Arteche Ds Trfmvguide en
Arteche Ds Trfmvguide en
Arteche Ds Trfmvguide en
INSTRUMENT
TRANSFORMERS
INDOOR / OUTDOOR
CAST RESIN CONSTRUCTION
This document may be subject to changes. Contact
ARTECHE to conrm the characteristics and
availability of the products described here.
MOVING TOGETHER
CONTENTS
Updates available at:
www.arteche.com/unitusa
The instrument transformers listed in this guide are the most common for the electrical
utilities and industries. ARTECHE has a much wider range of characteristics and models.
For any different detail than the ones listed, please contact ARTECHE or your local
representative/distributor.
15 kV VOLTAGE TRANSFORMER | 96
METERING UNITS | 174
25 kV COMBINED TRANSFORMER AND
25 kV VOLTAGE TRANSFORMER | 112
METERING UNITS | 182
34.5 kV VOLTAGE TRANSFORMER | 120 34.5 kV COMBINED TRANSFORMER AND
46 kV VOLTAGE TRANSFORMER | 124 METERING UNITS | 190
69 kV VOLTAGE TRANSFORMER | 128
5 kV CURRENT TRANSFORMER | 132
15 kV CURRENT TRANSFORMER | 134
25 kV CURRENT TRANSFORMER | 146
34.5 kV CURRENT TRANSFORMER | 152
46 kV CURRENT TRANSFORMER | 162
69 kV CURRENT TRANSFORMER | 168
Ratio correction factor: 1.003 Transformer Correction Factor = RCF + (/2600 ) = 1.003
Maximum allowable phase angle: +15.6 minutes + (-15.6/2600) = 0.997
Transformer Correction Factor = RCF (/2600) = 1.003- The ratio correction factor and phase angle for any point
(15.6/2600) = 0.997 inside the 0.3 class parallelogram, will always produce a
TCF between 0.997 and 1.003.
The ratio correction factor and phase angle for any point
inside the 0.3 class parallelogram for 100% rated current 1.006
Standard Class 0.3 means that from 100% of nominal current through the rating factor, accuracy is guaranteed to
be 0.3%, and from 10% of nominal current through 100% of nominal current accuracy is guaranteed to be 0.6%.
0.6% 0.3%
High Accuracy Class 0.15 means that from 100% of nominal current through the rating factor, accuracy is guaranteed
to be 0.15%, and from 5% of nominal current through 100% of nominal current accuracy is guaranteed to be 0.3%.
0.3% 0.15%
Accuracy Class 0.3S means that from 5% of nominal current through the rating factor, accuracy is guaranteed to
be 0.3%.
0.3%
Accuracy Class 0.15S means that from 5% of nominal current through the rating factor, accuracy is guaranteed to
be 0.15%.
0.15%
High Accuracy, Extended Range Class 0.15 means that from 1% of nominal current through the rating factor,
accuracy is guaranteed to be 0.15%. This goes beyond IEEE C57.13 requirements.
0.15%
INDOOR
OUTDOOR
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR
IN
NDO
DOORR
60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Resin Brown / Blue Window Type: 5 / Primary Bar Type: 7.3
Window Type:
3.66 (93) 3.15 (80)
3.40 (86)
6 (152.4)
MARKING H1 H2
(50.8 - 63.5)
(Single CONNEC-
2 - 2.5
Primary TIONS
Ratio) X1 X2
Secondary terminals.
Type: Quick Connector
Type: NEMA2 Material: Brass
Material: Copper Diameter: 1/4
Electrical characteristics
Power-Frequency
Current Continuous Continuous Withstand Voltage
Nominal (1 min)
Code Code Ratio Thermal Thermal
Window IEEE Metering Relay Voltage BIL
(Window (Bar (Primary: Current Current
Size Accuracy Accuracy System (kV) Primary & Secondary
type) type) Secondary) Rating Factor Rating Factor
(kV) Secondary Winding
(A) @ 30C @ 55C
(kVrms) (kVrms)
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR-OUTDOOR
60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Resin Blue 8.8
3.26 (82.80)
2 (50.8)
7.08 (179.83)
5 (127)
MARKING H1 H2
(Single CONNEC-
Primary TIONS
Ratio) X1 X2
Secondary terminals.
Type: Quick Connector
Material: Brass
Diameter: 1/4
Electrical characteristics
Power-Frequency Withstand
Continuous Continuous Voltage
Current Ratio Nominal (1 min)
Thermal Thermal
(Primary: IEEE Metering Relay Voltage
Code Current Current BIL (kV)
Secondary) Accuracy Accuracy System Primary &
Rating Factor Rating Factor @ Secondary
(A) (kV) Secondary
@ 30C 55C Winding (kVrms)
(kVrms)
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR
INDOOR-
INDOOR--
OUTDOOR
UL Recognized Component 60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Resin Blue Window Type: 10/12 / Primary Bar Type: 15
Window Type:
3.21 (81.5) 4.59 (116.5)
See
table
8.66 (220)
5 (127)
See
table
9.01 (229)
5 (127)
Drawing number: 4287182
MARKING H1 H2 H1 H2
2 (51)
(Single CONNEC-
Primary TIONS
Ratio) X1 X2 X1 X2 X3
Secondary terminals.
Type: Quick Connector
Type: NEMA2 Material: Brass
Material: Copper Diameter: 1/4
Electrical characteristics
Power-Frequency
Current Continuous Continuous Withstand Voltage
Nominal (1 min)
Code Code Ratio Thermal Thermal
Window IEEE Metering Relay Voltage BIL
(Window (Bar (Primary: Current Current
Size Accuracy Accuracy System (kV) Primary & Secondary
type) type) Secondary) Rating Factor Rating Factor
(kV) Secondary Winding
(A) @ 30C @ 55C
(kVrms) (kVrms)
735301010 735305010 2.56" 50:5 4.0 3.0 1.2 B0.1 - 0.6 10 4 2.5
735301020 735305020 2.56" 100:5 4.0 3.0 0.3 B0.1 C-10 0.6 10 4 2.5
735301040 735305040 2.56" 200:5 4.0 3.0 0.3 B0.5 C-30 0.6 10 4 2.5
735301060 735305060 3.15" 300:5 4.0 3.0 0.3 B0.5 C-30 0.6 10 4 2.5
735301080 735305080 3.15" 400:5 4.0 3.0 0.3 B0.5 C-30 0.6 10 4 2.5
735301100 735305100 3.15" 500:5 3.0 2.2 0.3 B0.5 C-30 0.6 10 4 2.5
735301120 735305120 3.15" 600:5 2.0 1.5 0.3 B0.5 C-30 0.6 10 4 2.5
735301160 735305160 3.15" 800:5 2.0 1.5 0.3 B0.5 C-20 0.6 10 4 2.5
735301200 735305200 3.15" 1000:5 2.0 1.5 0.3 B0.5 C-30 0.6 10 4 2.5
735301240 735305240 3.15" 1200:5 1.5 1.2 0.3 B1.8 C-30 0.6 10 4 2.5
735302040 735306040 2.56" 200/400:5 4.0/2.0 3.0/1.5 0.3 B0.2/0.3 B0.5 C-30/C-50 0.6 10 4 2.5
735302060 735306060 3.15" 300/600:5 3.0/2.0 2.2/1.5 0.3 B0.2/0.3 B0.5 C-20/C-40 0.6 10 4 2.5
735302080 735306080 3.15" 400/800:5 2.0/2.0 1.5/1.5 0.3 B0.2/0.3 B0.5 C-10/C-30 0.6 10 4 2.5
High Accuracy Extended Range 5% nominal current to Rating Factor
735307120 735308120 3.15" 600:5 2.0 1.5 0.15S B0.5 - 0.6 10 4 2.5
735300120 735309120 3.15" 600:5 3.0 2.0 0.15S B0.2 - 0.6 10 4 2.5
735307200 735308200 3.15" 1000:5 2.0 1.5 0.15S B0.5 - 0.6 10 4 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR-
UL Recognized Component
OUTDOOR
60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Resin Blue Tapered Type: 7.5 / Wide Type: 8.5
4.5 (114)
3.03 (77)
Wide Type:
6.2 (157.5)
9.06 (230)
4.5 (114)
MARKING H1 H2
(Single CONNEC-
Primary TIONS
Ratio) X1 X2
Secondary terminals.
Type: Quick Connector
Material: Brass
Diameter: 1/4
Electrical characteristics
Power-Frequency
Current Withstand Voltage
Continuous Continuous Nominal (1 min)
Code Code Ratio
Thermal Thermal IEEE Metering Relay Voltage BIL
(Tapered (Wide (Primary:
Current Rating Current Rating Accuracy Accuracy System (kV) Primary & Secondary
type) type) Secondary)
Factor @ 30C Factor @ 55C (kV) Secondary Winding
(A)
(kVrms) (kVrms)
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR-
UL Recognized Component
OUTDOOR
60 Hertz
Mechanical
cal characteristics
Insulation Material Color Weight (lbs.)
Resin Blue 13
2.62 (66.5)
5.25 (133)
6.38 (162)
8.25 (209.5)
7.5 (109.5)
Drawing number: 4287273
MARKING H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X3
SECONDARY TERMINALS
AND SHORT CIRCUIT DEVICE
CONNEC-
TIONS
Secondary terminals.
Type: Quick Connector
Material: Brass
Diameter: 1/4
Electrical characteristics
Power-Frequency Withstand
Voltage
Current Ratio Continuous Continuous Nominal (1 min)
Code (Primary: Thermal Current Thermal Current IEEE Metering Relay Voltage BIL
(Window type) Secondary) Rating Factor @ Rating Factor @ Accuracy Accuracy System (kV) Primary & Secondary
(A) 30C 55C (kV) Secondary Winding
(kVrms) (kVrms)
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR-
UL Recognized Component
OUTDOOR
60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Resin Blue 19
2.62 (66.5)
8.26 (209.8)
11.38 (289)
12.07 (306.5)
5.24 (133)
8.25 (209.5)
9.76 (248)
Drawing number: 4287275
MARKING H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X3
SECONDARY TERMINALS
AND SHORT CIRCUIT DEVICE
CONNEC-
TIONS
Secondary terminals.
Type: Quick Connector
Material: Brass
Diameter: 1/4
Electrical characteristics
Power-Frequency
Withstand Voltage
Current Ratio Continuous Continuous Nominal (1 min)
Code
(Primary: Thermal Current Thermal Current IEEE Metering Relay Voltage BIL
(Window
Secondary) Rating Factor @ Rating Factor @ Accuracy Accuracy System (kV) Primary & Secondary
type)
(A) 30C 55C (kV) Secondary Winding
(kVrms) (kVrms)
Notes:
ARTECHE ICP series are dry type indoor service current transformers.
The core is encapsulated with an impact-resistant polycarbonate which
provides excellent internal dielectric properties and mechanical strength,
ensuring a long mechanical and electrical life. The transformer is
maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses.
The windings are copper wire with copper plate double isolation. The
concentric distribution of the coils prevents magnetic ux leakage,
achieving greater accuracy and higher capacity to withstand mechanical
stresses in adverse operating conditions.
INDOOR
60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Polycarbonate Black 26
3.54 (90)
9.9 (251.5)
10 (254)
6.5 (165)
8.43 (214)
Drawing number: 4287899
1.38 (35)
ONE ONE
SECONDARY SECONDARY MULTIRATIO
MARKING H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X3 X4 X5
Electrical characteristics
Power-Frequency
Current Continuous Continuous Withstand Voltage
Nominal (1 min)
Ratio Thermal Thermal
Window Relay Voltage BIL
Code (Primary: Current Current IEEE Metering Accuracy
Size Accuracy System (kV) Primary & Secondary
Secondary) Rating Factor Rating Factor
(kV) Secondary Winding
(A) @ 30C @ 55C
(kVrms) (kVrms)
Notes:
ARTECHE ICP series are dry type indoor service current transformers.
The core is encapsulated with an impact-resistant polycarbonate which
provides excellent internal dielectric properties and mechanical strength,
ensuring a long mechanical and electrical life. The transformer is
maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses.
The windings are copper wire with copper plate double isolation. The
concentric distribution of the coils prevents magnetic flux leakage,
achieving greater accuracy and higher capacity to withstand mechanical
stresses in adverse operating conditions.
INDOOR
60 Hertz
Mechanical characteristics
Insulation Material Color Weight (lbs.)
Polycarbonate Black 54.8
6.93 (176)
6.5 (165)
10 (254)
10 (254)
8.43 (214)
1.38 (35) Drawing number: 4287900
ONE ONE
SECONDARY SECONDARY MULTIRATIO
MARKING H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X3 X4 X5
Electrical characteristics
Power-Frequency
Current Continuous Continuous Withstand Voltage
Nominal (1 min)
Ratio Thermal Thermal
Window Relay Voltage BIL
Code (Primary: Current Current IEEE Metering Accuracy
Size Accuracy System (kV) Primary & Secondary
Secondary) Rating Factor Rating Factor
(kV) Secondary Winding
(A) @ 30C @ 55C
(kVrms) (kVrms)
Notes:
The ARTECHE Over Bushing CT series are 600 V rated units designed
to t over a variety of specied bushing sizes. Primary current ratios are
available from 200:5 thru 5000:5 at 60 Hz with a Rating Factor of up to
4.0.
This Slip-Over type CT will operate with high accuracy for metering or
relay applications.
OUTDOOR
60 Hertz
Single, Dual and
Multi Ratios,
Window Type,
Metering/Relaying
Mechanical characteristics
The core and coil assembly is wound and tape The core of the CT is constructed from high
wrapped and is available in window sizes from 2.5 permeability grain oriented silicon steel
to 45 inches. The secondary leads are typically laminations which provide low core losses. The
#10 AWG or #12 AWG. The bushing insulation windings are constructed with copper wire
provides the dielectric protection for the CT. and copper plate double isolation. Concentric
distribution of the CT coils prevents magnetic ux
A metal housing covers the whole Current leakage, achieving greater accuracy and higher
Transformer. capacity to withstand mechanical stresses under
adverse operating conditions.
GROUND CONNECTION
(0.59)
2 HOLES TO CONDUIT
TERMINALS 1/4
PIPE 1NPT
ALUMINIUM TERMINAL BOX
55
25
8x 1.18x.59
1/2-UNC
13
5
35
Mounting Options
The ARTECHE Bushing CT is designed to be Through careful calculation, steel selection
externally mounted around the bushings of power and testing, existing current transformer
transformers, circuit breakers, underground characteristics can be matched with the ARTECHE
potheads or in switchgear. Bushing CT. Existing characteristic curve would
be required. Contact factory for other needs.
How to order
When ordering an ARTECHE Over Bushing CT,
include the following information:
4. Current ratio and taps, if any ___ (:5A or :1A | SR, DR, MR)
8. Lead length & type ___, size - ___(standard is #10 AWG TW)
NOTE Due to the many variations of mounting, Arteche does not supply mounting hardware.
Units are custom manufactured to customer specications. Contact factory to discuss other options.
Notes:
Mechanical characteristics
The core and coil assembly is wound and tape The core of the CT is constructed from high
wrapped and is available in window sizes from 2.5 permeability grain oriented silicon steel laminations
to 45 inches. which provide low core losses. The windings are
constructed with copper wire and copper plate
The secondary leads are typically #10 AWG or double insulated. All secondary windings are
#12 AWG. The bushing insulation provides the fully distributed around the core, which provides
dielectric protection for the CT. Optional TEFZEL low leakage reactance on each ratio, achieving
insulation for the CT is also available. greater accuracy and higher capacity to withstand
mechanical stresses under adverse operating
conditions.
NAME PLATE
2
D
-4
+1
D1
TYPE OF
CONNECTIONS
(Secondary
terminal)
How to order
When ordering an ARTECHE Bushing CT, include
the following information:
4. Current ratio and taps, if any ___ (:5A or :1A | Single Ratio, Double Ratio or Multi Ratio)
NOTE Due to the many variations of mounting, Arteche does not supply mounting hardware.
Please, dont hesitate to contact us to discuss other options.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
IINDOOR
ND OR
60 Hertz
ertz Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Secondary
Resin Gray* 32 terminals
1/4-UNC
Unfused 3.12 (79.2)
5.83 (144.3)
Nameplate
6.35 (161.3)
5.5 (139.7)
6.6 (167.6)
5.67 (144)
8.5 (215.9)
9.31 (236.5)
Fused
5.68 (144.3) 3.17 (80.5)
Nameplate
6.35 (161.3)
5.5 (139.7)
8.22 (208.8)
6.6 (167.6)
Secondary
5.67 (144)
terminals
1/4-UNC
8.5 (215.9)
9.31 (236.5)
Drawing number: 4286786
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Primary Secondary IEEE Metering Voltage BIL
Code Ratio Voltage Factor Burden
(V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
All units can be supplied either switchgear style, fuse clips only or fuses and clips. Please contact your commercial representant for further information.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
INDOOR
IN R
60 Hertz
tz Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
UL Recognized Component
nent
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 32
Unfused
6.3(160)
5(127)
5.67 (144)
Secondary
terminals
1/4-UNC
8.5 (215.9)
9.31 (236.5)
Drawing number: 4287876
Fused
6.3(160)
5.68 (144.3)
5(127)
Nameplate
5.5 (139.7)
6.35 (161.3)
7.26 (184.4)
6.13 (155.7)
Secondary
terminals
5.67 (144)
1/4-UNC
8.5 (215.9)
9.31 (236.5)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Primary Secondary IEEE Metering Voltage BIL
Code Ratio Voltage Factor Burden
(V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
All units can be supplied either switchgear style, fuse clips only or fuses and clips. Please contact your commercial representant for further information.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper
60 Hertz plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 60
10.6 (270.5)
8.07 (205)
8.85 (225)
H1
Sealable
cover
Secondary
terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753221020 20:1 2400/4160GY 120 0.6 W,X,M,Y 1.1 1.5 450 8.7 75 26 2.5
753221035 35:1 4200/7200GY 120 0.6 W,X 1.1 1.5 450 8.7 75 26 2.5
753221040 40:1 4800/8320GY 120 0.6 W,X 1.1 1.5 450 8.7 75 26 2.5
753221060 60:1 7200/12470GY 120 0.6 W,X 1.1 1.5 450 8.7 75 26 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
INDOOR ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
60 Hertz
Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 85
Unfused
Nameplate
9.25 (234.95)
9.83 (249.7)
Secondary
terminals
10.25 (260.35)
Fused 9 (228.6)
15.62 (396.75)
Nameplate
8 (203.2)
12.36 (314)
Secondary
terminals
10.25 (260.35)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Secon- Rated Voltage Thermal (1 min)
Primary IEEE Metering Voltage BIL
Code Ratio dary Voltage Factor Burden
(V) Accuracy System (kV) Primary & Secondary
(V) Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
All Units can be supplied either switchgear style, fuse clips only or fuses and clips. Please contact your commercial representant for further information.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 60
10.62 (270)
8.07 (205)
8.85 (225)
Sealable
cover Ground Secondary
connection terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Secon- IEEE Rated Voltage Thermal (1 min)
Primary Voltage BIL
Code Ratio dary Metering Voltage Factor Burden
(V) System (kV) Primary & Secondary
(V) Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753381060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.25 450 15 110 34 2.5
753381063 63.5:1 7620/13200GY 120 0.6 W,X,M,Y 1.1 1.25 450 15 110 34 2.5
753381070 70:1 8400/14550GY 120 0.6 W,X,M,Y 1.1 1.25 450 15 110 34 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 60
11.41 (290)
H1
11.22 (285)
Sealable
cover Secondary
terminals
Ground
connection
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753441060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
753441063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
753441070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
INDOOR mechanical stresses in adverse operating conditions.
60 Hertz
Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.) 15.31 (389)
Resin Gray* 85
9.25 (235)
Unfused
9.01 (228.85)
Nameplate
9.83 (249.68)
8 (203.2)
13.13 (333.5)
15.31 (389)
Fused
9.25 (235)
9.78 (248.4)
Nameplate
11.57 (294)
8 (203.2)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Secon- Rated Voltage Thermal (1 min)
Primary IEEE Metering Voltage BIL
Code Ratio dary Voltage Factor Burden
(V) Accuracy System (kV) Primary & Secondary
(V) Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
All Units can be supplied either switchgear style, fuse clips only or fuses and clips. Please contact your commercial representant for further information.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 62
H1
11.41 (290)
10.82 (275)
Sealable H2
cover
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753501060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 600 15 110 34 2.5
753501063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 600 15 110 34 2.5
753501070 70:1 8400/14450Y 120 0.3 W,X,M,Y 1.1 1.25 600 15 110 34 2.5
753501100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 600 15 110 34 2.5
753501110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 600 15 110 34 2.5
753501120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 600 15 110 34 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 60
11.4 (290)
11.22 (285)
H1
Sealable
cover Secondary
terminals
Ground
connection
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Secon- IEEE Rated Voltage Thermal (1 min)
Primary Voltage BIL
Code Ratio dary Metering Voltage Factor Burden
(V) System (kV) Primary & Secondary
(V) Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753741100 100:1 12000/20750GY 120 0.3 W,X,M,Y 1.1 1.5 600 25 125 50 2.5
753741120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.5 600 25 125 50 2.5
753741200 200:1 24000/24000GY 120 0.3 W,X,M,Y 1.1 1.5 600 25 125 50 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 66
7 (178)
12.79 (325) 5.9 (150)
11 (279)
10.82 (275)
H1
Sealable
cover Secondary
M8 terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Secon- IEEE Rated Voltage Thermal (1 min)
Marked Primary Voltage BIL
Code dary Metering Voltage Factor Burden
Ratio (V) System (kV) Primary & Secondary
(V) Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753541100 100:1 12000/20750GY 120 0.3 W,X,M,Y 1.1 1.5 750 25 125 50 2.5
753541120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.5 750 25 125 50 2.5
753541200 200:1 24000/24000GY 120 0.3 W,X,M,Y 1.1 1.5 750 25 125 50 2.5
Notes:
ARTECHE UE series are dry type indoor service voltage transformers. The
core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength, ensuring a long
mechanical and electrical life. The transformer is maintenance free.
The entire surface of the transformer is coated with a conductive layer that
is intended to be solidly grounded when energized. This allows for compact
INDOOR mounting inside switchgear or enclosures.
60 Hertz
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
4.92 (125)
10.8 (274)
11.98 (304)
H1
Sealable
cover Secondary
terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753681100 100:1 12000/20780GY 120 0.6 W,X,M 1.1 1.25 350 25 125 50 2.5
753681120 120:1 14400/24940GY 120 0.6 W,X,M 1.1 1.25 350 25 125 50 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 62
H1
9.92 (252)
10.86 (276)
Terminal
secondary
Ground
H2
connection
X1 X2
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
753801100 100:1 12000/20750Y 120 0.3 W,X,M,Y 1.1 1.25 600 25 125 50 2.5
753801120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 600 25 125 50 2.5
753801200 200:1 24000/24000Y 120 0.3 W,X,M,Y 1.1 1.25 600 25 125 50 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 97
7.87 (200)
14.76 (375) 8.74 (222)
13.77 (350)
13.77 (350)
H1
Sealable
cover Secondary
terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
754391175 175:1 20125/34500GY 115 0.3 W,X,M,Y 1.1 1.5 750 34.5 200 70 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
INDOOR
IN
NDOOR Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
60
6 0H
Hertz
rtz requirements.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 167
Unfused
16.14 (410) 9.45 (240) 7.87 (200)
14.44 (367)
13.46 (341.8)
11.8 (230)
Secondary A
Sealable terminals
cover
Fused
9.45 (240)
16.14 (410) 8.75 (222)
18 (457)
14.44 (367)
12.8 (325)
Sealable Secondary A
cover terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Secon- IEEE Rated Voltage Thermal (1 min)
Primary Voltage BIL
Code Ratio dary Metering Voltage Factor Burden
(V) System (kV) Primary & Secondary
(V) Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
UNFUSED
754260175 175:1 20125/34500GY 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754260300 300:1 34500/34500GY 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754260289 289:1 19942/34500GY 69 0.3 W,X,M,Y 1.1 1.5 1500 34.5 200 70 2.5
754260240 240:1 16100/27900GY 67.08 0.3 W,X,M,Y 1.1 1.5 1500 34.5 200 70 2.5
FUSED
754262175 175:1 20125/34500GY 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754262300 300:1 34500/34500GY 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754262200 200:1 24000/24000GY 120 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754262208 208.33:1 25000/25000GY 120 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754262220 220:1 26400/26400GY 120 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754262207 207.5:1 24900/24900GY 120 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754262240 240:1 27600/27600GY 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 99
7.87 (200)
H1
13.77 (350)
13.36 (415.5)
Terminal
secondary
H2
Sealable
Ground cover
connection
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
754421300 300:1 34500/34500Y 120 0.3 W,X,M,Y 1.1 1.5 751 34.5 200 70 2.5
Notes:
Unfused Fused
ARTECHE UC/UX/VC series are dry type indoor service voltage
transformers. The core is encapsulated with Type B epoxy resin which
provides excellent internal dielectric properties and mechanical strength,
ensuring a long mechanical and electrical life. The transformer is
maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
IN OOR
INDOOR
OR Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
60 Hertz
tz requirements.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 174
Unfused
16.14 (410)
A
13.46 (341.8)
14.44 (366.7)
7.87 (200)
B
15.94 (405)
Secondary
terminals 11.8 (230)
Sealable cover
Drawing number: 4287358
Fused
16.14 (410)
16.53 (420)
17.63 (448)
8.75 (222)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Primary Secondary Voltage BIL
Code Ratio Metering Voltage Factor Burden
(V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
UNFUSED
754610175 175:1 20125/34500Y 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754610240 240:1 27600/27600Y 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754610300 300:1 34500/34500Y 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
FUSED
754612175 175:1 20125/34500Y 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754612240 240:1 27600/27600Y 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
754612300 300:1 34500/34500Y 115 0.3 W,X,M,Y,Z 1.1 1.5 1500 34.5 200 70 2.5
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper
60 Hertz plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray * 38
15 (381)
6.13 (156)
7.07 (180)
5.75 (146)
9.62 (244)
5.51 (140)
(2 x 108)
2 x 4.25
2 x 5 (2 x 127)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short- Highest
Thermal (1 min)
Ratio time time IEEE Nominal
Current Relay BIL
Code (Primary: Thermal Mechanical Metering Voltage
Rating Accuracy (kV) Primary & Secondary
Secondary) Current Current Accuracy System
Factor @ Secondary Winding
(A) (kA/1s) (kApeak) (kV)
30C (kVrms) (kVrms)
Notes:
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 35.3
9.37 (238)
H2
5.5 (140)
10.03 (255)
H1
Sealable Secondary
cover terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AG Series are dry type indoor service current transformers. The
core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength, ensuring a long
mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 165.3
10.63 (270)
7.99 (203)
Terminal
13.18 (335)
Secondary
Box
Ground
connector
5.11 (130)
ONE TWO
SECONDARY SECONDARIES
MARKING H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2
Y1 Y2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 35.3
9.37 (238)
H2
5.5 (140)
10.03 (255)
H1
Sealable
cover
Secondary
terminals M6
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical
Mechan
h ical characteristics
Insulation Material Colors
Colo Weight (lbs.)
Resin
R i Gray*
G 63.8
5.90 (150)
H1
8.58 (217.932)
Nameplate
H2
1/4 Secondary
(6.35) terminals
11.69 (297)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 46.2
P2
10.6 (270.5)
8.6 (220)
Nameplate
Ground
connector P1
Secondary
(1/4) terminals
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
IINDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz
6 magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized
Recog
o nized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 55
23 (584)
6.79 (172.5)
3.94 (100)
10.34 (263)
9 (229)
5.13 (130)
Nameplate
9.63 (245)
Drawing number: 4287278
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 35.3
9.37 (238)
H2
5.5 (140)
10.03 (255)
H1
Sealable
cover
Secondary
terminals M6
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical
Mechan
h ical characteristics
Insulation Material Colors
Colo Weight (lbs.)
Resin
R i Gray*
G 63.8
5.90 (150)
H1
8.58 (217.932)
Nameplate
H2
1/4 Secondary
(6.35) terminals
11.69 (297)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 35.3
5.11 (130)
14.84 (377)
P1 P2
Sealable
cover
Secondary Connection
terminal to ground
5.51 (14)
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
751111001 5:5 1.2 0.5 1 0.3 B-0.5 C-50 34.5 200 70 2.5
751111002 10:5 1.2 1 2 0.3 B-0.5 C-50 34.5 200 70 2.5
751111003 15:5 1.2 1.5 3 0.3 B-0.5 C-50 34.5 200 70 2.5
751111004 20:5 1.2 2 4 0.3 B-0.5 C-50 34.5 200 70 2.5
751111005 25:5 1.2 2.5 5 0.3 B-0.5 C-50 34.5 200 70 2.5
751111006 30:5 1.2 3 6 0.3 B-0.5 C-50 34.5 200 70 2.5
751111008 40:5 1.2 4 8 0.3 B-0.5 C-50 34.5 200 70 2.5
751111010 50:5 1.2 5 10 0.3 B-0.5 C-50 34.5 200 70 2.5
751111015 75:5 1.2 7.5 15 0.3 B-0.5 C-50 34.5 200 70 2.5
751111020 100:5 1.2 10 20 0.3 B-0.5 C-50 34.5 200 70 2.5
751111030 150:5 1.2 15 30 0.3 B-0.5 C-50 34.5 200 70 2.5
751111040 200:5 1.2 20 40 0.3 B-0.5 C-50 34.5 200 70 2.5
751111060 300:5 1.2 30 60 0.3 B-0.5 C-50 34.5 200 70 2.5
751111080 400:5 1.2 40 80 0.3 B-0.5 C-50 34.5 200 70 2.5
751111120 600:5 1.2 50 95 0.3 B-0.5 C-50 34.5 200 70 2.5
751111160 800:5 1.2 60 120 0.3 B-0.5 C-50 34.5 200 70 2.5
751111200 1000:5 1.2 75 135 0.3 B-0.5 C-50 34.5 200 70 2.5
751111240 1200:5 1.2 84 150 0.3 B-0.5 C-50 34.5 200 70 2.5
Notes:
ARTECHE AC/CID Series are dry type indoor service current transformers.
The core is encapsulated with Type B epoxy resin which provides
excellent internal dielectric properties and mechanical strength, ensuring
a long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
INDOOR plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions.
UL Recognized Component
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 79.4
10.62 (270)
8.26 (210)
6.1 (155)
H1
7 (178)
13.97 (355)
H2
Secondary Sealable Connection 11.61 (295)
terminals cover to ground
13.89 (353)
Drawing number: 4286145
ONE
SECONDARY
MARKING H1 H2
(Single
Primary
Ratio) X1 X2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
751161001 5:5 1.2 0.5 1 0.3 B-1.8 C-100 34.5 200 70 2.5
751161002 10:5 1.2 1 2 0.3 B-1.8 C-100 34.5 200 70 2.5
751161003 15:5 1.2 1.5 3 0.3 B-1.8 C-100 34.5 200 70 2.5
751161004 20:5 1.2 2 4 0.3 B-1.8 C-100 34.5 200 70 2.5
751161005 25:5 1.2 2.5 5 0.3 B-1.8 C-100 34.5 200 70 2.5
751161006 30:5 1.2 3 6 0.3 B-1.8 C-100 34.5 200 70 2.5
751161008 40:5 1.2 4 8 0.3 B-1.8 C-100 34.5 200 70 2.5
751161010 50:5 1.2 5 10 0.3 B-1.8 C-100 34.5 200 70 2.5
751161015 75:5 1.2 7.5 15 0.3 B-1.8 C-100 34.5 200 70 2.5
751161020 100:5 1.2 10 20 0.3 B-1.8 C-100 34.5 200 70 2.5
751161030 150:5 1.2 15 30 0.3 B-1.8 C-100 34.5 200 70 2.5
751161040 200:5 1.2 20 40 0.3 B-1.8 C-100 34.5 200 70 2.5
751161060 300:5 1.2 30 60 0.3 B-1.8 C-100 34.5 200 70 2.5
751161080 400:5 1.2 40 80 0.3 B-1.8 C-100 34.5 200 70 2.5
751161120 600:5 1.2 50 95 0.3 B-1.8 C-100 34.5 200 70 2.5
751161160 800:5 1.2 60 120 0.3 B-1.8 C-100 34.5 200 70 2.5
751161200 1000:5 1.2 75 135 0.3 B-1.8 C-100 34.5 200 70 2.5
751161240 1200:5 1.2 84 150 0.3 B-1.8 C-200 34.5 200 70 2.5
Notes:
ARTECHE KCB series are dry type indoor service dead-front combination
CT-PT
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength, ensuring a long
mechanical and electrical life. The transformer is maintenance free.
The entire surface of the transformer is coated with a conductive layer that
is intended to be solidly grounded when energized. This allows for compact
mounting inside switchgear or enclosures.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
KCB 200 A KCB 600 A
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
INDOOR
60 Hertz Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
The primary terminals are standard 200 or 600 Ampere rated dead-front
bushing well and can be connected using IEEE 368 standard inserts and
elbow connectors.
The secondary terminals are 1/4 slotted screws with at and lock washers
located inside a metallic terminal cover with two 1 NPT conduit hubs. The
ground terminal is provided inside the terminal cover along with a manually
operated CT secondary shorting device for safety purposes.
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Metallized resin Gray 150
10 (254)
Secondary
terminals Terminal
1/4-20 box
V2 V2
VT
1 hole 7/16 to
C1
CT
C2
ground connection
19.84 (503)
Drawing number: 4286592 (200 A) / 4287655 (600 A)
KCB 600 A
3 (76)
ONE SECONDARY
H1 H2
MARKING
(Single
Primary
18.33 (466)
C1 C2
Ratio)
H0
V1 V2
Electrical characteristics
Power-Frequency
Withstand Voltage
Continuous (1 min)
Short- Short- IEEE
Current Thermal IEEE Metering Nominal
time time Metering Power
Ratio Current Accuracy Voltage BIL Power
Code Thermal Mechanical Accuracy frequency
(Primary: Rating [Voltage System (kV) frequency
Current Current [Current secondary
Secondary) Factor @ Transformer] (kV) applied
(kA/1s) (kApeak) Transformer] applied
30C voltage test
voltage test
(kVrms)
(kVrms)
770034011 5:5 2.0 0.5 1.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034021 10:5 2.0 1 2.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034031 15:5 2.0 1.5 3.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034041 20:5 2.0 2 5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034051 25:5 2.0 2.5 6.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034061 30:5 2.0 3 7.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034081 40:5 2.0 4 10 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034101 50:5 2.0 5 12.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034151 75:5 2.0 7.5 18.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770034201 100:5 2.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770035301 150:5 1.33 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770035401 200:5 1.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770031131 300:5 1.5 30 75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770031141 400:5 1.5 40 100 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770031151 600:5 1.0 60 150 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
ARTECHE KCB series are dry type indoor service dead-front combination
CT-PT
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength, ensuring a long
mechanical and electrical life. The transformer is maintenance free.
The entire surface of the transformer is coated with a conductive layer that
is intended to be solidly grounded when energized. This allows for compact
mounting inside switchgear or enclosures.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
KCB 200 A KCB 600 A
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
INDOOR
60 Hertz Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
The primary terminals are standard 200 or 600 Ampere rated dead-front
bushing well and can be connected using IEEE 368 standard inserts and
elbow connectors.
The secondary terminals are 1/4 slotted screws with at and lock washers
located inside a metallic terminal cover with two 1 NPT conduit hubs. The
ground terminal is provided inside the terminal cover along with a manually
operated CT secondary shorting device for safety purposes.
Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Metallized resin Gray 150
10 (254)
Secondary
terminals Terminal
1/4-20 box
V2 V2
VT
1 hole 7/16 to
C1
CT
C2
ground connection
19.84 (503)
Drawing number: 9449854 (200 A) / 4287736 (600 A)
KCB 600 A
3 (76)
ONE SECONDARY
18.33 (466)
H1 H2
MARKING
(Single
Primary
C1 C2
Ratio)
H0
V1 V2
Electrical characteristics
Power-Frequency
Withstand Voltage
Continuous (1 min)
Short- Short- IEEE
Current Thermal IEEE Metering Nominal
time time Metering Power
Ratio Current Accuracy Voltage BIL Power
Code Thermal Mechanical Accuracy frequency
(Primary: Rating [Voltage System (kV) frequency
Current Current [Current secondary
Secondary) Factor @ Transformer] (kV) applied
(kA/1s) (kApeak) Transformer] applied
30C voltage test
voltage test
(kVrms)
(kVrms)
770104016 5:5 2.0 0.5 1.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104026 10:5 2.0 1 2.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104036 15:5 2.0 1.5 3.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104046 20:5 2.0 2 5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104056 25:5 2.0 2.5 6.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104066 30:5 2.0 3 7.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104086 40:5 2.0 4 10 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104106 50:5 2.0 5 12.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104156 75:5 2.0 7.5 18.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770104206 100:5 2.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770105306 150:5 1.33 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770105406 200:5 1.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770101136 300:5 1.5 30 75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770101146 400:5 1.5 40 100 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770101156 600:5 1.0 60 150 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
OUTDOOR
60 Hertz The external layer can be manufactured with Hydrophobic Cycloaliphatic
Epoxy Resin (HCEP) which improves service life expectancy due to its
improved tracking and erosion resistance. HCEP additionally increases
the transformers weatherability and offers better performance in heavily
polluted environments.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
11.25 (286)
2 x 8.5 (2 x 216)
2 x 6.25 (2 x 159)
12 (305)
Terminal box
CONNEC-
TIONS
SINGLE SECONDARY
H1 H2 H1 H2
MARKING
(Single Fuse: 16A
Primary
Ratio) X1 X2 X1 X2
FUSED UNFUSED
Electrical characteristics
Power-Frequency
Continuous Rated Highest Withstand Voltage (1
Secon- IEEE Rated Voltage Thermal Nominal min)
Primary BIL
Code * (CEP) Ratio dary Metering Voltage Factor Burden Voltage
(V) (kV) Primary & Secondary
(V) Accuracy Factor 30 s (VA) System
(Un) (Un) (kV) Secondary Winding
(kVrms) (kVrms)
With FUSE in the secondary box
757091020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.5 1000 5 60 19 2.5
757091035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.5 1000 5 60 19 2.5
757091040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.5 1000 5 60 19 2.5
Without FUSE in the secondary box
757090020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.5 1000 5 60 19 2.5
757090035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.5 1000 5 60 19 2.5
757090040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.5 1000 5 60 19 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.62 (219)
17.8 (453)
H1
Lifting holes
3/4
2 holes to
conduit pipe
1 NPT 10 (254)
Drawing number:
Fused: 4286572 / 4286596+
Unfused: 4286820
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757061020 20:1 2400/4156GY 120 0.3 W,X,M,Y 1.1 1.5 750 5 60 19 2.5
2400/4156GY 0.3 W,X /
757063060 20/60:1 120 1.1 1.5 750 15 110 34 2.5
& 7200/12470GY 0.3W,X,M,Y
757061060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.5 750 15 110 34 2.5
757061063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.5 750 15 110 34 2.5
757061070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.5 750 15 110 34 2.5
757065020 20:1 2400/4156GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 5 60 19 2.5
2400/4156GY 0.3 W,X /
757066060 20/60:1 120 1.1 1.25 1500 15 110 34 2.5
& 7200/12470GY 0.3W,X,M,Y
757065060 60:1 7200/12470GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757065063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.25 1500 15 110 34 2.5
757065070 70:1 8400/14550GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757067020+ 20:1 2400/4156GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 5 60 19 2.5
2400/4156GY 0.3 W,X /
757068020+ 20/60:1 120 1.1 1.25 1500 15 110 34 2.5
& 7200/12470GY 0.3W,X,M,Y
+
757067060 60:1 7200/12470GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757067063+ 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.25 1500 15 110 34 2.5
757067070+ 70:1 8400/14550GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
Without FUSE in the secondary box
757064020 20:1 2400/4156GY 120 0.3 W,X,M,Y 1.1 1.5 750 5 60 19 2.5
757064060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.5 750 15 110 34 2.5
757064063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.5 750 15 110 34 2.5
757064070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.5 750 15 110 34 2.5
757060020 20:1 2400/4156GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 5 60 19 2.5
757060060 60:1 7200/12470GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757060063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.25 1500 15 110 34 2.5
757060070 70:1 8400/14550GY 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
+
Extended creepage distance
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.62 (219)
17.12 (235)
H1
Lifting holes
3/4
2 holes to
conduit pipe
1 NPT 10 (254)
Drawing number:
Fused: 4286570
Unfused: 4286769
CONNEC-
TIONS
SINGLE SECONDARY
H1 H2 H1 H2
MARKING
(Single
Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2
FUSED UNFUSED
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757031020 20:1 2400/4160GY 120 0.3 W,X,M,Y 1.1 1.5 500 5 60 19 2.5
757031035 35:1 4200/7280GY 120 0.3 W,X,M,Y 1.1 1.5 500 5 60 19 2.5
757031040 40:1 4200/4200GY 120 0.3 W,X,M,Y 1.1 1.5 500 5 60 19 2.5
757031042 42:1 5040/8730GY 120 0.3 W,X,M,Y 1.1 1.5 500 8.7 75 26 2.5
757031060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757031063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757031066 66.4:1 7968/13800GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757031067 66.67:1 8000/13856GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757031070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757035020 20:1 2400/4160GY 120 0.3 W,X,M,Y 1.1 1.25 750 5 60 19 2.5
757035035 35:1 4200/7280GY 120 0.3 W,X,M,Y 1.1 1.25 750 5 60 19 2.5
757035040 40:1 4200/4200GY 120 0.3 W,X,M,Y 1.1 1.25 750 5 60 19 2.5
757035042 42:1 5040/8730GY 120 0.3 W,X,M,Y 1.1 1.25 750 8.7 75 26 2.5
757035060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757035063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757035066 66.4:1 7968/13800GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757035067 66.67:1 8000/13856GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757035070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
Without FUSE in the secondary box
757034020 20:1 2400/4160GY 120 0.3 W,X,M,Y 1.1 1.5 500 5 60 19 2.5
757034035 35:1 4200/7280GY 120 0.3 W,X,M,Y 1.1 1.5 500 5 60 19 2.5
757034040 40:1 4200/4200GY 120 0.3 W,X,M,Y 1.1 1.5 500 5 60 19 2.5
757034042 42:1 5040/8730GY 120 0.3 W,X,M,Y 1.1 1.5 500 8.7 75 26 2.5
757034060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757034063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757034066 66.4:1 7968/13800GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757034067 66.67:1 8000/13856GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757034070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.5 500 15 110 34 2.5
757030020 20:1 2400/4160GY 120 0.3 W,X,M,Y 1.1 1.25 750 5 60 19 2.5
757030035 35:1 4200/7280GY 120 0.3 W,X,M,Y 1.1 1.25 750 5 60 19 2.5
757030040 40:1 4200/4200GY 120 0.3 W,X,M,Y 1.1 1.25 750 5 60 19 2.5
757030042 42:1 5040/8730GY 120 0.3 W,X,M,Y 1.1 1.25 750 8.7 75 26 2.5
757030060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757030063 63.5:1 7620/13200GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757030066 66.4:1 7968/13800GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757030067 66.67:1 8000/13856GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757030070 70:1 8400/14550GY 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.6 (219)
19 (485)
H1
Lifting holes
3/4
2 holes to
conduit pipe
10 (254)
1 NPT
Drawing number:
Fused: 4286573
Unfused: 4286821
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
2400/4156GY 0.3 W,X/
757393060 20/60:1 120 1.1 1.5 1000 15 110 34 2.5
& 7200/12470GY 0.3 W,X,M,Y
0.3 W,X,M,Y/
757393113 66.26/112.88:1 7620/13200GY 115/67.5 1.1 1.5 1000 15 110 34 2.5
0.6 W,X,M,Y
2400/4156GY 0.3 W,X/
757396060 20/60:1 120 1.1 1.25 1500 15 110 34 2.5
& 7200/12470GY 0.3 W,X,M,Y
0.3 W,X,M,Y/
757396113 66.26/112.88:1 7620/13200GY 115/67.5 1.1 1.25 1500 15 110 34 2.5
0.6 W,X,M,Y
Without FUSE in the secondary box
2400/4156GY 0.3 W,X/
757394060 20/60:1 120 1.1 1.5 1000 15 110 34 2.5
& 7200/12470GY 0.3 W,X,M,Y
0.3 W,X,M,Y/
757394113 66.26/112.88:1 7620/13200GY 115/67.5 1.1 1.5 1000 15 110 34 2.5
0.6 W,X,M,Y
2400/4156GY 0.3 W,X/
757398060 20/60:1 120 1.1 1.25 1500 15 110 34 2.5
& 7200/12470GY 0.3 W,X,M,Y
0.3 W,X,M,Y/
757398113 66.26/112.88:1 7620/13200GY 115/67.5 1.1 1.25 1500 15 110 34 2.5
0.6 W,X,M,Y
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.62 (219)
17.71 (450)
H1 H2 Lifting holes
3/4
2 holes to
conduit pipe
1 NPT 10 (254)
Drawing number:
Fused: 4286571
Unfused: 4286770
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio) X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Code * Primary Secondary IEEE Metering Voltage BIL
Ratio Voltage Factor Burden
(CEP) (V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757121020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121030 30:1 3600/3600Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
8400/14550Y
757123121 70/121.21:1 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
& 14545/14545Y
757121100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757121120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757129070 70:1 8400/14550Y 120 0.15 W,X 1.1 1.25 1000 15 110 34 2.5
757129100 100:1 12000/12000Y 120 0.15 W,X 1.1 1.25 1000 15 110 34 2.5
757129110 110:1 13200/13200Y 120 0.15 W,X 1.1 1.25 1000 15 110 34 2.5
757129120 120:1 14400/14400Y 120 0.15 W,X 1.1 1.25 1000 15 110 34 2.5
757125020 20:1 2400/4160Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125030 30:1 3600/3600Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125035 35:1 4200/4200Y 120 0.3 W,X,M,Y.Z 1.1 1.25 1500 15 110 34 2.5
757125040 40:1 4800/4800Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125060 60:1 7200/12470Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125070 70:1 8400/14550Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
8400/14550Y
757126121 70/121.21:1 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
& 14545/14545Y
757125100 100:1 12000/12000Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125110 110:1 13200/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757125120 120:1 14400/14400Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757126070 70:1 8400/14550Y 120 0.15 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757126100 100:1 12000/12000Y 120 0.15 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757126110 110:1 13200/13200Y 120 0.15 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757126120 120:1 14400/14400Y 120 0.15 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Code * Primary Secondary IEEE Metering Voltage BIL
Ratio Voltage Factor Burden
(CEP) (V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
Without FUSE in the secondary box
757124020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124030 30:1 3600/3600Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757124120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757120020 20:1 2400/4160Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120030 30:1 3600/3600Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120035 35:1 4200/4200Y 120 0.3 W,X,M,Y.Z 1.1 1.25 1500 15 110 34 2.5
757120040 40:1 4800/4800Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120060 60:1 7200/12470Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120070 70:1 8400/14550Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120100 100:1 12000/12000Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120110 110:1 13200/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757120120 120:1 14400/14400Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.62 (219)
17.7 (450)
H1 H2
Lifting holes
3/4
2 holes to
conduit pipe
1 NPT 10 (254)
Drawing number:
Fused: 4286569
Unfused: 4286774
CONNEC-
TIONS
SINGLE SECONDARY
H1 H2 H1 H2
MARKING
(Single
Fuse: 16A
Primary
Ratio) X1 X2 X1 X2
FUSED UNFUSED
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757021020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021042 42:1 5040/5040Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021066 66:1 7920/13700Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021115 115:1 13800/13800Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757021120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757025020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025042 42:1 5040/5040Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025066 66:1 7920/13700Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025115 115:1 13800/13800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757025120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
Without FUSE in the secondary box
757024020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024042 42:1 5040/5040Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024066 66:1 7920/13700Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024115 115:1 13800/13800Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757024120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 750 15 110 34 2.5
757020020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020042 42:1 5040/5040Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020066 66:1 7920/13700Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020115 115:1 13800/13800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757020120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.6 (219)
19 (485)
H1 H2
Lifting holes
3/4
2 holes to
conduit pipe
1 NPT
10 (254)
Drawing number:
Fused: 4286575
Unfused: 4286822
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757101020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101030 30:1 3600/3600Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
8400/14550Y
757103121 70/121.2:1 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
& 14545/14545Y
757101100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757101120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757105020 20:1 2400/4160Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105030 30:1 3600/3600Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105035 35:1 4200/4200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105040 40:1 4800/4800Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105060 60:1 7200/12470Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105070 70:1 8400/14550Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
8400/14550Y
757106121 70/121.2:1 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
& 14545/14545Y
757105100 100:1 12000/12000Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105110 110:1 13200/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757105120 120:1 14400/14400Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
Without FUSE in the secondary box
757104020 20:1 2400/4160Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104030 30:1 3600/3600Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104035 35:1 4200/4200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104040 40:1 4800/4800Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104070 70:1 8400/14550Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104100 100:1 12000/12000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104110 110:1 13200/13200Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757104120 120:1 14400/14400Y 120 0.3 W,X,M,Y 1.1 1.25 1000 15 110 34 2.5
757100020 20:1 2400/4160Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100030 30:1 3600/3600Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100035 35:1 4200/4200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100040 40:1 4800/4800Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100060 60:1 7200/12470Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100063 63.5:1 7620/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100070 70:1 8400/14550Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100100 100:1 12000/12000Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100110 110:1 13200/13200Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
757100120 120:1 14400/14400Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1500 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number. Additional ratings available upon request.
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.62 (219)
21 (533.4)
Lifting holes
3/4
2 holes to
conduit pipe
10 (254)
1 NPT
Drawing number:
Fused: 4286593
Unfused: 4286823
CONNEC-
TIONS
SINGLE SECONDARY
H1 H2 H1 H2
MARKING
(Single
Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2
FUSED UNFUSED
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757071060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757071100 100:1 12000/20780GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757079100 100:1 12000/20780GY 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757071110 110:1 13200/22860GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757079110 110:1 13200/22863GY 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757071120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757079120 120:1 14400/24250GY 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757071150 150:1 18000/18000GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757079150 150:1 18000/18000GY 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757071200 200:1 24000 /24000GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757079200 200:1 24000 /24000GY 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
Without FUSE in the secondary box
757070060 60:1 7200/12470GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757070100 100:1 12000/20780GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757070110 110:1 13200/22860GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757070120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757070150 150:1 18000/18000GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757070200 200:1 24000 /24000GY 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.6 (219)
20.86 (530)
H1
Lifting holes
3/4
2 holes to
conduit pipe
10 (254)
1 NPT
Drawing number:
Fused: 4286576
Unfused: 4286772
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757441100 100:1 12000/20784GY 120 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757441110 110:1 13200/22863GY 120 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757441120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
7200/12470GY & 0.3 W,X /
757443120 60/120:1 120 1.1 1.5 1000 25 150 50 2.5
14400/24940GY 0.3W,X,M,Y
757443200 120/200:1 14400/24940GY 120/72 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757445100 100:1 12000/20784GY 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757445110 110:1 13200/22863GY 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757445120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
7200/12470GY & 0.3 W,X /
757446120 60/120:1 120 1.1 1.25 1500 25 150 50 2.5
14400/24940GY 0.3W,X,M,Y
757446200 120/200:1 14400/24940GY 120/72 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
Without FUSE in the secondary box
757444100 100:1 12000/20784GY 120 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757444110 110:1 13200/22863GY 120 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757444120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757444200 120/200:1 14400/24940GY 120/72 0.3 W,X,M,Y 1.1 1.5 1000 25 150 50 2.5
757440100 100:1 12000/20784GY 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757440110 110:1 13200/22863GY 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757440120 120:1 14400/24940GY 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757448200 120/200:1 14400/24940GY 120/72 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.62 (219)
20.27 (515)
2 holes to
conduit pipe
1 NPT 10 (254)
Drawing number:
Fused: 4286574
Unfused: 4286824
CONNEC-
TIONS
SINGLE SECONDARY
H1 H2 H1 H2
MARKING
(Single
Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2
FUSED UNFUSED
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757141060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757141100 100:1 12000/20780Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757149100 100:1 12000/20780Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757141110 110:1 13200/22860Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757149110 110:1 13200/22860Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757141120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757149120 120:1 14400/24250Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757141150 150:1 18000/18000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757149150 150:1 18000/18000Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757141200 200:1 24000 /24000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757149200 200:1 24000 /24000Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
Without FUSE in the secondary box
757140060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757140100 100:1 12000/20780Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757140110 110:1 13200/22860Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757140120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757140150 150:1 18000/18000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757140200 200:1 24000 /24000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
8.6 (219)
20.74 (527)
H1 H2 Lifting holes
3/4
2 holes to
conduit pipe
1 NPT 10 (254)
Drawing number:
Fused: 4286577
Unfused: 4286771
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757201060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
7200/12470Y & 0.3 W,X /
757203120 60/120:1 120 1.1 1.25 1000 25 150 50 2.5
14400/24940Y 0.3W,X,M,Y
757201100 100:1 12000/20780Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757201110 110:1 13200/22860Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757201120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
0.3 W,X,M,Y /
757203200 120/200:1 14400/24250Y 120/72 1.1 1.25 1000 25 150 50 2.5
0.3 W,X,M,Y
757201150 150:1 18000/18000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757201200 200:1 24000 /24000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757209100 100:1 12000/20780Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757209110 110:1 13200/22860Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757209120 120:1 14400/24250Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757209150 150:1 18000/18000Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757209200 200:1 24000 /24000Y 120 0.15 W,X 1.1 1.25 1000 25 150 50 2.5
757205060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
7200/12470Y & 0.3 W,X /
757206120 60/120:1 120 1.1 1.25 1500 25 150 50 2.5
14400/24940Y 0.3W,X,M,Y
757205100 100:1 12000/20780Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757205110 110:1 13200/22860Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757205120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
0.3 W,X,M,Y /
757206200 120/200:1 14400/24250Y 120/72 1.1 1.25 1500 25 150 50 2.5
0.3 W,X,M,Y
757205150 150:1 18000/18000Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757205200 200:1 24000 /24000Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757206100 100:1 12000/20780Y 120 0.15 W,X 1.1 1.25 1500 25 150 50 2.5
757206110 110:1 13200/22860Y 120 0.15 W,X 1.1 1.25 1500 25 150 50 2.5
757206150 150:1 18000/18000Y 120 0.15 W,X 1.1 1.25 1500 25 150 50 2.5
Without FUSE in the secondary box
757204060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757204100 100:1 12000/20780Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757204110 110:1 13200/22860Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757204120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757204150 150:1 18000/18000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757204200 200:1 24000/24000Y 120 0.3 W,X,M,Y 1.1 1.25 1000 25 150 50 2.5
757200060 60:1 7200/12470Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757200100 100:1 12000/20780Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757200110 110:1 13200/22860Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757200120 120:1 14400/24940Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757200150 150:1 18000/18000Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
757200200 200:1 24000/24000Y 120 0.3 W,X,M,Y 1.1 1.25 1500 25 150 50 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
9.4 (240)
M12
7.87 (200)
28.14 (714.75)
H1
Lifting holes
3/4
2 holes to
conduit pipe 13.7 (350)
1 NPT
Drawing number:
Fused: 4286578
Unfused: 4286773
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
757861140 140:1 16800/29098GY 120 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757863240 140/240:1 16100/27886GY 115/67.08 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757861166 166:1 19920/34500GY 120 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757861175 175:1 20125/34857GY 115 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757863300 175/300:1 20125/34857GY 115/67.08 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
Without FUSE in the secondary box
757860140 140:1 16800/29098GY 120 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757868240 140/240:1 16100/27886GY 115/67.08 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757860166 166:1 19920/34500GY 120 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757860175 175:1 20125/34857GY 115 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
757868300 175/300:1 20125/34857GY 115/67.08 0.3 W,X,M,Y 1.1 1.73 1000 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
7.87 (200)
27.36 (695)
Lifting holes
H1 H2 3/4
2 holes to
conduit pipe
13.7 (350)
1 NPT
Drawing number:
Fused: 4286579
Unfused: 4286825
CONNEC-
TIONS
H1 H2 H1 H2 H1 H2 H1 H2
MARKING
(Single
Fuse: 16A Fuse: 16A
Primary
Ratio)
X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
With FUSE in the secondary box
69.25 / 8310/14393Y &
757923166 120 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
166:1 19920/34500Y
757921140 140:1 16800/29098Y 120 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757923240 140/240:1 16100/27886Y 115/67.08 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757921166 166:1 19920/34500Y 120 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757921175 175:1 20125/34857Y 115 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757923300 175/300:1 20125/34857Y 115/67.08 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757921220 220:1 26400/26400Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1000 34.5 200 70 2.5
757923400 240/400:1 27600/27600Y 115 / 69 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757921300 300:1 34500/34500Y 115 0.3 W,X,M,Y,Z 1.1 1.25 1000 34.5 200 70 2.5
757923500 300/500:1 34500/34500Y 115/69 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757929140 140:1 16800/29098Y 120 0.15 W,X 1.1 1.25 1000 34.5 200 70 2.5
757929166 166:1 19920/34500Y 120 0.15 W,X 1.1 1.25 1000 34.5 200 70 2.5
757929175 175:1 20125/34500Y 115 0.15 W,X 1.1 1.25 1000 34.5 200 70 2.5
757929200 200:1 26400/26400Y 115 0.15 W,X 1.1 1.25 1000 34.5 200 70 2.5
757929300 300:1 34500/34500Y 115 0.15 W,X 1.1 1.25 1000 34.5 200 70 2.5
Without FUSE in the secondary box
69.25 / 8310/14393Y &
757928166 120 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
166:1 19920/34500Y
757920140 140:1 16800/29098Y 120 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757928240 140/240:1 16100/27886Y 115/67.08 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757920166 166:1 19920/34500Y 120 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757920175 175:1 20125/34857Y 115 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757928300 175/300:1 20125/34857Y 115/67.08 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757920220 220:1 26400/26400Y 120 0.3 W,X,M,Y,Z 1.1 1.25 1000 34.5 200 70 2.5
757928400 240/400:1 27600/27600Y 115 / 69 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
757920300 300:1 34500/34500Y 115 0.3 W,X,M,Y,Z 1.1 1.25 1000 34.5 200 70 2.5
757928500 300/500:1 34500/34500Y 115/69 0.3 W,X,M,Y 1.1 1.25 1000 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
17.12 (435)
M12
15.74 (400)
40.55 (1030)
H1
19.68 (500)
CONNEC-
TIONS
ONE TWO
ONE TWO
SECONDARY SECONDARIES
SECONDARY SECONDARIES
WITH TAP WITH TAP
MARKING H1 H2 H1 H2 H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Y1 Y2 Y1 Y2 Y3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Code * Primary Secondary IEEE Metering Voltage BIL
Ratio Voltage Factor Burden
(CEP) (V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
757971240 240:1 27600/47804GY 115 0.3 W,X,M,Y,Z,ZZ 1.1 1.73 2500 46 250 95 2.5
0.3 W,X,M,Y,Z 1250 &
757972240 240 & 240:1 27600/47804GY 115 & 115 1.1 1.73 46 250 95 2.5
& 0.3 W,X,M,Y,Z 1250
757973400 240/400:1 27600/47804GY 115/69 0.3 W,X,M,Y,Z 1.1 1.73 2500 46 250 95 2.5
757979240 240:1 27600/47804GY 115 0.15 W,X,M,Y,Z 1.1 1.73 2500 46 250 95 2.5
240/400 115/69 & 0.3 W,X,M,Y,Z 1250 &
757972400 27600/47804GY 1.1 1.73 46 250 95 2.5
& 240/400:1 115/69 & 0.3 W,X,M,Y,Z 1250
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
15.74 (400)
38.81 (986)
H1 H2
19.68 (500)
CONNEC-
TIONS
ONE TWO
ONE TWO
SECONDARY SECONDARIES
SECONDARY SECONDARIES
WITH TAP WITH TAP
MARKING H1 H2 H1 H2 H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Y1 Y2 Y1 Y2 Y3
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Code * Primary Secondary IEEE Metering Voltage BIL
Ratio Voltage Factor Burden
(CEP) (V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
757981240 240:1 27600/47804Y 115 0.3 W,X,M,Y,Z,ZZ 1.1 1.25 3000 46 250 95 2.5
0.3 W,X,M,Y,Z & 1500 &
757982240 240 & 240:1 27600/47804Y 115 & 115 1.1 1.25 46 250 95 2.5
0.3 W,X,M,Y,Z 1500
757983400 240/400:1 27600/47804Y 115/69 0.3 W,X,M,Y,Z 1.1 1.25 3000 46 250 95 2.5
757981400 400:1 46000/46000Y 115 0.3 W,X,M,Y,Z,ZZ 1.1 1.25 3000 46 250 95 2.5
0.3 W,X,M,Y,Z & 1500 &
757982400 400 & 400:1 46000/46000Y 115 & 115 1.1 1.25 46 250 95 2.5
0.3 W,X,M,Y,Z 1500
757983666 400/666.66:1 46000/46000Y 115/69 0.3 W,X,M,Y,Z 1.1 1.25 3000 46 250 95 2.5
757989240 240:1 27600/47804Y 115 0.15 W,X,M,Y,Z 1.1 1.25 3000 46 250 95 2.5
757986400 240/400:1 27600/47804Y 115/69 0.15 W,X,M,Y 1.1 1.25 3000 46 250 95 2.5
757989400 400:1 46000/46000Y 115 0.15 W,X,M,Y,Z 1.1 1.25 3000 46 250 95 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Connector
TE-250
15.74 (400)
48.34 (1228)
Lifting holes
3/4
H1
2 holes to
conduit pipe
1 NPT Nameplate 19.68 (500)
MARKING H1 H2 H1 H2 H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Y1 Y2 Y1 Y2 Y3
Type: Quick Connector
Material: Brass
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
IEEE Rated Voltage Thermal (1 min)
Code * Primary Secondary Voltage BIL
Ratio Metering Voltage Factor Burden
(CEP) (V) (V) System (kV) Primary & Secondary
Accuracy Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
40250/
757551350 350:1 115 0.3 W,X,M,Y,ZZ 1.1 1.73 2500 69 350 140 2.5
69000GY
40250/
757553600 350/600:1 115/67.08 0.3 W,X,M,Y,Z 1.1 1.73 2500 69 350 140 2.5
69000GY
350/600 40250/ 115/67.08 & 0.3 W,X,M,Y,Z &
757552600 1.1 1.73 1250 & 1250 69 350 140 2.5
&350/600:1 69000GY 115/67.08 0.3 W,X,M,Y,Z
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE UR/VR series are dry type outdoor service voltage transformers.
The core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer of
Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays and the
effects of tracking and erosion on the exterior of the transformer ensuring a
long mechanical and electrical life. The transformer is maintenance free.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
15.75 (400)
43.88 (1114.5)
19.69 (500)
MARKING H1 H2 H1 H2 H1 H2 H1 H2
(Single
Primary
Ratio) X1 X2 X1 X2 X1 X2 X3 X1 X2 X3
Y1 Y2 Y1 Y2 Y3
Type: Quick Connector
Material: Brass
Approximate dimensions in inches (mm). * Brown color available upon request
Electrical characteristics
Power-Frequency
Continuous Rated Withstand Voltage
Nominal
Rated Voltage Thermal (1 min)
Code * Primary Secondary IEEE Metering Voltage BIL
Ratio Voltage Factor Burden
(CEP) (V) (V) Accuracy System (kV) Primary & Secondary
Factor 30 s (VA)
(kV) Secondary Winding
(Un) (Un)
(kVrms) (kVrms)
757561600 600:1 69000/69000Y 115 0.3 W,X,M,X,Y,Z,ZZ 1.1 1.73 4000 69 350 140 2.5
350/600 & 40250/69000Y or 197/115 & 0.3 W,X,M,X,Y,Z & 2000 &
757563600 1.1 1.73 69 350 140 2.5
350/600:1 69000/69000Y 115/67.08 0.3 W,X,M,X,Y,Z 2000
600/1039 & 115/66.4 & 0.3 W,X,M,X,Y,Z & 2000 &
757563103 69000/69000Y 1.1 1.73 69 350 140 2.5
350/600:1 197/115 0.3 W,X,M,X,Y,Z 2000
600 & 0.3 W,X,M,X,Y,Z & 2000 &
757562600 69000/69000Y 115 & 115 1.1 1.73 69 350 140 2.5
600:1 0.3 W,X,M,X,Y,Z 2000
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
CR Series are dry type outdoor service current transformers. The core is
encapsulated with Type B epoxy resin for excellence in internal dielectric
properties and mechanical strength. The external layer of Cycloaliphatic
resin provides resistance to ultraviolet rays and the effects of tracking and
erosion on the exterior of the module. The device is maintenance free,
ensuring a long mechanical and electrical life.
OUTDOOR
60 Hertz The core is built with silicon steel lamination. The blade is high permeability
grain oriented Type for low losses. The windings are copper wire with
copper plate double isolation. The concentric distribution of the coils
prevents magnetic ux leakage, achieving greater accuracy and higher
capacity to withstand mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray 43 13.3 3
9.37 (238)
2 x 8.5 (2 x 216)
2 x 6.83 (2 x 173)
12.4 (315)
7.87 (2 x 200)
Terminal box
Two holes to
9.38 (238) conduit pipe
A1 - NPT
10.5 (267) Drawing number: 4287594
11 (279)
H1 H2
/4
1
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-2 Type: TE-12-250 Type: Quick Connector
Material: Copper Material: Copper Material: Brass
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short- Highest
Thermal (1 min)
Ratio time time IEEE Nominal
Current Relay BIL
Code * (CEP) (Primary: Thermal Mechanical Metering Voltage
Rating Accuracy (kV) Primary & Secondary
Secondary) Current Current Accuracy System
Factor @ Secondary Winding
(A) (kA/1s) (kApeak) (kV)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 48.5 16.5 8
10.63 (270)
8.62 (219)
H1 H2
15.35 (390)
H1 H2
/4
1
MARKING
CONNEC- (Single X1 X2
TIONS Primary
Ratio)
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Shorting Link
756204001 5:5 3.0 0.5 1.25 0.3 B-0.5 - 15 110 34 2.5
756204002 10:5 3.0 1 2.5 0.3 B-0.5 - 15 110 34 2.5
756204003 15:5 3.0 1.5 3.75 0.3 B-0.5 - 15 110 34 2.5
756204004 20:5 3.0 2 5 0.3 B-0.5 - 15 110 34 2.5
756204005 25:5 3.0 2.5 6.25 0.3 B-0.5 - 15 110 34 2.5
756204006 30:5 3.0 3 7.5 0.3 B-0.5 - 15 110 34 2.5
756204008 40:5 3.0 4 10 0.3 B-0.5 - 15 110 34 2.5
756204010 50:5 3.0 5 12.5 0.3 B-0.5 - 15 110 34 2.5
756204015 75:5 3.0 7.5 18.75 0.3 B-0.5 - 15 110 34 2.5
756204020 100:5 3.0 10 25 0.3 B-0.5 - 15 110 34 2.5
756204030 150:5 3.0 15 37.5 0.3 B-0.5 - 15 110 34 2.5
756204040 200:5 3.0 20 50 0.3 B-0.5 - 15 110 34 2.5
756204060 300:5 3.0 30 75 0.3 B-0.5 - 15 110 34 2.5
756204080 400:5 3.0 40 100 0.3 B-0.5 - 15 110 34 2.5
756204120 600:5 2.0 60 150 0.3 B-0.5 - 15 110 34 2.5
756204160 800:5 1.5 60 150 0.3 B-0.5 - 15 110 34 2.5
756204200 1000:5 1.0 75 127.5 0.3 B-0.5 - 15 110 34 2.5
756204240 1200:5 1.0 90 162 0.3 B-0.5 - 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 68.3 16.5 8
12.05 (306)
8.62 (219)
H1 H2
15.35 (390)
10 (254)
Drawing number: 9448985
H1 H2
/4
1
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-2 Type: TE-12-250 Type: Quick Connector
Material: Copper Material: Copper Material: Brass
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
756231001 5:5 1.5 0.5 0.95 0.3 B-1.8 T150 15 110 34 2.5
756231002 10:5 1.5 1 1.9 0.3 B-1.8 T150 15 110 34 2.5
756231003 15:5 1.5 1.5 2.85 0.3 B-1.8 T150 15 110 34 2.5
756231004 20:5 1.5 2 3.8 0.3 B-1.8 T150 15 110 34 2.5
756231005 25:5 1.5 2.5 4.75 0.3 B-1.8 T150 15 110 34 2.5
756231006 30:5 1.5 3 5.7 0.3 B-1.8 T150 15 110 34 2.5
756231008 40:5 1.5 4 7.6 0.3 B-1.8 T150 15 110 34 2.5
756231010 50:5 1.5 5 9.5 0.3 B-1.8 T150 15 110 34 2.5
756231012 60:5 1.5 6 11.4 0.3 B-1.8 T150 15 110 34 2.5
756231015 75:5 1.5 7.5 14.25 0.3 B-1.8 T150 15 110 34 2.5
756231020 100:5 1.5 10 19 0.3 B-1.8 T150 15 110 34 2.5
756231030 150:5 1.5 15 28.5 0.3 B-1.8 T150 15 110 34 2.5
756231040 200:5 1.5 20 38 0.3 B-1.8 T150 15 110 34 2.5
756231060 300:5 1.5 30 57 0.3 B-1.8 T150 15 110 34 2.5
756231080 400:5 1.5 40 76 0.3 B-1.8 T150 15 110 34 2.5
756231120 600:5 1.5 60 86.7 0.3 B-1.8 T150 15 110 34 2.5
756231160 800:5 1.5 60 114 0.3 B-1.8 T150 15 110 34 2.5
756231200 1000:5 1.2 75 142.5 0.3 B-1.8 T150 15 110 34 2.5
756231240 1200:5 1.0 90 171 0.3 B-1.8 T150 15 110 34 2.5
756232002 10/20:5 2.0/1.5 2 3.8 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232005 25/50:5 2.0/1.5 5 9.5 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232006 30/60:5 2.0/1.5 6 11.4 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232010 50/100:5 2.0/1.5 10 19 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232015 75/150:5 2.0/1.5 15 28.5 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232020 100/200:5 2.0/1.5 20 38 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232030 150:300:5 2.0/1.5 30 57 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232040 200/400:5 2.0/1.5 40 76 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232060 300/600:5 2.0/1.5 60 86.7 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232080 400/800:5 1.2/1.2 60 114 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232100 500/1000:5 1.0/1.0 75 142.5 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756232120 600/1200:5 1.0/1.0 90 171 0.3B-0.5/0.3B-1.8 T75/T150 15 110 34 2.5
756239001 5:5 1.5 0.5 0.95 0.15B-0.9 - 15 110 34 2.5
756239002 10:5 1.5 1 1.9 0.15B-0.9 - 15 110 34 2.5
756239010 50:5 1.5 5 9.5 0.15B-0.9 - 15 110 34 2.5
756239015 75:5 1.5 7.5 14.25 0.15B-0.9 - 15 110 34 2.5
756239020 100:5 1.5 10 19 0.15B-0.9 - 15 110 34 2.5
756239120 600:5 1.5 60 86.7 0.15B-0.9 - 15 110 34 2.5
756239160 800:5 1.5 60 114 0.15B-0.9 - 15 110 34 2.5
756239200 1000:5 1.2 75 142.5 0.15B-0.9 - 15 110 34 2.5
756239240 1200:5 1.0 90 171 0.15B-0.9 - 15 110 34 2.5
756238001 5/10:5 2.0/1.5 1 1.9 0.15B-0.5/0.15B0.09 - 15 110 34 2.5
756238002 10/20:5 2.0/1.5 2 3.8 0.15B-0.5/0.15B0.09 - 15 110 34 2.5
756238060 300/600:5 2.0/1.5 60 86.7 0.15B-0.5/0.15B0.09 - 15 110 34 2.5
756238080 400/800:5 1.2/1.2 60 114 0.15B-0.5/0.15B0.09 - 15 110 34 2.5
756238100 500/1000:5 1.0/1.0 75 142.5 0.15B-0.5/0.15B0.09 - 15 110 34 2.5
756238120 600/1200:5 1.0/1.0 90 171 0.15B-0.5/0.15B0.09 - 15 110 34 2.5
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Shorting Link
756234001 5:5 1.5 0.5 0.95 0.3 B-1.8 T150 15 110 34 2.5
756234002 10:5 1.5 1 1.9 0.3 B-1.8 T150 15 110 34 2.5
756234003 15:5 1.5 1.5 2.85 0.3 B-1.8 T150 15 110 34 2.5
756234004 20:5 1.5 2 3.8 0.3 B-1.8 T150 15 110 34 2.5
756234005 25:5 1.5 2.5 4.75 0.3 B-1.8 T150 15 110 34 2.5
756234006 30:5 1.5 3 5.7 0.3 B-1.8 T150 15 110 34 2.5
756234008 40:5 1.5 4 7.6 0.3 B-1.8 T150 15 110 34 2.5
756234010 50:5 1.5 5 9.5 0.3 B-1.8 T150 15 110 34 2.5
756234012 60:5 1.5 6 11.4 0.3 B-1.8 T150 15 110 34 2.5
756234015 75:5 1.5 7.5 14.25 0.3 B-1.8 T150 15 110 34 2.5
756234020 100:5 1.5 10 19 0.3 B-1.8 T150 15 110 34 2.5
756234030 150:5 1.5 15 28.5 0.3 B-1.8 T150 15 110 34 2.5
756234040 200:5 1.5 20 38 0.3 B-1.8 T150 15 110 34 2.5
756234060 300:5 1.5 30 57 0.3 B-1.8 T150 15 110 34 2.5
756234080 400:5 1.5 40 76 0.3 B-1.8 T150 15 110 34 2.5
756234120 600:5 1.5 60 86.7 0.3 B-1.8 T150 15 110 34 2.5
756234160 800:5 1.5 60 114 0.3 B-1.8 T150 15 110 34 2.5
756234200 1000:5 1.2 75 142.5 0.3 B-1.8 T150 15 110 34 2.5
756234240 1200:5 1.0 90 171 0.3 B-1.8 T150 15 110 34 2.5
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 112.4 27.55 12
13,70 (348)
8.62 (219)
H1 H2
17.2 (437)
Lifting holes
3/4 (19)
H1 H2
4
/
1
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-2 Type: NEMA-4 Type: TE-12-250 Type: Quick Connector
Material: Copper Material: Copper Material: Copper Material: Brass
** Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Notes:
O
OUTDOOR The external layer can be manufactured with Hydrophobic Cycloaliphatic
60 Hertz
6 Epoxy Resin (HCEP) which improves service life expectancy due to its
improved tracking and erosion resistance. HCEP additionally increases
the transformers weatherability and offers better performance in heavily
polluted environments.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical
Mec
chan
hanical characteristics
Insulation Material Colors
C Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray*
G 78.2 24.4 10
12.05 (306)
H1 H2
8.62 (219)
18.11 (460)
H1 H2
/4
1
MARKING
CONNEC- (Single X1 X2
TIONS Primary
Ratio)
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 112.4 27.55 12
13,70 (348)
8.62 (219)
H1 H2
17.2 (437)
Lifting holes
3/4 (19)
H1 H2
4
/
1
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-2 Type: NEMA-4 Type: TE-12-250 Type: Quick Connector
Material: Copper Material: Copper Material: Copper Material: Brass
** Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions. The cores
and windings are located in the upper part of the transformer. This head is
coated with a conductive layer, which provides an adequate electric eld
control.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 550 37.6 11
H2 H1
13.77 (350)
40 (1016)
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: PM30MC0-1-4N-E Type: LZ-500 Type: Hex screw
Material: Aluminum Material: Copper Material: Steel
Range: 4/OTRE-500MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
756151001 5:5 2,0 0.5 0.95 0.3B-1.8 T-400 34.5 200 70 2.5
756151002 10:5 2,0 1 1.9 0.3B-1.8 T-400 34.5 200 70 2.5
756151003 15:5 2,0 1.5 2.85 0.3B-1.8 T-400 34.5 200 70 2.5
756151004 20:5 2,0 2 3.8 0.3B-1.8 T-400 34.5 200 70 2.5
756151005 25:5 2,0 2.5 4.75 0.3B-1.8 T-400 34.5 200 70 2.5
756151006 30:5 2,0 3 5.7 0.3B-1.8 T-400 34.5 200 70 2.5
756151008 40:5 2,0 4 7.6 0.3B-1.8 T-400 34.5 200 70 2.5
756151010 50:5 2,0 5 9.5 0.3B-1.8 T-400 34.5 200 70 2.5
756151015 75:5 2,0 6 11.4 0.3B-1.8 T-400 34.5 200 70 2.5
756151020 100:5 2,0 7.5 14.25 0.3B-1.8 T-400 34.5 200 70 2.5
756151030 150:5 2,0 10 19 0.3B-1.8 T-400 34.5 200 70 2.5
756151040 200:5 2,0 20 38 0.3B-1.8 T-400 34.5 200 70 2.5
756151060 300:5 2,0 30 57 0.3B-1.8 T-400 34.5 200 70 2.5
756151080 400:5 2,0 40 76 0.3B-1.8 T-400 34.5 200 70 2.5
756151120 600:5 2,0 50 9.5 0.3B-1.8 T-400 34.5 200 70 2.5
756151160 800:5 2,0 60 86.7 0.3B-1.8 T-400 34.5 200 70 2.5
756151200 1000:5 1.5 60 114 0.3B-1.8 T-400 34.5 200 70 2.5
756151240 1200:5 1.5 75 142.5 0.3B-1.8 T-400 34.5 200 70 2.5
756151400 2000:5 1.2 90 171 0.3B-1.8 T-800 34.5 200 70 2.5
756152001 10/20:5 3.0/2.0 2 3.8 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152005 25/50:5 3.0/2.0 5 9.5 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152006 30/60:5 3.0/2.0 6 11.4 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152010 50/100:5 3.0/2.0 10 19 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152015 75/150:5 3.0/2.0 15 28.5 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152020 100/200:5 3.0/2.0 20 38 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152030 150/300:5 3.0/2.0 30 57 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152040 200/400:5 3.0/2.0 40 76 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152060 300/600:5 3.0/2.0 60 86.7 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152080 400/800:5 3.0/2.0 60 114 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152100 500/1000:5 3.0/1.5 75 142.5 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152120 600/1200:5 3.0/1.5 90 171 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152150 750/1500:5 3.0/1.5 90 171 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756152200 1000/2000:5 2.4/1.2 90 171 0.3B-1.8/0.3B1.8 T400/T800 34.5 200 70 2.5
756152300 1500/3000:5 2.4/1.2 90 171 0.3B-1.8/0.3B1.8 T400/T800 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 134.4 36.2 15
13.7 (348)
8.62 (219)
19.5 (495)
H1 H2
/4
1
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-2 Type: TE-12-250 Type: Quick Connector
Material: Copper Material: Copper Material: Brass
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
756273001 5:5 3.0 0.5 1.25 0.3B-1.8 T100 34.5 200 70 2.5
756273002 10:5 3.0 1 2.5 0.3B-1.8 T100 34.5 200 70 2.5
756273003 15:5 3.0 1.5 3.75 0.3B-1.8 T100 34.5 200 70 2.5
756273004 20:5 3.0 2 5 0.3B-1.8 T100 34.5 200 70 2.5
756273005 25:5 3.0 2.5 6.25 0.3B-1.8 T100 34.5 200 70 2.5
756273006 30:5 3.0 3 7.5 0.3B-1.8 T100 34.5 200 70 2.5
756273008 40:5 3.0 4 10 0.3B-1.8 T100 34.5 200 70 2.5
756273010 50:5 3.0 5 12.5 0.3B-1.8 T100 34.5 200 70 2.5
756273015 75:5 3.0 7.5 18.75 0.3B-1.8 T100 34.5 200 70 2.5
756273020 100:5 3.0 10 25 0.3B-1.8 T100 34.5 200 70 2.5
756273030 150:5 3.0 15 37.5 0.3B-1.8 T100 34.5 200 70 2.5
756273040 200:5 3.0 20 50 0.3B-1.8 T100 34.5 200 70 2.5
756273060 300:5 3.0 30 75 0.3B-1.8 T100 34.5 200 70 2.5
756273080 400:5 3.0 40 100 0.3B-1.8 T100 34.5 200 70 2.5
756273120 600:5 2.0 60 150 0.3B-1.8 T100 34.5 200 70 2.5
756273160 800:5 1.5 60 150 0.3B-1.8 T100 34.5 200 70 2.5
756273200 1000:5 1.0 75 127.5 0.3B-1.8 T100 34.5 200 70 2.5
756273240 1200:5 1.0 90 162 0.3B-1.8 T100 34.5 200 70 2.5
756271001 5:5 1.5 0.5 0.95 0.3B-1.8 T200 34.5 200 70 2.5
756271002 10:5 1.5 1 1.9 0.3B-1.8 T200 34.5 200 70 2.5
756271003 15:5 1.5 1.5 2.85 0.3B-1.8 T200 34.5 200 70 2.5
756271004 20:5 1.5 2 3.8 0.3B-1.8 T200 34.5 200 70 2.5
756271005 25:5 1.5 2.5 4.75 0.3B-1.8 T200 34.5 200 70 2.5
756271006 30:5 1.5 3 5.7 0.3B-1.8 T200 34.5 200 70 2.5
756271008 40:5 1.5 4 7.6 0.3B-1.8 T200 34.5 200 70 2.5
756271010 50:5 1.5 5 9.5 0.3B-1.8 T200 34.5 200 70 2.5
756271012 60:5 1.5 6 11.4 0.3B-1.8 T200 34.5 200 70 2.5
756271015 75:5 1.5 7.5 14.25 0.3B-1.8 T200 34.5 200 70 2.5
756271020 100:5 1.5 10 19 0.3B-1.8 T200 34.5 200 70 2.5
756271040 200:5 1.5 20 38 0.3B-1.8 T200 34.5 200 70 2.5
756271060 300:5 1.5 30 57 0.3B-1.8 T200 34.5 200 70 2.5
756271080 400:5 1.5 40 76 0.3B-1.8 T200 34.5 200 70 2.5
756271100 500:5 1.5 50 9.5 0.3B-1.8 T200 34.5 200 70 2.5
756271120 600:5 1.2 60 86.7 0.3B-1.8 T200 34.5 200 70 2.5
756271160 800:5 1.0 60 114 0.3B-1.8 T200 34.5 200 70 2.5
756271200 1000:5 1.0 75 142.5 0.3B-1.8 T200 34.5 200 70 2.5
756271240 1200:5 1.0 90 171 0.3B-1.8 T200 34.5 200 70 2.5
756272002 10/20:5 2.0/1.5 2 3.8 0.3B-0.9/0.3B-1.8 T100/T200 34.5 200 70 2.5
756272005 25/50:5 2.0/1.5 5 9.5 0.3B-0.9/0.3B-1.8 T100/T200 34.5 200 70 2.5
756272006 30/60:5 2.0/1.5 6 11.4 0.3B-0.9/0.3B-1.8 T100/T200 34.5 200 70 2.5
756272010 50/100:5 2.0/1.5 10 19 0.3B-0.9/0.3B-1.8 T100/T200 34.5 200 70 2.5
756272015 75/150:5 2.0/1.5 15 28.5 0.3B-0.9/0.3B-1.8 T100/T200 34.5 200 70 2.5
756272020 100/200:5 2.0/1.5 20 38 0.3B-0.9/0.3B-1.8 T100/T200 34.5 200 70 2.5
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 253.5 47.83 19.3
15.31 (388.87)
Nameplate
24.68 (626.8)
9.84 (250)
Lifting holes
Secondary
1 hole 9/16 to 2 holes 1
terminals
ground connector to conduit
pipe NPT
9.84 (250)
Drawing number: 4286121
H1 H2
4
/
1
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
1500 A 2000 A
H1 H2
Type: NEMA-4 Type: LZ-250 Type: Quick Connector
Material: Copper Material: Copper Material: Brass
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
756861001 5:5 2.0 0.5 0.95 0.3B-1.8 T200 34.5 200 70 2.5
756861002 10:5 2.0 1 1.9 0.3B-1.8 T200 34.5 200 70 2.5
756861003 15:5 2.0 1.5 2.85 0.3B-1.8 T200 34.5 200 70 2.5
756861004 20:5 2.0 2 3.8 0.3B-1.8 T200 34.5 200 70 2.5
756861005 25:5 2.0 2.5 4.75 0.3B-1.8 T200 34.5 200 70 2.5
756861006 30:5 2.0 3 5.7 0.3B-1.8 T200 34.5 200 70 2.5
756861008 40:5 2.0 4 7.6 0.3B-1.8 T200 34.5 200 70 2.5
756861010 50:5 2.0 5 9.5 0.3B-1.8 T200 34.5 200 70 2.5
756861015 75:5 2.0 6 11.4 0.3B-1.8 T200 34.5 200 70 2.5
756861020 100:5 2.0 7.5 14.25 0.3B-1.8 T200 34.5 200 70 2.5
756861030 150:5 2.0 10 19 0.3B-1.8 T200 34.5 200 70 2.5
756861040 200:5 2.0 20 38 0.3B-1.8 T200 34.5 200 70 2.5
756861060 300:5 2.0 30 57 0.3B-1.8 T200 34.5 200 70 2.5
756861080 400:5 2.0 40 76 0.3B-1.8 T200 34.5 200 70 2.5
756861100 500:5 2.0 50 9.5 0.3B-1.8 T200 34.5 200 70 2.5
756861120 600:5 2.0 60 86.7 0.3B-1.8 T200 34.5 200 70 2.5
756861160 800:5 2.0 60 114 0.3B-1.8 T200 34.5 200 70 2.5
756861200 1000:5 1.5 75 142.5 0.3B-1.8 T200 34.5 200 70 2.5
756861240 1200:5 1.5 90 171 0.3B-1.8 T200 34.5 200 70 2.5
756862002 10/20:5 3.0/2.0 2 3.8 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862005 25/50:5 3.0/2.0 5 9.5 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862006 30/60:5 3.0/2.0 6 11.4 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862010 50/100:5 3.0/2.0 10 19 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862015 75/150:5 3.0/2.0 15 28.5 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862020 100/200:5 3.0/2.0 20 38 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862030 150/300:5 3.0/2.0 30 57 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862040 200/400:5 3.0/2.0 40 76 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862030 300/600:5 3.0/2.0 60 86.7 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862030 400/800:5 3.0/2.0 60 114 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862030 500/1000:5 3.0/1.5 75 142.5 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
756862030 600/1200:5 3.0/1.5 90 171 0.3B-1.8/0.3B1.8 T100/T200 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 322 44.68 13.8
13.77 (350)
22.04 (562.32)
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
1500 A 2000 A
H1 H2
Type: NEMA-4 Type: LZ-250 Type: Hex screw
Material: Copper Material: Copper Material: Steel
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak))
30C (kVrms) (kVrms)
756911001 5:5 1.5 0.5 0.95 0.3B-1.8 T400 34.5 200 70 2.5
756911002 10:5 1.5 1 1.9 0.3B-1.8 T400 34.5 200 70 2.5
756911003 15:5 1.5 1.5 2.85 0.3B-1.8 T400 34.5 200 70 2.5
756911004 20:5 1.5 2 3.8 0.3B-1.8 T400 34.5 200 70 2.5
756911005 25:5 1.5 2.5 4.75 0.3B-1.8 T400 34.5 200 70 2.5
756911006 30:5 1.5 3 5.7 0.3B-1.8 T400 34.5 200 70 2.5
756911008 40:5 1.5 4 7.6 0.3B-1.8 T400 34.5 200 70 2.5
756911010 50:5 1.5 5 9.5 0.3B-1.8 T400 34.5 200 70 2.5
756911015 75:5 1.5 6 11.4 0.3B-1.8 T400 34.5 200 70 2.5
756911020 100:5 1.5 7.5 14.25 0.3B-1.8 T400 34.5 200 70 2.5
756911030 150:5 1.5 10 19 0.3B-1.8 T400 34.5 200 70 2.5
756911040 200:5 1.5 20 38 0.3B-1.8 T400 34.5 200 70 2.5
756911060 300:5 1.5 30 57 0.3B-1.8 T400 34.5 200 70 2.5
756911080 400:5 1.5 40 76 0.3B-1.8 T400 34.5 200 70 2.5
756911100 500:5 1.5 50 9.5 0.3B-1.8 T400 34.5 200 70 2.5
756911120 600:5 1.5 60 86.7 0.3B-1.8 T400 34.5 200 70 2.5
756911160 800:5 1.5 60 114 0.3B-1.8 T400 34.5 200 70 2.5
756911200 1000:5 1.5 75 142.5 0.3B-1.8 T400 34.5 200 70 2.5
756911240 1200:5 1.5 90 171 0.3B-1.8 T400 34.5 200 70 2.5
756911400 2000:5 1.2 90 171 0.3B-1.8 T400 34.5 200 70 2.5
756911500 2500:5 1.2 90 171 0.3B-1.8 T400 34.5 200 70 2.5
756912002 10/20:5 3.0/1.5 2 3.8 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912005 25/50:5 3.0/1.5 5 9.5 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912006 30/60:5 3.0/1.5 6 11.4 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912010 50/100:5 3.0/1.5 10 19 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912015 75/150:5 3.0/1.5 15 28.5 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912020 100/200:5 3.0/1.5 20 38 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912030 150/300:5 3.0/1.5 30 57 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912040 200/400:5 3.0/1.5 40 76 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912060 300/600:5 3.0/1.5 60 86.7 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912080 400/800:5 3.0/1.5 60 114 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912100 500/1000:5 3.0/1.5 75 142.5 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912120 600/1200:5 3.0/1.5 90 171 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912150 750/1500:5 3.0/1.5 90 171 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
756912200 1000/2000:5 2.4/1.2 90 171 0.3B-1.8/0.3B1.8 T200/T400 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions. The cores
and windings are located in the upper part of the transformer. This head is
coated with a conductive layer, which provides an adequate electric eld
control.
H2 H1 (4)9/16 (14.2)
9.84 (250)
51.18 (1300)
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: PM30MC0-1-4N-E Type: LZ-500 Type: Hex screw
Material: Aluminum Material: Copper Material: Steel
Range: 4/OTRE-500MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
15.31 (385)
Nameplate
9.84 (250)
24.68 (626.87)
Lifting holes
Terminal secondary
box with NPT 1
Hole 9/16 to ground
Quick Connector
connection
9.84 (250)
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-4 Type: LZ-250 Type: Hex screw
Material: Copper Material: Copper Material: Steel
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
13.77 (350)
28.20 (716.20)
Lifting holes
Secondary
1 Hole 9/16 to 2 Holes 1
terminals
ground connector to conduit
pipe NPT
13.77 (350)
Nameplate
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
1500 A 2000 A
H1 H2
Type: NEMA-4 Type: LZ-250 Type: Hex screw
Material: Copper Material: Copper Material: Steel
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
magnetic ux leakage, achieving greater accuracy and higher capacity to
withstand mechanical stresses in adverse operating conditions. The cores
and windings are located in the upper part of the transformer. This head is
coated with a conductive layer, which provides an adequate electric eld
control.
H2 H1
13.78 (350)
62 (1576)
13.78 (350)
Terminal
Ground
box
connector
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: PM30MC0-1-4N-E Type: LZ-500 Type: Hex screw
Material: Aluminum Material: Copper Material: Steel
Range: 4/OTRE-500MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
9.84 (250)
30.7 (780)
Hole 9/16
to ground Terminal
connection Lifting holes secondary box
3/4 with 1 NPT 9.84 (250)
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
H1 H2
Type: NEMA-4 Type: LZ-250 Type: Hex screw
Material: Copper Material: Copper Material: Steel
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
13.77 (350)
34.44 (875.05)
Lifting holes
H1 H2
MARKING X1 X2
CONNEC- (Single
TIONS Primary
ONE SECONDARY with tap
Ratio)
1500 A 2000 A
H1 H2
Type: NEMA-4 Type: LZ-250 Type: Hex screw
Material: Copper Material: Copper Material: Steel
Range: 4TRE-250MCM X1 X2 Xn
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Code * Current IEEE Metering Relay Voltage BIL
(Primary: Thermal Mechanical
(CEP) Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30C (kVrms) (kVrms)
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
Notes:
ARTECHE KM series are dry type outdoor service combination CT-PT. The
core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer
of Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays
and the effects of tracking and erosion on the exterior of the transformer
ensuring a long mechanical and electrical life. The transformer is
maintenance free.
OUTDOOR
60 Hertz The external layer can be manufactured with Hydrophobic Cycloaliphatic
Epoxy Resin (HCEP) which improves service life expectancy due to its
improved tracking and erosion resistance. HCEP additionally increases
the transformers weatherability and offers better performance in heavily
polluted environments.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 209 23.7 13
14 (356) Nameplate
13 (330)
22 (559)
H1 H2
/4
1
C1 C2
H0
MARKING
V1 V2
CONNEC- (Single
Type: NEMA-2 Type: TE-12 250 Type: Quick Connector
TIONS Material: Copper Material: Copper Material: Brass Primary ONE SECONDARY
Range: 4TRE-250MCM Ratio) with tap
H1 H2
C1 C2 C3
H0
V1 V2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Code * Ratio Current Accuracy Voltage BIL
Thermal Mechanical Accuracy
(CEP) (Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770083011 5:5 3.0 0,5 1.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083021 10:5 3.0 1 2.7 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083031 15:5 3.0 1.5 4.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083041 20:5 3.0 2 5.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083051 25:5 3.0 2.5 6.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083061 30:5 3.0 3 8.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083071 40:5 3.0 4 10.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083081 50:5 3.0 5 13.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083091 75:5 3.0 7.5 20.3 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083101 100:5 3.0 10 27 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083111 150:5 3.0 15 40.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083121 200:5 3.0 20 54 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083131 300:5 3.0 30 81 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083141 400:5 3.0 40 108 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083151 600:5 2.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083161 800:5 1.5 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083171 1000:5 1.2 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083181 1200:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084041 10/20:5 2.0/1.5 2 5 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084081 25/50:5 2.0/1.5 5 12.5 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084121 100/200:5 2.0/1.5 20 50 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084151 300/600:5 2.0/1.5 60 150 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084161 400/800:5 2.0/1.5 60 150 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770083161 400/800:5 3.0/1.5 60 150 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084171 500/1000:5 2.0/1.2 75 127.5 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770084181 600/1200:5 2.0/1.0 90 162 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6 Z 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
32.1 (815)
L3 H1 H2
L2 H1 H2
L1 H1 H2
H1 H2 H1 H2 H1 H2
X1 X2 X1 X2 X1 X2
1 2 3 4 5 6 7 8 9 10
/4
1
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Code * Ratio Current Accuracy Voltage BIL
Thermal Mechanical Accuracy
(CEP) (Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770663011 5:5 3.0 0,5 1.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663021 10:5 3.0 1 2.7 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663031 15:5 3.0 1.5 4.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663041 20:5 3.0 2 5.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663051 25:5 3.0 2.5 6.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663061 30:5 3.0 3 8.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663071 40:5 3.0 4 10.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663081 50:5 3.0 5 13.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663091 75:5 3.0 7.5 20.3 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663101 100:5 3.0 10 27 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663111 150:5 3.0 15 40.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663121 200:5 3.0 20 54 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663131 300:5 3.0 30 81 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663141 400:5 3.0 40 108 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663151 600:5 2.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663161 800:5 1.5 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663171 1000:5 1.2 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
770663181 1200:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 15 110 34 2.5
* For HCEP Option add (H) to the end of the code number.
Additional ratings available upon request.
W
Drawing number: 4287215
CONNEC-
TIONS
Characteristics
Transformers Code * (CEP) Dimensions (in)
Weigth with
Type With FUSE in the Without FUSE in Aluminium
Current Potential W X Y Z rack (lb)
secondary box the secondary box
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
For detail electric characteristics see particular instrument transformer detail in its data sheet within this publication.
Notes:
The cabin
cabinet is made of #12 caliber stainless steel lamination (2.7 mm or 0.105
in) with M
Munsell Green #7GY 3.29/1.5 powder nish. The doors are pad-
lockable with a three point latch and a penta-head bolt.
The entire
entir surface of the transformer is coated with a conductive layer that
is intende
intended to be solidly grounded when energized. This allows for compact
mounting inside switchgear or enclosures.
The core is built with high permeability grain oriented silicon steel
laminatio
laminations for low losses. The windings are copper wire with copper plate
double is
isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
OUTDOOR mechanical stresses in adverse operating conditions.
60 Hertz
Partial Discharge measurements exceed the IEEE, CAN/CSA and
IECrequirements.
The primary bushing well connections are IEEE 386 compliant, rated 200 A
loadbreak or 600 A non load-break.. The secondary terminals are pre-wired to
a 10 position test switch and 9S meter socket in standard red/black colors.
Mechanical characteristics
Material Colors Weight (lbs.)
Stainless steel Munsell Green 992
8 x 0.75
(4) Lifting plates
W/5/8 - 11 Bolts
13
8 x 1.22
Air spring
35.2
38
32.28
4.5
26 44
50 45
L3 H1 H2
L2 H1 H2
L1 H1 H2
H1 H2 H1 H2 H1 H2
X1 X2 X1 X2 X1 X2
X1 X2 X1 X2 X1 X2
VT1 VT2 VT3 CT1 CT2 CT3
MARKING
1 2 3 4 5 6 7 8 9 10
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Ratio Current Accuracy Voltage BIL
Code Thermal Mechanical Accuracy
(Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770574011 5:5 2.0 0.5 1.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574021 10:5 2.0 1 2.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574031 15:5 2.0 1.5 3.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574041 20:5 2.0 2 5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574051 25:5 2.0 2.5 6.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574061 30:5 2.0 3 7.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574081 40:5 2.0 4 10 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574101 50:5 2.0 5 12.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574151 75:5 2.0 7.5 18.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770574201 100:5 2.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770575301 150:5 1.33 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770575401 200:5 1.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770571131 300:5 1.5 30 75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770571141 400:5 1.5 40 100 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
770571151 600:5 1.0 60 150 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 15 110 34 2.5
ARTECHE KM series are dry type outdoor service combination CT-PT. The
core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer
of Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays
and the effects of tracking and erosion on the exterior of the transformer
ensuring a long mechanical and electrical life. The transformer is
maintenance free.
OUTDOOR
60 Hertz The external layer can be manufactured with Hydrophobic Cycloaliphatic
Epoxy Resin (HCEP) which improves service life expectancy due to its
improved tracking and erosion resistance. HCEP additionally increases
the transformers weatherability and offers better performance in heavily
polluted environments.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 230 32.6 16
14 (356) Nameplate
13 (330)
24.5 (622)
Lifting
Holes
2 holes to conduit 1 hole 9/16
pipe 1 to ground 10 (254)
connection
H1 H2
/4
1
C1 C2
H0
MARKING
V1 V2
CONNEC- (Single
Type: NEMA-2 Type: TE-12 250 Type: Quick Connector
TIONS Material: Copper Material: Copper Material: Brass Primary ONE SECONDARY
Range: 4TRE-250MCM Ratio) with tap
H1 H2
C1 C2 C3
H0
V1 V2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Code * Ratio Current Accuracy Voltage BIL
Thermal Mechanical Accuracy
(CEP) (Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770061016 5:5 1.5 0.5 1.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061026 10:5 1.5 1 2.7 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061036 15:5 1.5 1.5 4.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061046 20:5 1.5 2 5.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061056 25:5 1.5 2.5 6.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061066 30:5 1.5 3 8.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061076 40:5 1.5 4 10.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061086 50:5 1.5 5 13.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061096 75:5 1.5 7.5 20.3 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061106 100:5 1.5 10 27 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061116 150:5 1.5 15 40.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061126 200:5 1.5 20 54 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061136 300:5 1.5 30 81 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061146 400:5 1.5 40 108 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061156 600:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061166 800:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061176 1000:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770061186 1200:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064046 10/20:5 2.0/1.5 2 5 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064086 25/50:5 2.0/1.5 5 12.5 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064126 100/200:5 2.0/1.5 20 50 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064136 150/300:5 2.0/1.5 30 75 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770066136 150/300:5 4.0/2.0 30 75 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064156 300/600:5 2.0/1.5 60 150 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064176 500/1000:5 2.0/1.2 75 127.5 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770064186 600/1200:5 2.0/1.0 90 162 0.3 B0.2/B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
The core is built with high permeability grain oriented silicon steel
OUTDOOR laminations for low losses. The windings are copper wire with copper plate
60 Hertz double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
32.1 (815)
L3 H1 H2
L2 H1 H2
L1 H1 H2
H1 H2 H1 H2 H1 H2
X1 X2 X1 X2 X1 X2
Type: NEMA-2 Type: TE-12 250 Material: Copper
Material: Copper Range: 4TRE-250MCM X1 X2 X1 X2 X1 X2
CONNEC- VT1 VT2 VT3 CT1 CT2 CT3
MARKING
TIONS SECONDARY TERMINAL
/4
1 2 3 4 5 6 7 8 9 10
1
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Code * Ratio Current Accuracy Voltage BIL
Thermal Mechanical Accuracy
(CEP) (Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770681016 5:5 1.5 0.5 1.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681026 10:5 1.5 1 2.7 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681036 15:5 1.5 1.5 4.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681046 20:5 1.5 2 5.4 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681056 25:5 1.5 2.5 6.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681066 30:5 1.5 3 8.1 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681076 40:5 1.5 4 10.8 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681086 50:5 1.5 5 13.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681096 75:5 1.5 7.5 20.3 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681106 100:5 1.5 10 27 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681116 150:5 1.5 15 40.5 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681126 200:5 1.5 20 54 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681136 300:5 1.5 30 81 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681146 400:5 1.5 40 108 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681156 600:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681166 800:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681176 1000:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
770681186 1200:5 1.0 60 162 0.3 B-0.5 0.3 W,X,M,Y/0.6Z 25 150 50 2.5
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
W
Drawing number: 4287228
CONNEC-
TIONS
Characteristics
Transformers Code * (CEP) Dimensions (in)
Weigth with
Type With FUSE in the Without FUSE in Aluminium
Current Potential W X Y Z rack (lb)
secondary box the secondary box
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
For detail electric characteristics see particular instrument transformer detail in its data sheet within this publication.
Notes:
The cabin
cabinet is made of #12 caliber stainless steel lamination (2.7 mm or 0.105
in) with M
Munsell Green #7GY 3.29/1.5 powder nish. The doors are pad-
lockable with a three point latch and a penta-head bolt.
The entire
entir surface of the transformer is coated with a conductive layer that
is intende
intended to be solidly grounded when energized. This allows for compact
mounting inside switchgear or enclosures.
The core is built with high permeability grain oriented silicon steel
laminatio
laminations for low losses. The windings are copper wire with copper plate
double is
isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
OUTDOOR mechanical stresses in adverse operating conditions.
60 Hertz
Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC
requirements.
The primary bushing well connections are IEEE 386 compliant, rated 200 A
loadbreak or 600 A non load-break. The secondary terminals are pre-wired
to a 10 position test switch and 9S meter socket in standard red/blackcolors.
Mechanical characteristics
Material Colors Weight (lbs.)
Stainless steel Munsell Green 992
8 x 0.75
(4) Lifting plates
W/5/8 - 11 Bolts
13
8 x 1.22
Air spring
35.2
38
32.28
4.5
26 44
50 45
L3 H1 H2
L2 H1 H2
L1 H1 H2
H1 H2 H1 H2 H1 H2
X1 X2 X1 X2 X1 X2
X1 X2 X1 X2 X1 X2
VT1 VT2 VT3 CT1 CT2 CT3
MARKING
1 2 3 4 5 6 7 8 9 10
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Ratio Current Accuracy Voltage BIL
Code Thermal Mechanical Accuracy
(Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770584016 5:5 2.0 0.5 1.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584026 10:5 2.0 1 2.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584036 15:5 2.0 1.5 3.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584046 20:5 2.0 2 5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584056 25:5 2.0 2.5 6.25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584066 30:5 2.0 3 7.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584086 40:5 2.0 4 10 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584106 50:5 2.0 5 12.5 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584156 75:5 2.0 7.5 18.75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770584206 100:5 2.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770585306 150:5 1.33 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770585406 200:5 1.0 10 25 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 150 50 2.5
770581136 300:5 1.5 30 75 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770581146 400:5 1.5 40 100 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
770581156 600:5 1.0 60 150 0.3 B-0.5 0.3 W,X,M,Y/1.2Z 25 125 50 2.5
ARTECHE KM series are dry type outdoor service combination CT-PT. The
core is encapsulated with Type B epoxy resin which provides excellent
internal dielectric properties and mechanical strength. The external layer
of Cycloaliphatic Epoxy Resin (CEP) provides resistance to ultraviolet rays
and the effects of tracking and erosion on the exterior of the transformer
ensuring a long mechanical and electrical life. The transformer is
maintenance free.
OUTDOOR
60 Hertz The external layer can be manufactured with Hydrophobic Cycloaliphatic
Epoxy Resin (HCEP) which improves service life expectancy due to its
improved tracking and erosion resistance. HCEP additionally increases
the transformers weatherability and offers better performance in heavily
polluted environments.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
double isolation. The concentric distribution of the coils prevents magnetic
ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
Mechanical characteristics
Insulation Material Colors Weight (lbs.) Creepage distance (in) Strike distance (in)
Resin Gray* 264 46 21
13 (330)
28.7 (729)
Lifting
holes
3/4 2 holes to conduit 1 hole 9/16
pipe 1 to ground 10 (254)
connection
H1 H2
/4
1
C1 C2
H0
MARKING
V1 V2
CONNEC- (Single
Type: NEMA-2 Type: TE-12 250 Type: Quick Connector
TIONS Material: Copper Material: Copper Material: Brass Primary ONE SECONDARY
Range: 4TRE-250MCM Ratio) with tap
H1 H2
C1 C2 C3
H0
V1 V2
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Code * Ratio Current Accuracy Voltage BIL
Thermal Mechanical Accuracy
(CEP) (Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770073017 5:5 3.0 0.5 1.4 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073027 10:5 3.0 1 2.7 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073037 15:5 3.0 1.5 4.1 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073047 20:5 3.0 2 5.4 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073057 25:5 3.0 2.5 6.8 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073067 30:5 3.0 3 8.1 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073077 40:5 3.0 4 10.8 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073087 50:5 3.0 5 13.5 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073097 75:5 3.0 7.5 20.3 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073107 100:5 3.0 10 27 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073117 150:5 3.0 15 40.5 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073127 200:5 3.0 20 54 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073137 300:5 3.0 30 81 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073147 400:5 3.0 40 108 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073157 600:5 2.0 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770071167 800:5 1.5 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770071177 1000:5 1.2 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770071187 1200:5 1.0 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074047 10/20:5 2.0/1.5 2 5,4 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074087 25/50:5 2.0/1.5 5 13,5 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074127 100/200:5 2.0/1.5 20 54 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074157 300/600:5 2.0/1.5 60 162 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074167 400/800:5 2.0/1.5 60 162 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770073167 400/800:5 3.0/1.5 60 162 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074177 500/1000:5 2.0/1.2 60 162 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770074187 600/1200:5 2.0/1.0 60 162 0.3B-0.5/B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
The core is built with high permeability grain oriented silicon steel
laminations for low losses. The windings are copper wire with copper plate
OUTDOOR double isolation. The concentric distribution of the coils prevents magnetic
60 Hertz ux leakage, achieving greater accuracy and higher capacity to withstand
mechanical stresses in adverse operating conditions.
33 (838)
L3 H1 H2
L2 H1 H2
L1 H1 H2
H1 H2 H1 H2 H1 H2
X1 X2 X1 X2 X1 X2
Type: NEMA-2 Type: TE-12 250 Material: Copper X1 X2 X1 X2 X1 X2
Material: Copper Range: 4TRE-250MCM
CONNEC- VT1 VT2 VT3 CT1 CT2 CT3
MARKING
TIONS SECONDARY TERMINAL
/4
1 2 3 4 5 6 7 8 9 10
1
Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Short- Short- IEEE
Current Thermal IEEE Metering Nominal (1 min)
time time Metering
Code* Ratio Current Accuracy Voltage BIL
Thermal Mechanical Accuracy
(CEP) (Primary: Rating [Voltage System (kV) Primary & Secondary
Current Current [Current
Secondary) Factor @ Transformer] (kV) Secondary Winding
(kA/1s) (kApeak) Transformer]
30C (kVrms) (kVrms)
770693017 5:5 3.0 0.5 1.4 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693027 10:5 3.0 1 2.7 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693037 15:5 3.0 1.5 4.1 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693047 20:5 3.0 2 5.4 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693057 25:5 3.0 2.5 6.8 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693067 30:5 3.0 3 8.1 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693077 40:5 3.0 4 10.8 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693087 50:5 3.0 5 13.5 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693097 75:5 3.0 7.5 20.3 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693107 100:5 3.0 10 27 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693117 150:5 3.0 15 40.5 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693127 200:5 3.0 20 54 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693137 300:5 3.0 30 81 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693147 400:5 3.0 40 108 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693157 600:5 2.0 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693167 800:5 1.5 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693177 1000:5 1.2 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
770693187 1200:5 1.0 60 162 0.3 B-1.8 0.3 W,X,M,Y/1.2Z 34.5 200 70 2.5
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
X
Z
W
Drawing number: 4287229
CONNEC-
TIONS
Characteristics
Transformers Code * (CEP) Dimensions (in)
Weigth with
Type With FUSE in the Without FUSE in Aluminium
Current Potential W X Y Z rack (lb)
secondary box the secondary box
* For HCEP Option add (H) to the end of the code number.
Approximate dimensions in inches.
For detail electric characteristics see particular instrument transformer detail in its data sheet within this publication.
Notes:
Arteche USA
18503 Pines Blvd. Suite 313.
Pembroke Pines, Florida 33029
Phone: 954 438 9499
Updates: ARTECHE_DS_trfMVGuide_EN
Fax: 954 438 9959 Version: D1
info@artecheusa.com
www.arteche.com/unitusa ARTECHE