = 152 kV and 342 A, respectively. (c) The power at the sending end of the transmission line is

PS = 3V ,S I ,S cos = 3 ( 87,800)( 342 )( 0.751) = 67.7 MW


The power at the receiving end of the transmission line is

PR = 3V ,R I ,R cos = 3 ( 63,500)( 370)( 0.85) = 59.9 MW


Therefore the losses in the transmission line are approximately 7.8 MW. (d) The angle is 15.35. It is about 1/4 of the way to the lines static stability limit.