Basics
Basics
2. What are taps and when are they used? Taps are 7. Can Acme Transformers be reverse connected?
provided on some transformers on the high voltage winding ACME dry-type distribution transformers can be reverse
to correct for high or low voltage conditions, and still deliver connected without a loss of kVA rating, but there are
full rated output voltages at the secondary terminals. certain limitations. Transformers rated 1 kVA and larger
Standard tap arrangements are at two-and-one-half and single phase, 3 kVA and larger three phase can be reverse
five percent of the rated primary voltage for both high and connected without any adverse effects or loss in kVA
low voltage conditions. For example, if the transformer has capacity. The reason for this limitation in kVA size is, the
a 480 volt primary and the available line voltage is running turns ratio is the same as the voltage ratio. Example: A
at 504 volts, the primary should be connected to the 5% transformer with a 480 volt input, 240 volt output— can
tap above normal in order that the secondary voltage be have the output connected to a 240 volt source and thereby
maintained at the proper rating. The standard ASA and become the primary or input to the transformer, then the
NEMA designation for taps are “ANFC” (above normal full original 480 volt primary winding will become the output
capacity) and “BNFC” (below normal full capacity). or 480 volt secondary. On transformers rated below 1 kVA
single phase, there is a turns ratio compensation on the
3. What is the difference between “Insulating,” low voltage winding. This means the low voltage winding
“Isolating,” and “Shielded Winding” transformers? has a greater voltage than the nameplate voltage indicates
Insulating and isolating transformers are identical. These at no load. For example, a small single phase transformer
terms are used to describe the isolation of the primary having a nameplate voltage of 480 volts primary and 240
and secondary windings, or insulation between the two. volts secondary, would actually have a no load voltage
A shielded transformer is designed with a metallic shield of approximately 250 volts, and a full load voltage of 240
between the primary and secondary windings to attenuate volts. If the 240 volt winding were connected to a 240 volt
transient noise. This is especially important in critical source, then the output voltage would consequently be
applications such as computers, process controllers and approximately 460 volts at no load and approximately
many other microprocessor controlled devices. All two, 442 volts at full load. As the kVA becomes smaller, the
three and four winding transformers are of the insulating or compensation is greater— resulting in lower output voltages.
isolating types. Only autotransformers, whose primary and When one attempts to use these transformers in reverse, the
secondary are connected to each other electrically, are not transformer will not be harmed; however, the output voltage
of the insulating or isolating variety. will be lower than is indicated by the nameplate.
4. Can transformers be operated at voltages other than 8. Can a Single Phase Transformer be used on a
nameplate voltages? In some cases, transformers can be Three Phase source? Yes. Any single phase transformer
operated at voltages below the nameplate rated voltage. In can be used on a three phase source by connecting the
NO case should a transformer be operated at a voltage in primary leads to any two wires of a three phase system,
excess of its nameplate rating, unless taps are provided for regardless of whether the source is three phase 3-wire or
this purpose. When operating below the rated voltage, the three phase 4-wire. The transformer output will be single
kVA capacity is reduced correspondingly. For example, if phase.
a 480 volt primary transformer with a 240 volt secondary is
operated at 240 volts, the secondary voltage is reduced to 9. Can Transformers develop Three Phase power
120 volts. If the transformer was originally rated 10 kVA, the from a Single Phase source? No. Phase converters or
reduced rating would be 5 kVA, or in direct proportion to the phase shifting devices such as reactors and capacitors are
applied voltage. required to convert single phase power to three phase.
load is 40 amperes, such as a motor, and the secondary insulation class 130°C. Compound filled transformers use
voltage is 240 volts, then 240 x 40 equals 9600 VA. A 10 insulation class 180°C. Larger ventilated transformers are
kVA (10,000volt-amperes) transformer is required. ALWAYS designed to use 220°C insulation. All of these insulation
SELECT THE TRANSFORMER LARGER THAN THE ACTUAL systems will normally have the same number of years
LOAD. This is done for safety purposes and allows for operating life. A well designed transformer, observing these
expansion, in case more load is added at a later date. For 3 temperature limits, will have a life expectancy of 20-25
phase kVA, multiply rated volts x load amps x 1.73 (square years.
root of 3) then divide by 1000. 17. Why should Dry-Type Transformers never be over-
(4) Determine whether taps are required. Taps are loaded? Overloading of a transformer results in excessive
usually specified on larger transformers. temperature. This excessive temperature causes
(5) Use the selection charts in Section I. overheating which will result in rapid deterioration of the
11. What terminations are provided? Primary and insulation and cause complete failure of the transformer coils.
Secondary Terminations are provided on ACME Dry-Type 18. Are temperature rise and actual surface
Transformers as follows: temperature related? No. This can be compared with an
No lugs— lead type connection on ordinary light bulb. The filament temperature of a light bulb
0-25 kVA single phase can exceed 2000 degrees, yet the surface temperature of
0-15 kVA three phase the bulb is low enough to permit touching with bare hands.
Bus-bar terminations 19. What is meant by “impedance” in transformers?
Impedance is the current limiting characteristic of a
(drilled to NEMA standards)
transformer and is expressed in percentage.
37.5 -250 kVA single phase
25-500 kVA three phase Total Winding Temperature °C
12. Can 60 Hz transformers be used at higher frequencies? 220
ACME transformers can be used at frequencies above 60 Hz 30
up through 400 Hz with no limitations provided nameplate
voltages are not exceeded. However, 60 Hz transformers will
180
have less voltage regulation at 400 Hz than 60 Hz.
25
13. What is meant by regulation in a transformer?
Voltage regulation in transformers is the difference between 130
the no load voltage and the full load voltage. This is usually 150
10
expressed in terms of percentage. For example: A transformer 105
delivers 100 volts at no load and the voltage drops to 95 COIL HOT SPOT 10 115
DIFFERENTIAL
volts at full load, the regulation would be 5%. ACME dry- 80
AV. WINDING
type distribution transformers generally have regulation RISE
55
from 2% to 4%, depending on the size and the application 40
AMBIENT 40 40 40
for which they are used.
AGENCY: UL/ANSI 1561 MARCH 1987
14. What is temperature rise in a transformer?
Temperature rise in a transformer is the temperature of Figure A
the windings and insulation above the existing ambient or
surrounding temperature. 20. Why is impedance important? It is used for determining
15. What is “Class” in insulation? Insulation class the interrupting capacity of a circuit breaker or fuse employed
was the original method used to distinguish insulating to protect the primary of a transformer. Example: Determine
materials operating at different temperature levels. Letters a minimum circuit breaker trip rating and interrupting capacity
were used for different designations. Letter classifications for a 10 kVA single phase transformer with 4% impedance,
have been replaced by insulation system temperatures to be operated from a 480 volt 60 Hz source.
in degrees Celsius. The system temperature is the Calculate as follows:
maximum temperature at the hottest spot in the winding
(coil). Graphical representations of six insulation systems Normal Full Load Current =
recognized by Underwriters’ Laboratories, Inc. are shown in Nameplate Volt Amps 10,000 VA
= =
Figure A. These systems are used by Acme for a large part Line Volts 480 V
of the product line. 20.8 Amperes
16. Is one insulation system better than another?
Not necessarily. It depends on the application and the Maximum Short Circuit Amps =
cost benefit to be realized. Higher temperature class Full Load Amps 20.8 Amps
= =
insulation systems cost more and larger transformers are more 4% 4%
expensive to build. Therefore, the more expensive insulation 520 Amps
systems are more likely to be found in the larger kVA units.
The breaker or fuse would have a minimum interrupting rating
Referring to Figure A, small fractional kVA transformers use of 520 amps at 480 volts.
Example: Determine the interrupting capacity, in amperes, of 25. Can transformers listed in this catalog be reconnected
a circuit breaker or fuse required for a 75 kVA, three phase as autotransformers to increase their kVA rating? Several
transformer, with a primary of 480 volts delta and secondary standard single phase transformers listed in this catalog can
of 208Y/120 volts. The transformer impedance (Z) = 5%. If the be connected as autotransformers. The kVA capacity will
secondary is short circuited (faulted), the following capacities be greatly increased when used as an autotransformer,
are required: in comparison to the nameplate kVA as an insulating
transformer. Examples of autotransformer applications are
Normal Full Load Current = changing 600 volts to 480 volts in either single phase or three
Volt Amps 75,000 VA phase; changing 480 volts to 240 volts single or three phase
3 3 x Line Volts 3 3 x 480 V or vice versa; or the developing of a fourth wire (neutral) from
90 Amps a 480 volt three phase three wire system for obtaining 277
volts single phase. This voltage is normally used for operating
Maximum Short Circuit Line Current = fluorescent lamps or similar devices requiring 277 volts. For
Full Load Amps = 90 Amps further details showing kVA and voltage combinations for
5% 5% various autotransformer connections refer to Page 30 and 31
1,800 Amps in this catalog.
26. Are ACME Transformers shown in this catalog U.L.
The breaker or fuse would have a minimum interrupting rating of
Listed? All of the transformers, with few exceptions, are
1,800 amps at 480 volts.
listed by Underwriters’ Laboratories and have met their
NOTE: The secondary voltage is not used in the calculation. rigorous requirements. We are also prepared to have
The reason is the primary circuit of the transformer is the only transformers, which are not presently listed, submitted for
winding being interrupted. listing to Underwriters’ upon the customer’s request. Please
21. Can Single Phase Transformers be used for Three Phase contact the factory for details.
applications? Yes. Three phase transformers are sometimes 27. Is CSA certification available for transformers shown in
not readily available whereas single phase transformers can this catalog? Most ACME transformers shown in this catalog
generally be found in stock. Three single phase transformers can are certified by Canadian Standards Association. They have
be used in delta connected primary and wye or delta connected been designed and tested in accordance with the latest
secondary. They should never be connected wye primary to wye specifications. Please contact the factory if further details
secondary, since this will result in unstable secondary voltage. are required.
The equivalent three phase capacity when properly connected 28. What is BIL and how does it apply to transformers listed
of three single phase transformers is three times the nameplate in this catalog?
rating of each single phase transformer. For example: Three BIL is an abbreviation for Basic Impulse Level. Impulse tests
10 kVA single phase transformers will accommodate a 30 kVA are dielectric tests that consist of the application of a high
three phase load. frequency steep wave front voltage between windings, and
22. Does ACME provide “Zig-Zag” Grounding Transformers? between windings and ground. The Basic Impulse Level of
Yes. Please refer to Page 31 for a special diagram which a transformer is a method of expressing the voltage surge
can be used to connect standard single phase off-the-shelf (lightning, switching surges, etc.) that a transformer will
transformers in a three phase zig-zag manner. This system can tolerate without breakdown. All transformers manufactured
be used for either grounding or developing a fourth wire from in this catalog, 600 volts and below, will withstand the NEMA
a three phase neutral. An example would be to change a 480 standard BIL rating, which is 10 KV. This assures the user
V — three phase — three wire system to a 480Y/277 V — three that he will not experience breakdowns when his system is
phase — four wire system. properly protected with lightning arrestors or similar surge
23. What color are ACME Dry-Type Transformers? protection devices.
ASA 61 (NEMA) light gray is used on all enclosed transformers 29. What is polarity, when associated with a transformer?
from .050 to 1000 kVA. Polarity is the instantaneous voltage obtained from the primary
24. How do you select a transformer to operate in an ambient winding in relation to the secondary winding. Transformers 600
higher than 40° centigrade? volts and below are normally connected in additive polarity —
When the ambient exceeds 40°C use the following chart for that is, when tested the terminals of the high voltage and low
de-rating standard transformers. voltage windings on the left hand side are connected together,
refer to diagram below. This leaves one high voltage and
Maximum Ambient Maximum Percentage H1 H2
Temperature of Loading
240 VOLT
40°C (104°F) 100% INPUT
50°C (122°F) 92%
360
60°C (140°F) 84% ADDITIVE VOLT VOLT
POLARITY METER READING
120 VOLT
Instead of ordering custom built transformers to operate in OUTPUT
ambients higher than 40°C, it is more economical to use a
standard transformer of a larger kVA rating. x2 x1
one low voltage terminal unconnected. When the transformer voltage is low the torque and the horsepower of the motor
is excited, the resultant voltage appearing across a will drop proportionately to the square of the voltage. For
voltmeter will be the sum of the high and low voltage example: If the voltage were to drop to 70% of nominal, then
windings. This is useful when connecting single phase motor horsepower and torque would drop to 70 % squared
transformers in parallel for three phase operations. Polarity is a or 49% of the motor nameplate rating.
term used only with single phase transformers. If the motor is used for starting a high torque load, the motor
30. What is exciting current? Exciting current, when may stay at approximately 50% of normal running speed as
used in connection with transformers, is the current or amperes illustrated by the graph below:
required for excitation. The exciting current on most lighting
and power transformers varies from approximately 10% on 100
SPEED (PERCENT OF
SYNCHROUS SPEED)
small sizes of about 1 kVA and smaller to approximately .5%
80
to 4% on larger sizes of 750 kVA. The exciting current is made
up of two components, one of which is a real component and 60
is in the form of losses or referred to as no load watts; the other 40
STALL
ZONE
is in the form of reactive power and is referred to as kVAR.
20
31. Will a transformer change Three Phase to single phase?
A transformer will not act as a phase changing device when
50 100 150 200 250
attempting to change three phase to single phase. There
is no way that a transformer will take three phase in and TORQUE (PERCENT OF FULL LOAD TORQUE)
deliver single phase out while at the same time presenting SPEED vs TORQUE FOR A TYPICAL THREE PHASE
INDUCTION TYPE SQUIRREL CAGE MOTOR
a balanced load to the three phase supply system. There
are, however, circuits available to change three phase to two
phase or vice versa using standard dual wound transformers. The underlying problem is low voltage at the motor terminals.
Please contact the factory for two phase applications. If the ampere rating of the motor and transformer overcurrent
32. Can air cooled transformers be applied to motor loads? device falls within the motor’s 50% RPM draw requirements,
This is an excellent application for air cooled transformers. a problem is likely to develop. The overcurrent device may not
Even though the inrush or starting current is five to seven open under intermediate motor ampere loading conditions.
times normal running current, the resultant lower voltage Overheating of the motor and/or transformer would occur,
caused by this momentary overloading is actually beneficial possibly causing failure of either component.
in that a cushioning effect on motor starting is the result. The This condition is more pronounced when one transformer is
tables on Pages 11 and 12 illustrate some typical transformer used to power one motor and the running amperes of the
requirements for use with motor applications. motor is in the vicinity of the full load ampere rating of the
33. How is an Acme Drive Isolation Transformer (DIT) transformer. The following precautions should be followed:
different than a General Purpose Tranformer? (1) When one transformer is used to operate one motor, the
DITs, as the name implies, are designed to be used with running amperes of the motor should not exceed 65% of
motor drives (AC and DC) and to provide isolation from the the transformer’s full load ampere rating.
service line. They are specifically designed to withstand the (2) If several motors are being operated from one transformer,
“short circuit like” duty imposed by the firing of the thyristors. avoid having all motors start at the same time. If this is
Harmonics generated by drives create added loads on the impractical, then size the transformer so that the total
transformer. Therefore, it is important that a transformer running current does not exceed 65% of the transformer’s
of equal or greater kVA to that recommended by the drive full load ampere rating.
manufacturer be installed for a particular motor application.
35. Why are Small Distribution Transformers not used for
34. How are transformers sized to operate Three Phase Industrial Control Applications?
induction type squirrel cage motors? The minimum Industrial control equipment demands a momentary overload
transformer kVA rating required to operate a motor is capacity of three to eight times normal capacity. This is most
calculated as follows: prevalent in solenoid or magnetic contactor applications where
Minimum Transformer kVA = inrush currents can be three to eight times as high as normal
Running Load Amperes x 1.73 sealed or holding currents but still maintain normal voltage at
this momentary overloaded condition. Distribution transformers
x Motor Operating Voltage
are designed for good regulation up to 100 percent loading,
1000 but their output voltage will drop rapidly on momentary
NOTE: If motor is to be started more than once per hour add overloads of this type making them unsuitable for high inrush
20% additional kVA. applications.
Care should be exercised in sizing a transformer for an Industrial control transformers are designed especially
induction type squirrel cage motor as when it is started, for maintaining a high degree of regulation even at eight
the lock rotor amperage is approximately 5 to 7 times the times normal load. This results in a larger and generally more
running load amperage. This severe starting overload will expensive transformer. For a complete listing of ACME
result in a drop of the transformer output voltage. When the industrial control transformers, refer to Section V.
36. Can 4-Winding Single Phase Transformer be auto- 38. What is meant by “Balanced Loading” on Single Phase
connected? Yes. There are occasions where 480 volts single Transformer applications? Since most single phase
phase can be stepped down to 240 volts single phase by transformers have a secondary voltage of 120/240, they will
autoconnecting a standard 4-winding isolating transformer be operated as a three wire system. Care must be taken
as shown in Figure 1. If connected in this manner, the in properly distributing the load as the transformer secondary
nameplate kVA is doubled. For example: A 10 kVA load can consists of 2 separate 120 volt windings. Each 120 volt
be applied to a 5 kVA 4-winding transformer if connected per winding is rated at one-half the nameplate kVA rating. For
Figure 1. example: A 10 kVA transformer, 120/240 volt secondary is to
service an 8 kVA load at 240 volts and two 1 kVA loads at
480V 120 volts each.
240V
H1 H3 H2 H4 X1 X3 X2 X4
B 10 KVA
A (NEUTRAL)
If incorrect method is used, phase B will have an 18 kVA If the incorrect method is used, winding A will be loaded
load which is 3 kVA above its normal capacity of 15 kVA and at 6 kVA, and winding B will be loaded at 4 kVA. These
failure will result even though we only have a total load of 27 do total 10 kVA but, since each winding is only rated at
kVA on a 45 kVA transformer. 5 kVA (1/2 of nameplate rating), we have an overloaded
transformer and a certain failure.
Enclosure Definitions
Type 1 Enclosures — are intended for indoor use, 120V 1 KVA
primarily to provide a degree of protection against
240V 8 KVA
contact with the enclosed equipment.
Type 2 Enclosures — are intended for indoor use, 120V 1 KVA
3. If the load nameplate expresses a rating in kVA, a transformer can be 10 83 48 41 36 26 22.7 20.8 16.7
directly selected from the charts. Choose from a group of transformers with 15 125 72 62 54 39 34 31 25
primary and secondary voltages matching those you have just determined. 25 208 120 104 90 65 57 52 41
A. Select a transformer with a standard kVA capacity equal to or greater than 37.5 312 180 156 135 98 85 78 62
50 416 240 208 180 131 114 104 83
that needed to operate the load. 75 625 360 312 270 197 170 156 125
B. Primary taps are available on most models to compensate for line voltage 100 833 480 416 361 263 227 208 166
variations. (Refer to question #2 in the Transformer Questions and Answers 167 1391 802 695 602 439 379 347 278
Section on page 6.) 250 2083 1201 1041 902 657 568 520 416
C. When load ratings are given only in amperes, tables 1 and 2 or the following
formulas may be used to determine proper kVA size for the required transformer. TABLE 2
(1) To determine kVA when volts and amperes are known: Full Load Amperes
Single Phase A.C. Motors {
kVA = Volts x Amps
1000 MIN.
HORSE- 115 V 208 V 230 V TRANS-
(2) To determine Amperes when kVA and volts are known: POWER FORMER
KVA
kVA x 1000 / 4.4 2.4 2.2 .53
Amps = 1 6
Volts /
1 4 5.8 3.2 2.9 .70
Single Phase Example /
1 3 7.2 4.0 3.6 .87
TABLE 3
1. Determine electrical load Full Load Current in Amperes–
A. Voltage required by load. Three Phase Circuits
B. Amperes or kVA required by load. kVA 208 V 240 V 380 V 440 V 480 V 600 V
C. Frequency in Hz (cycles per second). 3 8.3 7.2 4.6 3.9 3.6 2.9
D. Verify load is designed to operate on three phase. 4.5 12.5 10.8 6.8 5.9 5.4 4.3
6 16.6 14.4 9.1 7.8 7.2 5.8
All the above information is standard data normally obtained from equipment
nameplates or instruction manuals. 9 25 21.6 13.7 11.8 10.8 8.6
15 41 36 22.8 19.6 18.0 14.4
2. Determine supply voltage 22.5 62 54 34.2 29 27 21.6
A. Voltage of supply (source). 30 83 72 45.6 39 36 28
B. Frequency in Hz (cycles per second). 45 124 108 68.4 59 54 43
The frequency of the line supply and electrical load must be the same. A three 75 208 180 114 98 90 72
phase transformer is selected which is designed to operate at this frequency 112.5 312 270 171 147 135 108
having a primary (input) equal to the supply voltage and a secondary (output)
150 416 360 228 196 180 144
equal to the voltage required by the load.
225 624 541 342 294 270 216
3. If the load nameplate expresses a rating in kVA, a transformer can be 300 832 721 456 392 360 288
directly selected from the charts. Choose from the group of transformers 500 1387 1202 760 655 601 481
with primary and secondary voltages matching that which you have 750 2081 1804 1139 984 902 721
just determined. 1000 2775 2405 1519 1312 1202 962
A. Select a transformer with a standard kVA capacity equal to or greater than
that needed to operate the load.
B. Primary taps are available on most models to compensate for line voltage TABLE 4
variations. (Refer to question #2 in the Transformer Questions and Answers Full Load Amperes
Section on page 6.) Three Phase A.C. Motors {
MIN.
C. When load ratings are given only in amperes, tables 3 and 4 or the following HORSE- 208 V 230 V 460 V 575 V TRANS-
formulas may be used to determine proper kVA size for the required transformer. POWER FORMER
KVA
(1) To determine three phase kVA when volts and amperes are known: /
1 2 2.2 2.0 1.0 0.8 0.9
Three Phase kVA = /
3 4 3.1 2.8 1.4 1.1 1.2
Volts x Amps x 1.73 1 4.0 3.6 1.8 1.4 1.5
1000 2 7.5 6.8 3.4 2.7 2.7
(2) To determine Amperes when kVA and volts are known: 3 10.7 9.6 4.8 3.9 3.8
3 Phase kVA x 1000 5 16.7 15.2 7.6 6.1 6.3
Amps =
Volts x 1.73 10 31 28 14 11 11.2
15 46 42 21 17 16.6
Three Phase Example 20 59 54 27 22 21.6
Question: Select a transformer to fulfill the following conditions. Load is a three phase 25 75 68 34 27 26.6
induction motor, 25 horsepower @ 240 volts, 60 Hz and a heater load of 4 kilowatts @
30 88 80 40 32 32.4
240 volts single phase. The supply voltage is 480Y/277, three phase, 4 wire.
40 114 104 52 41 43.2
Answer: Compute the kVA required. Motor — From table 4 the current is 68 amps. 50 143 130 65 52 52
240 volts x 68 amps x 1.73 = 28.2 kVA 60 170 154 77 62 64
1000 75 211 192 96 77 80
(The kVA can also be obtained from table 4). 100 273 248 124 99 103
125 342 312 156 125 130
Heater — 4 kVA 150 396 360 180 144 150
A three phase transformer must be selected so that any one phase is not overloaded. 200 528 480 240 192 200
Each phase should have the additional 4 kVA rating required by the heater even though
{ When motor service factor is greater than 1,
the heater will operate on one phase only. So, the transformer should have a minimum increase full load amps proportionally.
kVA rating of 28.2 + 4 + 4 + 4 or 40.2 kVA. Refer to the appropriate selection chart. Example: If service factor is 1.15, increase
A 480 delta primary — 240 delta secondary transformer may be used on a 4 wire, above amp values by 15%.
480Y/277 volt supply. The fourth wire (neutral) is not connected to the transformer. To Volts x Amps x 1.73
not overload the transformer, a 45 kVA transformer should be selected. 3 Phase kVA =
1000
NOTE: Any two wires of the 240 volts, 3 phase developed by the secondary of the NOTE: If motors are started more than once per
transformer may be used to supply the heater. Any 2 wires of a 3 phase system is hour, increase minimum transformer kVA by 20%.
single phase.
FEATURES
Q UL listed, CSA certified and UL-3R enclosures meets or
exceeds all listing criteria including NEMA, ANSI and OSHA
standards.
Q Shielded for cleaner power.
Q Encapsulated and completely enclosed design electrical
grade silica and resin compounds completely enclose the
core and coil to seal out all moisture and air. UL Type 3R
enclosure for indoor or outdoor service. Encapsulation eliminates
corrosion and insulation deterioration.
Q Quiet operation with sound levels well below NEMA standards.
Q Long life UL class 155°C insulation system. 115°C rise thru
.750 kVA; 180°C insulation system, 115°C rise, 1 kVA and above.
APPLICATIONS
FEATURES Q Harsh industrial locations
Q UL listed, CSA certified and UL-3R enclosure meets
or exceeds all listing criteria including NEMA, ANSI and Q Corrosive chemical exposure
OSHA standards. Q Waste water treatment facilities
Q UL Class 180°C insulation system. 115°C rise. Q Coastal or marine applications with high salt mist
Q Extra large front access wiring compartment through 9 kVA; Q Any application where painted cold roll steel is not adequate
top access through 75 kVA for easier installation and cooler
case temperatures.
Q Completely enclosed — suitable for indoor/outdoor
service. Consult selection charts for details. Excellent for
dust or lint laden atmosphere.
Q Encapsulated — electrical grade silica and resin
compound completely encloses the core and coil.
Encapsulation seals out all moisture and air, eliminating
corrosion and insulation deterioration.
Q High efficiency and excellent regulation.
Q Sound levels below NEMA standards.
Q Keyhole mounting slots permit installation of mounting
bolts prior to hanging transformer and are accessible from
the front. Lifting ears for easy installation.
Q Wiring connections can be made outside of wiring
compartment due to the use of flexible leads.
Q 3-9 kVA provided with dual size knockouts in sides and
bottom of wiring compartment.
Q Termination — copper lead wire.
Q Electrostatic shielding provided on all 60 Hz isolation
transformers.
VENTILATED
SINGLE PHASE 37.5 to 250 kVA
THREE PHASE 25 to 1000 kVA
FEATURES
Q With weather shield, UL Type 3R enclosure type 2 enclosure
without weather shield. UL listed and CSA certified.
Q UL Class 220°C insulation system, 150°C rise.
Q Extra large wiring compartment for easier installation and
cooler case temperatures.
Q NEMA standard bus bar terminals, no special tools
needed to make clearly marked connections. Tap
changing easily accomplished with jumpers.
Q Aluminum windings for increased insulation life, cooler
operation, lower losses.
Q Noise and vibration isolating pads standard to assure
quiet operation.
Q Large permanently legible nameplates on front.
Q Single phase units can be banked for 3 phase service.
Q All units have ground studs for use with non-metallic
conduit.
Q Suitable for wall or “trapeze” mounting. Wall brackets are
available for units up to 50 kVA single and 75 kVA
three phase.
Q Other models are available with class 220°C insulation
and either 115°C or 80°C rise operating temperature. Refer
to Opti-Miser ® Section.
Q Termination — single phase 37.5 to 100 kVA, copper bus;
167 to 250 kVA, aluminum bus. Three phase 27 to 225 kVA,
copper bus; Groups D, G & J 30 to 225 kVA and all 275 to
1000 kVA, aluminum bus.
Q Electrostatic shielding provided on all 60 Hz
isolation transformers. Not available on Groups D1 and G.
SINGLE PHASE
GROUP I
240 X 480 PRIMARY VOLTS — 120/240 SECONDARY VOLTS — FOUR WINDINGS — 1Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
{ .05 T153004 6.41 (16.3) 3.14 (8.0) 3.05 (7.7) 4 (1.8) W 0.875 (2.2) NA 1–A
{ .10 T153005 7.16 (18.2) 3.89 (9.9) 3.67 (9.3) 5 (2.3) W 0.875 (2.2) NA 1–A
{ .15 T153006 7.16 (18.2) 3.89 (9.9) 3.67 (9.3) 7 (3.2) W 0.875 (2.2) NA 1–A
{ .25 T253007S 8.68 (22.0) 4.08 (10.4) 3.88 (9.9) 10 (4.5) W 0.50-0.75 (1.3-1.9) NA 2–B
{ .50 T253008S 9.06 (23.0) 4.37 (11.1) 4.20 (10.7) 15 (6.8) W 0.50-0.75 (1.3-1.9) NA 2–B
{ .75 T253009S 9.68 (24.6) 4.75 (12.1) 4.50 (11.4) 19 (8.6) W 0.50-0.75 (1.3-1.9) NA 2–B
1.00 T253010S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W 0.50-0.75 (1.3-1.9) NA 2–B
1.50 T253011S 11.62 (29.5) 5.50 (14.0) 5.13 (13.0) 30 (13.6) W 0.50-0.75 (1.3-1.9) NA 2–B
2.00 T253012S 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W 0.50-0.75 (1.3-1.9) NA 2–B
3.00 T253013S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 2–C
3.00 T2530134S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 3–C
5.00 T253014S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 2–C
5.00 T2530144S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 3–C
7.50 T2535153S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 4–D
10.00 T2535163S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 125 (56.7) W 0.75-1.25 (1.9-3.2) NA 4–D
15.00 T2535173S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 170 (77.1) W 1.00-1.50 (2.5-3.8) NA 4–D
25.00 T2535183S 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 250 (113.0) W 1.00-1.50 (2.5-3.8) NA 4–D
37.50 TP530193S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 280 (127.0) F| NA WSA1 5–E
50.00 TP530203S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 350 (158.8) F| NA WSA1 5–E
75.00 TP530213S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 430 (195.0) F NA WSA3 5–E
100.00 TP530223S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 525 (238.0) F NA WSA4 5–E
167.00 TP530233S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1050 (476.3) F NA WSA5 5–E
250.00 TP530243S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1440 (653.2) F NA WSA5 5–E
Notes: 0.05 through 25.0 kVA encapsulated (exempt from TP1), 37.5 through 250.0 kVA TP1 compliant
GROUP I – 316SS
316 STAINLESS STEEL
240 X 480 PRIMARY VOLTS — 120/240 SECONDARY VOLTS — FOUR WINDINGS — 1Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
0.25 T253007SS 8.68 (22.0) 4.08 (10.4) 3.88 (9.9) 10 (4.5) W NA NA 2-B
0.50 T253008SS 9.06 (23.0) 4.37 (11.1) 4.20 (10.7) 15 (6.8) W NA NA 2-B
0.75 T253009SS 9.68 (24.6) 4.75 (12.1) 4.50 (11.4) 19 (8.6) W NA NA 2-B
1.00 T253010SS 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W NA NA 2-B
1.50 T253011SS 11.62 (29.5) 5.50 (14.0) 5.13 (13.0) 30 (13.6) W NA NA 2-B
2.00 T253012SS 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W NA NA 2-B
3.00 T253013SS 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W NA NA 3-C
5.00 T253014SS 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W NA NA 3-C
7.50 T253515SS 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W NA NA 4-D
10.00 T253516SS 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 125 (56.7) W NA NA 4-D
15.00 T253517SS 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 170 (77.1) W NA NA 4-D
25.00 T253518SS 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 250 (113.0) W NA NA 4-D
Notes: 0.25 through 25.0 kVA encapsulated (exempt from TP1)
{Suitable for 50/60 Hz.
|Wall mounting brackets are available for these sizes, refer to page 133.
GROUP IA
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
240 X 480 PRIMARY VOLTS — COPPER WINDINGS — 120/240 SECONDARY VOLTS — FOUR WINDINGS — 1Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
7.50 TC535153S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 100 (45.4) W 0.75-1.25 (1.9-3.2) NA 4–D
10.00 TC535163S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 120 (54.4) W 0.75-1.25 (1.9-3.2) NA 4–D
15.00 TC535173S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 160 (72.6) W 1.00-1.50 (2.5-3.8) NA 4–D
25.00 TC535183S 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 250 (113.0) W 1.00-1.50 (2.5-3.8) NA 4–D
37.50 TPC530193S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 295 (133.8) F| NA WSA1 5–E
50.00 TPC530203S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 378 (172.0) F| NA WSA1 5–E
Notes: 7.5 through 25.0 kVA encapsulated (exempt from TP1), 37.5 through 50.0 kVA TP1 compliant
GROUP II
NON-VENTILATED TRANSFORMERS — 240 X 480 PRIMARY VOLTS — 120/240 SECONDARY VOLTS — FOUR WINDINGS — 1Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
37.50 TE2530193S 35.47 (90.1) 31.90 (81.0) 26.90 (68.3) 430 (195.0) F| NA NA 5–H
50.00 TE2530203S 35.47 (90.1) 31.90 (81.0) 26.90 (68.3) 430 (195.0) F| NA NA 5–H
75.00 TE2A530213S 35.47 (90.1) 31.90 (81.0) 26.90 (68.3) 525 (238.0) F NA NA 5–H
100.00 TE1530223S 42.00 (106.7) 40.00 (101.6) 30.00 (76.2) 775 (352.0) F NA NA 5–H
Notes: 37.5 through 100.0 kVA non-ventilated (exempt from TP1)
GROUP IV
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
{ .05 T153104 6.41 (16.3) 3.14 (8.0) 3.05 (7.7) 4 (1.8) W 0.875 (2.2) NA 8–A
{ .10 T153105 7.16 (18.2) 3.89 (9.9) 3.67 (9.3) 5 (2.3) W 0.875 (2.2) NA 8–A
{ .15 T153106 7.16 (18.2) 3.89 (9.9) 3.67 (9.3) 7 (3.2) W 0.875 (2.2) NA 8–A
{ .25 T253107S 8.68 (22.0) 4.08 (10.4) 3.88 (9.9) 10 (4.5) W 0.50-0.75 (1.3-1.9) NA 9–B
{ .50 T253108S 9.06 (23.0) 4.37 (11.1) 4.20 (10.7) 15 (6.8) W 0.50-0.75 (1.3-1.9) NA 9–B
{ .75 T253109S 9.68 (24.6) 4.75 (12.1) 4.50 (11.4) 19 (8.6) W 0.50-0.75 (1.3-1.9) NA 9–B
1.00 T253110S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W 0.50-0.75 (1.3-1.9) NA 9–B
1.50 T253111S 11.62 (29.5) 5.50 (14.0) 5.13 (13.0) 30 (13.6) W 0.50-0.75 (1.3-1.9) NA 9–B
2.00 T253112S 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W 0.50-0.75 (1.3-1.9) NA 9–B
3.00 T2531131S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 10–C
5.00 T2531141S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 10–C
7.50 T2536151S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 10–D
10.00 T2536161S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 125 (56.7) W 0.75-1.25 (1.9-3.2) NA 10–D
15.00 T2536171S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 170 (77.1) W 1.00-1.50 (2.5-3.8) NA 10–D
25.00 T2536181S 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 250 (113.0) W 1.00-1.50 (2.5-3.8) NA 10–D
37.50 TP531193S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 275 (125.0) F| NA WSA1 11-E
50.00 TP531203S 29.90 (76.0) 28.15 (71.5) 22.37 (56.8) 340 (154.0) F| NA WSA2 11–E
75.00 TP531213S 35.47 (90.0) 31.90 (81.0) 26.88 (68.3) 430 (195.0) F NA WSA3 11-E
100.00 TP531223S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 525 (238.0) F NA WSA4 11-E
167.00 TP531233S 45.60 (115.8) 39.5 (100.3) 35.5 (90.2) 1050 (476.3) F NA WSA5 11-E
Notes: 0.05 kVA through 25.0 kVA encapsulated (exempt from TP1), 37.5 through 167.0 kVA C802 compliant
GROUP V
208 PRIMARY VOLTS — 120/240 SECONDARY VOLTS — THREE WINDINGS — 1Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
37.5 TP536491S 25.48 (64.7) 24.39 (62.0) 19.37 (49.2) 257 (117.0) F| N/A WSA1 58–E
50.0 TP536503S 25.48 (64.7) 24.39 (62.0) 19.37 (49.2) 340 (154.2) F| N/A WSA1 17–E
75.0 TP536513S 35.40 (89.9) 31.90 (81.0) 26.88 (68.2) 420 (190.5) F| N/A WSA3 17–E
Notes: 1.0 kVA through 25.0 kVA encapsulated (exempt from TP1), 37.5 through 75 kVA TP1 compliant
GROUP VII
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
1.0 T279740S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 23 (10.4) W 0.50-0.75 (1.3-1.9) NA 23–B
1.5 T279741S 11.62 (29.5) 5.50 (14.0) 5.13 (13.0) 30 (13.6) W 0.50-0.75 (1.3-1.9) NA 23–B
2.0 T279742S 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 37 (16.8) W 0.50-0.75 (1.3-1.9) NA 23–B
3.0 T279743S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 23–C
5.0 T279744S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 23–C
7.5 T279745S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 105 (47.6) W 0.75-1.25 (1.9-3.2) NA 63–D
10.0 T279746S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 124 (56.2) W 0.75-1.25 (1.9-3.2) NA 63–D
15.0 T279747S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 171 (77.6) W 1.00-1.50 (2.5-3.8) NA 63–D
25.0 T279748S 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 261 (118.4) W 1.00-1.50 (2.5-3.8) NA 63–D
GROUP VIII
AUTO-TRANSFORMERS
240 PRIMARY VOLTS — 120/240 SECONDARY VOLTS — 1Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
1.0 T253060 9.06 (23.0) 4.37 (11.1) 4.20 (10.7) 15 (6.8) W 0.50-0.75 (1.3-1.9) NA 12–B
1.5 T253061 9.68 (24.6) 4.50 (11.4) 4.51 (11.5) 19 (8.6) W 0.50-0.75 (1.3-1.9) NA 12–B
2.0 T253062 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W 0.50-0.75 (1.3-1.9) NA 12–B
3.0 T253063 11.62 (29.5) 5.50 (14.0) 5.13 (13.0) 30 (13.6) W 0.50-0.75 (1.3-1.9) NA 12–B
5.0 T253064 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W 0.50-0.75 (1.3-1.9) NA 12–B
7.5 T253065 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 12–C
10.0 T253066 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 12–D
15.0 T253067 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 12–D
GROUP IX
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
EXPORT MODEL
190/200/208/220 X 380/400/416/440 PRIMARY VOLTS
120/240 SECONDARY VOLTS — 1Ø, 50/60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
* 1.0 TF217437S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W 0.50-0.75 (1.3-1.9) NA 14–B
* 2.0 TF217439S 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W 0.50-0.75 (1.3-1.9) NA 14–B
* 3.0 TF249873S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 14–C
* 5.0 TF252520S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 14–C
* 7.5 TF252794S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 14–D
* 10.0 TF252795S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 125 (56.7) W 0.75-1.25 (1.9-3.2) NA 14–D
* 15.0 TF252796S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 170 (77.1) W 1.00-1.50 (2.5-3.8) NA 14–D
* 25.0 TF252797S 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 300 (136.0) W 1.00-1.50 (2.5-3.8) NA 14–D
* CE Marked
GROUP X
EXPORT MODEL|
190/208/220/240 x 380/416/440/480 PRIMARY VOLTS –– 120/240 SECONDARY VOLTS –– 1Ø, 50/60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
*1.0 TF279260S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W 0.50-0.75 (1.3-1.9) NA 64–B
*2.0 TF279261S 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W 0.50-0.75 (1.3-1.9) NA 64–B
*3.0 TF279262S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 64–C
*5.0 TF279263S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 64–C
*7.5 TF279264S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 64–D
*10.0 TF279265S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 125 (56.7) W 0.75-1.25 (1.9-3.2) NA 64–D
*15.0 TF279266S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 170 (77.1) W 1.00-1.50 (2.5-3.8) NA 64–D
*25.0 TF279267S 18.44 (46.8) 16.13 (41.0) 13.34 (33.9) 300 (136.1) W 1.00-1.50 (2.5-3.8) NA 64–D
* CE Marked
GROUP XI
EXPORT MODEL|
190/200/208/220 x 380/400/416/440 PRIMARY VOLTS –– 110/220 SECONDARY VOLTS –– 1Ø, 50/60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
*1.0 TF279300S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 24 (10.9) W 0.50-0.75 (1.3-1.9) NA 65–B
*2.0 TF279301S 13.00 (33.0) 5.50 (14.0) 5.13 (13.0) 38 (17.2) W 0.50-0.75 (1.3-1.9) NA 65–B
*3.0 TF279302S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 55 (24.9) W 0.75-1.25 (1.9-3.2) NA 65–C
*5.0 TF279303S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 65–C
*7.5 TF279304S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 115 (52.2) W 0.75-1.25 (1.9-3.2) NA 65–D
* CE Marked
{ Wall mounting brackets are available for these sizes, refer to page 133.
| Maximum exciting current 5% at 50 Hz.
GROUP XII
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
0.25 GP12250S 8.68 (22.0) 4.08 (10.4) 3.88 (9.9) 12 (5.4) W 0.50-0.75 (1.3-1.9) NA 78-B
0.50 GP12500S 9.06 (23.0) 4.37 (11.1) 4.20 (10.7) 19 (8.6) W 0.50-0.75 (1.3-1.9) NA 78-B
1.00 GP121000S 10.50 (26.7) 5.50 (14.0) 5.13 (13.0) 30 (13.6) W 0.50-0.75 (1.3-1.9) NA 78-B
3.00 GP123000S 11.50 (29.2) 10.31 (26.2) 7.13 (18.1) 58 (26.3) W 0.75-1.25 (1.9-3.2) NA 78-C
5.00 GP125000S 14.38 (36.5) 10.31 (26.2) 7.13 (18.1) 80 (36.3) W 0.75-1.25 (1.9-3.2) NA 78-C
10.00 GP1210000S 15.19 (38.6) 13.50 (34.3) 10.84 (27.5) 125 (56.7) W 0.75-1.25 (1.9-3.2) NA 78-D
15.00 GP1215000S 16.94 (43.0) 14.12 (35.9) 11.59 (29.4) 161 (70.0) W 1.00-1.50 (2.5-3.8) NA 79-D
GROUP A
208 DELTA PRIMARY VOLTS –– 480Y/277 SECONDARY VOLTS –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
15.0 T3793671S 18.86 (48.0) 20.30 (51.6) 9.03 (22.9) 245 (111.0) F{ NA NA 48–I
30.0 TP793684S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 330 (150.0) F{ NA WSA1 46–E
45.0 TP793694S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 400 (181.0) F{ NA WSA1 46–E
75.0 TP793704S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 530 (240.0) F{ NA WSA2 46–E
112.5 TP793714S 35.47 (90.1) 31.90 (81.0) 26.90 (68.3) 750 (340.0) F NA WSA3 46–E
150.0 TP793724S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 950 (430.9) F NA WSA4 46–E
225.0 TP793734S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1200 (544.0) F NA WSA4 46–E
300.0 TP793744S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1550 (703.0) F NA WSA5 46–E
Notes: 15 kVA unit encapsulated (exempt from TP1), 30 through 300 kVA TP1 compliant
GROUP B
240 DELTA PRIMARY VOLTS –– 208Y/120 SECONDARY VOLTS –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
9.0 T2A533601S 14.03 (36.0) 17.77 (45.1) 11.52 (29.3) 180 (81.6) W 0.75-1.25 (1.9-3.2) NA 18–F
15.0 T3533611S 18.86 (48.0) 20.30 (51.6) 9.03 (23.0) 250 (113.0) F{ NA NA 18–I
30.0 TP533624S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 325 (147.0) F{ NA WSA1 19–E
45.0 TP533634S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 350 (158.8) F{ NA WSA1 19–E
75.0 TP533644S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 450 (204.1) F{ NA WSA2 19–E
112.5 TP533654S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 696 (294.8) F NA WSA3 19–E
150.0 TP533664S 41.52 (105.5) 32.90 (84.0) 29.87 (75.9) 978 (412.8) F NA WSA4 19–E
225.0 TP533674S 41.52 (105.5) 32.90 (84.0) 29.87 (75.9) 1200 (544.0) F NA WSA4 19–E
Notes: 9.0 through 15.0 kVA units encapsulated (exempt from TP1), 30 kVA through 225 kVA TP1 compliant
{ Wall mounting brackets are available for these sizes, refer to page 133.
| Consult factory for wiring diagram.
GROUP D
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
480 DELTA PRIMARY VOLTS –– 208Y/120 SECONDARY VOLTS –– MAY BE USED ON A 4 WIRE 480Y/277 VOLT SUPPLY –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
3.0 T2A533081S 10.38 (26.4) 12.37 (31.4) 7.47 (19.0) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 21–F
6.0 T2A533091S 11.83 (30.0) 14.17 (36.0) 8.82 (22.4) 140 (63.5) W 0.75-1.25 (1.9-3.2) NA 21–F
9.0 T2A533101S 14.03 (36.0) 17.77 (45.1) 11.52 (29.3) 180 (81.6) W 0.75-1.25 (1.9-3.2) NA 21–F
15.0 T3533111S 18.86 (48.0) 20.30 (51.6) 9.03 (22.9) 250 (113.0) F{ NA NA 21–I
30.0 TP533123S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 290 (132.0) F{ NA WSA1 22–E
45.0 TP533133S 25.50 (64.7) 24.39 (61.9) 19.37 (49.2) 400 (181.0) F{ NA WSA1 22–E
75.0 TP533143S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 500 (226.8) F{ NA WSA2 22–E
112.5 TP533153S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 750 (340.0) F NA WSA3 22–E
150.0 TP533163S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 970 (440.0) F NA WSA4 22–E
225.0 TP1533173S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1200 (544.0) F NA WSA4 22–E
300.0 TP533183S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1550 (703.0) F NA WSA5 22–E
500.0 TP1533193S 57.80 (146.8) 45.60 (115.8) 41.50 (105.4) 2480 (1125.0) F NA WSA7 22–G
750.0 TP1533213S 62.80 (159.5) 54.00 (137.2) 41.50 (105.4) 3600 (1633.0) F NA WSA6 22–G
1000.0 TP1533222S 62.80 (159.5) 54.00 (137.2) 41.50 (105.4) 4300 (1950.0) F NA WSA6 80–G
Notes: 3.0 through 15.0 kVA units encapsulated (exempt from TP1), 30.0 through1000.0 kVA TP1 compliant
GROUP D2
480 DELTA PRIMARY VOLTS –– COPPER WINDINGS –– 208Y/120 SECONDARY VOLTS, 150°C RISE –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
15.0 TC533111S* 18.90 (48.0) 20.30 (51.6) 9.00 (22.9) 245 (111.1) F{ NA NA 21–I
30.0 TPC533123S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 346 (157.0) F{ NA WSA1 22–E
45.0 TPC533133S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 397 (180.1) F{ NA WSA1 22–E
75.0 TPC533143S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 521 (236.3) F{ NA WSA2 22–E
112.5 TPC533153S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 766 (347.5) F NA WSA3 22–E
150.0 TPC533163S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1026 (465.4) F NA WSA4 22–E
225.0 TPC533173S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1300 (589.7) F NA WSA4 22–E
300.0 TPC533183S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1551 (703.5) F NA WSA5 22–E
500.0 TPC533193S 57.80 (146.8) 45.00 (114.3) 41.50 (105.4) 2819 (1278.7) F NA WSA7 22–E
* NOTE: TC-53311-1S––Encapsulated, 115° C Rise, 180°C Insulation (TP1 exempt), 30.0 through 500 kVA TP1 compliant
{ Wall mounting brackets are available for these sizes, refer to page 133.
| Consult factory for wiring diagram.
GROUP D4
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
115°C RISE
480 DELTA PRIMARY VOLTS — 208Y/120 SECONDARY VOLTS — MAY BE USED ON A 4 WIRE 480Y/277 VOLT SUPPLY — 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
30.0 TP533121S 29.48 (74.9) 28.15 (71.5) 22.37 (56.8) 360 (163.3) F{ NA WSA2 22-E
45.0 TP533131S 29.48 (74.9) 28.15 (71.5) 22.37 (56.8) 417 (189.2) F{ NA WSA2 22-E
75.0 TP533141S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 536 (243.1) F{ NA WSA3 22-E
112.5 TP533151S 41.50 (105.4) 32.90 (83.6) 29.90 (75.9) 760 (344.7) F NA WSA4 22-E
150.0 TP533161S 41.50 (105.4) 32.90 (83.6) 29.90 (75.9) 950 (430.9) F NA WSA4 22-E
225.0 TP533171S 45.59 (115.8) 39.50 (100.3) 35.50 (90.2) 1567 (712.3) F NA WSA5 22-E
300.0 TP533181S 45.59 (115.8) 39.50 (100.3) 35.50 (90.2) 1553 (705.9) F NA WSA5 22-E
500.0 TP533191S 57.84 (146.9) 45.50 (115.6) 41.50 (105.4) 2808 (1276.4) F NA WSA7 22-G
GROUP D5
80°C RISE
480 DELTA PRIMARY VOLTS — 208Y/120 SECONDARY VOLTS — MAY BE USED ON A 4 WIRE 480Y/277 VOLT SUPPLY — 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
30.0 TP533128S 25.49 (64.7) 24.39 (61.9) 19.37 (49.2) 364 (165.1) F{ NA WSA1 22–E
45.0 TP533138S 29.48 (74.9) 28.15 (71.5) 22.37 (56.8) 500 (226.8) F NA WSA2 22–E
75.0 TP533148S 35.90 (91.2) 31.90 (81.0) 26.88 (68.3) 698 (316.6) F NA WSA3 22–E
112.5 TP533158S 41.50 (105.4) 32.90 (83.6) 29.90 (75.9) 963 (437.7) F NA WSA4 22–E
150.0 TP533168S 41.50 (105.4) 32.90 (83.6) 29.90 (75.9) 1145 (520.4) F NA WSA4 22–E
For Copper Wound Transformers Consult Factory
For Additional Low Temperature Rise 115° and 80°C Units Consult Factory
GROUP F
ENCAPSULATED TRANSFORMERS, 115°C RISE
480 DELTA PRIMARY VOLTS — 208Y/120 SECONDARY VOLTS — 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
30.0 T3793123S 24.81 (63.0) 27.13 (68.9) 11.14 (28.3) 613 (278.1) F NA NA 22–I
45.0 T3793133S 25.31 (64.3) 30.18 (76.7) 12.76 (32.4) 780 (354.0) F NA NA 22–I
75.0 T3793143S 26.82 (68.1) 34.68 (88.1) 15.25 (38.7) 1126 (511.0) F NA NA 22–I
Notes: 30.0 through 75.0 kVA encapsulated (TP1 exempt)
{ Wall mounting brackets are available for these sizes, refer to page 133.
24 ACME ELECTRIC U MILWAUKEE, WI U 800.334.5214 U acmetransformer.com
SECTION
1
GROUP F – 316 SS
DRY-TYPE DISTRIBUTION TRANSFORMERS
GROUP G
480 DELTA PRIMARY VOLTS –– 240 DELTA / 120 TAP SECONDARY VOLTS
MAY BE USED ON A 4 WIRE 480Y/277 VOLT SUPPLY –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA| CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
3.0 T2A-533281S 10.38 (26.4) 12.37 (31.4) 7.47 (19.0) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 25–F
6.0 T2A-533291S 11.83 (30.0) 14.17 (36.0) 8.82 (22.4) 140 (63.5) W 0.75-1.25 (1.9-3.2) NA 25–F
9.0 T2A-533401S 14.03 (36.0) 17.77 (45.1) 11.52 (29.3) 180 (81.6) W 0.75-1.25 (1.9-3.2) NA 25–F
15.0 T3-533411S 18.86 (47.9) 20.30 (51.6) 9.03 (22.9) 250 (113.0) F{ NA NA 25–I
30.0 TP1533423S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 325 (147.0) F{ NA WSA1 26–E
45.0 TP1533433S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 400 (181.0) F{ NA WSA1 26–E
75.0 TP1533443S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 500 (226.8) F{ NA WSA2 26–E
112.5 TP1533453S 35.47 (91.2) 31.90 (81.0) 26.88 (68.3) 750 (340.0) F NA WSA3 26–E
150.0 TP1533463S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1125 (510.0) F NA WSA4 26–E
225.0 TP1533473S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1200 (544.0) F NA WSA4 26–E
300.0 TP1533483S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1550 (703.0) F NA WSA5 26–G
500.0 TP1533493S 62.00 (157.5) 54.00 (137.2) 42.00 (106.7) 2675 (1213.0) F NA WSA7 26–G
750.0 TP1533503S 62.80 (159.5) 54.00 (137.2) 41.50 (105.4) 3408 (1545.8) F NA WSA6 26–G
Notes: 3.0 through 15.0 kVA units encapsulated (TP1 exempt), 30.0 through 750.0 kVA TP1 compliant. 3.0 kVA through 750.0 kVA provided with 120V lighting
tap limited to 5% of nameplate rating.
{ Wall mounting brackets are available for these sizes, refer to page 133.
GROUP I
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
15.0 T335000153S 18.86 (48.0) 20.30 (51.6) 9.03 (22.9) 250 (113.0) F{ NA NA 31–I
30.0 TP35000303S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 325 (147.0) F{ NA WSA2 31–E
45.0 TP135000453S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 400 (181.0) F{ NA WSA2 31–E
75.0 TP35000753S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 600 (272.0) F{ NA WSA2 31–E
112.5 TP35001123S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 710 (322.0) F NA WSA3 31–E
150.0 TP35001503S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1155 (524.0) F NA WSA4 31–E
225.0 TP35002253S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 1210 (548.8) F NA WSA4 31–E
300.0 TP35003003S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1600 (726.0) F NA WSA5 31–E
Notes: 15.0 kVA unit encapsulated (TP1 exempt), 30.0 through 300.0 kVA TP1 compliant
GROUP J
600 DELTA PRIMARY VOLTS –– 208Y/120 SECONDARY VOLTS –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
3.0 T2A-793301S 10.38 (26.4) 12.37 (31.4) 7.47 (19.0) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 28–F
6.0 T2A-793311S 11.83 (30.0) 14.17 (36.0) 8.82 (22.4) 140 (63.5) W 0.75-1.25 (1.9-3.2) NA 28–F
9.0 T2A-793321S 14.03 (36.0) 17.77 (45.1) 11.52 (29.3) 180 (81.6) W 0.75-1.25 (1.9-3.2) NA 28–F
15.0 T3-793331S 18.86 (47.9) 20.30 (51.6) 9.03 (22.9) 250 (113.0) F{ NA NA 28–I
30.0 TP131023S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 325 (147.0) F{ NA WSA1 29–E
45.0 TP131033S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 400 (181.0) F{ NA WSA1 29–E
75.0 TP131043S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 600 (272.0) F{ NA WSA2 29–E
112.5 TP-131053S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 750 (340.0) F NA WSA3 29-E
150.0 TP-131063S 41.52 (105.5 32.90 (83.6) 29.87 (75.9) 970 (440) F NA WSA4 29-E
225.0 TP-131073S 41.52 (105.5 32.90 (83.6) 29.87 (75.9) 1200 (544) F NA WSA4 29-E
300.0 TP-130993S 45.60 (115.8) 39.50 (100.3) 35.50 (90.2) 1550 (703.0) F NA WSA5 29-E
500.0 TP-131123S 57.84 (146.9) 45.00 (114.3) 41.50 (105.4) 2480 (1125.0) F NA WSA7 29-E
750.0 TP-131133S 62.84 (159.6) 54.00 (137.2) 41.50 (105.4) 3600 (1633.0) F NA WSA6 29-E
Notes: 3.0 through 15.0 kVA encapsulated (TP1 exempt), 30.0 through 75.0 kVA TP1 compliant
{ Wall mounting brackets are available for these sizes, refer to page 133.
GROUP M
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
GROUP 0
208 DELTA PRIMARY VOLTS –– 208Y/120 SECONDARY VOLTS –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
3.0 T2A792681S 10.38 (26.4) 12.37 (31.4) 7.47 (19.0) 75 (34.0) W 0.75-1.25 (1.9-3.2) NA 60–F
6.0 T2A792691S 11.83 (30.0) 14.17 (36.0) 8.82 (22.4) 140 (63.5) W 0.75-1.25 (1.9-3.2) NA 60–F
9.0 T2A792701S 14.03 (36.0) 17.77 (45.1) 11.52 (29.3) 180 (81.6) W 0.75-1.25 (1.9-3.2) NA 60–F
15.0 T3-792711S 18.86 (48.0) 20.30 (51.6) 9.03 (22.9) 245 (111.0) F{ NA NA 60–I
30.0 TP792724S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 300 (136.0) F{ NA WSA1 61–E
45.0 TP792734S 25.48 (64.7) 24.39 (61.9) 19.37 (49.2) 365 (166.0) F{ NA WSA1 61–E
75.0 TP792744S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 500 (227.0) F{ NA WSA2 61–E
Notes: 3.0 through 15.0 kVA units are encapsulated (TP1 exempt), 30.0 through 75.0 kVA units are TP1 compliant
GROUP P
600 DELTA PRIMARY VOLTS –– 240 DELTA/120 TAP SECONDARY VOLTS –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
30.0 TP131423S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 299 (135.6) F{ NA WSA1 69–E
45.0 TP131433S 25.48 (64.7) 24.39 (61.9) 19.37 (49.2) 353 (160.1) F{ NA WSA1 69–E
75.0 TP131443S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 463 (210.0) F{ NA WSA2 69–E
Notes: 30.0 through 75.0 kVA units TP1 compliant
GROUP Q
240 DELTA PRIMARY VOLTS –– 480Y/277 SECONDARY VOLTS –– 3Ø, 60 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
15.0 T3-796931S 18.86 (48.0) 20.30 (51.6) 9.03 (22.9) 245 (111.1) F{ NA NA 70–I
30.0 TP796944S 25.50 (64.8) 24.39 (61.9) 19.37 (49.2) 330 (149.7) F{ NA WSA1 71–E
45.0 TP796954S 25.48 (64.7) 24.39 (61.9) 19.37 (49.2) 380 (172.4) F{ NA WSA1 71–E
75.0 TP796964S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 455 (206.4) F{ NA WSA2 71–E
112.5 TP796974S 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 687 (311.6) F NA WSA3 71–E
150.0 TP796984S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 973 (441.3) F NA WSA4 71–E
Notes: 15 kVA unit encapsulated (TP1 exempt), 30.0 through 150.0 kVA TP1 compliant
{Wall mounting brackets are available for these sizes, refer to page 133.
GROUP T
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
15.0 T3795511S 20.80 (52.8) 20.90 (53.1) 10.20 (25.9) 435 (197.3) F NA NA 24–I
30.0 T2A795523S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 365 (165.6) F{ NA WSA1 20–E
45.0 T2A795533S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 468 (212.3) F{ NA WSA2 20–E
75.0 T2A795543S 35.47 (90.1) 31.90 (80.0) 26.88 (68.3) 693 (314.3) F NA WSA3 20–E
112.5 T2A795553S 41.52 (105.5) 32.90 (83.6) 29.87 (75.9) 970 (440.0) F NA WSA4 20–E
Notes: 50 Hz units (TP1 exempt)
GROUP U
440 DELTA PRIMARY VOLTS –– 220Y/127 SECONDARY VOLTS –– 3Ø, 50 Hz
APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
kVA CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
10.0 TF220105S 18.90 (48.0) 20.30 (51.6) 9.00 (22.9) 245 (111.1) F{ NA NA 73–I
15.0 TF220155S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 291 (132.0) F{ NA WSA1 73–E
25.0 TF220255S 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 375 (170.1) F{ NA WSA1 73–E
50.0 TF220505S 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 437 (198.2) F{ NA WSA2 73–E
Notes: 50 Hz units (TP1 exempt)
{ Wall mounting brackets are available for these sizes, refer to page 133.
GROUP V
1 DRY-TYPE DISTRIBUTION TRANSFORMERS
15.0 T379083S 18.86 (47.9) 20.30 (51.6) 9.03 (22.9) 300 (136.1) F{ NA NA 75-I
30.0 TP79085S 29.90 (75.9) 28.15 (71.5) 22.37 (56.8) 511 (231.8) F NA WSA2 74-E
45.0 TP79087S 25.50 (64.8) 24.39 (62.0) 19.37 (49.2) 540 (244.9) F NA WSA1 74-E
75.0 TP79088S 35.90 (91.2) 31.90 (81.0) 26.88 (68.3) 703 (318.9) F NA WSA3 74-E
Notes: 15.0 kVA unit encapsulated (TP1 exempt), 30.0 through 75.0 kVA units TP1 compliant
AUTO-TRANSFORMERS
600 PRIMARY VOLTS –– 480 SECONDARY VOLTS –– 3Ø, 60 Hz
480 PRIMARY VOLTS –– 380 SECONDARY VOLTS –– 3Ø, 50/60 Hz ALTERNATE RATING
kVA APPROX. DIMENSIONS APPROX. TYPE MTG. WEATHER Wiring Diagrams &
600 Pri. 480 Pri. CATALOG NO. Inches (Cm.) SHIP WEIGHT W – Wall KNOCKOUTS SHIELD Design Figures
480V Sec. 380 Sec. HEIGHT WIDTH DEPTH Lbs. (Kg.) F – Floor Inches (Cm.) P/N Begin on Page 122
15.0 12.0 T2527031} 15.21 (38.6) 19.25 (48.9) 7.37 (18.7) 104 (47.2) W NA NA 56–F
30.0 24.0 T2527051} 15.21 (38.6) 19.25 (48.9) 7.37 (18.7) 152 (68.9) W NA NA 56–F
45.0 36.0 T2527071} 15.21 (38.6) 19.25 (48.9) 7.37 (18.7) 156 (70.8) W NA NA 56–F
75.0 60.0 T3527101} 18.86 (47.9) 20.30 (51.6) 9.03 (22.9) 300 (136.1) F{ NA NA 56–I
112.5 90.0 T2A527121~ 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 325 (147.0) F NA WSA1 57–E
150.0 120.0 T2A527131~ 25.50 (64.8) 24.40 (62.0) 19.40 (49.3) 350 (158.8) F NA WSA1 57–E
225.0 180.0 T2A527151~ 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 600 (272.0) F NA WSA2 57–E
300.0 240.0 T2A527171~ 29.41 (74.7) 28.15 (71.5) 22.37 (56.8) 650 (294.8) F NA WSA2 57–E
450.0 360.0 T2A527181~ 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 750 (340.0) F NA WSA3 57–E
500.0 400.0 T2A527191~ 35.47 (90.1) 31.90 (81.0) 26.88 (68.3) 790 (358.3) F NA WSA3 57–E
Notes: Auto-Transformers TP1 exempt
{ Wall mounting brackets use PL-79911. } These units are encapsulated with a 115° C temperature rise.
| If used on unbalanced loads, these units should only be used on a 4 wire ~ These units are ventilated with 150° C temperature rise.
system with the supply neutral connected to the transformer. If used on
balanced loads, such as motor loads, then they may be used on a 3 wire Wall mounting brackets use PL-79912.
system without a neutral or 4th wire.
600 A
12.0 11.55 14.40 9.5 11.55 14.40 2 T253011S 15 OR
B
C
480
17.0 16.33 20.41 13.5 16.33 20.41 2 T253012S 25 VOLTS
X X
25.0 24.06 30.01 20.0 24.06 30.01 2 T2530134S 30
X X
TR
#2
S.
NS
AN
X X
.
H H
{ kVA capacity of three phase autotransformer bank, using two single phase, 60 Hz transformers
connected open delta.
| Catalog No. is for 1 transformer, 2 units are required.
} Can be reverse connected with no change in kVA.
~For transformer dimensions, refer to appropriate table in section 1, page 17.
For proper overcurrent protection, refer to Article 450-4 of N.E.C.
The diagrams above are for illustration purposes only. Please contact the factory for construction details.
Each Acme transformer is shipped with detailed wiring diagrams. Refer to nameplate located inside the front
cover for specific voltage tap combinations.
See Footnote|
H H H
H H H
H H H
H H H
NEUTRAL
TRANS. #1 TRANS. #2 TRANS. #3
Each Acme transformer is shipped with detailed wiring diagrams. Refer to nameplate located inside the front
cover for specific voltage tap combinations.
THREE PHASE
VOLTAGES AVAILABLE ACME VOLTAGES AVAILABLE ACME
TYPE OF TYPE OF
KVA DRAWING KVA DRAWING
INPUT OUTPUT CIRCUIT INPUT OUTPUT CIRCUIT
RANGE NO. RANGE NO.
208 Delta 208Y/120 3-75 Isolation A-125879 416Y/240 208Y/120 3-15 Isolation A-700319
208 Delta 208Y/120 3-86 Auto Zig-Zag { A-125895 416Y/240 208Y/120 22.5-75 Isolation A-700322
208 Delta 240 Delta/120 1.68-25.2 O.D. ISO A-700314 480 Delta 240 Delta/120 1.68-5.04 O.D. ISO Hi-Leg { A-125849
208 Delta 240 Delta 3-75 Isolation A-125880 480 Delta 240 Delta/120 3.36 O.D. ISO Hi-Leg { A-125850
208 Delta 416Y/240 3-75 Isolation A-700598 480 Delta 240 Delta/120 5.04 O.D. ISO Hi-Leg { A-125851
208 Delta 416Y/240 112.5-300 Isolation A-700591 480 Delta 240 Delta/120 8.4 O.D. ISO Hi-Leg { A-125852
208Y/120 208Y/120 3-75 Isolation A-125857 480 Delta 240 Delta/120 12.6-25.2 O.D. ISO Hi-Leg { A-125853
208Y/120 374Y/216 22.5-75 Isolation A-125883 480 Delta 240 Delta/120 42 O.D. ISO Hi-Leg { A-125854
208Y/120 374Y/216 112.5-750 Isolation A-102730 480 Delta 240 Delta/120 63-266 O.D. ISO Hi-Leg { A-111702
208Y/120 480Y/277 3-75 Isolation B-39881 (pg 2) 480 Delta 240 Delta 1.68-8.4 O.D. ISO A-32817-B
240 Delta 208Y/120 3-15 Isolation A-125855 480 Delta 240 Delta 5.04-8.4 O.D. ISO A-125872
240 Delta 208Y/120 9-15 Isolation A-102723 480 Delta 240 Delta 12.6-42 O.D. ISO A-125873
240 Delta 208Y/120 22.5-75 Isolation A-102722-B 480 Delta 240 Delta 63-420 O.D. ISO A-125874
240 Delta 208Y/120 112.5-750 Isolation A-125856 480 Delta 416Y/240 3-15 Isolation A-125875
240 Delta 208Y/120 3-75 Isolation A-125858 480 Delta 416Y/240 9-15 Isolation A-125876
240 Delta 240 Delta 3-75 Isolation A-125859 480 Delta 416Y/240 22.5-75 Isolation A-125877
240 Delta 240Y/138 10.3-258.75 Auto Zig-Zag { A-125896 480 Delta 416Y/240 112.5-750 Isolation A-125878
240 Delta 374Y/216 22.5-75 Isolation A-125881 480 Delta 394Y/228 9-15 Isolation A-125884
240 Delta 374Y/216 112.5-750 Isolation A-125882 480 Delta 394Y/228 22.5-75 Isolation A-125885
240 Delta 480Y/277 3-75 Isolation B-39881 (pg 1) 480 Delta 394Y/228 112.5-750 Isolation A-125886
380 Delta 240 Delta 3-75 Isolation A-700592 600 Delta 208Y/120 3-6 Isolation A-102758
380 Delta 240 Delta 112.5-300 Isolation A-700593 600 Delta 208Y/120 9-75 Isolation A-125863
380 Delta 228 Delta 1.4-7.0 O.D. Auto A-35633 600 Delta 208Y/120 112.5-500 Isolation A-125864
380 Delta 228 Delta 4.2-7.0 O.D. Auto A-125892 600 Delta 240 Delta 3-6 Isolation A-125860
380 Delta 228 Delta 10.4-34.5 O.D. Auto A-125893 600 Delta 240 Delta 9-75 Isolation A-125861
380 Delta 228 Delta 51-227 O.D. Auto A-125894 600 Delta 240 Delta 112.5-500 Isolation A-125862
380 Delta 416Y/240 3-75 Isolation A-700599 600 Delta 240 Delta/120 1.68-2.52 O.D. ISO Hi-Leg { A-125865
380 Delta 416Y/240 112.5-300 Isolation A-700594 600 Delta 240 Delta/120 3.36 O.D. ISO Hi-Leg { A-125866
380Y/220 240 Delta 3-75 Isolation A-700600 600 Delta 240 Delta/120 5.04-25.2 O.D. ISO Hi-Leg { A-125867
380Y/220 240 Delta 112.5-300 Isolation A-700595 600 Delta 240 Delta/120 42 O.D. ISO Hi-Leg { A-125868
416Y/240 440 Delta 3-75 Isolation A-700602 600 Delta 240 Delta/120 63-168 O.D. ISO Hi-Leg { A-125869
416Y/240 440 Delta 112.5-300 Isolation A-700597 600 Delta 240 Delta 1.68-3.36 O.D. ISO A-33227-A
416 Delta 240 Delta 3-75 Isolation A-700601 600 Delta 240 Delta 5.04-42 O.D. ISO A-125870
416 Delta 240 Delta 112.5-300 Isolation A-700596 600 Delta 240 Delta 63-280 O.D. ISO A-125871
KEY:
O.D. — Open Delta
ISO — Isolation
AUTO — Autotransformer