Transformer Protection
Transformer Protection
Fault level
Extent of
damage Duration of
fault
Winding failures
Voltage
regulating load
changers
Transformer Transformer
faults bushing failure
Transformer core
problem
Miscellaneous
failures
Insulation
breakdown
Time
Improve cooling
Ageing of
system of
insulation
possible
Temperature
Condition Over heating
Reduced load
leading to faults due to excitation
Oil
contamination%
& oil leakage
Reduced cooling
FAULT OF TRANSFORMER
Earth fault on H.V external connection
Phases to phase fault on H.V external connection
Internal earth fault on H.V windings
Internal phase to phase fault on H.V windings.
Short circuit between turns L.V windings.
Earth fault on L.V external winding
Phase to phase fault on L.V external connection.
Internal earth fault on L.V windings
Internal phase to phase fault on L.V winding
Short circuit b/w turn L.V windings
Earth fault on tertiary windings
Short circuit b/W turns tertiary windings
Sustained system phase to phase fault
Sustained system earth fault
Differential relay
220/132/11KV AUTO
TRANSFORMER
Thermal over load
relay
Overall percentage
biased differential
relay
L.H&H.V Connection
circulating protection
Over excitation
relay
Overall percentage
biased differential
relay
L.H&H.V Connection
circulating
protection
Tertiary over
current protection
Tap changer
buchhloz relay
MECHANICAL Winding
PROTECTION: Temperature
0IL
temperature
Pressure
relieve valve
Factors:
The shape, magnitude and duration of the inrush
current depend on the factors:
Size of power transformer
Source Impendence
The magnetic properties of the core i.e.
saturation density
The remanence of core
Resistance in power system from source to
transformer.
The moment when transformer is switch on.
Effect of magnetising current
Appears on one side of transformer only
Seen as fault by differential relay
Normal steady state magnetising current is less than relay
setting
Transient magnetising inrush could cause relay to operate
The vector group shows the connection of
windings of transformer and numerical index
(hour numbers) for displacement of vector of
two star voltages.
Capital Letter DY11 Small
letter ( clock dial reference)
The first capital letter donates the connection
of high voltage winding of transformer
The small letter represent the connection of
low voltage secondary winding of transformer
Yy0d5
Current
IF(LV) IF(HV)
1.2IF(LV)
Use of Instantaneous Overcurrent
Protection
Source LV
50
51
Differential Protection
Overall differential protection may be justified for larger
transformers (generally > 5MVA).
Provides fast operation on any winding
Measuring principle :
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to maintain stability
for heavy thro fault current
Biasing allows mismatch between CT outputs.
It is essential for transformers with tap changing facility.
Another important requirement of transformer differential
protection is immunity to magnetising inrush current.
PROTECTED ZONE
HV LV
R
Correct application of differential
protection requires CT ratio and winding
connections to match those of
transformer.
CT secondary circuit should be a
replica of primary system.
Consider :
(1) Difference in current magnitude
(2) Phase shift
(3) Zero sequence currents
Biased Differential Scheme
Differentia
l
Current
I1 - I2 OPERATE
I1 BIAS BIAS I2
I1 - I2
OPERATE RESTRAIN
I1 + I2 Mean Thro
2 Current
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10% rated
Restricted E/F Protection
Low Voltage Windings (2)
A B C N
Protected zone
REF
n
`
Combined Differential and Restricted
Earthfault Protection
A2 A1 a1 a2 P1 P2
S1 S2
P1 S1 P2
REF
S2 P1
P2
S1
S2
To differential relay
Integral Vectorial and Ratio
Compensation
Power transformer
Ratio
correction
Vectorial
correction
Differential
Virtual interposing CT element Virtual interposing CT
In Zone Earthing Transformer
a1 a2
P1 P2
A1 A2 P2 P1
S2 S1
S2 S1 T2 T1 P1 P2
Three Winding Transformer
63MVA 25MVA
132KV 11KV
300/5 1600/5
50MVA
33KV
1000/5
Twice
Normal
Flux
Normal
Flux
Normal
No
Load No Load
Current Current at
Twice Normal
Flux
Parallel Transformers
T1 N A B C
T2
Inter-Turn Fault
CT
E
Load
Shorted
turn
Oil conservator
3 minimum
Transformer
Buchholz Relay
Petcock
Alarm bucket Counter balance
weight
Mercury switch
Oil level
Trip bucket
Aperture adjuster
2m
V = kf
Causes
m
Low frequency
High voltage Ie
Geomagnetic disturbances
Effects
Tripping of differential element (Transient overfluxing)
Damage to transformers (Prolonged overfluxing)
EFFECTS OF OVER FLUXING:
Increase in magnetizing current
Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts
(cause by stray flux)
V/Hz Overfluxing Protection
V K
f
Settings
Pick-up 1.5 to 3.0 i.e. 110V x 1.05 = 2.31
50Hz
DT setting range 0.1 to 60 seconds
V/H CHARACTERISTIC:
Over-fluxing Relay
Ex
G
VT
AVR RL
THERMAL OVERLOAD:
EFFECT OF OVER LOAD ON TRANSFORMER
INSULATION LIFE:
Overheating Protection
Trip
I load
Alarm
TD
setting
On
Top oil of I load Fan
power control
transformer Off
On
Pump
control
Off
Heater Temp. indication
Local
Thermal Temperature Remote
replica sensing resistor
Overload Protection
Overcurrent protection designed for fault
condition
Thermal replica provides better protection
for overload
Time
Current based
Flexible characteristics
Single or dual time constant
Reset facility
Non-volatile Current
Thermal Overload Oil Filled Transformers
Trip time (s)
10000 Single
characteristic:
= 120 mins
1000
Dual characteristic
100
Single
10 characteristic:
1 2 3 4 5 6 = 5 mins
Current (multiple of thermal setting)
ZA
DIGITAL RELAYS FOR TRANSFORMER
THERMAL WINDING PROTECTION