C-Linx Configuration Software Fike Corporation
Miscellaneous Settings
AC Trouble Delay 12 hours
Abort Type 2
Panel Walktest Enabled
Fan Restart Automatic Restart
Auxiliary Loop Module Module Present
Auxiliary Power Module Module Present
Aux Battery Supervision Disabled
Transformer Type 120VAC
Main Battery Supervision Enabled
SLC Wiring Style Style 4 - Class B
Ground Fault Supervision L1 Enb L2 Enb
Unsilence Time 24 hours
Silence Reminder Enabled
Silence Inhibit Enabled
Silence Mode ULC Silence Mode
Auto Alarm Silence 4 Hours
Panel Sync Protocol System Sensor
Panel Switch Operation Drill/Silence/Acknowledge Switches Enabled
Positive Alarm Sequence Disabled
New Device Record Missing Trb Disabled
Auto Message Sent at 12:00AM Disabled
Eclipse Device Error Device Error is Trouble
AHU Fire Dept Key Not Required to restart AHU
Latch Super/Trb event on LCD First Supervisory or Trouble Event Latched on LCD
Addressable Devices
Type Custom Message 1 Custom Message 2
Adr
Function Custom Message 3 Zone 1 Zone 2 Zone 3 Zone 4
Pull Station Module 'CORREA C-1 ' 'PULSADOR ALARMA A '
1-001
Manual Alarm 'LOOP 1-001 ' 024 000 000 010
Pull Station Module 'CORREA C-1 ' 'PULSADOR ALARMA B '
1-002
Manual Alarm 'LOOP 1-002 ' 024 000 000 000
Control Module 'CORREA C-1 ' 'MODULO BALIZAS '
1-003
Output 'LOOP 1-003 ' 024 000 000 000
Control Module 'CORREA C-2 ' 'MODULO BALIZAS '
1-004
Output 'LOOP 1-004 ' 025 000 000 000
Control Module 'TORRE 6 ' 'BALIZAS TORRE '
1-005
Output 'LOOP 1-005 ' 034 024 025 027
Page 2 of 8
C-Linx Configuration Software Fike Corporation
Page 3 of 8
C-Linx Configuration Software Fike Corporation
Page 4 of 8
C-Linx Configuration Software Fike Corporation
Page 5 of 8
C-Linx Configuration Software Fike Corporation
Page 6 of 8
C-Linx Configuration Software Fike Corporation
Page 7 of 8
C-Linx Configuration Software Fike Corporation