Micom Relay Calculation

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 12
At a glance
Powered by AI
The document describes settings and calculations for various types of relays used in substation protection like line differential, overcurrent, earth fault, directional and thermal overload relays. It also provides details on transformer differential relay matching calculations.

The relays described are line differential relay, overcurrent and earth fault relay, directional relay, thermal overload relay and transformer differential relay.

The formulas used for calculating restraining (Ir) and differential (Id) currents for transformer matching are: Ir = {( Iam,x,a – Iam,zero,a) + (Iam,x,z – Iam,zero,z) / 2} Id = ( Iam,x,a – Iam,zero,a) - (Iam,x,z – Iam,zero,z)

MiCOM P54X - LINE DIFFERENTIAL Enter The Value In Yellow Cells Only

RELAY SETTING

Is1 = 0.225 0 0.23


LINE DIFF CHARCTERISTICS
Is2 = 2 0.25 0.25

k1 = 10.00% 0.5 0.28


10.00
k2 = 65.00% 0.75 0.30
9.50
Ph CT Correction = 1 1 0.33
9.00
Remote correction factor = 1 1.25 0.35
8.50
Test Mode = Disabled 1.5 0.38

DIFF CURRENT (Id)


8.00 1.75 0.40
Charcteristics 7.50 2 0.43
2.25 0.59
7.00
Pickup |Ιdiff| > Ιs1 / (1 - 0.5 k1) 2.5 0.75
6.50
Slope 1 |Ιdiff| > k1.| Ιbias| + Ιs1 2.75 0.91
6.00
Slope 2 |Ιdiff| > k2.| Ιbias| - (k2 - k1). Ιs2 + Ιs1 3 1.08
5.50
3.25 1.24
Operation (Pickup) 5.00
3.5 1.40
4.50
Min. Op. Current = 0.237 Amps 3.75 1.56
4.00 4 1.73
Slope check 3.50 4.25 1.89
Current Injection = LOCAL RELAY 3.00 4.5 2.05

Injected Bias Current = 1.000 Amps 2.50 4.75 2.21


Expected Diff. Current = 0.275 Amps Slope 1 2.00 5 2.38
5.25 2.54
1.50
Slope Calculation 5.5 2.70
1.00
CT Ratio = = 2000 /1 5.75 2.86
0.50
Relay 1 Current = = 1 (Injected sec) 6 3.03
0.00
Relay 2 Current = = 0.55 (Injected sec) 0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 2.75
6.253 3.25(Ib)
BIAS CURRENT
3.53.19
3.75 4 4.25 4.5 4.75 5 5.25 5.5 5.75 6 6.25 6.5

Relay 1 Primary = = 2000 (Calculated Primary) 6.5 3.35

Relay 2 Primary= = 1100 (Calculated Primary)

Calculated Bias = 1550 (Calculated Primary) 0.775 Secondary

Calculated Differential = 900 (Calculated Primary) 0.45 Secondary


Calculated Slope = 0.29
R - Axis R'' - Axis R - Axis R'' - Axis
ZONE REACH Z Ѳ R Ph R Gd TIME X - Axis
(Ph) (Ph) (Gd) (Gd) IMPORTANCE

1 F 3.95 80 4 8 0.000 3.890 2.000 0.500 4.938 1.235 R - Axis = Resistance / (1+Ke)

2 F 7.34 80 6 12 0.600 7.228 3.000 0.750 7.407 1.852 Y - Axis = Impedence * sin(Ѳ)

3 F 11.29 80 12 24 1.000 11.118 6.000 1.500 14.815 3.704 R'' - Axis = 25% of R - Axis

P F 12 70 15 0 0.000 11.276 7.500 1.875 0.000 0.000 Y'' - Axis = 0 ̷̷̸ 330

4 R 12 70 15 15 1.000 11.276 7.500 1.875 9.259 2.315 For Phase Fault Ke is 1

Ke & KѲ is Grounding Factor

Ke 0.62 KѲ -6 Z TiltѲ -3 Zone P is Forward Reverse Selectable

Enter The Value In Yellow Cells Only F R

For Phase Fault Grabh :


X
LINE / ZONE ZONE 1 ZONE 2 ZONE 3 ZONE P ZONE 4

LINE 1 0.00 330 0.00 330 0.00 330 0.00 330 -11.28 177

LINE 2 2.000 80 3.000 80 6.000 80 7.500 70 -7.500 70


LINE 3

4
LINE 3 3.890 177 7.228 177 11.118 177 11.276 177 0.00 330

E
LIN
LINE 4 -0.500 260 -0.750 260 -1.500 260 -1.875 250 1.875 250

E2
LIN

LI N
E3

2E
R

LIN
For Ground Fault Grabh : R' LINE 1 LIN

E4
E 1

LIN
ZONE 1 ZONE 2 ZONE 3 ZONE P ZONE 4
LINE / ZONE
PH Φ PH Φ PH Φ PH Φ PH Φ

LINE 1 0.00 330 0.00 330 0.00 330 0.00 330 -11.28 177

LINE 2 4.938 80 7.407 80 14.815 80 0.000 70 -9.259 70

LINE 3 3.890 177 7.228 177 11.118 177 11.276 177 0.00 330 X'

LINE 4 -1.235 260 -1.852 260 -3.704 260 0.000 250 2.315 250
OVERCURRENT & EARTH FAULT
RELAY SETTING ###
###

Current Set (Is) = 0.88 ###

TMS = 0.18 ###

Curve Selected = IEC S Inverse ###


###
Charcteristics ###
K ###
Trip time t = Tx +L
( I / Is ) α - 1 ###
###
Operation ###
###
Current Injected (I) = 1.00 ###

Trip time = 9.844 Secs ###

###

Enter The Value In Yellow Cells Only


###
DIRECTIONAL ###
RELAY SETTING ###
OPERATING
DIRECTION CHAR ANGLE I FAULT REF VOLT ANGLE (ANTI
CLOCK) ###
R YB 45 225 ###
Reverse 45 Y BR 285 105 ###
B RY 165 345 ###
###
THERMAL OVERLOAD
RELAY SETTING

Time Constant = 2
Largest Phase current = 2

Full Load Current rating = 0.83

Pre Loading = 0.00%


Alarm Setting = 90.00%

Charteristics

Trip Time = -‫ح‬loge((I2)-(K.IFLC)2)/(I2-IP2)

Operation
Trip time = 25.27 Secs
Alarm = 22.74 Secs

Enter The Value In Yellow Cells Only


MiCOM P643 TRANSFORMER DIFFERENTIAL RELAY Dyn1 VECTOR GROUP SLOPE CALCULATION

SLOPE 1 SLOPE 2
R Y B R Y B
variable current Ia 1.926 2.891 1.93 2.893 1.205 variable current Ia 4.593 5.372 4.599 5.378

Fixed current Ib 2 3 2 3 1.25 3 Fixed current Ib 4.5 5 4.5 5 4.5 5

Ir 1.963 2.946 1.965 2.947 1.228 1.289 Ir 4.565 5.226 4.569 5.23 1.934 2.148

Calculated Id 0.489 0.735 0.493 0.737 0.307 -2.578 Calculated Id 1.397 1.86 1.403 1.867 -3.867 -4.297

M1 25.03 24.85 -4729.51 M1 70.05 70.2 -200.93

Ir 1.966 2.948 1.968 2.952 Ir 4.573 5.233 4.578 5.24


Measured Id 0.491 0.733 0.494 0.739 Measured Id 1.403 1.863 1.402 1.868

M1 24.64 24.9 #DIV/0! M1 69.7 70.39 #DIV/0!


* yellow cells are manual entering values
FORMULAS FOR Dyn1 VECTOR GROUP TRANSFORMER MATCHING FACTOR
Simulate differential and restraining currents such that they lie in the region over and under the curve. Kam,a = 1.719 Kam,b = 1.289
Restraining current Ir = {( Iam,x,a – Iam,zero,a) + (Iam,x,z – Iam,zero,z) / 2} Differential current Id = ( Iam,x,a – Iam,zero,a) - (Iam,x,z – Iam,zero,z)

Ir = {( Ia*Kam,a – (Ia*Kam,a)/3) + (Ib*Kam,b – (Ib*Kam,b)/3) / 2} Id = ( Ia*Kam,a – (Ia*Kam,a)/3) - (Ib*Kam,b – (Ib*Kam,b)/3)


EX: Ir = {(Ia*6.824*0.667)+ (Ib*1.705*0.667) / 2} EX: Id = {(Ia*6.824*0.667)+ (Ib*1.705*0.667) / 2} \
Ir = {(4.552Ia + 1.137Ib) / 2} Id = {(4.552Ia + 1.137Ib) / 2} fNzrd; nry;tk;
MiCOM P643 TRANSFORMER DIFFERENTIAL RELAY Dyn1 VECTOR GROUP SLOPE CALCULATION

SLOPE 1 SLOPE 2
R Y B R Y B
variable current Ia 0.607 0.67 0.605 0.668 0.609 0.673 variable current Ia 1.763 2.887 1.768 2.893 1.776 2.891

Fixed current Ib 0.9 1 0.9 1 0.9 1 Fixed current Ib 2 3 2 3 2 3

Ir 0.888 0.983 0.887 0.981 0.89 0.986 Ir 2.327 3.698 2.331 3.703 2.338 3.701

Calculated Id 0.295 0.32 0.291 0.316 0.298 0.325 Calculated Id 1.361 2.455 1.37 2.466 1.383 2.462

M1 26.32 26.6 28.13 M1 79.8 79.88 79.16

Ir 0.891 0.985 0.894 0.989 0.895 0.988 Ir 2.337 3.716 2.339 3.723 2.346 3.722
Measured Id 0.293 0.319 0.298 0.324 0.297 0.324 Measured Id 1.371 2.471 1.366 2.477 1.377 2.478

M1 27.66 27.37 29.03 M1 79.77 80.27 80.01


* yellow cells are manual entering values
FORMULAS FOR Dyn1 VECTOR GROUP TRANSFORMER MATCHING FACTOR
Simulate differential and restraining currents such that they lie in the region over and under the curve. Kam,a = 1.706 FOR DELTA 1.706
Restraining current Ir = {( Iam,x,a + 1/√3 Iam,x,b) / 2} Differential current Id = { Iam,x,a - 1/√3 Iam,x,b } Kam,b = 1.426 FOR STAR 0.823301
Ir = {( Ia*Kam,a + 1/√3(Ib*Kam,b)) / 2} Id = { Ia*Kam,a - 1/√3(Ib*Kam,b) }

EX: Ir = {(Ia*1.706+ (1/√3(Ib*1.426))) / 2} EX: Id = { Ia*1.706 - (1/√3(Ib*1.426)) } \


Ir = {(1.706Ia + 0.823Ib) / 2} Id = { 1.706Ia - 0.823Ib } fNzrd; nry;tk;
***
MiCOM P643 TRANSFORMER DIFFERENTIAL RELAY Dyn1 VECTOR GROUP SLOPE CALCULATION

SLOPE 1 SLOPE 2
R Y B R Y B
variable current Ia 1.204 1.928 2.891 1.206 1.928 2.894 1.203 1.928 2.892 variable current Ia 3.975 4.599 5.377 3.979 4.601 5.381 3.974 4.597 5.375
Fixed current Ib 1.25 2 3 1.25 2 3 1.25 2 3 Fixed current Ib 4.1 4.5 5 4.1 4.5 5 4.1 4.5 5
Ir 1.227 1.964 2.946 1.228 1.964 2.947 1.226 1.964 2.946 Ir 4.039 4.569 5.229 4.042 4.57 5.232 4.039 4.568 5.228

Calculated Id 0.306 0.491 0.735 0.308 0.491 0.739 0.304 0.491 0.736 Calculated Id 1.032 1.403 1.865 1.037 1.406 1.87 1.031 1.401 1.863

M1 24.96 24.85 24.96 24.86 25.23 25.07 25.34 24.95 25.12 M1 70 69.45 70.43 69.89 70.09 70 69.94 70 69.97

Ir 1.228 1.969 2.951 1.23 1.968 2.955 1.228 1.968 2.953 Ir 4.047 4.577 5.238 4.052 4.58 5.244 4.048 4.579 5.24
Measured Id 0.307 0.493 0.736 0.306 0.491 0.737 0.306 0.492 0.737 Measured Id 1.032 1.404 1.869 1.035 1.405 1.871 1.031 1.402 1.869
M1 25.1 24.75 24.9 25.07 24.92 24.99 25.14 24.87 24.99 M1 70.28 70.19 70.35 70.08 70.18 70.13 69.87 70.65 70.3
* yellow cells are manual entering values
FORMULAS FOR Dyn1 VECTOR GROUP TRANSFORMER MATCHING FACTOR
Simulate differential and restraining currents such that they lie in the region over and under the curve. Kam,a = 1.719 Kam,b = 1.289

Restraining current Ir = {( Iam,x,a – Iam,zero,a) + (Iam,x,z – Iam,zero,z) / 2} Differential current Id = ( Iam,x,a – Iam,zero,a) - (Iam,x,z – Iam,zero,z)

Ir = {( Ia*Kam,a – (Ia*Kam,a)/3) + (Ib*Kam,b – (Ib*Kam,b)/3) / 2} Id = ( Ia*Kam,a – (Ia*Kam,a)/3) - (Ib*Kam,b – (Ib*Kam,b)/3)

EX: Ir = {(Ia*6.824*0.667)+ (Ib*1.705*0.667) / 2} EX: Id = {(Ia*6.824*0.667)+ (Ib*1.705*0.667) / 2} \


Ir = {(4.552Ia + 1.137Ib) / 2} Id = {(4.552Ia + 1.137Ib) / 2} fNzrd; nry;tk;
Y PHASE GRABH

x-axis = Ibias 0 1.228 1.968 2.952 4.049 4.578 5.24

y-axis = Idiff 0.3 0.308 0.494 0.739 1.035 1.402 1.868

1.8

1.6
Axis Title

1.4

1.2

0.8

0.6

0.4

0.2

0
0 1.228 1.968 2.952
Axis Title 4.049 4.578 5.24
actual

250 249.6 0 248.5 -119.8 253.3 119.8

500 499.6 0 498.8 -120 499.2 120.2

1000 1001 0 1003 -120.2 1001 120.2

750 750.2 0 744.8 -119.5 746.1 120.5

1500 1499 0 1502 -119.9 1492 120.1

3000 3003 0 3002 -120 3001 120

0.262 0.261 -0.38314176 0.262 0 0.259 -1.14503817

0.349 0.348 -0.28735632 0.348 -0.28653295 0.349 0

Ir 8.042 9.79 11.48 8.023 9.724 11.44

Measured Id 2.425 2.936 3.45 2.403 2.929 3.435

M1 29.23 30.41 29.81 30.92 29.49 30.2


1.32 -0.166667

0.24 0.166667 2.602 3.162 3.724

0.3 0.166667 1.4 1.7 2

0.693333 0.416667 8.053 9.739 11.57

0.533333 0.083333 2.414 2.917 3.457

0.1 0

8.045 9.761 11.52

2.41 2.939 3.457

30.83 29.45 30.13