Carrier 466
Carrier 466
Carrier 466
Data
50BR,BZ
Single-Package
Cooling Units
Features/Benefits
Application versatility
Carrier air conditioning technology
leads the way with a proven line of
single-package cooling units
Models 50BR and BZ. These 50BR
(water-cooled) and 50BZ (condenserless) systems are available in 5 convenient sizes, ranging from 60,000
to 180,000 Btuh, to ideally meet the
needs for cooling restaurants, retail
stores, warehouses, offices, and building additions.
These units can be installed in the
equipment room or the conditioned
space and specified for either ducted
applications or free-blow applications with an accessory plenum.
Form 50B-1PD
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,5
Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,7
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-29
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31,32
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35,36
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-40
Features/Benefits (cont)
FAN SWITCH
(Hidden)
Physical data
50
UNIT SIZE
NOMINAL CAPACITY (TONS)
OPERATING WEIGHT (lb)
Base Unit
Plenum
COMPRESSOR
Model
Quantity
Rpm
Oil Charge (oz)
Steps of Control
OPERATING CHARGE
No. of Circuits...Charge
HOLDING CHARGE**
Nitrogen
CONDENSER WATER TYPE
Quantity
Nominal Gpm
Gpm Range
Max Working Pressure (psig)
Min Entering Water (F)
Max Entering Water (F)
Water Volume (Gal)
INDOOR FAN
Nominal Cfm
Cfm Range
Available Static (in. wg)
Fan Size (in.)
Number of Fans
Standard Speed Range (Rpm)
Max Allowable Rpm
Motor Rpm
Belt Quantity...Type
Fan Pulley (in.)
Motor Pulley (in.)
Nominal Hp...Frame Size
Fan Shaft Size (mm)
Motor Shaft Size (in.)
Center Distance (in.)
INDOOR COIL
Number of Rows...Fin/in.
Face Area (sq ft)
RETURN AIR FILTERS
Quantity...Size (in.)
CONTROLS
High Pressure Cutout (psig)
Cut-in (psig)
Low Pressure Cutout (psig)
Cut-in (psig)
Fusible Plug
Time GuardT II Device
CONNECTIONS
Water Connection Type (BR Only)
Water (in.) (BR Only)
Refrigerant Connection Type (BZ Only)
Hot Gas Connection (in.) Quantity...Size
Liquid Connection (in.)
Quantity...Size
BR
BZ
BR
006
5
BZ
BR
008
712
560
530
620
580
40
44
SR58
1
SR75
1
44
1
50
1
1...6.1**
1...7.4
1...7.7**
No
Yes
No
1
15
10-20
400
45
105
0.86
2000
1500-2500
0.50
12 x 12
1
650-920
1350
1725
1...A28
5.2
2.7-3.7
1...56
20
58
18
3...14
4.9
1...20 x 16
1...20 x 20
BZ
BZ
880
820
60
Carrier Scroll
SR58
2
3500
44/44
2
1...8.1
2...6.1**
2...7.4
395
300
7
27
280
180
7
27
395
300
7
27
1...12
1...12
1...12
1...12
950
870
SR58/SR75
1/1*
SR75
2
44/50
2
50/50
2
2...7.6**
Quantity...Size
1...58
1...78
Quantity...Size
Quantity...Type
1...12
1...12
2...12
NOTE: Fan wheel, bearing, and shaft bore sizes are in metric units. Contact your local representative
for correct replacement parts.
197
910
73
112
Flare Connection
2...12
2...12
2...58
980
66
24 V Provided in Unit
280
395
280
180
300
180
7
7
7
27
27
27
203 F
5 Minutes on Each Circuit
BZ
016
15
2...6.1/7.4*
Yes
No
Yes
No
Yes
Tube-in-Tube (Steel Shell with Copper Tube)
1
22
30
36
15-30
20-40
24-48
400
400
400
45
45
45
105
105
105
2.42
0.86
2.42
280
180
7
27
BR
014
12
*Circuit 1/Circuit 2.
Based on 25 ft of interconnecting tubing (standard liquid-line size, 50BZ only).
**Factory charged.
BR
012
10
2...7.7**
2...8.1
No
Yes
2
45
30-60
400
45
105
2.42
6000
4500-7500
1.10
15 x 15
2
1220-1530
1530
1725
1...B33
5.7
4.1-5.3
5...184T
25
118
14
3...14
12.4
1...16 x 20
3...20 x 25
395
300
7
27
280
180
7
27
395
300
7
27
112
2...12
2...12
1...78,
1...58
2...12
2...12
2...12
2...78
2...12
CAPACITY (Btuh)
58,000
78,000
115,000
133,000
145,000
54,500
77,000
109,000
134,000
136,000
145,000
162,000
EER
12.2
12.5
12.5
11.6
10.7
9.1
9.4
9.0
9.3
10.3
9.0
9.4
LEGEND
ARI Air Conditioning and Refrigeration Institute
EER Energy Efficiency Ratio
*Requires 2 9AB units.
Field-installed accessories
Supply-air discharge plenum Field installed with adjustable horizontal and vertical louvers for controlled freeblow into the conditioned space. Mounts easily on top of
base unit. Matches unit styling.
Heating coils Field installed for hot water or steam with
convenient field piping connections on side of unit.
NOTE: Accessory ducted return-air filter rack required.
Evaporator defrost thermostat For winter start control on 50BZ units. Package provides coil freeze-up protection under low ambient temperature start-up conditions.
Thermostats A complete line of Carrier thermostats is
available to meet any control requirements, including
Carrier TEMP System thermostats for diagnostics and communicating capability.
197
DIM
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
T
006
mm
1970
1040
580
295
483
312
624
428
392
22
357
60
100
390
174
206
356
008
Ft-In.
6- 5916
3- 41516
1-102732
0-1158
1- 61516
1- 0932
2- 0916
1- 42732
1- 3716
0- 078
1- 2116
0- 238
0- 31516
1- 31132
0- 678
0- 818
1- 2
mm
1970
1231
580
295
483
312
624
428
410
22
357
60
100
390
174
206
356
Ft-In.
6- 5916
4- 01532
1-102732
0-1158
1- 61516
1- 0932
2- 0916
1- 42732
1- 418
0- 078
1- 2116
0- 238
0- 31516
1- 31132
0- 678
0- 818
1- 2
UNIT 50BR
012
mm
Ft-In.
1980
6- 51516
1422
4- 73132
700
2- 3916
335
1- 1316
353
1- 12932
304
0-113132
796
2- 7516
338
1- 1516
410
1- 418
18
0- 02332
341
1- 1716
140
0- 512
200
0- 778
125
0- 42932
121
0- 434
391
1- 31332
200
0- 778
356
1- 2
014
mm
1980
1613
700
335
353
304
796
396
410
18
357
140
200
125
121
391
230
356
016
Ft-In.
6- 51516
5- 312
2- 3916
1- 3316
1- 12932
0-113132
2- 7516
1- 31932
1- 418
0- 02332
1- 2116
0- 512
0- 778
0- 42932
0- 434
1- 31332
0- 9116
1- 2
mm
1980
1804
700
335
353
304
796
428
410
18
357
140
200
125
121
391
268
356
Ft-In.
6- 51516
5-11132
2- 3916
1- 3316
1- 12932
0-113132
2- 7516
1- 42732
1- 418
0- 02332
1- 2116
0- 512
0- 778
0- 42932
0- 434
1- 31332
0-10916
1- 2
DIM
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
S
T
U
V
006
mm
1970
1040
580
295
483
312
624
428
392
22
357
60
100
390
104
108
45
509
Ft-In.
6- 5916
3- 41516
1-102732
0-1158
1- 61516
1- 0932
2- 0916
1- 42732
1- 3716
0- 078
1- 2116
0- 238
0- 31516
1- 31132
0- 4332
0- 414
0- 134
1- 8
008
mm
1970
1231
580
295
483
312
624
428
410
22
357
60
100
390
104
108
45
509
Ft-In.
6- 5916
4- 01532
1-102732
0-1158
1- 61516
1- 0932
2- 0916
1- 42732
1- 418
0- 078
1- 2116
0- 238
0- 31516
1- 31132
0- 4332
0- 414
0- 134
1- 8
UNIT 50BZ
012
mm
Ft-In.
1980
6- 51516
1422
4- 73132
700
2- 3916
335
1- 1316
353
1- 12932
304
0-113132
796
2- 7516
338
1- 1516
410
1- 418
18
0- 02332
341
1- 1716
140
0- 512
200
0- 778
125
0- 42932
200
0- 778
476
1- 634
961
3- 11316
014
mm
1980
1613
700
335
353
304
796
396
410
18
357
140
200
125
230
476
961
Ft-In.
6- 51516
5- 312
2- 3916
1- 3316
1- 12932
0-113132
2- 7516
1- 31932
1- 418
0- 02332
1- 2116
0- 512
0- 778
0- 42932
0- 9116
1- 634
3- 11316
mm
1980
1804
700
335
353
304
796
428
410
18
357
140
200
125
268
476
961
016
Ft-In.
6- 51516
5-11132
2- 3916
1- 3316
1- 12932
0-113132
2- 7516
1- 42732
1- 418
0- 02332
1- 2116
0- 512
0- 778
0- 42932
0-10916
1- 634
3- 11316
Given:
Cooling Requirements
Total Cooling Capacity
(TC/Btuh)
Sensible Cooling Capacity
(SHC/Btuh)
Evaporator Air Quantity
(cfm)
Summer Entering-Air
Conditions:
Entering dry bulb (edb)
Entering wet bulb (ewb)
Entering Condenser
Water Temperature
(Water-Cooled Selection)
Entering-water temperature (ewt)
Entering Condenser Air
Temperature (AirCooled Selection) (EAT)
Flow Rate (gpm)
Unit Voltage
Heating Requirements
Total Heating Load
(TC/Btuh)
Winter Entering-Air
Temperature (edb)
Entering Hot Water
Temperature (ewt)
OR
Steam Pressure Available
(psig)
Fan Requirements
External Static Pressure
Required ESP (in. wg)
50BR012
Water-Cooled
50BZ012
Air-Cooled
120,000
111,000
84,000
84,000
4,000
4,000
82 F
67 F
82 F
67 F
85 F
95 F
20
460 v
460 v
236,000
236,000
60 F
60 F
200 F
200 F
0.6
0.6
Performance data
Cooling capacity notes
1. Water gpm values are calculated using a 0.0005 fouling
factor.
5. All combinations use R-22. Unless otherwise designated, ratings are at optimum charge.
BYPASS
FACTOR
(BF)
.05
.10
.20
.30
.35
LEGEND
SHC Sensible Heat Capacity
Correction Factor = 1.10 x (1 BF) x (db 80).
The following formulas may be used:
sensible capacity (Btuh)
1.10 x cfm
lwb = Wet-bulb temperature corresponding to enthalpy of air leaving
evaporator coil (hlwb )
ldb = edb
hlwb = h ewb
Where:
hewb = Enthalpy of air entering evaporator coil.
EWT
(F)
GPM
PRESSURE
DROP
Ft
65
Psig
10
5.7
2.4
12.5
9.1
3.8
15
12.2
5.1
10
5.7
2.4
12.5
9.1
3.8
15
12.2
5.1
17.5
16.3
6.8
10
5.7
2.4
12.5
9.1
3.8
15
12.2
5.1
17.5
16.3
6.8
12.5
9.1
3.8
15
12.2
5.1
17.5
16.3
6.8
75
85
95
1500 / 0.13
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
68.0
32.9
3.55
68.2
32.9
3.46
68.4
33.0
3.40
66.1
32.1
3.92
66.3
32.2
3.81
66.4
32.3
3.75
66.5
32.3
3.70
64.0
31.4
4.32
64.2
31.4
4.21
64.3
31.5
4.14
64.4
31.5
4.09
62.0
30.6
4.65
62.2
30.7
4.57
62.2
30.7
4.52
67
62.3
40.9
3.49
62.5
41.0
3.40
62.7
40.7
3.35
60.4
40.1
3.85
60.6
40.2
3.75
60.7
40.3
3.69
60.8
40.3
3.65
58.5
39.3
4.25
58.7
39.4
4.15
58.8
39.4
4.08
58.9
39.5
4.04
56.6
38.5
4.59
56.7
38.6
4.52
56.8
38.6
4.45
62
56.9
48.7
3.43
57.1
48.8
3.35
57.3
49.2
3.39
55.2
47.9
3.79
55.4
48.0
3.70
55.4
48.0
3.65
55.5
48.0
3.61
53.4
47.0
4.19
53.6
47.1
4.10
53.6
47.1
4.04
53.7
47.1
3.99
51.7
46.1
4.54
51.8
46.2
4.47
51.9
46.2
4.42
2500 / 0.19
67
66.5
51.3
3.55
66.7
51.4
3.46
66.8
51.4
3.40
64.4
50.5
3.91
64.6
50.6
3.81
64.7
50.6
3.74
64.8
50.7
3.70
62.2
49.6
4.31
62.4
49.7
4.20
62.6
49.8
4.13
62.6
49.8
4.08
60.1
48.8
4.64
60.2
48.8
4.57
60.3
48.8
4.51
62
61.9
61.3
3.50
62.1
61.5
3.41
62.2
61.5
3.35
60.1
59.9
3.86
60.2
60.1
3.76
60.4
60.2
3.70
60.5
60.2
3.66
58.2
58.2
4.26
58.4
58.4
4.16
58.5
58.5
4.09
58.6
58.6
4.04
56.5
56.5
4.60
56.6
56.6
4.53
56.7
56.7
4.48
57
61.6
61.6
3.50
61.7
61.7
3.41
61.8
61.8
3.35
59.9
59.9
3.85
60.1
60.1
3.76
60.2
60.2
3.70
60.3
60.3
3.66
58.2
58.2
4.26
58.4
58.4
4.16
58.5
58.5
4.09
58.6
58.6
4.04
56.5
56.5
4.60
56.6
56.6
4.53
56.7
56.7
4.48
LEGEND
Bypass Factor
Entering Wet Bulb
Entering-Water Temperature (F)
Gallons per minute
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
EWT
(F)
GPM
PRESSURE
DROP
Ft
65
Psig
15
8.4
3.5
18.8
12.4
5.2
22.5
16.8
7.0
15
8.4
3.5
18.8
12.4
5.2
22.5
16.8
7.0
26.3
22.0
9.2
15
8.4
3.5
18.8
12.4
5.2
22.5
16.8
7.0
26.3
22.0
9.2
18.8
12.4
5.2
22.5
16.8
7.0
26.3
22.0
9.2
75
85
95
2250 / 0.08
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
92.3
45.4
4.28
92.6
45.5
4.13
92.8
45.6
4.03
89.5
44.3
4.85
89.8
44.4
4.69
90.0
44.5
4.59
90.1
44.6
4.52
86.7
43.3
5.46
86.9
43.4
5.30
87.1
43.4
5.19
87.2
43.5
5.12
83.9
42.3
5.95
84.1
42.3
5.84
84.2
42.4
5.76
67
84.5
57.2
4.23
84.7
57.2
4.09
84.9
57.3
4.01
81.9
56.1
4.79
82.1
56.1
4.64
82.3
56.2
4.55
82.4
56.3
4.49
79.3
55.0
5.39
79.5
55.0
5.24
79.6
55.1
5.14
79.7
55.1
5.07
76.8
53.9
5.88
77.0
54.0
5.78
77.1
54.0
5.71
10
LEGEND
Bypass Factor
Entering Wet Bulb
Entering-Water Temperature (F)
Gallons per minute
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
62
77.3
68.4
4.18
77.5
68.5
4.06
77.6
68.6
3.98
75.0
67.3
4.73
75.2
67.4
4.60
75.3
67.4
4.52
75.4
67.5
4.46
72.7
66.1
5.32
72.9
66.2
5.18
72.9
66.2
5.09
73.0
66.3
5.03
70.4
64.9
5.81
70.5
65.0
5.72
70.6
65.0
5.65
3750 / 0.13
67
89.6
72.0
4.26
89.9
72.1
4.12
90.2
72.2
4.03
86.7
70.8
4.84
87.0
70.9
4.68
87.2
71.0
4.58
87.3
71.0
4.51
83.7
69.6
5.45
84.0
69.7
5.29
84.1
69.7
5.18
84.3
69.8
5.11
80.9
68.4
5.94
81.7
68.4
5.83
81.2
68.5
5.75
62
84.1
84.1
4.24
84.3
84.3
4.10
84.5
84.5
4.01
81.8
81.8
4.80
82.0
82.0
4.65
82.2
82.2
4.56
82.3
82.3
4.50
79.4
79.4
5.40
79.6
79.6
5.25
79.7
79.7
5.15
79.8
79.8
5.08
77.2
77.2
5.90
77.4
77.4
5.80
77.4
77.4
5.72
57
84.1
84.1
4.24
84.3
84.3
4.10
84.5
84.5
4.01
81.8
81.8
4.80
82.0
82.0
4.65
82.1
82.1
4.56
82.3
82.3
4.50
79.4
79.4
5.40
79.6
79.6
5.25
79.7
79.7
5.15
79.8
79.8
5.08
77.2
77.2
5.90
77.4
77.4
5.80
77.4
77.4
5.72
EWT
(F)
GPM
PRESSURE
DROP
Ft
65
Psig
20
5.7
2.4
25
9.1
3.8
30
12.2
5.1
20
5.7
2.4
25
9.1
3.8
30
12.2
5.1
35
16.3
6.8
20
5.7
2.4
25
9.1
3.8
30
12.2
5.1
35
16.3
6.8
25
9.1
3.8
30
12.2
5.1
35
16.3
6.8
75
85
95
3000 / 0.06
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
134.4
65.1
7.23
134.9
65.3
7.01
135.3
65.4
6.87
130.6
63.6
8.02
131.0
63.8
7.77
131.3
63.9
7.62
131.6
64.0
7.51
126.4
62.1
8.90
126.9
62.2
8.64
127.2
62.4
8.47
127.5
62.4
8.34
122.5
60.6
9.60
122.8
60.7
9.42
123.0
60.8
9.29
67
123.1
81.2
7.13
123.6
81.3
6.92
123.8
81.5
6.79
119.5
79.6
7.91
119.9
79.8
7.68
120.1
79.9
7.54
120.4
80.0
7.43
115.6
77.9
8.79
116.1
78.1
8.54
116.4
78.2
8.39
116.5
78.3
8.27
111.9
76.4
9.51
112.1
76.5
9.33
112.4
76.6
9.21
62
112.6
96.7
7.03
113.0
96.9
6.84
113.2
97.0
6.72
109.2
95.0
7.81
109.6
95.2
7.60
109.9
95.3
7.47
110.0
95.4
7.37
105.6
93.2
8.68
106.0
93.4
8.46
106.3
93.5
8.31
106.4
93.6
8.21
102.1
91.5
9.41
102.4
91.6
9.26
102.6
91.7
9.14
5000 / 0.10
67
131.2
101.7
7.22
131.8
101.9
7.00
132.1
120.1
6.86
127.1
100.1
8.00
127.7
100.2
7.76
128.0
100.4
7.61
128.2
100.5
7.94
122.7
98.3
8.88
123.2
98.5
8.62
123.6
98.6
8.45
123.9
98.7
8.34
118.6
96.6
9.59
118.9
96.7
9.40
119.1
96.9
9.27
62
122.4
121.4
7.13
122.8
121.7
6.93
123.1
122.0
6.79
118.8
118.6
7.92
119.2
118.9
7.69
119.5
119.5
7.55
119.6
119.4
7.44
115.1
115.1
8.81
115.5
115.5
8.55
115.7
115.7
8.40
115.9
115.9
8.28
111.8
111.8
9.51
112.0
112.0
9.35
112.2
112.2
9.22
57
121.9
121.9
7.13
122.3
122.3
6.92
122.5
122.5
6.79
118.6
118.6
7.92
119.0
119.0
7.69
119.5
119.5
7.55
119.6
119.6
7.44
115.1
115.1
8.81
115.5
115.5
8.55
115.7
115.7
8.40
115.9
115.9
8.28
111.8
111.8
9.51
112.0
112.0
9.35
112.2
112.2
9.22
LEGEND
Bypass Factor
Entering Wet Bulb
Entering-Water Temperature (F)
Gallons per minute
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
11
EWT
(F)
GPM
PRESSURE
DROP
Ft
65
Psig
25
6.0
2.5
31
9.1
3.8
37.5
12.5
5.2
25
6.0
2.5
31
9.1
3.8
37.5
12.5
5.2
44
16.3
6.8
25
6.0
2.5
31
9.1
3.8
37.5
12.5
5.2
44
16.3
6.8
31
9.1
3.8
37.5
12.5
5.2
44
16.3
6.8
85
95
3750 / 0.08
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
158.9
77.7
7.81
159.3
77.8
7.57
159.6
77.9
7.40
154.2
75.9
8.76
154.5
76.0
8.50
154.9
76.1
8.32
155.0
76.2
8.19
149.4
74.1
9.81
149.8
74.2
9.53
150.0
74.3
9.33
150.2
74.3
9.20
144.8
72.3
10.65
145.1
72.4
10.44
145.3
72.5
10.30
67
145.4
97.2
7.71
145.7
97.4
7.49
146.0
97.5
7.34
141.1
95.4
8.64
141.4
95.5
8.41
141.6
95.6
8.25
141.8
95.7
8.11
136.7
93.6
9.66
137.0
93.7
9.42
137.3
93.8
9.24
137.4
93.8
9.12
132.4
91.7
10.53
132.6
91.8
10.34
132.8
91.9
10.20
62
132.9
116.2
7.61
133.2
116.3
7.41
133.4
116.4
7.27
129.1
114.3
8.53
129.3
114.4
8.31
129.5
114.5
8.17
129.7
114.5
8.06
125.0
112.2
9.54
125.3
112.3
9.31
125.5
112.4
9.15
125.6
112.5
9.04
121.1
110.2
10.40
121.3
110.3
10.23
121.4
110.3
10.11
12
LEGEND
Bypass Factor
Entering Wet Bulb
Entering-Water Temperature (F)
Gallons per minute
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
6250 / 0.12
67
154.6
122.1
7.80
155.1
122.1
7.56
155.3
122.3
7.39
149.7
120.0
8.74
149.9
120.2
8.49
150.2
120.3
8.31
150.5
120.4
8.18
144.4
117.9
9.79
144.8
118.0
9.51
145.1
118.1
9.32
145.3
118.2
9.18
139.6
115.9
10.63
139.8
116.0
10.42
140.0
116.1
10.28
62
144.3
144.0
7.72
144.6
144.3
7.50
144.8
144.8
7.34
140.2
140.2
8.66
140.5
140.5
8.42
140.7
140.7
8.25
140.9
140.9
8.14
136.3
136.3
9.69
136.6
136.6
9.44
136.7
136.7
9.26
136.9
136.9
9.13
132.4
132.4
10.55
132.6
132.6
10.36
132.7
132.7
10.23
57
144.1
144.1
7.72
144.4
144.4
7.50
144.8
144.8
7.34
140.2
140.2
8.66
140.5
140.5
8.42
140.7
140.7
8.25
140.8
140.8
8.14
136.3
136.3
9.69
136.6
136.6
9.44
136.7
136.7
9.26
136.9
136.9
9.13
132.4
132.4
10.55
132.6
132.6
10.36
132.7
132.7
10.23
EWT
(F)
GPM
PRESSURE
DROP
Ft
65
Psig
30
8.4
3.5
37.5
12.4
5.2
45
16.8
7.0
30
8.4
3.5
37.5
12.4
5.2
45
16.8
7.0
52
22.0
9.2
30
8.4
3.7
37.5
12.4
5.2
45
16.8
7.0
52
22.0
9.2
37.5
12.4
5.2
45
16.8
7.0
52
22.0
9.2
75
85
95
4500 / 0.09
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
72
184.3
90.8
8.73
184.8
91.0
8.45
185.1
91.1
8.25
178.6
88.6
9.89
179.2
88.8
9.58
179.5
88.9
9.38
179.8
89.1
9.24
172.9
86.5
11.15
173.5
86.7
10.82
173.7
86.8
10.60
173.9
86.9
10.45
167.7
84.6
12.16
167.9
84.7
11.93
168.2
84.7
11.77
67
168.7
114.3
8.63
169.1
114.5
8.37
169.3
114.6
8.19
163.5
112.2
9.76
163.9
112.3
9.48
164.2
112.4
9.30
164.4
112.5
9.17
158.4
110.0
10.98
158.8
110.2
10.69
159.0
110.3
10.50
159.2
110.3
10.36
153.4
108.0
12.00
153.7
108.1
11.79
153.9
108.1
11.65
62
154.3
137.0
8.53
154.7
137.1
8.30
154.8
137.3
8.13
149.8
134.7
9.63
150.1
134.8
9.39
150.3
134.9
9.22
150.5
135.0
9.10
145.1
132.3
10.83
145.4
132.5
10.57
145.7
132.6
10.39
145.8
132.6
10.26
140.6
130.0
11.83
140.8
130.1
11.66
140.9
130.2
11.53
7500 / 0.14
67
178.5
143.9
8.72
179.0
144.1
8.43
179.5
144.3
8.24
172.6
141.5
9.86
173.1
141.8
9.57
173.6
141.8
9.37
173.9
141.9
9.23
166.7
139.0
11.11
167.1
139.2
10.79
167.4
139.4
10.58
167.7
139.5
10.43
161.1
136.7
12.12
161.4
136.8
11.90
161.7
136.9
11.74
62
167.8
167.8
8.65
168.2
168.2
8.38
168.5
168.5
8.20
163.2
163.2
9.79
163.5
163.5
9.50
163.8
163.8
9.31
164.0
164.0
9.18
158.5
158.5
11.02
158.9
158.9
10.72
159.1
159.1
10.52
159.3
159.3
10.38
154.0
154.0
12.04
154.3
154.3
11.83
154.4
154.4
11.69
57
167.8
167.8
8.65
168.2
168.2
8.38
168.5
168.5
8.20
163.2
163.2
9.79
163.5
163.5
9.50
163.8
163.8
9.31
164.0
164.0
9.18
158.5
158.5
11.02
158.9
158.9
10.72
159.1
159.1
10.52
159.3
159.3
10.38
154.0
154.0
12.04
154.3
154.3
11.83
154.4
154.4
11.69
LEGEND
Bypass Factor
Entering Wet Bulb
Entering-Water Temperature (F)
Gallons per minute
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
13
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1500 / 0.13
72
74.2
36.8
4.64
71.7
35.8
5.07
69.2
34.8
5.51
66.4
33.7
6.01
63.5
32.6
6.56
60.5
31.4
7.15
57.4
30.2
7.77
67
68.2
44.3
4.53
65.9
43.2
4.96
63.5
42.1
5.39
61.0
41.0
5.88
58.5
39.9
6.46
55.8
38,7
7.04
52.9
37.5
7.64
62
62.7
51.7
4.47
60.5
50.6
4.89
58.4
49.5
5.31
56.1
48.4
5.79
53.6
47.2
6.32
51.1
46.0
6.88
48.3
44.7
7.47
57
56.9
56.9
4.38
55.3
55.3
4.79
53.7
53.7
5.21
52.0
52.0
5.73
50.2
50.2
6.25
48.3
48.3
6.81
46.3
46.3
7.41
14
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
2500 / 0.19
72
81.4
43.7
5.08
78.4
42.6
5.52
75.4
41.5
5.96
72.2
40.3
6.47
68.9
39.1
7.02
65.4
37.9
7.62
61.7
36.6
8.25
67
75.1
55.1
4.97
72.3
54.0
5.40
69.5
52.9
5.84
66.6
51.7
6.33
63.8
50.5
6.92
60.5
49.3
7.51
57.1
47.9
8.13
62
69.2
67.3
4.89
66.6
65.5
5.32
64.0
63.7
5.75
61.2
61.2
6.24
58.7
58.7
6.78
56.2
56.2
7.37
53.5
53.5
7.98
57
67.2
67.2
4.85
65.2
65.2
5.30
63.3
63.3
5.74
60.9
60.9
6.21
58.7
58.7
6.79
56.2
56.2
7.38
53.6
53.6
8.00
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
1500 / 0.08
72
69.2
34.4
6.80
66.7
33.4
7.37
64.2
32.5
7.94
61.5
31.5
8.56
58.6
30.4
9.22
55.6
29.3
9.93
52.4
28.2
10.7
67
63.3
42.3
6.67
61.0
41.4
7.22
58.7
40.4
7.76
56.1
39.3
8.35
53.5
38.3
8.98
50.8
37.1
9.64
47.8
35.9
10.3
62
57.8
50.0
6.55
55.6
49.0
7.07
53.5
47.9
7.59
51.3
46.8
8.16
48.9
45.6
8.75
46.4
44.2
9.37
43.9
42.8
10.0
57
54.5
54.5
6.44
52.8
52.8
6.96
51.2
51.2
7.47
49.4
49.4
8.03
47.6
47.6
8.62
45.6
45.6
9.24
43.5
43.5
9.87
2500 / 0.13
72
73.4
41.2
8.27
71.4
40.5
8.21
69.4
39.8
8.16
66.7
38.9
8.46
63.1
37.6
9.47
59.7
36.5
10.2
56.1
35.3
10.9
67
67.3
53.4
8.10
65.5
52.7
8.04
63.8
52.0
7.98
61.3
51.0
8.27
58.0
49.6
9.23
54.9
48.3
9.91
51.7
46.9
10.6
62
62.8
62.6
7.95
61.4
61.3
7.90
60.0
60.0
7.84
57.7
57.7
8.43
55.4
55.4
9.06
52.9
52.9
9.74
50.3
50.3
10.4
57
62.8
62.8
7.86
61.4
61.4
7.80
60.1
60.1
7.75
57.7
57.7
8.43
55.9
55.9
8.65
53.1
53.1
9.63
50.5
50.5
10.3
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
15
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
2250 / 0.08
72
96.7
48.8
5.82
93.6
47.7
6.44
90.4
46.5
7.09
87.2
45.3
7.79
83.9
44.1
8.54
80.5
42.9
9.35
76.9
41.6
10.2
67
89.0
60.9
5.71
86.1
59.7
6.31
83.3
58.5
6.95
80.4
57.3
7.63
77.4
56.1
8.36
74.2
54.8
9.13
71.0
53.5
9.96
62
81.8
72.4
5.62
79.3
71.2
6.19
76.7
69.9
6.82
74.1
68.6
7.48
71.4
67.1
8.19
68.6
65.6
8.94
65.8
64.1
9.73
57
78.1
78.1
5.57
76.1
76.1
6.15
74.1
74.1
6.76
72.0
72.0
7.43
69.7
69.7
8.13
67.4
67.4
8.90
65.3
65.3
9.83
16
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
3750 / 0.13
67
95.6
77.7
6.27
92.4
76.4
6.88
89.1
75.1
7.53
85.8
73.7
8.23
82.4
72.2
8.98
78.9
70.7
9.77
75.3
69.1
10.6
62
90.1
90.1
6.20
87.5
87.5
6.79
85.0
85.0
7.45
82.3
82.3
8.14
79.7
79.7
8.95
76.7
76.7
9.71
73.7
73.7
10.5
57
90.2
90.2
6.21
87.6
87.6
6.81
85.1
85.1
7.49
82.4
82.4
8.18
79.6
79.6
8.92
76.7
76.7
9.71
73.8
73.8
10.6
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
2250 / 0.08
72
93.6
47.7
6.35
90.5
46.5
7.04
87.3
45.3
7.79
83.8
44.0
8.53
80.2
42.8
9.37
76.5
41.5
10.2
72.8
40.1
11.1
67
86.5
59.8
6.23
83.4
58.6
6.85
80.6
57.4
7.57
77.6
56.2
8.33
74.3
54.8
9.13
70.8
53.4
9.94
67.3
52.0
10.8
62
79.7
71.4
6.07
77.1
70.1
6.72
74.6
68.8
7.42
71.7
67.3
8.10
68.8
65.7
8.90
65.8
64.1
9.72
62.8
62.3
10.6
57
76.6
76.6
6.02
74.4
74.4
6.62
72.3
72.3
7.32
70.1
70.1
8.07
67.8
67.8
8.89
65.1
65.1
9.68
62.2
62.2
10.4
3750 / 0.13
72
99.8
58.1
6.96
96.3
56.9
7.67
92.6
55.6
8.42
88.6
54.3
9.18
84.6
53.0
10.0
80.6
51.6
10.9
76.4
50.2
11.8
67
92.6
76.5
6.83
89.1
75.1
7.47
85.9
73.7
8.21
82.5
72.3
8.99
78.8
70.6
9.80
75.0
68.9
10.6
71.2
67.2
11.5
62
87.8
87.8
6.71
85.2
85.2
7.39
82.6
82.6
8.14
79.6
79.6
8.86
76.6
76.6
9.70
73.4
73.4
10.6
70.3
70.3
11.5
57
87.8
87.8
6.71
85.2
85.2
7.39
82.4
82.4
8.09
79.6
79.6
8.86
76.6
76.6
9.69
73.4
73.4
10.6
70.1
70.1
11.4
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
17
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3000 / 0.06
72
141.0
70.2
9.36
137.0
68.4
10.2
132.0
66.6
11.1
126.0
64.6
12.1
121.0
62.8
13.2
116.0
60.7
14.3
111.0
58.8
15.7
67
130.0
86.9
9.15
126.0
85.0
10.0
121.0
83.1
10.9
117.0
81.3
11.9
112.0
79.2
12.9
107.0
77.1
14.1
102.0
75.1
15.3
62
119.0
103.0
8.88
116.0
101.0
9.78
112.0
99.1
10.7
107.0
97.0
11.6
103.0
94.8
12.7
98.3
92.4
13.8
93.2
89.7
14.9
57
113.0
113.0
8.83
110.0
110.0
9.69
107.0
107.0
10.6
103.0
103.0
11.5
99.7
99.7
12.6
96.0
96.0
13.7
92.2
92.2
15.0
18
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
5000 / 0.10
72
152.0
85.0
10.2
146.0
83.1
11.1
141.0
81.3
12.0
135.0
79.3
13.0
129.0
77.4
14.1
123.0
75.2
15.2
117.0
73.3
16.6
67
140.0
111.0
9.99
135.0
109.0
10.9
130.0
107.0
11.7
125.0
105.0
12.8
120.0
102.0
13.8
114.0
100.0
15.0
107.0
97.1
16.1
62
131.0
131.0
9.73
127.0
127.0
10.7
123.0
123.0
11.6
119.0
119.0
12.6
115.0
115.0
13.7
110.0
110.0
14.8
105.0
105.0
16.0
57
131.0
131.0
9.73
127.0
127.0
10.7
123.0
123.0
11.6
119.0
119.0
12.6
115.0
115.0
13.7
110.0
110.0
14.8
105.0
105.0
16.0
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3000 / 0.06
72
142.0
70.4
9.03
137.0
68.7
9.93
133.0
67.1
10.8
129.0
65.4
11.8
123.0
63.4
12.8
118.0
61.5
14.0
113.0
59.5
15.3
67
131.0
87.1
8.85
127.0
85.4
9.74
123.0
83.7
10.6
118.0
81.9
11.6
114.0
79.9
12.6
108.0
77.8
13.7
103.0
75.6
14.9
62
120.0
103.0
8.69
117.0
102.0
9.57
113.0
99.7
10.4
109.0
97.7
11.4
104.0
95.5
12.4
100.0
93.3
13.5
95.2
90.7
14.7
57
113.0
113.0
8.58
111.0
111.0
9.46
108.0
108.0
10.3
104.0
104.0
11.3
101.0
101.0
12.3
97.3
97.3
13.4
93.2
93.2
14.6
5000 / 0.10
72
152.0
85.1
9.88
147.0
83.5
10.8
142.0
81.9
11.7
137.0
79.9
12.6
131.0
78.0
13.7
125.0
76.1
14.9
119.0
73.9
16.1
67
141.0
111.0
9.69
136.0
109.0
10.6
132.0
107.0
11.5
127.0
105.0
12.4
121.0
103.0
13.5
116.0
101.0
14.6
110.0
98.3
15.8
62
132.0
132.0
9.54
128.0
128.0
10.4
125.0
125.0
11.3
121.0
121.0
12.3
116.0
116.0
13.3
112.0
112.0
14.5
107.0
107.0
15.8
57
132.0
132.0
9.54
128.0
128.0
10.4
125.0
125.0
11.3
121.0
121.0
12.3
116.0
116.0
13.3
112.0
112.0
14.5
107.0
107.0
15.8
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
19
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3750 / 0.08
72
163.0
82.3
10.8
158.0
80.3
11.9
152.0
78.2
13.0
146.0
76.1
14.1
140.0
73.9
15.4
134.0
71.7
16.8
128.0
69.3
18.2
67
150.0
103.0
10.5
145.0
101.0
11.6
140.0
98.5
12.7
135.0
96.4
13.8
130.0
94.2
15.1
124.0
91.8
16.4
118.0
89.3
17.7
62
138.0
122.0
10.2
134.0
120.0
11.3
130.0
118.0
12.4
125.0
115.0
13.5
120.0
113.0
14.7
115.0
110.0
16.0
110.0
107.0
17.4
57
133.0
133.0
10.2
129.0
129.0
11.2
125.0
125.0
12.2
121.0
121.0
13.4
117.0
117.0
14.6
113.0
113.0
15.9
108.0
108.0
17.3
20
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
6250 / 0.12
72
174.0
99.7
11.8
168.0
97.8
12.9
162.0
95.8
14.1
155.0
93.5
15.2
148.0
91.2
16.5
142.0
89.1
17.9
134.0
86.6
19.3
67
161.0
131.0
11.5
156.0
129.0
12.6
150.0
126.0
13.7
144.0
124.0
14.9
138.0
122.0
16.2
132.0
119.0
17.5
125.0
116.0
18.9
62
153.0
153.0
11.4
148.0
148.0
12.5
143.0
143.0
13.5
138.0
138.0
14.7
133.0
133.0
16.0
128.0
128.0
17.3
123.0
123.0
18.8
57
152.0
152.0
11.4
148.0
148.0
12.5
143.0
143.0
13.5
138.0
138.0
14.7
133.0
133.0
16.0
128.0
128.0
17.3
122.0
122.0
18.8
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3750 / 0.08
72
153.0
78.4
10.2
148.0
76.6
11.3
143.0
74.8
12.4
137.0
72.6
13.5
130.0
70.3
14.8
123.0
67.8
16.1
116.0
65.3
17.5
67
143.0
99.5
10.0
137.0
97.3
11.1
132.0
95.0
12.1
126.0
92.7
13.3
120.0
90.3
14.5
114.0
87.8
15.8
108.0
85.2
17.2
62
132.0
119.0
9.85
128.0
117.0
10.9
123.0
114.0
11.9
118.0
112.0
13.1
113.0
109.0
14.3
107.0
106.0
15.6
101.0
101.0
16.9
57
127.0
127.0
9.77
123.0
123.0
10.8
120.0
120.0
11.9
115.0
115.0
13.0
111.0
111.0
14.2
106.0
106.0
15.6
101.0
101.0
16.9
6250 / 0.12
72
163.0
96.1
11.1
157.0
94.0
12.2
150.0
91.9
13.3
144.0
89.6
14.5
136.0
87.2
15.8
129.0
84.7
17.1
121.0
82.1
18.5
67
153.0
128.0
11.0
147.0
125.0
12.1
140.0
122.0
13.1
134.0
120.0
14.3
127.0
117.0
15.5
120.0
113.0
16.8
114.0
110.0
18.2
62
146.0
146.0
10.9
141.0
141.0
12.0
136.0
136.0
13.0
130.0
130.0
14.2
125.0
125.0
15.5
119.0
119.0
16.8
113.0
113.0
18.2
57
145.0
145.0
10.9
140.0
140.0
11.9
135.0
135.0
13.0
130.0
130.0
14.2
125.0
125.0
15.4
119.0
119.0
16.8
113.0
113.0
18.2
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
21
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
3750 / 0.08
72
167.0
83.9
10.0
162.0
81.9
11.1
157.0
80.0
12.2
152.0
78.0
13.3
146.0
76.0
14.6
140.0
73.9
15.9
134.0
71.6
17.3
67
154.0
104.0
9.89
149.0
102.0
10.9
144.0
100.0
12.0
139.0
98.1
13.1
134.0
96.0
14.3
129.0
93.7
15.6
123.0
91.4
17.0
62
142.0
124.0
9.78
137.0
122.0
10.8
133.0
119.0
11.8
128.0
117.0
12.9
124.0
115.0
14.1
119.0
112.0
15.3
114.0
109.0
16.7
57
135.0
135.0
9.71
131.0
131.0
10.7
128.0
128.0
11.7
124.0
124.0
12.8
120.0
120.0
14.0
116.0
116.0
15.3
112.0
112.0
16.6
22
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
6250 / 0.12
72
180.0
102.0
11.0
174.0
99.8
12.1
168.0
97.7
13.1
162.0
95.7
14.3
155.0
93.4
15.5
148.0
91.2
16.8
141.0
88.9
18.3
67
166.0
133.0
10.8
160.0
131.0
11.9
155.0
128.0
12.9
149.0
126.0
14.1
144.0
124.0
15.3
137.0
121.0
16.6
131.0
118.0
18.0
62
156.0
156.0
10.7
151.0
151.0
11.8
147.0
147.0
12.8
143.0
143.0
14.0
138.0
138.0
15.2
133.0
133.0
16.5
128.0
128.0
17.9
57
156.0
156.0
10.7
151.0
151.0
11.8
147.0
147.0
12.8
143.0
143.0
14.0
138.0
138.0
15.2
133.0
133.0
16.5
128.0
128.0
17.9
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
4500 / 0.09
72
184.0
94.0
12.1
178.0
91.7
13.2
172.0
89.5
14.5
165.0
87.1
15.8
159.0
84.8
17.2
152.0
82.2
18.7
145.0
79.7
20.2
67
170.0
118.0
11.8
164.0
116.0
12.9
159.0
113.0
14.1
153.0
111.0
15.4
147.0
109.0
16.8
140.0
106.0
18.2
133.0
103.0
19.6
62
157.0
141.0
11.5
152.0
138.0
12.6
147.0
136.0
13.7
141.0
133.0
15.0
136.0
130.0
16.4
131.0
127.0
17.8
125.0
124.0
19.3
57
151.0
151.0
11.3
147.0
147.0
12.4
143.0
143.0
13.6
138.0
138.0
14.9
134.0
134.0
16.3
129.0
129.0
17.8
125.0
125.0
19.3
7500 / 0.14
72
196.0
114.0
13.2
189.0
112.0
14.5
182.0
110.0
15.7
175.0
107.0
17.1
168.0
105.0
18.5
160.0
102.0
20.0
152.0
99.8
21.5
67
181.0
151.0
12.9
175.0
148.0
14.1
169.0
146.0
15.3
163.0
143.0
16.6
156.0
140.0
18.0
149.0
136.0
19.5
142.0
133.0
21.0
62
173.0
173.0
12.7
167.0
167.0
13.9
162.0
162.0
15.1
157.0
157.0
16.4
152.0
152.0
17.9
146.0
146.0
19.4
140.0
140.0
20.9
57
173.0
173.0
12.7
168.0
168.0
13.9
162.0
162.0
15.1
157.0
157.0
16.4
152.0
152.0
17.9
146.0
146.0
19.4
140.0
140.0
20.9
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
23
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
4500 / 0.09
72
185.0
94.4
11.6
179.0
92.3
12.8
174.0
90.1
14.1
168.0
87.9
15.4
161.0
85.5
16.8
154.0
83.0
18.2
147.0
80.4
19.8
67
171.0
118.0
11.3
166.0
116.0
12.5
160.0
114.0
13.7
155.0
112.0
15.0
149.0
109.0
16.4
142.0
107.0
17.8
136.0
104.0
19.3
62
158.0
141.0
11.1
153.0
139.0
12.2
148.0
136.0
13.4
143.0
134.0
14.6
138.0
131.0
16.0
132.0
128.0
17.4
127.0
125.0
19.0
57
152.0
152.0
11.0
148.0
148.0
12.1
144.0
144.0
13.3
140.0
140.0
14.5
135.0
135.0
15.9
131.0
131.0
17.3
126.0
126.0
18.9
24
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
7500 / 0.14
72
197.0
115.0
12.8
191.0
113.0
14.0
184.0
110.0
15.3
177.0
108.0
16.6
170.0
106.0
18.0
162.0
103.0
19.5
154.0
100.0
21.0
67
183.0
151.0
12.4
177.0
149.0
13.7
171.0
146.0
14.9
165.0
144.0
16.2
158.0
141.0
17.5
151.0
137.0
19.0
144.0
134.0
20.6
62
174.0
174.0
12.3
169.0
169.0
13.5
164.0
164.0
14.7
159.0
159.0
16.0
153.0
153.0
17.4
148.0
148.0
18.9
141.0
141.0
20.4
57
174.0
174.0
12.3
169.0
169.0
13.5
164.0
164.0
14.7
159.0
159.0
16.0
153.0
153.0
17.4
147.0
147.0
18.9
141.0
141.0
20.4
65
75
85
95
105
115
125
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
4500 / 0.09
72
185.0
94.1
12.2
179.0
91.9
13.5
172.0
89.7
14.7
166.0
87.3
16.0
159.0
84.9
17.4
153.0
82.5
18.9
145.0
79.8
20.5
67
171.0
118.0
11.9
165.0
116.0
13.1
159.0
114.0
14.3
153.0
111.0
15.6
147.0
109.0
16.9
141.0
106.0
18.4
134.0
103.0
19.9
62
157.0
141.0
11.6
152.0
139.0
12.8
147.0
136.0
13.9
142.0
133.0
15.2
136.0
130.0
16.5
131.0
127.0
17.9
125.0
123.0
19.5
57
151.0
151.0
11.4
147.0
147.0
12.6
143.0
143.0
13.8
139.0
139.0
15.1
134.0
134.0
16.4
129.0
129.0
17.9
124.0
124.0
19.4
7500 / 0.14
72
196.0
114.0
13.4
189.0
112.0
14.6
182.0
110.0
15.9
175.0
107.0
17.2
168.0
105.0
18.6
160.0
102.0
20.1
151.0
99.2
21.7
67
182.0
151.0
13.1
176.0
148.0
14.3
169.0
146.0
15.5
163.0
143.0
16.8
156.0
140.0
18.2
149.0
137.0
19.6
142.0
133.0
21.2
62
173.0
173.0
12.8
168.0
168.0
14.1
162.0
162.0
15.3
157.0
157.0
16.6
151.0
151.0
18.0
145.0
145.0
19.5
139.0
139.0
21.1
57
173.0
173.0
12.8
168.0
168.0
14.1
163.0
163.0
15.3
158.0
158.0
16.6
152.0
152.0
18.0
146.0
146.0
19.5
139.0
139.0
21.1
LEGEND
Bypass Factor
Entering Wet Bulb
Compressor Motor Power Input (kilowatts)
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh), Gross
25
AIR
CFM
1500
2000
2500
2250
3000
3750
3000
4000
5000
3750
5000
6250
4500
6000
7500
NONFREEZE
STEAM*
TC
LAT
116
130
134
120
147
115
97
100
118
96
132
93
118
96
137
92
153
88
164
99
177
92
231
91
209
102
234
95
256
91
HOT WATER
TC
101
117
131
172
211
239
211
247
276
243
292
323
307
363
396
LAT
120
112
107
131
125
119
125
117
111
120
114
107
122
115
108
Gpm
10
12
13
17
21
24
21
25
28
24
29
32
30
36
39
PD
3.7
4.6
5.8
3.5
4.6
5.5
4.6
5.8
6.8
5.0
6.0
7.1
5.1
6.2
7.4
UNIT
50BR,BZ
006
008
012
014
016
LEGEND
LAT Leaving-Air Temperature (F)
PD Pressure Drop (ft of water)
TC Total Capacity (1000 Btuh)
*Nonfreeze steam coil 1-ROW available on all 50BR,BZ sizes.
Nonfreeze coil ratings based on
2 psig steam, 60 F entering air.
Hot water coil All hot water coils are 2-row. The 2-row hot water coil
ratings based on 200 F entering water temperature,
20 F water temperature drop, 60 F entering air.
NOTES:
1. Maximum allowable leaving air temperature 140 F.
2. Maximum operating limit for heating coils is 200 psig or 400 F.
3. To obtain capacities other than those given above, multiply the Btuh
value from the Accessory Heating Coil Ratings table by the proper
value from the Heating Capacity Factors table.
4. Formulas:
Btuh
Final temp (F) = edb (entering dry bulb) (F) +
1.10 x cfm
Btuh
Gpm =
500 x water temp drop (F)
5. Reduced airflow (dirty filters, loose or broken fan belt, etc.) over coil
during cooling cycle may result in freeze-up of nearby heating coil.
Since units normally require a low-pressure switch cutout setting at
about 5 F, use of a freeze-up thermostat is recommended if heating
coil is not drained or filled with an antifreeze solution.
6. Field-supplied thermostat and control valve are required when using
accessory heating coils.
26
AIR QTY
(Cfm)
1500
2000
2500
2250
3000
3750
3000
4000
5000
3750
5000
6250
4500
6000
7500
HEATING COILS
Nonfreeze
Hot
Steam
Water
.04
.04
.05
.05
.08
.08
.02
.04
.04
.08
.06
.12
.04
.08
.07
.14
.10
.21
.04
.08
.06
.14
.08
.21
.05
.10
.07
.16
.09
.23
ACCESSORIES
Discharge
& Plenum
.05
.10
.15
.13
.21
.26
.21
.29
.35
.22
.30
.36
.23
.31
.35
50
60
70
80
1.11
1.14
1.19
1.25
1.03
1.07
1.11
1.18
.96
1.00
1.05
1.11
.89
.93
.98
1.04
.82
.86
.91
.97
Entering
Water
Temp (F)
180
200
220
180
200
220
180
200
220
50
60
70
80
1.06
1.22
1.39
.98
1.15
1.32
.91
1.08
1.25
.98
1.15
1.32
.91
1.08
1.25
.83
1.00
1.18
.90
1.07
1.24
.83
1.00
1.17
.76
.93
1.10
.83
1.00
1.17
.75
.93
1.10
.68
.85
1.03
.75
.92
1.09
.68
.85
1.02
.60
.78
.95
NOTE: Shading indicates unsafe operating area. Unit damage may occur.
NOTE: Shading indicates unsafe operating area. Unit damage may occur.
27
NOTE: Shading indicates unsafe operating area. Unit damage may occur.
NOTE: Shading indicates unsafe operating area. Unit damage may occur.
28
NOTE: Shading indicates unsafe operating area. Unit damage may occur.
29
Electrical data
UNIT
50BR,BZ
006
008
012
014
016
V-PH-HZ
(3 ph, 60 Hz)
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
VOLTAGE
RANGE
Min
Max
187
253
414
506
518
632
187
253
414
506
518
632
187
253
414
506
518
632
187
253
414
506
518
632
187
254
414
506
518
632
COMPRESSOR 1
COMPRESSOR 2
RLA
16.0
8.0
6.4
18.9
9.5
8.0
16.0
8.0
6.4
18.9
9.5
8.0
18.9
9.5
8.0
RLA
16.0
8.0
6.4
16.0
8.0
6.4
18.9
9.5
8.0
LRA
125.0
66.5
27.0
146.0
73.0
50.0
125.0
66.5
27.0
146.0
73.0
50.0
146.0
73.0
50.0
LEGEND
FLA
Full Load Amps
LRA
Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protective Device (see Note 1)
NEC
National Electrical Code
RLA
Rated Load Amps
*Min Ckt Amps and MOCP Amps values per NEC (see Note 1).
The overcurrent protective device for the unit shall be fuse only (see
Note 1).
30
LRA
125.0
66.5
27.0
125.0
66.5
27.0
146.0
73.0
50.0
INDOOR
FAN MOTOR
Hp
FLA
4.0/4.0
1
1.8
1.4
5.7/5.7
112
2.6
2.1
7.5/7.5
2
3.4
2.7
10.6/10.6
3
4.8
3.9
16.7/16.7
5
7.6
6.1
POWER SUPPLY*
MCA
25.0/25.0
12.4
9.4
29.8/29.8
15.0
12.1
43.5/43.5
21.4
16.7
50.2/50.2
24.7
20.3
59.2/59.2
29.0
24.1
MOCP
40/40
15
15
40/40
20
20
50/50
25
20
60/60
30
25
75/75
35
30
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (NEC Articles 430 and 440), the overcurrent protective device for the unit shall be either circuit breaker (where available) or fuse, except those units marked (), which shall be fuse only.
Canadian units may be fuse or circuit breaker.
2. Wire sizing amps are a sum of 125% of the compressor RLA plus
100% of indoor fan motor FLA.
3. Motors are protected against primary single phasing condition.
4. Indoor fan motors are 3-phase motors of same voltage as unit.
5. Three-phase voltage imbalance must not exceed 2%.
197
C
CB
CLO
CONT
CR
EQUIP
FSW
GND
HPS
IFM
Contactor
Circuit Breaker
Compressor Lockout
Continuous
Control Relay
Equipment
Fan Switch
Ground
High-Pressure Switch
Indoor Fan Motor
LEGEND
IFTP
LPS
NEC
TB
TC
TDR
TRAN
197
31
LEGEND
C
CB
CLO
CONT
CR
EQUIP
GND
HPS
IFM
IFTP
32
Contactor
Circuit Breaker
Compressor Lockout
Continuous
Control Relay
Equipment
Ground
High-Pressure Switch
Indoor Fan Motor
Indoor Fan Trip
LPS
NEC
TB
TC
TDR
TRAN
Low-Pressure Switch
National Electrical Code
Terminal Block
Thermostat, Cooling
Time-Delay Relay
Transformer
Field Wiring
Factory Wiring
Operating sequence
All units require the addition of one of 3 types of thermostat accessory packages to complete the control circuit. The
sequence of operation will vary depending on which package is selected as follows:
Unit-mounted thermostat
When the unit power is on to the unit and the selector
switch is set to the OFF position, the unit is completely
deenergized.
Fan circulation When the selector switch is set to the
FAN position, the indoor-fan motor will operate to provide
ventilation.
Cooling When the selector switch is set to the COOL
position, the indoor fan will operate continuously. When
the thermostat located behind the return grilles closes (on a
call for cooling), the control relay closes. This will energize
the outdoor fans (50BZ units only) and immediately close
the compressor contactor. On 008-016 units, a second stage
will close if additional demand is required and will start the
second-stage compressor and outdoor fan (50BZ units only).
When the thermostat is satisfied, the second stage compressor will stop first (008-016 units only), and then the first
stage compressor will stop when cooling demand is satisfied. A 5-minute timer will prevent the compressor(s) from
restarting for 5 minutes after the compressor(s) has stopped.
The outdoor fan(s) (50BZ units only) will stop with the
compressor(s).
Room-mounted thermostat
The unit uses an electronic or mechanical thermostat mounted
in the conditioned space. The factory-supplied, unit-mounted
selector switch is not used.
When the unit power is on, if the thermostat selector
switch is set to the OFF position, the unit is completely
deenergized.
Fan circulation When the thermostat selector switch
is set to the FAN position, the indoor-fan motor will operate to provide ventilation.
Cooling The indoor fan will operate continuously or
when the compressor runs, depending on the setting of the
All units
The control circuit incorporates a current-sensing lockout
relay (Cycle-LOC) that locks off the compressor(s) when
any safety device is activated (low- or high-pressure switches
or compressor internal overload). If any compressor safety
device opens, the compressor(s) will stop and a 24-v signal
will be sent to the X connection of the low-voltage terminal
strip. The signal may be used to light an indicator light on
the thermostat to show that service is required on the unit.
Since the unit is protected by the Cycle-LOC device, the
compressor(s) will not restart following a safety interruption
unless the thermostat is satisfied without cooling operation.
To reset the Cycle-LOC control device, manually turn the
fan switch to the OFF position, then back to the ON
position.
33
LEGEND
NEC National Electrical Code
NOTES:
1. Wiring and piping shown are general points-of-connection guides only and are
not intended for, or to include, all details for specific installations.
2. All wiring must comply with applicable local and national codes.
34
Application data
Refrigerant piping
For applications with condensers located above the cooling
unit, hot gas loops above condenser prevent liquid in condenser from draining at shutdown. Loops and check valves
in discharge line prevent oil and condenser refrigerant from
draining to compressor at shutdown. If condenser is below
the cooling unit, loop at condenser may be omitted. If piping runs prevent drainback, loops may be omitted.
Regardless of remote condenser location, a check valve
must be installed in the discharge line in each refrigerant
circuit, downstream from the hot-gas muffler, as close to
compressor as possible. The check valve prevents migration of refrigerant back to the compressor.
Refrigerant piping OD should not be smaller than unit
connection size.
Liquid lift
The amount of liquid lift available before refrigerant flashing occurs depends on the amount of liquid subcooling in
the system.
All 9AB, 09BY, and 09DE condensers have positive subcooling when applied with optimum charge. With subcooling, it is possible to overcome an appreciable friction drop
and/or static head (due to elevation of the liquid metering
device above the condenser).
When 9AB, 09BY, and 09DE condensers are applied
with minimum charge, no positive subcooling in condenser
is realized; therefore, if subcooling is required it must be obtained by external means.
The average amount of liquid lift available from 9AB,
09BY, and 09DE condensers is shown in accompanying
table.
UNIT
20
63
65
55
62
65
68
70
75
9AB6
09BY006
9AB8
09BY008
09BY012
09BY014
09BY016
09DE016
30
55
61
48
59
61
65
66
71
*Allows 7 psig drop for liquid line accessories and 2 F liquid line loss,
with optimum charge.
Condensing Temperature Entering-Air Temperature (dry bulb).
NOTE: Data is based on 15 F subcooling.
CONDENSER USAGE
MODEL
50BZ
006
008
012
014
016
006
1
09DE
016
1
1
*Circuit 2.
Circuit 1.
NOTE: Where there are no quantities of condensers listed, the combination is not recommended. See Application Data literature for more information on condenser combinations.
CIRCUIT
006
008
1
1
1
2
1
2
1
2
012
014
016
UNIT CONNECT
SIZE
HG
12
12
12
12
12
12
12
12
LIQ
12
12
12
12
12
12
12
12
0 to 25
HG
LIQ
5 8
1 2
7 8
1 2
5 8
1 2
5 8
1 2
7 8
1 2
5 8
1 2
7 8
1 2
7 8
1 2
26 to 50
HG
LIQ
78
1 2
78
1 2
78
1 2
78
1 2
78
1 2
78
1 2
78
1 2
78
1 2
LENGTH
51 to 75
HG
LIQ
7 8
1 2
7 8
1 2
7 8
1 2
7 8
1 2
7 8
1 2
7 8
1 2
7 8
1 2
7 8
1 2
OF RUN (ft)
76 to 100
HG
LIQ
7 8
12
5 8
1 1 8
7 8
12
7 8
12
1
5
1 8
8
7 8
12
5 8
1 1 8
5 8
1 1 8
101 to 125
HG
LIQ
7 8
1 2
5 8
118
7 8
1 2
7 8
1 2
1
5 8
1 8
7 8
1 2
5 8
118
5 8
118
126 to 150
HG
LIQ
7 8
5 8
5 8
118
7 8
5 8
7 8
5 8
1
5
1 8
8
7 8
5 8
5 8
118
5 8
118
LEGEND
HG Hot Gas
LIQ Liquid
35
36
Part 1 General
1.01 SYSTEM DESCRIPTION
Indoor vertical water-cooled packaged cooling unit utilizing a hermetic scroll compressor(s) for cooling duty.
1.02 QUALITY ASSURANCE
A. Units shall be rated in accordance with ARI Standard
210/240 or 360.
B. Unit shall be designed to conform to ANSI/ASHRAE
15, latest revision safety code, and UL Standard 1995,
and shall be UL listed under both American and
Canadian Standards.
C. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
1.03 DELIVERY, STORAGE AND HANDLING
To be according to manufacturers recommendations.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece, water-cooled cooling unit consisting of scroll refrigerant compressor(s),
fan section, coil section, factory wiring, piping and
controls, and a system charge of refrigerant (R-22)
included. Unit may be used with or without ductwork.
B. Unit Cabinet:
Cabinet shall be constructed of zinc surface alloyed
steel with a baked enamel finish, and fully insulated
and shall be capable of withstanding Federal test method
Standard No. 141 (Method 6061) 500-hour salt spray
test.
C. Fan Section:
1. Fan shall be double inlet, centrifugal wheel with
forward curved blades, designed for continuous operation. Fan wheel and scroll shall be constructed
of steel with corrosion resistant finish, and statically and dynamically balanced.
2. Fan shall be belt drive with an adjustable pitch motor pulley, with permanently lubricated, ball-bearing
type bearings.
D. Compressor:
Hermetic scroll compressor(s) with internal vibration
isolators.
E. Coil:
1. Evaporator coil shall have aluminum plate fins mechanically bonded to seamless copper tubes with
all joints brazed. Tube sheet openings shall be
swaged to prevent tube wear.
2. Direct expansion coil shall be designed and tested
in accordance with ANSI/ASHRAE 15, latest revision safety code.
F. Filter:
Filter frame shall be installed upstream of the cooling
coil, to take a 1-in. thick cleanable or disposable type
commercially available filter. Disposable filters will be
supplied with the unit.
G. Condenser:
Condenser shall be of the tube-in-tube type, seamless
with no interior joints, and have a maximum working
water side pressure of 400 psig.
H. Operating Characteristics:
Unit shall be capable of providing a constant volume
of conditioned air at a specified static pressure within
the units normal operating range. Air discharge to
be horizontally free blow, or vertically through ductwork as shown on contract drawings. Unit shall have
single-stage cooling capacity control (006,008) or
2-stage capacity control (012-016).
I. Controls and Safeties:
Unit shall have one of the following control systems:
1. Unit-mounted thermostat mounted in the unit
return air. Unit shall be furnished with a factorymounted fan control switch to control fan operation and turn off the unit.
2. Room-mounted thermostat shall be mounted in the
conditioned space. Thermostat shall be either electromechanical or electronic type. Thermostat subbase shall control fan operation and be capable of
turning unit on and off.
3. Room-mounted thermostat with communicating
capability. This thermostat shall operate like the
standard room-mounted thermostat and shall provide the additional benefit of being able to communicate with building systems to facilitate unit
operation and control.
In addition, units shall have the following factoryinstalled safeties: high- and low-pressure switches,
overtemperature, current lockout, and inherent automatic fan motor overload.
J. Electrical Requirements:
All electrical wiring shall enter the unit cabinet at a
single location. Control circuit is 24 v, suitable for an
optional 24-v thermostat.
K. Refrigerant Components:
Refrigerant circuit components include thermal expansion valve(s), filter drier(s), and charging service
valve(s).
37
38
E. Coil:
1. Evaporator coil shall have aluminum plate fins mechanically bonded to seamless copper tubes with
all joints brazed. Tube sheet openings shall be
swaged to prevent tube wear.
2. Direct expansion coil shall be designed and tested
in accordance with ANSI/ASHRAE 15, latest revision safety code.
F. Filter:
Filter frame shall be installed upstream of the cooling
coil to take a 1-in. thick cleanable or disposable type
commercially available filter. Disposable filters will be
supplied with the unit.
G. Operating Characteristics:
Unit shall be capable of providing a constant volume
of conditioned air at a specified static pressure within
the units normal operating range. Air discharge to
be horizontally free blow, or vertically through ductwork as shown on contract drawings. Unit shall have
single-stage cooling capacity control (006,008) or
2-stage capacity control (012-016).
H. Controls and Safeties:
Unit shall have one of the following control systems:
1. Unit-mounted thermostat mounted in the unit return air. Unit shall be furnished with a factorymounted fan control switch to control fan operation and turn off the unit.
2. Room-mounted thermostat shall be mounted in the
conditioned space. Thermostat shall be either electromechanical or electronic type. Thermostat subbase shall control fan operation and be capable of
turning unit on and off.
3. Room-mounted thermostat with communicating
capability. This thermostat shall operate like the
standard room-mounted thermostat, and shall provide the additional benefit of being able to communicate with building systems to facilitate unit
operation and control.
In addition, units shall have the following factoryinstalled safeties: high- and low-pressure switches,
overtemperature, current lockout, and inherent automatic fan motor overload.
I. Electrical Requirements:
All electrical wiring shall enter the unit cabinet at a
single location. Control circuit is 24 v, suitable for an
optional 24-v thermostat.
J. Refrigerant Components:
Refrigerant circuit components include thermal expansion valve(s), filter drier(s), and charging service
valve(s).
39
4. Thermostats:
A complete line of thermostats shall be available
to meet any application control requirements.
5. Ducted Return-Air Filter Rack:
This accessory shall be used with ducted return or
heating coil applications to provide easy access to
filters.
6. Liquid Line Solenoid:
The liquid line solenoid accessory shall be used on
long-line applications and shall provide a shutoff
valve to start and stop refrigerant flow.
2-95
197
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
Tab 2a 2b 7a 7b
Page 40
Printed in U.S.A.
PC 111
Form 50B-1PD
Replaces: New