This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx
Scheme Rules, IECEx 02 and Operational Documents as amended.
STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was
found to comply with the following standards:
IEC 60079-0 : 2004 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition:4.0
IEC 60079-1 : 2007-04 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:6
IEC 60079-15 : 2005-03 Electrical apparatus for explosive gas atmospheres Part 15: Construction, test and Marking of Type of
Edition:3 Protection "n" electrical apparatus
IEC 60079-7 : 2006-07 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4
IEC 61241-0 : 2004 Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
Edition:1
IEC 61241-1 : 2004 Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
Edition:1
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the
Test Report:
GB/SIR/QAR06.0011/00 GB/SIR/QAR07.0009/02
IECEx Certificate
of Conformity
Certificate No: IECEx SIR 06.0043X Issue No: 7
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
The E** series Type ranges of cable glands consist of a male-threaded front entry component containing an elastomeric
sealing ring and a Nylon 6 skid washer which effect flameproof sealing onto the cable inner sheath and is intended to
screw into an entry point of its associated enclosure in accordance with relevant codes of practice. The flameproof seal is
actuated by an adjoining coupling component. The coupling component is attached to a main body. Their mating thread
may be fitted with an optional ‘O’ ring seal to provide increased ingress protection. Clamping of the armoured or braided
cable is effected by a combination of the coupling component, main body and the different optional armour cone and
armour sleeve combinations being fastened together. An outer seal nut, containing an elastomeric sealing ring and a Nylon
6 ferrule, threads onto the main body and effects environmental sealing onto the cable outer sheath. Cable clamping is
achieved with the outer seal arrangement.
The E** type cable glands shall only be used where the temperature, at the point of entry, is between -60°C to
1. +130°C.
2. The E** type cable glands terminated on braided cables are not suitable for group I applications.
3. The E** type cable glands are fitted with one specific size of FLP sealing ring per gland size as supplied
4. The E** type cable glands used for terminating braided cables are only suitable for fixed installations. Cables must
be effectively clamped to prevent pulling or twisting.
5. The E** type of cable gland entry component threads may need additional sealing to maintain the ingress
protection rating as applicable to the associated equipment in which it will be attached.
6. When assembled for fitting to flexible conduit, the conduit shall be effectively clamped to prevent twisting and
pulling
IECEx Certificate
of Conformity
Certificate No: IECEx SIR 06.0043X Issue No: 7
Annex:
C = Fitted with the alternative cast integral earth lug entry component.
W = Fitted with single plain armour cone & reversible armour sleeve to suit SWA cables.
X = Fitted with single grooved armour cone & reversible armour sleeve to suit STA, strip armoured,
pliable wire armoured and braided cables
U = Fitted with reversible armour cone & reversible armour sleeve to suit SWA, STA, strip
armoured, pliable wire armoured and braided cables.
1 = Standard circular armoured and braided cables.
2 = Inner seal fitted with additional metallic continuity diaphragm for the use with inner lead sheathed SWA,
strip armoured and braided cables.