Breaker Logic L
Breaker Logic L
Breaker Logic L
DOCUMENT TITLE:
Client
Project Consultant
No
Project No.
Document / Drawing No.
4-9336-300-003
PROJECT CONSULTANT:
nd
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV UAS -2A Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V UAS-2A Breaker opened
6.6KV UAS -2A Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV UAS -2B Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V UAS-2B Breaker opened
6.6KV UAS -2B Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V UAS-2A Breaker Trip Operated
6.6KV UAS-2A Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V UAS-2B Breaker Trip Operated
6.6KV UAS-2B Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V UAS Bus Coupler Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Remote:
415V UAS-2A Breaker opened
415V UAS-2A Breaker not tripped
Close
415V UAS-2B Breaker Closed
415V UAS B/C trip not operated
OR
415V UAS-2B Breaker opened
415V UAS-2B Breaker not tripped
Close
415V UAS-2A Breaker Closed
415V UAS B/C trip not operated
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV ESP -2A Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V ESP-2A Breaker opened
6.6KV ESP -2A Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV ESP -2B Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V ESP-2B Breaker opened
6.6KV ESP -2B Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ESP-2A Breaker Trip Operated
6.6KV ESP-2A Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ESP-2B Breaker Trip Operated
6.6KV ESP-2B Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ESP Bus Coupler Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Remote:
415V ESP-2A Breaker opened
415V ESP-2A Breaker not tripped
415V ESP-2B Breaker Closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
Boiler UAS (PMCC) -2A Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Boiler MCC -2A Breaker opened
Boiler UAS (PMCC) -2A Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
Boiler UAS (PMCC) -2B Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Boiler MCC -2B Breaker opened
Boiler UAS (PMCC) -2B Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
Boiler MCC -2A Breaker Trip Operated
Boiler UAS (PMCC) - 2A Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
Boiler MCC -2B Breaker Trip Operated
Boiler UAS (PMCC) - 2B Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
Boiler MCC Bus Coupler Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Remote:
Boiler MCC -2A Breaker opened
Boiler MCC -2A Breaker not tripped
Boiler MCC-2B Breaker Closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
TG UAS (PMCC) -2A Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
TG MCC -2A Breaker opened
TG UAS (PMCC) -2A Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
TG UAS (PMCC) -2B Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
TG MCC -2B Breaker opened
TG UAS (PMCC) -2B Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
TG MCC-2A BREAKER
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
TG MCC -2A Breaker Trip Operated
TG UAS (PMCC) - 2A Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
TG MCC-2B BREAKER
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
TG MCC -2B Breaker Trip Operated
TG UAS (PMCC) - 2B Breaker opened
Open
CLOSE PERMISSIVES
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
TG MCC - BC BREAKER
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
TG MCC Bus Coupler Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Remote:
TG MCC -2A Breaker opened
TG MCC -2A Breaker not tripped
TG MCC-2B Breaker Closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV ACC -2A Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V ACC-2A Breaker opened
6.6KV ACC -2A Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV ACC -2B Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V ACC-2B Breaker opened
6.6KV ACC -2B Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
6.6KV ACC -2C Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
415V ACC-2C Breaker opened
6.6KV ACC -2C Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ACC-2A Breaker Trip Operated
6.6KV ACC-2A Breaker opened
Open
CLOSE PERMISSIVES
Bus Coupler opened Condition
415V ACC Bus Coupler-1 opened
6.6KV ACC-2A Breaker closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ACC-2C Breaker Trip Operated
6.6KV ACC-2C Breaker opened
Open
CLOSE PERMISSIVES
Bus Coupler opened Condition
415V ACC Bus Coupler-2 opened
6.6KV ACC-2C Breaker closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
REV
DOC. NO:
DATE
4-9336-300-003
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ACC-2B Breaker Trip Operated
6.6KV ACC-2B Breaker opened
Open
CLOSE PERMISSIVES
Bus Coupler-1 opened Condition
415V ACC Bus Coupler-1 opened
6.6KV ACC-2B Breaker closed
415V ACC-2B Breaker not tripped
Close
Close
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ACC Bus Coupler-1 Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Remote:
415V ACC-2A Breaker opened
415V ACC-2A Breaker not tripped
415V ACC-2B Breaker Closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
415V ACC Bus Coupler-2 Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
Remote:
415V ACC-2C Breaker opened
415V ACC-2C Breaker not tripped
415V ACC-2B Breaker Closed
Close
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
REV
DOC. NO:
DATE
4-9336-300-003
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
PROTECTIONS
N/E UAS (PMCC) -2A Trip Operated
Open
Open comments from screen
CLOSE PERMISSIVES
N/E MCC -2A Breaker opened
N/E UAS (PMCC) -2A Trip not operated
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Close/Open command from DCS
Local
Close/Open
Available
Available
Trip
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
CLOSE PERMISSIVES
POWER INITIAL RESTORE
Remote selected
UAS TIE not in trip condition
Independent selected in AIM switch
Close
Close
CHECKS
POWER INITIAL RESTORE:
Close command given with Bus energised condition
AIM Switch in independent
No Close
Independent selected
SHUTDOWN PARALLEL
Selector Switch kept in local mode and feedback in DCS
Selector Switch kept in remote mode and feedback in DCS
Local
Remote
Close
No open
Available
Trip
Shutdown parallel
selected
Opened
REMARKS
1) Breaker cannot be open from DCS
2) After closing of TIE breaker UAT incomer automatically opened from hardware inter lock
PROJECT:
CLIENT:
OPG GUJARAT
DOCUMENT:
REV
DOC. NO:
4-9336-300-003
DATE
Sr. No
DESCRIPTION
Equipment
1
21.04.14
REQUIREMENT
OBSERVATION / REMARKS
CLOSE PERMISSIVES:
STARTUP PARALLEL:
Manual selected in AIM selector switch
Remote selected
UAT incomer trip not operated
PT selector switch in incomer
Close
CHECKS
Selector Switch kept in local mode and feedback in DCS
Selector Switch kept in remote mode and feedback in DCS
Local
Remote
Close
No open
Available
Trip
Startup parallel
selected
Auto required
Opened
REMARKS
1) Breaker cannot be open from DCS.
2) After closing of UAT incomer UAS TIE breaker automatically opened from hardware inter lock.
3) After completion of startup parallel AIM switch should be kept in Auto mode for auto changeover operation.