Technical Data
Generator circuit-breaker system type
HECS-100XLp
HECS-130XLp
HECS-130XXLp
25.3
25.3
25.3
General
Rated maximum voltage
kV
Rated frequency
Hz
50/60
50/60
50/60
A rms
up to 18000
up to 18000
up to 23000
A rms
up to 17000
up to 17000
up to 21500
kV rms
60 (80)
60 (80)
60(80)
kV rms
70 (88)
70 (88)
70 (88)
kV peak
125 (150)
125 (150)
125 (150)
kV peak
145 (165)
145 (165)
145 (165)
kA peak
300
360
360
kA, 3s
100
130
130
kA peak
300
360
360
kA rms
100
130
130
Opening time
ms
34 5
34 5
ms
68
68
68
CO
20000
20000
20000
kA peak
300
360
360
kA, 3s
100
130
130
kA peak
300
360
360
kA, 1s
100
130
130
Circuit-breaker
Rated peak withstand current
Rated short-time withstand current
Rated short-circuit making current
Rated short-circuit breaking current
Rated operating sequence
CO - 30min - CO
34 5
Disconnector
Rated peak withstand current
Rated short-time withstand current
Operating time
Earthing Switch
Rated peak withstand current
Rated short-time withstand current
Operating time
The above data are not limiting values. Additional data on request. We reserve the right to alter data and technical details without notice.
Equipment Options
1
2
3
4
5
6
7
8
9
Generator circuit-breaker
Line disconnect switch
Earthing switch
Starting switch for SFC connection
Manual short-circuiting connection
(by removal of cover)
Surge capacitor
Current transformers
Voltage transformers
Surge arrester
2 | ABB
8
G
Dimension Drawing
HECS-XLp
1400-1500
min. 2975
960
3000 *)
2200
3470 *)
Transformer Side
Generator Side
1000 *)
1700
N(1400-1800)
N(1400-1800)
640
400 *)
3740 + 2N *)
N = Phase distance
*) min. space required for erection and maintenance
ABB | 3
Dimension Drawing
HECS-XXLp
1400-1500
min. 2975
960
Generator Side
1000 *)
1700
N(1600-1800)
3740 + 2N *)
N = Phase distance
*) min. space required for erection and maintenance
4 | ABB
N(1600-1800)
640
400 *)
3000 *)
2200
3470 *)
Transformer Side