Write Up ON Automatic Turbine Tester: Consultant: Development Consultant Pvt. LTD
Write Up ON Automatic Turbine Tester: Consultant: Development Consultant Pvt. LTD
Write Up ON Automatic Turbine Tester: Consultant: Development Consultant Pvt. LTD
00-----
WRITE UP
ON
AUTOMATIC TURBINE TESTER
Consultant:
TYPE OF PRODUCT
CARD
CODE
DATE
23.09.09
23.09.09
23.09.09
ITEM
NO.
SHT.NO 01
NO.OF
VAR.
NO. OF
ITEMS
REV.
00
NO. OF SHT. 14
------------------------------------------------------------------------------------Page 1 of 14-------
GENERAL:
The safety devices (protective devices) protect the turbine from impermissible
operating conditions. On response of a safety device, the HP & IP stop valves
close. Closure of control valves is initiated by secondary fluid pressure reduction.
The Automatic Turbine Tester is used to check / test at a regular interval the
function of the safety devices of the turbine and its 'stop and control valves',
while it is in operation, without causing actual turbine trip.
The Automatic Turbine tester has been divided into two sub-groups viz.
(i) Sub-group Safety Devices.
(ii) Sub-group HP/IP valves.
Each sub-group is further sub-divided into sub-tests for each individual device
covered under the sub-group. The switching on of the sub group control and
subtests shall be in the following modes.
1.1
The selection of the sub-group and sub-test shall be manual from OWS in
control room.
1.2
Both the sub groups are so interlocked that operation of only one subgroup shall
be possible at a time.
1.3
Any of the subgroups can be switched ON or OFF of the concerned SGC by the
control buttons for SGC- ON/OFF in OWS. As a result, the display AUTO ON
will glow in CRT.
1.4
Any one subtest of the switched-on subgroup can now be selected by clicking
the concerned control button 'SELECTION ON'. As a result, the lamp 'DEVICE
RELEASED' shall glow on the corresponding CRT display. The individual sub-test
selection are also mutually interlocked, so that only one selection and hence one
sub-test can be executed at a time. The selection can be cancelled by clicking
the control button 'SGC ON/OFF'.
1.5
After a subtest has been selected, the subgroup program shall be started by
clicking the control buttons for START UP in OWS. If the initial conditions for
the test are fulfilled, the display (in CRT) `PROGRAM RUNNING` will glow.
------------------------------------------------------------------------------------Page 2 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----Otherwise the subtest will be blocked and the missing initial conditions will be
indicated in code form on the criteria display.
1.6
1.7
Once started, the testing cannot be switched over to another subtest or the SGC
cannot be switched off, before the program selected has been completed. If a
subtest selected has been completed successfully the display `TEST COMPLETED
SUCCESSFULLY' shall glow and the reset program shall start automatically.
1.8
If a fault e.g. "Running time exceeded" is detected during a test, the respective
pretest or main test shall be discontinued immediately and the shut down i.e.
reset program be started automatically. The missing criteria and concerned step
number shall be indicated on the criteria and step display indications. Fault
alarms can be acknowledged by clicking upon the display button 'SGC ON/OFF
only.
1.9
2.0
------------------------------------------------------------------------------------Page 3 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----de-energized resulting turbine trip and the reset program to be started
simultaneously. During testing, two limit value monitors provide over speed
signal for protection of turbine against actual over speed.
The turbine trip is prevented due to Automatic Testing of the 'Safety Devices'
but the general annunciations are activated. This allows testing of appropriate
part of the alarm annunciation system also. The Automatic Tester thereof
monitors the timings of all commands and the execution. If the monitoring time
is exceeded, the reset program is started in order to re-establish the initial
condition.
2.1
2.1.1 PRETEST
The pretest will be performed before each subtest (MAIN TEST). If this test is
completed successfully it is assured that the protective logic and remote trip
devices during testing are in working order.
Step 1: - In the step 1 a signal is issued to indicate that pretest is 'ON' and two
commands are issued to energize the test trip solenoid valves (MAX51AA201 +
202) (Ref. clause 2.5) causing control fluid pressure to build up at the
changeover valve. A similar command will again be issued with the help of signal
<D> once the test solenoid valves 1 & 2 are individually tested for successful
operation in step 2 & 3. Within 4 sec. of wait/check time the pressure at switch
MAX51CP208 should be established.
Step 2:-In step 2 a simulated over speed signal is fed to de- energize the 'test
trip solenoid valve 1' (MAX51AA201) (Ref. clause 2.5). This should result in
depressurization of the control fluid before the changeover valve. The pressure
at switch MAX51CP207 must drop but the pressure at switch MAX51CP206
should not change as the 'test trip solenoid valve 2' MAX51AA202 is still
energized. These check back criteria indicate the healthiness of the solenoid
valve MAX51AA201 as well as speed limit value monitor 1.
------------------------------------------------------------------------------------Page 4 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----Step 3: - In step 3, a similar simulated over speed signal is used to de-energize
the "test trip solenoid valve 2" (MAX51AA202). This time the depressurization of
control fluid should take place between the two test solenoid valves, and this
check back criterion by pressure switch MAX51CP205 ensures the healthiness of
2nd test trip solenoid valve MAX51AA202 as well as speed limit value monitor
2.The monitoring time is 3 secs as in step 2.
Step 4: - In step 4, no command is issued but a deliberate waiting time has
been introduced to allow, re-energisation of the two test solenoid valves to
provide control fluid up to the changeover valve.
Step 5: - In step 5, a command is issued to actuate the changeover solenoid
valve MAX61AA201. This initiates draining of control fluid between the solenoid
valve and changeover valve. The pressure differential causes the change over
valve to move to the test position, which is annunciated in the panel insert.
The check back criteria viz. test position of the changeover valve, trip fluid and
auxiliary start up fluid pressure, together with the signal from step 5 generate
signal 'Pretest end (completed).
2.1.2 MAIN TEST
(A) MAIN TEST of Remote Trip Device 1 & 2 (Remote trip solenoid valve 1:
MAX52AA001 & Remote trip solenoid valve 2: MAX52AA002)
Step 6: - In this step a command is issued to test the Remote Trip Solenoid
Valve MAX52AA001, if release for this is present. The solenoid valve is energized
causing the control oil supply to be blocked and the trip oil circuit to be
connected to drain instantaneously. The tripping devices MAX51AA005 & 006
move immediately to trip position. The trip fluid and auxiliary trip fluid pressures
collapse and the control fluid between the Remote Trip Solenoid valves only
maintain its normal pressure, while the pressure before the tripping devices 1&2
collapse. The completion of the test is indicated in the MMI through a status
lamp 'Test completed successfully' and the reset program is initiated
automatically to restore all the devices tripped to the normal operating position.
Then, if the other remote trip device is released, and the pretest is over,
command is issued to test the Remote Trip Solenoid Valve MAX52AA002 in the
same manner and after the test is over, it is annunciated in the panel insert and
reset program is initiated.
(B) MAIN TEST of over speed Trip Device MYA10AA001 + 002:
Step 7: - This step is enabled if over speed Trip Devices have been released and
'pretest' is over, a command is issued in this step to drive the ' over speed test
Unit' motor MAX62AA001M to open a part and provide the test oil. This test oil
builds up gradually and acts through line MAX62 on the effective area of fly bolt,
test oil pressure test being directly indicating the percentage of the over speed
simulation. If the bolts are functioning correctly, they will come out into the trip
------------------------------------------------------------------------------------Page 5 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----position when the predetermined pressure is reached and operate the trip lever
to depressurize auxiliary trip fluid circuit instantaneously. This results in tripping
of the Tripping devices 1 and 2 and collapse of the over speed Trip devices and
pressure of test oil are also taken as check back criteria for completion of the
test. If the over speed trip devices trip a little earlier before the set test oil
pressure builds up to set value, it is annunciated in the panel insert and the
reset program started automatically to restore all the devices tripped to their
normal operating positions.
2.2
2.2.1 Step 51
This step is initiated as soon as the reset program starts. A command is issued
to drive the over speed trip test device back to its normal position until the limit
switch actuates. But the check back monitoring is continued until the test oil
pressure is reduced to a negligible value. This double check back is necessary to
ensure that the trip setting of over speed is not reduced by any residual test oil
pressure.
At the same instant two more commands are issued to switch on disconnection
relays of channel 1 & 2 in order to switch off the remote trip relays 1 & 2
(MAX52AA001 + 002), provided anyone of these remote trip relays are on. This
is to avoid spurious turbine trip after the safety devices have been restored to
their normal operating positions. The status in panel insert indicates that
resetting is on.
The check-back signals in this step ensure that the safety devices are in their
normal operating positions and no simulated trip condition is present. After all
the check-back criteria are present, the reset program proceeds to step 52.
There is also a bypass condition which bypasses all the above criteria except
those which ensure that the over speed trip device unit is in normal operating
positions and the collapse of test oil pressure. This bypass is effective when the
------------------------------------------------------------------------------------Page 6 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----turbine has tripped. This is because of the reason mentioned at para 2.2.2(i)
below. Step 51 is also enabled from step 53 for recycling purposes.
2.2.2 Step 52
In this step command is issued to energize the reset solenoid valves MAX48AA
201 & 202 so that auxiliary start up fluid is supplied with control fluid which
forces all safety devices viz. Tripping Devices (MAX51AA005 & 006), Manual
Turbine Trips (Levers 1&2) and over speed trip devices (MAY10AA001+002), to
return back to their operating position, and the trip fluid pressure then builds up
to normal values. After 6 sec. time which will allow completion of this resetting
the reset solenoid valve MAX48AA201 is de-energized to shutoff the control fluid
supply through it and thus cause pressure at MAX48CP201 to drop. The
additional 4 sec in the waiting time has been envisaged to allow sufficient time
for the establishment of this check back criterion for signal <T> to enable step
53.
The check-backs are bypassed in the case of reset program due to turbine trip
or exceeding of running time for the following purposes (i) & (ii):
i) In the event of turbine trip during test, the pretest or main test is discontinued
immediately and the reset (shutdown) program started under protection. In the
reset program only ' over speed trip device' is restored to its operating position
so that the turbine can be restarted with the over speed trip device in its normal
operating position.
ii) If the running time of the pretest or a main test exceeds (due to non-fulfillment of a
step criterion), the pretest or main test currently running is discontinued and the
reset program started under protection to restore the normal operating position.
If the running time exceeds during reset program the respective step is held up
and the resetting can be restarted again, to repeat the resetting when the
missing criterion is made available.
The fault causing the running time to exceed is to be eliminated immediately
keeping the turbine monitoring equipment under observation.
2.2.3 Step 53:
As soon as the step 53 is enabled the reset solenoid valve MAX48AA202 is deenergized and the auxiliary start up fluid pressure between the two reset
solenoid valves also collapses which is taken as one of the check back criteria.
The other check back criteria are the same as those of step 52. Here again
waiting time and all check-back criteria are bypassed in case of resetting due to
turbine trip [ref. para 2.2.2(i)]. Also ref. Para 2.2.2 (ii) for the requirement of
manual resetting.
2.2.4 Step 54
------------------------------------------------------------------------------------Page 7 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----In this step command is issued to close the solenoid valve MAX61AA201 by
reenergizing it. This closes the drain port and control fluid pressure builds up
which pushes the changeover valve to its normal working position. Additional 3
sec. in waiting/check time has been provided for ensuring trip fluid pressure
building to normal value through tripping devices. The status indication of
'change over valve' in test position is also removed. Another command is issued
here simultaneously to reset all the memories to register cancellation of all the
selection.
2.2.5 Step 55
In this final step, after change over valve has changed to normal working
position,
commands are issued to de-energize the remote trip test solenoids 1 & 2
(MAX51AA201 & 202), by resetting the memory circuits. This is the last step of
returning to normal operating conditions and the check back criteria are the
collapse of pressure of the control fluid between the remote trip test solenoids
and before the changeover valve. The program remains stay-put here by
resetting the memory, unless the sub-group is switched off or unless another
sub-test is initiated. The status indication "resetting on" is also removed after
getting the check back criteria.
2.3
2.3.1 The released signal for any of the safety devices, to be used as one of the
release criteria for start-up program as well as enabling criteria of the respective
main test, shall be generated if all of the following conditions are present:
(i)
(ii)
(iii)
(iv)
The push button 'selection on' on the panel insert of the concerned safety device
switched-on.
Main test of the respective sub-test not at its end.
None of the safety devices released.
Sub group safety devices switched-on.
2.3.2 The released signal shall be reset (removed) if any of the following conditions
are present:
(i)
(ii)
(iii)
2.3.3 The memories for release signal generation for testing of "speed limit value
monitors" at the time of PRETEST [ref. clause 2.1.1 (step 2&3)], are set from
the signals of step 1 & step 3. They are reset by completion of individual testing
or by command from step 51.
------------------------------------------------------------------------------------Page 8 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----2.4
2.4.1 Signals 'Change over valve test position', 'one or more monitors tripped',
'remote trip during test on' and 'trip devices resetting on' shall be generated for
annunciation on the respective text display tiles of panel insert, provided subgroup is switched on and the devices are in the respective conditions.
2.4.2 Separate signals as applicable representing completion of main test of respective
safety devices are issued for indication 'Test completed successfully' on the
respective tiles of panel insert as well as for the purpose of interlock as per
clause 2.3.1(ii). These signals shall continue to persist unless the memories are
reset by switching off the sub-group control.
2.4.3 Signals for indicating 'pretest', 'Main Test', 'Resetting' and 'fault' conditions at
the text display tiles of MMI and signal representing trip by over speed during
testing for central annunciation are generated. These are described below.
2.4.3.1 The signal 'Pretest ON' shall be generated by setting the memory due to
command from step 1. The signal shall persist unless the memory is reset by
any one of the following conditions: i) Pretest end.
ii) Command from step 51 issued.
iii) Subgroup control is switched off.
2.4.3.2 The signal 'Main Test On' shall be generated if pretest is completed or the main
test of valves is on (ref. clause 3.4). The signal shall persist unless the memory
is reset by command from step 51 and the 'Main Test valves ON' signal memory
is reset by command from step 51 of sub-group valves.
2.4.3.3 The signal 'resetting ON' shall be generated by setting any of the memories by
command from step 51 of the respective subgroups (also ref. clause 3.4). The
signal shall persist unless both the memories are reset by signal issued after
respective resetting is complete. The memory will also reset if SGC is switched
off.
2.4.3.4 If the turbine is tripped during testing or running time is exceeded, a 'fault'
alarm is generated, which disappears on acknowledgement by pressing "SGC ON/OFF" control pushbutton.
2.4.3.5 The signal 'Trip by over speed during test' shall be generated if turbine speed,
sensed by any or both of the speed limit value monitors exceeds 110% while
changeover valve is in test position.
2.5
------------------------------------------------------------------------------------Page 9 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----(MAX51AA201 & 202), if the turbine speed, sensed by the speed limit value
monitors 1&2, is less than 110% or the release for testing of speed limit value
monitor is present.
On successful completion of testing of speed limit value monitors in step 2 & 3
of PRETEST, a signal is fed to de-energize the test trip solenoid valves
MAX51AA201 & 202, and the memories to reset.
After step 4 the two commands 'Control Fluid provide' are again issued which
will energize the two test solenoids. The two solenoids will remain energized and
the two memories will continue in set position to ensure turbine protection
during testing.
The memories will reset and the test solenoid valves de-energized, if any of the
following conditions are present: i)
ii)
iii)
iv)
The conditions (ii) through (iv) mentioned above shall cause the turbine to trip.
3.0
------------------------------------------------------------------------------------Page 10 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00-----
All testing equipment is part of the trip fluid system, which is depressurized in
the event of a trip. Thus in the event of an actual turbine trip during testing, the
closing of valve is no way effected regardless of the stage of testing reached.
This is also applicable for control valves because there is no interference with
the secondary fluid circuit and therefore, the pressure there can be reduced
without difficulty.
3.1
------------------------------------------------------------------------------------Page 11 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----- i.e. testing of one HP/IP valve combination. Automatically the "reset program"
is initiated and the end of a test annunciated through the corresponding control
display "Test completed successfully".
3.2
3.2.1 Step 51
In this step, the memory of 'Main test valve' ON is reset (ref. clause 3.4 below)
to stop 'Main Test' on indication on the panel (ref. clause 2.4.3.2). The signal
"resetting on" is generated and annunciated in the panel insert (ref. clause
2.4.3.3).
The bypass condition of the waiting time is applicable when the concerned stop
valve is already open up to 100%.
3.2.2: Step 52
In this step command is issued for tightening of the spring between the piston
and the piston disc, of the selected stop valve. The reset solenoid valve
MAX47AA211 etc. is energized to move the test valve MAX47AA011 (or its
equivalent in other valve combination) to its test position and allow trip fluid to
press over the piston and compress the spring till the piston seats on the disc.
This causes a rise in pressure (>6 kg/cm2) above the piston and indicates
completion of preloading of the servomotor. This condition gets stabilized within
the waiting time of 40 seconds, and then the program proceeds to step 53. But
if the selected stop valve is already open or the turbine is tripped, then this
waiting time is by passed.
3.2.3 Step 53
In this step, a command is issued to de-energize the test solenoid MAX61AA211
(or its equivalent in other valve combination) of the stop valve of the selected
valve combination, to allow trip fluid to flow below the piston of stop valve,
------------------------------------------------------------------------------------Page 12 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----through the test valve. The check back criteria is the building up of pressure in
the trip fluid line between the test solenoid and the test valve.
The check back criteria and the waiting time are bypassed if the concerned stop
valve is already open, or if the turbine has tripped.
3.2.4: Step 54
In this step commands are issued to open the stop valve by de-energizing the
reset solenoid valve and the test solenoid valve to drive them to operating
positions, which make the test valve (MAX47AA011 etc.) to go back to its initial
position and allows the fluid pressure above the piston of the stop valve to
drain. The resultant pressure differential causes the pre-loaded piston/piston
disc unit to open the stop valve to 100% position.
A deliberate waiting time had been envisaged to take care of the time required
for smooth building up of the pressure. Again this waiting time is bypassed if the
turbine trips during testing.
3.2.5: Step 55
After the stop valve has opened up to 100%, the concerned control valve is
actuated to open by driving the actuator in the open direction. Operating on the
feedback of the control valve servomotor, this causes the control valve to be
returned to a position corresponding to secondary fluid pressure. Here again,
the load is kept constant by the EHC acting on the other SV/CV combination, at
the same time. The motor continues to run until the actuator is brought to
normal position sensed by the limit switches as check back criteria. The stroking
time of the valve is also used here for monitoring satisfactory operation of this
step of the reset program.
3.2.6: Step 56
This step is set after the resetting is successfully completed and here the
monitoring time is blocked and the program remains stay put. An interlock
cancels the selection (release) by resetting the memories and removes the
resetting on annunciation on the panel insert (ref. clause 2.4.3.3). If another
subtest is selected the program runs again, or else sub group control is switched
off.
3.3:
3.3.1 The 'Released' signal for any of the valve combinations are generated/canceled
in the same way as done for safety devices (ref. clauses 2.3.1 and 2.3.2).
There is one more interlock for the testing of IP valves. The "release" signal for
IP valves are cancelled if the "secondary fluid pressure to IP control valves",
------------------------------------------------------------------------------------Page 13 of 14-------
-------------------------------------------------------------------------4-18000-76-416, Rev.00----becomes less than 5 Kg/cm2. This condition ensures that the testing of IP can
only be done if both the IP control valves are fully open.
3.2.2 Separate signals, as applicable, representing completion of main test of
respective valve combinations are issued for indication 'Test completed
successfully' on the respective tiles of panel insert as well as for interlock for
issuing 'released' signal. The signals shall continue to persist unless the
memories are reset by switching off the sub-group control.
3.4
------------------------------------------------------------------------------------Page 14 of 14-------