Water Temperature Control - Recirculation Systems

Digital
The Brain® Model DMC40
DMC40 is a fully Digital Mixing Center (DMC) designed specifically to
be the primary water temperature controller in a continuously pumped
circulating hot water system.

Digital technology provides enhanced water temperature control


accuracy which resists zero system demand “Temperature Creep”
without the use of a manual throttling valve or a temperature activated
pump shut-off device (aquastat).

Operational Specifications (DRV40)


• +/-2°F DRV water temperature control at peak, moderate or zero
fixture demand on hot water system designed for continuous
recirculation
• 2˚F minimum recirculating water temperature differential
• LCD display which indicates: set point, delivered temperature,
error codes and alarm conditions capable of BAS and mobile
connectivity
• Programmable set point range of 81-158°F (27-70°C) capable of
BAS or mobile monitoring and adjustment
• Programmable thermal disinfection range of 158-185°F (70-85°C)
• Programmable 1st level hi/lo temp alarm display capable of BAS
or mobile alerting
• Automatic safe closure of hot water inlet in response to: inlet
supply failure, 110V power failure, or programmable high
temperature error
• Automatic safe closure of hot water inlet powered by a
replaceable lithium battery monitored for low-level alerting

Technical Specifications (DRV40)


• 100-240V AC
• Polymer Electronics Enclosure
• Stainless Steel Valve Construction
• Lead Free compliant
• Maximum inlet HW supply temperature 185°F (85°C)
• Minimum Continuous Recirculation - 5 GPM (19 LPM)
• Minimum System Draw Off - 0 GPM
• Conforms to ASSE 1017, CSA B125.3-11, UL E357437, and CE
• Operational water pressure of 10-150 psig (7-10 barg)
• Display in °C or °F
• Shipping weight 340 lbs (154 kg)
• Integral MODBUS RTU for direct connectivity to BAS, or SAGE®

Connectivity
RS485 Serial Port – Integral MODBUS RTU for direct connectivity
to BAS. Seamless integration with SAGE® (BS) connectivity options.

See DMC40BS for SAGE® (BS) module available with specific


ProtoCessor cards for BAS Connectivity to systems which operate on
Modbus TCP, BACnet™, or LonWorks™ protocols. Mobile Connectivity
may be enabled by a customer activated no-term subscription.

Mobile Connectivity features smart hot water system dashboard


monitoring, secure remote programming, multi-location view,
temperature and system diagnostic alerts, with unlimited digital
documentation and automated report generation.

For a submittal drawing, refer to D40805.


GRecirculation Systems - Digital (GPM and PSIG)
Model Pressure Drop (PSIG)
Minimum System Draw-Off Maximum Flow @7.5 ft/sec. CV
DMC40 5 10 15 20
GPM 48 70 85 98 0 41 22

Recirculation Systems - Digital (LPM and BARG)


Model Pressure Drop (BARG)
Minimum System Draw-Off Maximum Flow @7.5 ft/sec. CV
DMC40 0.3 0.7 1.0 1.4
LPM 181.7 265.0 321.8 371.0 0 155 22