Edtvn042125 FTKZ V
Edtvn042125 FTKZ V
Edtvn042125 FTKZ V
FTKZ-V Series
EDTVN042125
Split Type
Air Conditioners
FTKZ-V Series
FTKZ25VVMV RKZ25VVMV
FTKZ35VVMV RKZ35VVMV
Cooling Only FTKZ50VVMV RKZ50VVMV
FTKZ60VVMV RKZ60VVMV
FTKZ71VVMV RKZ71VVMV
1. Power Supply ..........................................................................................2
2. Functions.................................................................................................3
3. Specifications ..........................................................................................4
4. Dimensions .............................................................................................7
4.1 Indoor Unit................................................................................................7
4.2 Outdoor Unit .............................................................................................8
5. Wiring Diagrams......................................................................................9
5.1 Indoor Unit................................................................................................9
5.2 Outdoor Unit ...........................................................................................10
6. Piping Diagrams....................................................................................11
6.1 Indoor Unit..............................................................................................11
6.2 Outdoor Unit ...........................................................................................12
7. Capacity Tables ....................................................................................14
7.1 Cooling Only...........................................................................................14
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................17
8. Operation Limit......................................................................................18
9. Sound Level ..........................................................................................19
9.1 Measuring Location ................................................................................19
9.2 Indoor Unit..............................................................................................20
9.3 Outdoor Unit ...........................................................................................21
10.Electric Characteristics..........................................................................23
11.Installation Manual ................................................................................24
11.1 25/35 Class ............................................................................................24
11.2 50/60/71 Class .......................................................................................34
12.Operation Manual..................................................................................44
12.1 English....................................................................................................44
12.2 Vietnamese ..........................................................................................126
13.Optional Accessories ..........................................................................208
13.1 Indoor Unit............................................................................................208
13.2 Outdoor Unit .........................................................................................208
1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKZ25VVMV RKZ25VVMV
FTKZ35VVMV RKZ35VVMV
1 phase, 220 - 230 - 240 V, 50 Hz
FTKZ50VVMV RKZ50VVMV 1 phase, 220 - 230 V, 60 Hz
FTKZ60VVMV RKZ60VVMV
FTKZ71VVMV RKZ71VVMV
2. Functions
FTKZ50/60/71VVMV
FTKZ50/60/71VVMV
RKZ50/60/71VVMV
RKZ50/60/71VVMV
FTKZ25/35VVMV
FTKZ25/35VVMV
RKZ25/35VVMV
RKZ25/35VVMV
Category Functions Category Functions
Basic Functions Inverter (with inverter power control) Health & Air quality filter
Cleanliness (enzyme blue / PM2.5) (option)
Refer to
Operation limit for cooling
P. 18 Deodorizing filter (enzyme blue)
Operation limit for heating — — Titanium apatite deodorizing filter
(option)
PAM control
Standby electricity saving Dust collection filter (PM2.5) (option)
Compressor Oval scroll compressor — — Mould proof air filter (prefilter)
Swing compressor Wipe-clean panel
Rotary compressor — — Washable panel — —
Reluctance DC motor Removable drain-pan
Comfortable Power-airflow flap — — Mould proof operation
Airflow
Power-airflow dual flaps Mould proof operation with streamer — —
Power-airflow diffuser — — Heating dry operation — —
Wide-angle louvres Good-sleep cooling operation — —
Auto-swing (up and down) Odour removing
with position indication
Flash streamer
Auto-swing (left and right) Timer Weekly timer — —
with position indication
24-hour ON/OFF timer
3D airflow Count up-down ON/OFF timer
Comfort airflow mode Night set mode
(COANDA flap: ceiling) Worry Free Auto-restart after power failure
(Reliability &
Comfort Control Auto fan speed Durability) Self-diagnosis with remo-con
Indoor unit quiet operation Wiring error check — —
Outdoor unit quiet operation Anti-corrosion treatment of outdoor
Intelligent eye (auto energy saving) heat exchanger fins
3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKZ25VVMV FTKZ35VVMV
Model
Outdoor Unit RKZ25VVMV RKZ35VVMV
kW 2.5 (1.2 ~ 3.6) / 1.250 3.5 (1.2 ~ 4.1) / 1.750
Capacity
Btu/h 8,500 (4,100 ~ 12,300) / 4,300 11,900 (4,100 ~ 14,000) / 6,000
Rated (Min. ~ Max.) / Half
kcal/h 2,150 (1,030 ~ 3,100) / 1,070 3,010 (1,030 ~ 3,530) / 1,500
Moisture Removal L/h 0.9 1.2
Running Current (Rated) A 2.3 3.9
Power Consumption
W 455 (160 ~ 890) / 199 790 (160 ~ 1,120) / 297
Rated (Min. ~ Max.) / Half
Power Factor (Rated) % 89.9 92.1
COP (Rated) W/W 5.49 4.43
CSPF Wh/Wh 7.24 6.68
Liquid mm 6.4 6.4
Piping
Connections Gas mm 9.5 9.5
Drain mm 16.0 16.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 20 20
Max. Interunit Height Difference m 15 15
Chargeless m 10 10
Amount of Additional Charge of
g/m 20 20
Refrigerant
Indoor Unit FTKZ25VVMV FTKZ35VVMV
Front Panel Colour (Munsell No.) Two Tone White (B-613), Light Gray (B-617) Two Tone White (B-613), Light Gray (B-617)
H 14.6 (516) 15.2 (537)
M m³/min 11.0 (388) 12.3 (434)
Airflow Rate
L (cfm) 7.0 (247) 7.9 (279)
SL 4.9 (173) 5.6 (198)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 30 30
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof
Running Current (Rated) A 0.31 0.32
Power Consumption (Rated) W 30 32
Power Factor (Rated) % 44.0 45.5
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 300 × 920 × 240 300 × 920 × 240
Packaged Dimensions (H × W × D) mm 341 × 1,000 × 386 341 × 1,000 × 386
Weight (Mass) kg 13 13
Gross Weight (Gross Mass) kg 18 18
Sound
Pressure H / M / L / SL dB(A) 42 / 33 / 26 / 19 43 / 35 / 28 / 19
Level
Outdoor Unit RKZ25VVMV RKZ35VVMV
Casing Colour Ivory White Ivory White
Heat
Fin / Spec. Tube Waffle Fin / 7 Hi-XD Tube Waffle Fin / 7 Hi-XD Tube
Exchanger
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC25DXD 1YC25DXD
Motor Output W 800 800
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.375 0.375
Type R-32 R-32
Refrigerant
Charge kg 0.77 0.77
H m³/min 26.9 (950) 26.9 (950)
Airflow Rate
SL (cfm) 23.0 (812) 23.0 (812)
Type Propeller Propeller
Fan
Motor Output W 28 28
Running Current (Rated) A 2.00 3.60
Power Consumption (Rated) W 425 758
Power Factor (Rated) % 96.6 95.7
Starting Current A 2.3 3.9
Dimensions (H × W × D) mm 550 × 675 × 284 550 × 675 × 284
Packaged Dimensions (H × W × D) mm 605 × 798 × 373 605 × 798 × 373
Weight (Mass) kg 27 27
Gross Weight (Gross Mass) kg 32 32
Sound
Pressure H / SL dB(A) 46 / 43 47 / 44
Level
Drawing No. 3D133028A 3D133029A
Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Piping Length kcal/h = kW × 860
Btu/h = kW × 3412
Indoor ; 27°CDB / 19°CWB cfm = m³/min × 35.3
7.5 m
Outdoor ; 35°CDB / 24°CWB
Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Piping Length kcal/h = kW × 860
Btu/h = kW × 3412
Indoor ; 27°CDB / 19°CWB cfm = m³/min × 35.3
7.5 m
Outdoor ; 35°CDB / 24°CWB
Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Piping Length kcal/h = kW × 860
Btu/h = kW × 3412
Indoor ; 27°CDB / 19°CWB cfm = m³/min × 35.3
7.5 m
Outdoor ; 35°CDB / 24°CWB
4. Dimensions
4.1 Indoor Unit
FTKZ25/35VVMV
3D132634
FTKZ50/60/71VVMV
3D132635
RKZ25/35VVMV
C: 3D133100
RKZ50/60/71VVMV
C: 3D122092
5. Wiring Diagrams
5.1 Indoor Unit
FTKZ25/35VVMV
3D131859A
FTKZ50/60/71VVMV
3D131864A
RKZ25/35VVMV
3D131857
RKZ50/60/71VVMV
3D111967B
6. Piping Diagrams
6.1 Indoor Unit
FTKZ25/35VVMV
4D132880
FTKZ50/60/71VVMV
4D132881
RKZ25/35VVMV
3D131796
RKZ50VVMV
3D131797
RKZ60/71VVMV
3D131798
7. Capacity Tables
7.1 Cooling Only
FTKZ25VVMV + RKZ25VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 14.6
BF 0.31
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133103
FTKZ35VVMV + RKZ35VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 15.2
BF 0.16
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133104
FTKZ50VVMV + RKZ50VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 18.0
BF 0.09
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133105
FTKZ60VVMV + RKZ60VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 22.1
BF 0.11
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133106
FTKZ71VVMV + RKZ71VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 22.1
BF 0.11
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133108
90
5 10 15 20 (m)
Piping length
90
80
Range of the refrigerant additional
charge
5 10 15 20 25 30 (m)
Piping length
7.2.3 71 Class
(R-32)
(%)
100
Capacity correction factor
90
80
Range of the refrigerant
additional charge
5 10 15 20 25 30 (m)
Piping length
Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.
8. Operation Limit
RKZ25/35/50/60/71VVMV
4D073983S
9. Sound Level
9.1 Measuring Location
1m 1m
0.8 m
MICROPHONE
MICROPHONE
4D132502 4D132503
FTKZ50VVMV FTKZ60VVMV
4D132505 4D133033
FTKZ71VVMV
4D132506
4D132508 4D132509
RKZ50VVMV RKZ60VVMV
4D132511 4D133034
RKZ71VVMV
4D132512
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB.
RHz : Rated Operating Frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)
3D133109A
3P620953-15F
3P620953-16F
EN_3P620957-13G
EN_3P620957-14G
12.2 Vietnamese
12.2.1 25/35 Class
VN_3P620957-13G
VN_3P620957-14G
Manual No.
Option Name Model Name
Installation Manual Operation Manual
Wiring adaptor for timer clock / remote controller1 3 4
1 (normal open pulse contact / normal open contact) KRP413BB1S 3P248024-2H —
Manual No.
Option Name Model Name
Installation Manual Operation Manual
1 Air direction adjustment grille KPW937F4 3P561128-1 —
2 Drain plug KKP937A4 — —
Specifications, designs and other content appearing in this brochure are current as of February 2021 but subject to change without notice.