Port Side Exhaust Kit: Installation Procedure
Port Side Exhaust Kit: Installation Procedure
Port Side Exhaust Kit: Installation Procedure
53-1001181-04
*53-1001181-04*
August 31, 2009
Asia-Pacific Headquarters
Brocade Communications Systems China HK, Ltd.
No. 1 Guanghua Road
Chao Yang District
Units 2718 and 2818
Beijing 100020, China
Tel: +8610 6588 8888
Fax: +8610 6588 9999
E-mail: china-info@brocade.com
European Headquarters
Brocade Communications Switzerland Srl
Centre Swissair
Tour B - 4me tage
29, Route de l'Aroport
Case Postale 105
CH-1215 Genve 15
Switzerland
Tel: +41 22 799 5640
Fax: +41 22 799 5641
E-mail: emea-info@brocade.com
Asia-Pacific Headquarters
Brocade Communications Systems Co., Ltd. (Shenzhen WFOE)
Citic Plaza
No. 233 Tian He Road North
Unit 1308 13th Floor
Guangzhou, China
Tel: +8620 3891 2000
Fax: +8620 3891 2111
E-mail: china-info@brocade.com
Document History
The following table lists all published versions of the Port Exhaust Kit Installation Procedure.
Title
Publication number
Summary of changes
Date
53-0001181-01
New document.
November 2008
53-0001181-02
Corrections to document.
December 2008
53-0001181-03
Corrections to document.
December 2008
53-0001181-04
Corrections to document.
August 2009
2 of 20
Air flows into the Brocade DCX-4S Backbone through its non-port side and out through the exhaust vent on the side
of the unit, The Port-Side Exhaust Mount Kit is designed to route this airflow out the exhaust vents on the port side of
the unit while mounted in the equipment cabinet. This document provides instructions to install a Brocade DCX-4S
Backbone in a 19 in. (48.26 cm) Electronic Industries Association (EIA) cabinet using the following Brocade Port-Side
Exhaust Mount Kits:
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installing the DCX-4S in equipment cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety
Observe the caution notice in this manual. The caution notice has an ID, which is displayed in parentheses (C015).
Use this ID to locate the translation of this caution notice in the Brocade Product Safety Notices.
CAUTION
Use safe lifting practices when moving the product. (C015)
NOTE
A fully populated Brocade DCX-4S weighs 103.50 kg (228.20 lb) with four FC8-48 port cards installed (192 ports) and
requires a hydraulic or assisted lift to install it.
Installation guidelines
ATTENTION
To ensure adequate cooling, install the chassis with the air intake (nonport side) facing the cool-air aisle.
Follow these general installation guidelines:
The shelf in the kit is 1 U high, so you need a total of 9 U of cabinet space to install the shelf and the Brocade
DCX-4S Backbone. 1U is equal to 4.45 cm (1.75 in.).
To allow the quick removal of all power from the chassis, use AC power sources that are easily accessible and
located near the chassis.
Verify that the additional weight of the chassis does not exceed the weight limits of the cabinet.
Plan for cable management before installing the chassis. Cables can be managed in a variety of ways, such as
by routing cables below the chassis, to either side of the chassis, through cable channels on the sides of the
cabinet, or using patch panels. Refer to the products DCX-4S Backbone Hardware Reference Manual for
specific information.
3 of 20
Ensure that one or two dedicated electrical branch circuits with the following characteristics are available:
- 200-240 VAC, 50-60 Hz (refer to the corresponding Hardware Reference Manual for additional electrical
specifications)
Grounded outlets are installed by a licensed electrician and compatible with the power cords
Supply circuit, line fusing, and wire size are adequate, according to the electrical rating on the chassis
nameplate
Located close to the enterprise-class platform chassis and easily accessible
To maximize fault tolerance, connect each power cord to a separate power source.
Ensure that all equipment installed in the cabinet is grounded through a reliable branch circuit connection. Do
not rely on a secondary connection to a branch circuit, such as a power strip.
Ensure that the product fans have access to a total minimum airflow of 350 cubic ft (9.91 cubic meters) per
minute. Do not block intake vents. Allow for a minimum of 14 in. (35.66 cm) clearance.
Ensure that the air temperature on the air intake side is less than 104o Fahrenheit (40o Celsius) during
operation.
Time required
Allow approximately one hour to unpack and install a chassis in a cabinet.
Tools required
The following tools are required when installing the rack mount kit:
CAUTION
Use safe lifting practices when moving the product. (C015)
NOTE
A fully populated Brocade DCX-4S weighs 103.50 kg (228.20 lb) with four FC8-48 port cards installed (192 ports) and
requires a hydraulic or assisted lift to install it.
4 of 20
b.
Remove the lid and the kits and foam from the top of the chassis.
c.
Lift the cardboard box off the chassis and remove the plastic bag from around the chassis.
Save the packing materials for use when returning the old chassis.
d.
Leave the chassis on top of the plastic shipping tray if the chassis must be transported to the installation
location.
2. Use a pallet jack or other assisted lift to transport the new chassis to the installation area. Doorways must be
wider than 36 in. (91 cm) to accommodate the chassis on the pallet.
3. Remove the Port-Side Exhaust kit, accessory kit, packing foam, and antistatic plastic from the chassis and set
aside.
Parts list
The following parts list refers to items illustrated in Figure 1 on page 6.
TABLE 1
Hardware for Port-Side Exhaust Kit for 27 to 31 in. (68.58 to 78.74 cm) cabinets
Item
Description
Quantity
Top rail
Duct
Shelf
12
10-32 x .63 in.(1.60 cm) Phillips screw with square cone washer
12
10-32 clip nut for cabinets that have rails with round holes
10-32 retainer nut for cabinets that have rails with square holes
Alignment washer for cabinets that have rails with square holes
12
5 of 20
FIGURE 1
Port-Side Exhaust Kit assembly for 27 to 31 in. (68.58 to 78.74 cm) cabinets
I-3
I-2
I-4
I-5
B
I-6
I-1
I-7
Port Side
(Exhaust)
6 of 20
10-32 x .5"
10-32 x .63"
Alignment Washer
6-32 x .25"
Torque requirements
Use the following torque settings when tightening screws that secure the rack mount kit and DCX-4S to the
equipment cabinet.
TABLE 2
Screw size
Torque
FIGURE 2
31
30
30
29
28
Clip or Retainer
Nut Locations
for DCX-4S
Retainer Nut
(Item G)
29
Rail
28
27
27
26
26
25
25
Rail
24
23
Clip or Retainer
Nut Locations
for Shelf
24
Note
23
7 of 20
The shelf can be adjusted to a length of between 27 and 31 inches (68.58 and 78.74 cm) to accommodate
your cabinet size. To lengthen or shorten the shelf, loosen the four 6-32 screws in the four slots on the shelf
(I-4 through I-7 in Figure 1 on page 6) and adjust the shelf to the desired length. Once adjusted, tighten the
four 6-32 screws.
b.
Secure the shelf to the cabinet with eight 10-32 screws with washers (E in Figure 1 on page 6), two screws
in each corner of the shelf (see Figure 3). Tighten screws according to specifications under Torque
requirements on page 7.
FIGURE 3
Port Side
(Exhaust)
4. Install the air-duct assembly by inserting it down into the side slot on the shelf. Ensure that the tabs of the duct
align and engage with the slots in the shelf.
8 of 20
FIGURE 4
5. Install the top-rail assembly (A in Figure 1 on page 6) to the air-duct assembly: Refer to Figure 5 on page 10.
a.
The top-rail assembly can be adjusted to a length of between 27 and 31 inches (68.58 to 78.74 cm) to fit on
the inside of the cabinet rails. To lengthen or shorten the top-rail assembly, loosen the two 6-32 screws (I-3
in Figure 1 on page 6) and adjust the top-rail assembly to the desired length. The length will be
approximately the length of the adjustable shelf. Once adjusted, tighten the two 6-32 screws.
b.
Insert the top-rail assembly down into the air-duct assembly and then secure the top-rail assembly to the
air-duct assembly with two 6-32 screws, one screw on each side of the air-duct assembly (I-1 and I-2 in
Figure 1 on page 6). Tighten screws according to specifications under Torque requirements on page 7.
9 of 20
FIGURE 5
Install screws
Install
screws
Install
screws
6. Secure the top-rail assembly to the cabinet with four 10-32 screws, two screws on each end of the top-rail
assembly.
CAUTION
Use safe lifting practices when moving the product. (C015)
3. If applicable, lock the wheels of the lift.
4. Carefully lift the DCX-4S and slide it into the cabinet.
5. Secure the DCX-4S to the cabinet with six 10-32 screws with washers. Tighten screws according to
specifications under Torque requirements on page 7.
10 of 20
NOTE
Screws, clip nuts, and retainer nuts to secure the DCX-4S to the cabinet are provided in the DCX-4S hardware
accessory kit.
FIGURE 6
DCX-4S with 27 to 31 in. (68.58 to 78.74 cm) Port-Side Exhaust Kit installed in cabinet
NOTE
For rails with round holes, use the clip nuts (F in Figure 1 on page 6) on the rails for securing the 10-32 screws.
For rails with square holes, use the retainer nuts (G in Figure 1 on page 6). Also refer to Figure 2 on page 7.
6. Install the DCX-4S door and required cable management system using instructions in the corresponding DCX-4S
Backbone Hardware Reference Manual.
11 of 20
TABLE 3
Hardware for Port-Side Exhaust Kit for 18-in. to 24 in. (45.72 to 60.96 cm) cabinets
Item
Description
Quantity
Top rail
Top rail mounting brackets for 18-20 in., (45.72-50.8 cm) 20-22-in. (50.8-55.88 cm),
and 22-24.in (55.88-60.96 cm) cabinets
Duct
Shelf
Shelf saddle
12
12
10-32 clip nut for cabinets that have rails with round holes
10-32 retainer nut for cabinets that have rails with square holes
Alignment washer for cabinets that have rails with square holes
12
12 of 20
FIGURE 7
Port-Side Exhaust Kit assembly for 18 to 24 in. (45.72 to 60.96 cm) cabinets
K-3
K-3
K-3
K-2
C
K-1
Port Side
(Exhaust)
10-32 x .5"
10-32 x .63"
Alignment Washer
6-32 x .25"
13 of 20
Torque requirements
Use the following torque settings when tightening screws that secure the rack mount kit and DCX-4S to the
equipment cabinet.
TABLE 4
Screw size
Torque
FIGURE 8
31
30
30
29
28
Clip or Retainer
Nut Locations
for DCX-4S
Retainer Nut
(Item G)
29
Rail
28
27
27
26
26
25
25
Rail
24
23
14 of 20
Clip or Retainer
Nut Locations
for Shelf
24
Note
23
3. Install the shelf saddle (E in Figure 7 on page 13) to the nonport side of the equipment cabinet .Install the
saddle in the same vertical location as where the shelf installs on the port side of the rack. In using Clip and
retainer nut locations on cabinet rails on page 14 as example, if the shelf is installed in location 23 on the port
side, install the saddle in location 23 on the nonport side. Ensure that the words THIS SIDE UP on the saddle
face towards the port side of the rack (refer to Figure 9).
Secure the saddle to the equipment cabinet using four 10-32 screws with washers (G in Figure 7 on page 13),
two screws on each side of the saddle. Tighten screws according to specifications under Torque requirements
on page 14.
FIGURE 9
Install
screws
Port Side
(Exhaust)
Install screws
NOTE
For rails with round holes, use the clip nuts (H in Figure 7 on page 13) on the rails for securing 10-32 screws. For
rails with square holes, use the retainer nuts (I in Figure 7 on page 13). Also refer to Figure 8 on page 14.
4. Place the shelf (D in Figure 7 on page 13) on the saddle then secure it to the cabinet rails using four 10-32
screws with washers (G in Figure 1 on page 6). Tighten screws according to specifications under Torque
requirements on page 14.
15 of 20
FIGURE 10
Install screws
Port Side
(Exhaust)
Install screws
NOTE
For rails with round holes, use the clip nuts on the front rails for securing 10-32 screws. For rails with square
holes, use the retainer nuts (H and I in Figure 7 on page 13). Also refer to Figure 8 on page 14.
5. Install the air-duct assembly (C in Figure 7 on page 13) by inserting it down into the side-slot on the shelf.
Ensure that the tabs of the duct align and engage with the slots in the shelf. Also refer to Figure 11 on page 17.
16 of 20
FIGURE 11
7.
a.
Determine the size of the top-rail inner bracket that you will need to install on the top rail so that the top rail
will fit on the inside of the equipment cabinet rails. Remove the appropriate bracket from the accessory kit.
Note that the accessory kit contains three sizes, depending the depth of your equipment cabinet (B in
Figure 7 on page 13).
b.
Secure the top-rail inner bracket to the top-rail assembly with two 6-32 screws (K-3 in Figure 7 on page 13).
Tighten screws according to specifications under Torque requirements on page 14.
Insert the top-rail assembly (with the top-rail inner bracket attached) down into the air-duct assembly and
then secure the top-rail assembly to the air-duct assembly with two 6-32 screws, one screw on each side of
the air-duct assembly (K-1 and K-2 in Figure 7 on page 13). Also refer to Figure 12 on page 18.
b.
Secure the top-rail assembly to the rack. Refer to Figure 12 on page 18.
For rails with round holes
Use two 10-32 screws with washers (G in Figure 7 on page 13) on each end of the top rail assembly. Tighten
screws according to specifications under Torque requirements on page 14.
For rails with square holes
Use the two standard 10-32 screws (F in Figure 7 on page 13) with blue Loctite on the threads and
alignment washers (J in Figure 7 on page 13) on each end of the top rail assembly. Tighten screws
according to specifications under Torque requirements on page 14.
17 of 20
FIGURE 12
CAUTION
Use safe lifting practices when moving the product. (C015)
3. If applicable, lock the wheels of the lift.
4. Carefully lift the DCX-4S and slide it into the cabinet.
5. Secure the DCX-4S to the cabinet with six 10-32 screws with washers, three screws on each side (Figure 13 on
page 19). Tighten screws according to specifications under Torque requirements on page 14.
NOTE
Screws, clip nuts, and retainer nuts for securing the DCX-4S to the equipment rack are included in the DCX-4S
hardware accessory kit.
18 of 20
FIGURE 13
DCX-4S with 18 to 24 in. (45.72 to 60.96 cm) Port-Side Exhaust Kit installed in cabinet
NOTE
For rails with round holes, use the clip nuts on the front rails for securing 10-32 screws. For rails with square
holes, use the retainer nuts (H and I in Figure 7 on page 13). Also refer to Figure 8 on page 14.
6. Install the DCX-4S door and required cable management system using instructions in the DCX-4S Backbone
Hardware Reference Manual.
19 of 20
20 of 20