Owner'S and Operator'S Manual: Vertical, Water-Cooled 4-Cycle Diesel Engine
Owner'S and Operator'S Manual: Vertical, Water-Cooled 4-Cycle Diesel Engine
California Proposition 65
WARNING
Breathing diesel engine exhaust exposes you to chemicals known to the State of California to
cause cancer and birth defects or other reproductive harm.
Always start and operate the engine in a well ventilated area.
If in an enclosed area, vent the exhaust to the outside.
Do not modify or tamper with the exhaust system.
Do not idle the engine except as necessary.
For more information go to www.P65warnings.ca.gov/diesel.
WARNING
Cancer and reproductive Harm-
www.P65Warnings.ca.gov
WARNING
Batteries, battery posts, terminals and related accessories contain lead and lead compounds, and
other chemicals known to the State of California to cause cancer and birth defects or other
reproductive harm. WASH HANDS AFTER HANDLING.
CAUTION
Do not operate the Generator, or any other appliance, before you have read and understood the
instructions for use and keep near for ready use.
DGK70F
X753-006 86 2
X753801-000 3
Introduction
Thank you for purchasing this Shindaiwa soundproof diesel engine generator.
This manual has been created to ensure safe usage of this generator. Be sure to read this
manual before operation. Improper operation/handling of this generator will result in an
accident or malfunction.
Handling/Operation of this generator can only be performed by persons who understand the
contents of this manual and can handle/operate the generator in a safe manner. Persons who
suffer from an illness, are taking medicine or not feeling well such that safe operation would
be negatively affected must not operate this generator.
Work performed using this generator and handling/operation of this generator must be in
accordance with corresponding laws and regulations based on such laws. Consult with the
authorized distributor where this generator was purchased if you have any inquiries regarding
the corresponding laws.
Always be sure to include this manual when loaning out this generator and instruct operating
personnel to read this manual before operation.
Store this manual in a specified location where it will be secure and available for consulting at
any time. Order another copy from the authorized distributor where this generator was
purchased if this manual becomes dusty, grimy or torn.
Consult with the authorized distributor where this generator was purchased if you have any
inquiries regarding any points related to this generator and manual.
When inquiring about this generator, be sure to provide the model name and serial number.
Note that CAUTION items can also lead to major accidents under some circumstances
if not correctly followed.
All caution notices are important. Be sure to follow all of them.
Table of Contents
1. Safety Instructions ······························································ 2
2. Specifications ····································································· 6
2-1. Specifications·································································· 6
2-2. Ambient Conditions ·························································· 7
3. Applications········································································ 7
4. Part Names ········································································· 7
4-1. External View/Part Names ················································· 7
4-2. Operation Panel Configuration ········································· 10
5. Equipment ········································································ 11
5-1. Three-phase and Single-phase simultaneous Output ············ 11
5-2. Available Output Monitor ················································· 11
5-3. Spill Containment··························································· 11
5-4. Warning Indicators ························································· 12
5-5. SCR (Selective Catalytic Reduction) System and Indicators ··· 15
5-6. Meters and Gauges ························································ 18
5-7. Fuel Piping Switch (3Way Fuel Valve) ································ 21
5-8. Load Bank Control Switch ··············································· 22
6. Transport/Installation ························································· 22
6-1. Transport Procedures ····················································· 22
6-2. Installation Procedures ··················································· 23
7. Load Connections ····························································· 24
7-1. Load Cable Selection ····················································· 24
7-2. Connecting Load Cables ················································· 24
8. Pre-Operation Inspection ··················································· 28
8-1. Checking Engine Oil ······················································· 28
8-2. Checking Coolant ·························································· 29
8-3. Checking the Fan Belt ···················································· 30
8-4. Checking the Fuel ·························································· 31
8-5. Checking the DEF(Diesel Exhaust Fluid) ···························· 32
8-6. Checking the Spill Containment ········································ 32
8-7. Checking for Fuel, Oil and Coolant Leak····························· 33
8-8. Checking the Battery ······················································ 33
9. Operating Procedures ························································ 34
9-1. Initial Startup/Pre-Check ················································· 34
9-2. 240/480V Switching Selection ·········································· 36
9-3. Procedures during Operation ··········································· 36
9-4. Stopping Operation ························································ 37
9-5. Protective Functions ······················································· 38
9-6. Connecting with External Fuel Tank ··································· 39
10. Inspection/Maintenance ···················································· 40
11. Long-Term Storage ·························································· 54
12. Troubleshooting ······························································ 55
13. Generator Circuit Diagram ················································ 58
14. Engine Electrical Circuit Diagram ······································ 59
1
1. Safety Instructions
WARNING : INJURY
Close all doors and lock them during operation.
Do not open the check door during operation. Keep away from moving parts such as
cooling fan and fan belt.
Always be sure to stop the engine and remove the starter key when performing inspection
or maintenance.
Use the lifting hook to lift the machines, and do not lift up by using tie downs. Use of such
could result in the generator falling.
Do not lift any additional weight such as fuel tanks or trailers.
No persons should ever be under a lifted generator.
Always be sure to check that the breakers on load side and switches for any equipment
using the generator are at OFF before turning the breaker to ON. Also be sure to advise
personnel on the load side that power will be turned on or off before operating the breaker.
Do not modify the equipment and do not operate with parts removed.
Do not use the fuel tank lifting hook to lift up when the fuel tank that contains fuel, and also
do not lift up with the fuel tank and spill containment as a single unit. Doing so could result
in the tank falling.
2
CAUTION : EXPLOSION
Never use or recharge the battery if the fluid level is below the minimum level.
Do not create sparks or bring flame near the battery as it generates flammable gas.
CAUTION : FIRE
Do not carry flammable items (such as fuel, gas and paint) or items that are highly
combustible near the generator as the muffler, exhaust gas and other parts become
extremely hot.
Position this generator 3 ft. (1 m) or more from walls or other hindrances, and on a level
surface.
Do not connect the generator output to indoor wiring.
This generator uses diesel fuel. Always be sure to stop the engine and not bring flames
close when inspecting fuel or refueling. Wait until the engine has cooled before performing
such procedures.
If fuel spills, always be sure to open the spill containment drain valve and drain off the
spilled fuel.
Do not operate the equipment with liquid accumulated in the spill containment.
If fuel or oil is leaking, repair the leaking location before operating.
Always be sure to wipe up any spilled fuel or oil.
Allow the generator to cool before covering with the protective cover.
Never allow flame to come close to the generator.
Always make sure that the engine is stopped when working on piping.
After working on the piping, check that there is no fuel leakage.
Absolutely never inspect or perform maintenance to the equipment near fire or other open
flame.
Do not put anything other than DEF (gasoline, diesel fuel, etc.) in the DEF tank. Also, do
not put DEF diluted with water or other liquids.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
Do not open the radiator cap immediately after stopping the engine. Doing so will result in
hot steam gushing out.
Hot steam gushes out from the coolant sub-tank if the generator overheats. Do not touch
the coolant sub-tank.
Always be sure to stop the engine and allow the engine to cool when performing inspection
or maintenance of engine oil. Opening the oil level gauge or oil filler cap during operation
will result in hot oil gushing out.
While the engine is running, the SCR system is purging, and immediately after operating,
the SCR system and exhaust piping is extremely hot. Be careful not to inadvertently touch
them.
Do not touch the SCR system and surrounding components immediately after stopping the
engine as they are still extremely hot.
3
CAUTION : INJURY
Always be sure to use lifting hooks when lifting up the generator, and slowly lift it straight
up.
Personnel performing lifting work must wear protective gear such as helmets, safety shoes
and gloves.
Remove the wood ties if using anchors to secure the generator.
Position the generator on a level stable surface so that it cannot slide or move in any
manner.
Before starting operation, always be sure to turn off all switches of equipment using the
generator and all breakers to OFF.
Do not move the generator during operation.
Do not operate the generator if it has been modified or any parts have been removed.
Securely fix the equipment with rope or similar item so that it cannot move when
transporting by truck or other vehicle.
4
■ Warning /Caution Label Locations
If warning or caution labels become damaged and difficult to read, replace with new labels in
the indicated locations. Order labels using part number indicated in the parenthesis.
FUEL TANK
BATTERY
15
5
2. Specifications
2-1. Specifications
Model Unit DGK70F
Generator Type - Revolving Field Brushless
Rated Frequency Hz 60
kVA 70
Three phase
kW 56
Rated Output(Prime)
kVA 42 [21] *1
Single phase
kW 42 [21] *1
kVA 77
Three phase
kW 61.6
Standby Output
kVA 46.2 [23.1] *1
Single phase
Alternator
kW 46.2 [23.1] *1
Three phase V 208/240/ [480] *1
Rated Voltage
Single phase V 120/139/240/[277] *1
Three phase-208V A 168
Three phase-240V A 168
Rated Current Three phase-480V A 84
Single phase-120V A 175×2 [87.5 x 2]*1
Single phase-240V A 175 [175]*1
Power Factor - Three phase 0.8, Single phase 1.0
Insulation class - F
Excitation - Self Excitation (brushless)
No. of Poles - 4
Type - Vertical Water-Cooled 4-Cycle Diesel
Model(Manufacturer) - 4JJ1X(ISUZU)
No. of Cylinders
(in./mm) 4(3.76x4.13/95.4x104.9)
(bore × stroke)
Continuous Rated Output hp 86.5
Rated Speed rpm 1,800
Displacement cu.in./liters 183/2.999
Combustion System - Direct injection (Turbo-charged)
Cooling Method - Water cooled
Starting Method - Electric
Engine
6
2-2. Ambient Conditions
Use this generator in ambient conditions as described below. Failure to provide these
conditions can result in problems such as malfunction, insufficient output and reduced
durability.
3. Applications
Power source for submerged pumps and similar civil engineering equipment
Power source for lighting and similar equipment
Power source for electrical tools and household appliances
4. Part Names
Tie-Down
Spill Containment
Drain Plug
Inspection/Cleaning
Panel
Spill Containment
Terminal Cover
Drain Valve
Fuel Drain Plug
7
SCR Check Panel
Tie-Down
DEF Tank
Check Panel
Fan Guard
Radiator
Intercooler Alternater
Check Door
8
Oil Level Gauge
Air Cleaner Oil Filler Oil Filter Coolant Sub-Tank
Fan Guard
Engine
Check Door
Alternator Check Door
Fuel Filter
(Pre)
Battery
Muffler
(SCR)
Dosing Module
DEF Tank
Accessories
Owner’s Engine
and Warranty
Operator’s Manual
Manual
9
4-2. Operation Panel Configuration
10
5. Equipment
WARNING : INJURY
Do not open the check door during operation. Keep away from moving parts such as
cooling fan and fan belt.
Always be sure to stop the engine and remove the starter key when performing
inspection or maintenance.
11
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
CAUTION : FIRE
If fuel or oil is leaking, repair the leaking location before operating.
The bed of this generator is equipped with the spill containment (structure for preventing
leakage of liquid) so that any spilled liquid will not leak to outside of the generator when oil or
fuel is spilled or leak. Before starting operation, check if there is accumulated liquid in the spill
containment. Flush out any liquid that has accumulated.
(Refer to section “8-6. Checking the Spill Containment” for inspection procedures. )
(Refer to section “10. Inspection/Maintenance (12) Flushing Liquid in Spill Containment”
for flushing procedures.)
The generator is equipped with the following in order to prevent liquid from spilling in case you
forget to flush the liquid: The operation panel is equipped with the SPILL CONTAINMENT
CHECKING indicator that illuminates when its sensor is triggered as the spill containment
capacity accumulated enough liquid to reach to about 15.2gal (57.4 liters).
If the liquid stored in the spill containment exceeds approximately about 26.4gal (100 liters)
during operation, the SPILL CONTAINMENT OVERFLOW WARNING indicator illuminates, and
the engine will be automatically stopped. If this occurs, flush the liquid stored in the spill
containment.
(Refer to section “10. Inspection/Maintenance (12) Flushing Liquid in Spill Containment”.)
< Note >
Water can also accumulate in the spill containment due to rain entering into the generator.
Accordingly, you should periodically flush liquid accumulated within the generator. However,
you should flush water according to the frequency/amount of rainfall.
The types of liquids that can accumulate in the spill containment include oil, fuel, coolant,
battery fluid and DEF such that it is not possible to distinguish between rainwater and other
liquids. Dispose of flushed liquids according to the applicable laws and regulations.
5-4. Warning Indicators
WARNING : INJURY
Do not open the check door during operation. Keep away from moving parts such as
cooling fan and fan belt.
Always be sure to stop the engine and remove the starter key when performing
inspection or maintenance.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
12
This generator is equipped with the following warning indicators: BATTERY (battery charge),
OIL PRESS (engine oil pressure), WATER TEMP (coolant temperature), OVER SPEED
(engine overspeed), AIR FILTER (air cleaner clogging), SPILL CONTAINMENT (spill
containment amount), and ENGINE (engine malfunction). When the engine starts, all the lamps
will be lights off. An indicator illuminates if a malfunction/fault occurs during operation and the
engine automatically stops depending on the fault type. Moving the starter switch from STOP to
RUN causes the BATTERY warning indicator to illuminates and ENGINE for warning indicator
to illuminates approximately 3 sec.
(1) BATTERY (Battery Charge) Warning Indicator (Low Battery Voltage)
The BATTERY warning indicator illuminates when charging is not possible during operation. If
this occurs, contact authorized distributor where the generator was purchased.
< Note >
This battery charging warning indicator cannot detect battery deterioration or insufficient
battery fluid. (Refer to section “8-8. Checking the Battery”.)
(2) OIL PRESS (Engine Oil Pressure) Warning Indicator (Low Oil Press.)
CAUTION: BURNS
Always be sure to stop the engine and allow the engine to cool when performing
inspection or maintenance of engine oil. Opening the oil gauge or oil filler cap during
operation will result in hot oil gushing out.
If the engine oil pressure drops below 7 psi (0.48 x 100 kPa) during operation, the OIL PRESS
warning indicators illuminates, and the engine will be automatically stopped.If this occurs,
check the engine oil level and add engine oil until it reaches the maximum level.
< Note >
This oil pressure warning indicator cannot detect oil deterioration. Change the engine oil
periodically. (Refer to section “8-1. Checking Engine Oil”.)
(3) WATER TEMP (Coolant Temperature) Warning Indicator (High Water Temp.)
CAUTION: BURNS
Do not open the radiator cap immediately after stopping the engine.Do so will result in
hot steam gushing out.
Hot steam gushes out from the coolant sub-tank if the generator overheats. Do not
touch the coolant sub-tank.
If the coolant temperature rises above 212°F(100℃) during operation, the WATER TEMP
warning indicators illuminates, and the engine will be automatically stopped. If this occurs, hot
steam will gush out of the coolant sub-tank. Check the coolant sub-tank coolant level after the
generator cools and add coolant to the coolant sub-tank if it is insufficient. (Refer to section “8-2.
Checking Coolant”.) If the coolant is at the specified amount, it is probable that the fan belt is
loose or there is a coolant leak. Wait for the engine to cool down and inspect for these
problems.
< Note >
The coolant temperature cannot be detected if the coolant level is excessively low. Always be
sure to check the coolant level in the radiator coolant sub-tank before starting operation.
13
(4) OVER SPEED (Engine Overspeed) Warning Indicator
This generator is equipped with a function such that the engine is automatically stopped if an
engine fault occurs causing the engine speed to increase excessively. If the engine speed rose
above 2070rpm during operation, the OVER SPEED warning indicators and ENGINE warning
indicators illuminates, and the engine will be automatically stopped. If this occurs, it is probable
that some malfunction has occurred in the engine. Contact authorized distributor where the
generator was purchased.
(5) AIR FILTER (Air Cleaner Clogging) Warning Indicator
The AIR FILTER warning indicator illuminates if the air cleaner element becomes clogged
during operation. If it illuminates, immediately stop the engine and clean or replace the air
cleaner element.
(Refer to section “10. Inspection/Maintenance (3) Air Filter Element Cleaning/Replacement”.)
(6) SPILL CONTAINMENT (Spill Containment Amount) Checking Indicator
The SPILL CONTAINMENT checking indicator illuminates if the liquid
stored in the spill containment exceeds approximately about 15.2gal
(57.4 liters) during operation. If it illuminates, immediately stop the
engine and flush the liquid stored in the spill containment.
(Refer to section “10. Inspection/Maintenance (12) Flushing Liquid
in Spill Containment”.) SPILL CONTAINMENT
Checking Indicator
< Note >
The engine may not be stopped only if the spill containment checking Indicator illuminates
during operation.
When the spill containment checking Indicator illuminates during operation, stop the engine,
check for fuel, oil, cooling water and DEF leakage, and repair as necessary.
Do not use the equipment with liquid accumulated in the spill containment. Drain the spill
containment before using.
(7) SPILL CONTAINMENT (Spill Containment Amount) Overflow Warning Indicator
If the liquid stored in the spill containment exceeds approximately
about 26.4gal (100 liters) during operation, the SPILL
CONTAINMENT overflow warning indicator illuminates, and the
engine automatically stops. If this occurs, flush the liquid stored in
the spill containment.
(Refer to section “10. Inspection/Maintenance (12) Flushing
SPILL CONTAINMENT
Liquid in Spill Containment”.) Overflow Warning Indicator
< Note >
Although the fluids that can leak internally consist of oil, fuel, cooling water and DEF, the spill
containment does not have a function that can separate rainwater that has leaked into the
equipment from these internally leaked fluids. Properly dispose of liquid drained from the spill
containment in a manner according to the applicable laws and regulations.
(8) ENGINE (Engine Malfunction) Warning Indicator
The ENGINE warning indicator illuminates if the coolant temperature is high, the oil pressure is
low, the engine overspeeds, the battery voltage is low or some other engine fault occurs during
operation. If this occurs, a malfunction code is displayed on the engine and available output
monitors, and the engine automatically stops or the engine output is reduced.
If the ENGINE warning indicator illuminates, contact the authorized distributor where the
generator was purchased.
14
5-5. SCR (Selective Catalytic Reduction) System and Indicators
WARNING : INJURY
Do not open the check door during operation. Keep away from moving parts such as
cooling fan and fan belt.
Always be sure to stop the engine and remove the starter key when performing
inspection or maintenance.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
While the engine is running, the SCR system is purging, and immediately after
operating, the SCR system and exhaust piping is extremely hot. Be careful not to
inadvertently touch them.
In order to meet requirements set forth by EPA Tier4 (Final), the SCR system is equipped to
reduce nitrogen oxides (NOx) in exhaust emissions, and Diesel Exhaust Fluid (DEF) is used as
a reducing agent.
Use DEF that is compliant with the ISO (International Organization for Standardization) 22241
standard defined for AUS 32, or the API (American Petroleum Institute) standards.
DEF, or other similar urea fluids, may be called AdBlueⓇ depending on region.
AdBlueⓇ is a registered trademark of Verband der Automobilindustrie (VDA).
15
■ DEF LEVEL Lamp Action
PERIODIC PURGE
Purge runs automatically after certain period of operating time. PERIODIC PURGE is lit
during operation.
FORCE PURGE
Purge forcibly runs in case that PERIODIC PURGE fails twice. FORCE PURGE is lit during
operation.
< Note >
During purging, electrical output capacity decreases to 80% of the rated output. Available
output capacity can be confirmed by Available Output Monitor.
FORCE PURGE failure does not stop the engine. Instead, the engine warning lamp will be lit.
In this case, contact distributor or dealer and ask for repair.
White smoke may be temporarily seen from the tailpipe during purging, but it is not a sign of
malfunction.
Smell of ammonia may be noticed during purging, but it is not a sign of malfunction.
Abnormal noise can be heard during purging, but it is not a sign of malfunction.
16
■ SCR System Purge Lamp Action
LAMP PERIODIC FORCE
PURGE
MODE PURGE PURGE
○ ○
PERIODIC PURGE -
(Turn ON) (Turn ON)
○ ○
FORCE PURGE -
(Turn ON) (Turn ON)
REFILL DEF
It is lit when the amount of DEF decreases to 10% or less.
Replenish DEF when it is lit.
EXH. SYSTEM
It lights up when abnormality of SCR System is detected.
Please contact distributor or dealer for repair.
ESCAPE MODE
It is lit when ESCAPE MODE is engaged.
(Refer to section "5-5. (4) Operating Escape Mode")
NO POWER (SHUTDOWN)
It is lit when the engine stops due to DEF shortfall or SCR system error.
Contact the authorized distributor where the generator was purchased.
Stage-Ⅰ ○ ○ ○
- -
Warning (Turn ON) (Turn ON) (Turn ON)
Stage-Ⅱ ○ ○ ○
- -
Early Inducement (Slow Blinking) (Turn ON) (Turn ON)
Stage-Ⅲ
○ ○ ○ ○
Final Inducement -
(Quick Blinking) (Turn ON) (Turn ON) (Turn ON)
(Engine Shutdown)
○ ○ ○ ○
ESCAPE MODE -
(Quick Blinking) (Turn ON) (Turn ON) (Turn ON)
17
1 Turn the Starter switch to RUN/PREHEAT. Control Box
2 Loosen the knob on the operation panel and
open the panel.
3 Press the escape mode switch (blue button) in
the control box. (Make sure that the escape
mode lamp is lit.)
4 Close the operation panel and tighten the knob.
5 Change the switch to START and start the
engine.
< Note >
Knob Operation Panel
ESCAPE MODE is available for total up to 30
minutes.On and after 30 minutes, the procedure
above described is never applicable, and the engine Escape Mode Switch
never restarts. (Blue Button)
Upon completing repair during ESCAPE MODE, it
automatically switches back to the normal mode.
Oil Press
Displays the pressure of the engine lubrication system. Normal pressure displayed during
operation should generally between 43 and 85 psi (2.90-5.90 x 100 kPa) depending on
usage. However, the pressure may rise above this range just after starting a cold engine. Idle
the engine until it reaches the normal pressure.
18
(3) Fuel Level
It shows the amount of fuel in the tank.
All lamps are lit when the amount reaches to the maximum level, and FULL is lit.
The lit lamp decreases as the amount of fuel in the tank reaches to EMPTY.
The fuel level on the control panel will only display the fuel level for the internal fuel tank.
(1) Voltmeter
The voltmeter displays the three-phase output
voltage (voltage between L1-L3). Check that 240
V is displayed during operation. Output voltage for
single-phase three-wire (voltage between U-W) is
the same voltage as the three-phase output
voltage (voltage between L1-L3). Accordingly, use
the voltage meter displayed value as a reference.
* Check that 480 V is displayed during operation if using at the three-phase 480 V setting. The
voltage of single-phase three-wire output of “U-W Voltage” is a value that is one half of the
displayed voltage meter value.
(2) Ammeter
Displays the output current (phase current) of the generator. Turn the ammeter selector switch
to “L1+U” to display the output current of the three-phase L1 phase and single-phase U phase.
Turn the switch to “L3+W” to display the output current of the three-phase L3 phase and
single-phase W phase. “L2” displays the output current of three-phase output terminal L2.
< Note >
If measuring the output current for a single-phase three-wire type, turn the ammeter selector
switch to “L1+U” or “L3+W”. The voltage cannot be accurately measured if set to “L2”.
(3) Frequency Meter
Displays the frequency of the power source. Check that 60 Hz is displayed during operation.
Indicators
19
Switches
START
Position where the engine is started. If you remove your hand from the key, it returns to RUN
automatically.
(2) Breaker
This switch is for transmitting electrical power to the load side. Turn to ON position to output
voltage to the output terminals. Output to the load side is cut off when there is a short circuit or
overload on the load side.
< Note >
Do not turns off/on the breaker manually to operate or stop a load.
(3) Breaker Trip Selector Switch
This switch is for selecting the tripping order of the three-phase and single-phase breaker when
there is a short circuit or overload on the load side. If the three-phase or single-phase breaker
is selected for precedence in tripping, the selected breaker will trip first when the total generator
output exceeds the rated capacity.
After that, the other breaker will also trip if the generator output exceeds the rated capacity
again.
Switch Selection
“3 1”: The three-phase breaker trips first followed by the single-phase breaker.
“Simultaneous (3 1)”: The three-phase and single-phase breakers trip simultaneously.
“1 3”: The single-phase breaker trips first followed by the three-phase breaker.
20
(4) Ammeter Selector Switch
This switch is for selecting the output current indicated by the ammeter. Change the switch to
display the following output terminal current on the ammeter.
Switch Selection
“L1+U”: Three-phase L1 phase + Single-phase three-wire U phase (total)
“L2”: Three-phase L2 phase
“L3+W”: Three-phase L3 phase + Single-phase three-wire W phase (total)
< Note >
If measuring the output current for a single-phase three-wire type, turn the ammeter selector
switch to “L1+U” or “L3+W”. The voltage cannot be accurately measured if set to “L2”.
CAUTION : FIRE
Always make sure that the engine is stopped when working on piping.
Always be sure to wipe up any spilled fuel.
After working on the piping, check that there is no fuel leakage.
Change the three-way fuel valve to switch to supply fuel from the external tank. In that case,
the internal fuel tank will not be used.
(1) If using the internal fuel tank
Change the lever of the three-way fuel valve turned to the “B” side to supply fuel from the
internal tank. It is turned to the “B” side when the generator is shipped from the factory.
< Note >
When disconnecting piping from the external tank, turn the lever to the “B” side, and attach
the bundled plug (R1/2”) to the external tank fuel inlet/return.
(2) If using an external fuel tank
Connect hoses from the external fuel tank to the external fuel inlet and the external fuel return.
Change the lever of the 3way fuel valve to the “A” side to supply fuel from the external tank.
Refer to “9-6. Connecting with External Fuel Tank” for corresponding procedures.
21
3Way Fuel Valve
6. Transport/Installation
WARNING : INJURY
Do not lift up the unit using tie down. Use of such could result in the generator falling.
No persons should ever be under a lifted generator.
CAUTION : INJURY
Always be sure to use lifting hooks when lifting up the generator, and raise it slowly at
a completely vertical angle.
Personnel performing lifting work must wear protective gear such as helmets, safety
shoes and gloves.
Do not move the generator during operation.
22
(2) Transport
When transporting this generator, tie rope to the left and right tie downs, and securely fix the
generator.
Lifting Tie-Down
Hook
CAUTION : FIRE
Do not carry flammable items (such as fuel, gas and paint) or items that are highly
combustible near the generator as the muffler, exhaust gas and other parts become
extremely hot.
Operate this generator 3 ft. (1 m) or more from walls or other hindrances, and on a
level surface.
Remove the wood ties if using anchors to secure the generator.
Do not connect the generator output to indoor wiring.
If installing this generator, set up barriers or fencing completely around the boundary line of
the construction area and take measures to prevent persons not involved in the construction
from entering the area.
Position this generator on a hard, flat and leveled surface.
Position this generator 3 ft. (1 m) or more from walls or other hindrances so that the operation
panel door and left/right check doors are accessible for internal inspection/maintenance.
< Note >
This generator is manufactured presupposing that it will be installed on a flat, hard and
leveled surface. Accordingly, care must be taken as using under any other installation
conditions can result in a fault or malfunction.
Do not place any objects where they will interfere with the radiator or muffler exhaust ports.
Objects interfering with these ports will result in reduced engine output, overheating, and
electrical component fault/malfunction.
Operating the equipment in dusty or excessively salty location can result in a clogged radiator
or overheating resulting in malfunction/fault or reduced insulation of electrical components.
Be sure to thoroughly inspect and perform maintenance if using in such locations.
23
7. Load Connections
Select cable for use that has sufficient thickness and an allowable current for use, and distance
from the generator to the equipment using the generator.
< Note >
Select cable with a thickness that ensures that the voltage drop across the cable will be within
5% of the rated voltage.
Load Cable Selection Tables
(Ex.) If used voltage is 240 V and voltage drops by 12 V.
Three-phase: Cabtyre cables
(Unit: AWG)
Length 100 ft (30 m) 200 ft 300 ft 400 ft 500 ft 600 ft
Current or less (61 m) (91 m) (122 m) (152 m) (183 m)
50 A 10 8 6 4 4 2
100 A 8 4 2 1 1 1/0
150 A 6 2 1 1/0 2/0 3/0
200 A 4 1 1/0 2/0 3/0 4/0
24
CAUTION : FIRE
Do not connect the generator output to indoor wiring.
L1 L2 L3 N GROUND
Load
For single-phase load:
Terminal voltage is 139/277 V.
L1 L2 L3 N GROUND
L1 L2 L3 N GROUND
25
(2) Single-Phase Three-Wire Output Terminal and Receptacle
For single-phase three-wire type load:
U-W terminal voltage is 240 V.
U-N terminal voltage is 120 V.
W-N terminal voltage is 120 V.
N GROUND U W N GROUND U W
Load
Load Load
CON2 CON4
Load Load Load
Load Load
26
Power available for use by each output terminal and receptacle are as show below.
N GROUND U W
CON5,CON6,CON7
120V
(U-N)
CON1 CON3
Load Load
CON2 CON4
Load Load Load
Load Load
Use is possible up to the kVA as shown below.
(Unit: kVA)
1-phase 240/120 V
1-phase, 3-wire 1-phase 120 V receptacle
receptacle Total
output terminal
CON1 CON2 CON3 CON4 CON5 CON6 CON7
U-W 42/ [21]* 42/ [21]*
U-N 21/ [10.5]* Total 2.4 Total 2.4 12 12 12 21/ [10.5]*
W-N 21/ [10.5]* 21/ [10.5]*
* Figures in brackets are used when set to 480 V.
< Note >
If using a single-phase 120 V (between output terminals U-N and W-N), connect an
equivalent load between U-N and W-N.
If using a single-phase three-wire output terminal simultaneously with a receptacle output,
make sure that currents passing through each phase is less than the rated current of this
generator.
If using at the three-phase 480 V setting, the output voltage of the single-phase three-wire
type is single-phase 240/120 V, which is the same as the three-phase 240 V setting.
Accordingly, care must be taken to not draw an excessive load as the available power is only
one half.
27
8. Pre-Operation Inspection
WARNING : INJURY
Do not open the check door during operation. Keep away from moving parts such as
cooling fan and fan belt.
Always be sure to stop the engine and remove the starter key when performing
inspection or maintenance.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
CAUTION : FIRE
Always be sure to wipe up any spilled fuel or oil.
Not Too
OK Enough Much
MAX
Oil Level Gauge
Oil Filler MIN :Oil Level
28
(2) Engine Oil Viscosity Grades
Use a diesel engine oil with an appropriate viscosity corresponding to the ambient temperature
(refer to the table).
Relation of Viscosity/Temperature
Temp.
-22 5 32 59 77 86 104
(°F)
SAE 10W-30
SAE 10W-40
SAE 15W-40
CAUTION: BURNS
Do not open the radiator cap immediately after stopping the engine.Do so will result in
hot steam gushing out.
Hot steam gushes out from the coolant sub-tank if the generator overheats. Do not
touch the coolant sub-tank.
Check that the sub-tank coolant level is in between FULL and LOW. If the sub-tank coolant is
lower than the LOW level, add coolant to the sub-tank and radiator.
(1) Filling the Sub-Tank
1 Remove the sub-tank cap. Sub-Tank
2 Fill the sub-tank with coolant until it reaches the
FULL line.
3 Re-attach the cap.
FULL
LOW
29
< Note >
Use GM SPEC 6277M or equivalent.
Use a 50:50 mix of Long Life Coolant (LLC).
Always use potable water when mixing the coolant.
Use LLC with the same mixture ratio in the coolant sub-tank.
Do not increase the LLC mixture ratio unless necessary. Doing so could result in overheating
or another fault/malfunction.
If adding LLC, be sure to use the same brand/type that is still in the generator.
Do not mix different brands/types. Doing so could result in a chemical reaction and the
creation of toxic substances.
Change the LLC every 1,000 hours or every year.
LLC is a toxic substance. Wear rubber gloves and other protective wear when handling.
If someone mistakenly ingests LLC, induce vomiting immediately and seek medical care.
If LLC gets on skin or clothing, wash with water immediately.
LLC is flammable. Store in a location where flame is prohibited and it cannot be accessed by
children.
Engine coolant could leak if the radiator is not completely tightened or there is a gap in the
seating face. Always be sure to securely tighten the radiator cap.
Do not add engine coolant past the FULL level line of the coolant sub-tank.
(3) Coolant Capacity
Total Coolant Capacity
3.7 (0.4) gal
Value in parenthesis is the sub-tank capacity.
8-3. Checking the Fan Belt
(1) Fan Belt Tension
Press the middle of the fan belt with a force of approx.98N and (98N)
check whether the amount of deflection is within the range of
standard values.
Standard value
[amount of deflection]
New belt 0.17 ~ 0.20 in
When reused 0.26 ~ 0.29 in
Bolt
Fan Guard
30
(3) Fan Belt Adjustment
1 Remove the fan guard.
Fixed Bolt Adjusting Bolt
2 Loosen the Fixed bolts and Mounting Bolt of the alternator.
3 Turn the adjusting bolt until the belt tension falls within the
standard value range.
4 Securely tighten the Fixed bolts and Mounting Bolt of the
alternator to the specified torque.
5 Attach the fan guard.
CAUTION : FIRE
This generator uses diesel fuel. Always be sure to stop the engine and not bring
flames close when inspecting fuel or refueling. Wait until the engine has cooled before
performing such procedures.
If fuel spills, always be sure to open the spill containment drain valve and drain off the
spilled fuel.
(Refer to section “10. Inspection/Maintenance (12) Flushing Liquid in Spill
Containment”.)
31
8-5. Checking the DEF(Diesel Exhaust Fluid)
CAUTION : FIRE
Do not put anything other than DEF (gasoline, diesel fuel, etc.) in the DEF tank. Also,
do not put DEF diluted with water or other liquids.
CAUTION : FIRE
If fuel or oil is leaking, repair the leaking location before operating.
Open the check door and check the inside of the spill containment. Flush out any accumulated
liquid. Refer to section “10. Inspection/Maintenance (12) Flushing Liquid in Spill
Containment” for flushing procedures.
< Note >
The types of liquids that can accumulate in the spill containment include oil, fuel, coolant,
battery fluid and DEF such that it is not possible to distinguish between rain water and other
liquids. Dispose of flushed liquids according to the related laws and regulations.
32
8-7. Checking for Fuel, Oil and Coolant Leak
CAUTION : FIRE
If fuel or oil is leaking, repair the leaking location before operating.
Open the check door and check for fuel, oil and coolant leakage from fuel piping connections
and similar locations.
8-8. Checking the Battery
California Proposition 65
WARNING
Batteries, battery posts, terminals and related accessories contain lead and lead
compounds, and other chemicals known to the State of California to cause cancer and
birth defects or other reproductive harm. WASH HANDS AFTER HANDLING.
CAUTION : EXPLOSION
Never use or recharge the battery if the fluid level is below the minimum level.
Do not create sparks or bring flame near the battery as it generates flammable gas.
1 Check the fluid level, and add distilled water until it reaches the upper level when the fluid
level is near the lower level.
2 Check the terminals for looseness and tighten properly.
< Note >
It is necessary to recharge the battery when the specific gravity of the battery fluid is 1.23 or
less. Request the authorized distributor where the generator was purchased to recharge the
battery.
Upper Level
Lower Level
Hold-Down
Clamp
33
Replacing the Battery
1 Remove the battery negative (-) cable.
(Always be sure to remove the negative (-) side first.)
2 Remove the battery hold-down clamp.
3 Remove the battery positive (+) cable.
4 Remove the battery.
* Install the battery by performing the above procedures in the reverse order.
(First connect the positive (+) cable of the replaced battery.)
< Note >
Do not disconnect the battery cable immediately after the engine stop. The SCR continues to
operate for approximately 3 minutes even after the starter switch is set to the “OFF” position.
Wait for at least 3 minutes before disconnecting the battery cables.
9. Operating Procedures
WARNING : INJURY
Always be sure to check that the breakers on load side and switches for any
equipment using the generator are at OFF before turning the breaker to ON. Also be
sure to advise personnel on the load side that power will be turned on before
operating the breaker.
Close all doors and lock them during operation.
CAUTION : FIRE
Do not carry flammable items (such as fuel, gas and paint) or items that are highly
combustible near the generator as the muffler, exhaust gas and other parts become
extremely hot.
Position this generator 3 ft. (1 m) or more from walls or other hindrances, and on a
level surface.
CAUTION : INJURY
Do not operate the generator if it has been modified or any parts have been removed.
Position the generator on a level stable surface so that it cannot slide or move in any
manner.
Before starting operation, always be sure to turn off all switches of equipment being
used and all breakers to OFF.
34
< Note >
Check that the surrounding area is safe before starting the engine.
When there are multiple workers who are working together, they must mutually signal each
other before starting the engine.
Do not use in an area with high temperature or humidity, or an area with a large amount of
dust.
Do not open any doors during operation. Operating with door open can negatively affect
cooling effect, resulting in an equipment malfunction.
Use ear protection if the level of noise is high. Failure to do so could result in hearing damage.
Please be careful about a strong wind and the opening and shutting of the door. If a door is
opened suddenly and is closed, and a finger might be sandwiched.
5 After starting the engine, remove your hand from the starter switch.
6 Let engine idles for approximately for five minutes.
7 Turn the Throttle switch to RUN.
8 Adjust the voltage regulator dial to the specified voltage.
9 Turn the breakers to ON to start AC power delivery.
35
9-2. 240/480V Switching Selection
1 Turn the three-phase and single-phase breakers on the operation panel to OFF and stop
operation.
2 Turn the lever of the voltage selector switch to the desired output setting.
3 Three-phase 240/480 V power is output to the three-phase output terminal. Refer to
section “7-2. Connecting Load Cables”.
4 Start the engine and turn the three-phase breaker to ON to transmit power to the
three-phase output terminal.
3-Phase 1-Phase
Breaker Breaker
Push
3-P 240V 3-P 480V
Padlock Hole
Starter Switch
36
< Note >
If abnormal, stop using this generator and request authorized distributor where the generator
was purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltmeter and finely adjust voltage using the voltage regulator
dial.
Bleeding air from the fuel system when the engine stops due to running out of fuel
1 Add fuel to the generator.
2 Turn the starter switch to RUN, activate the Air Bleeder Plug
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
1 Turn the switches and breakers on the load side to OFF.
2 Turn the three-phase and single-phase breakers on the operation panel to OFF.
3 Turn the Throttle switch to IDLING.
4 The engine cools down for approximately three minutes.
5 Turn the starter switch to STOP.
37
9-5. Protective Functions
WARNING : INJURY
Do not open the check door during operation. Keep away from moving parts such as
cooling fan and fan belt.
Always be sure to stop the engine and remove the starter key when performing
inspection or maintenance.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
Hot steam gushes out from the coolant subtank if the generator overheats. Do not
touch the coolant subtank.
This generator is equipped with functions to automatically stop operation when there is a
fault/malfunction during operation, and one to warn the operator of the fault location by use of
indicator lamps. Check the fault location when the engine is automatically stopped or an
indicator lamp illuminates to stop the engine.
38
9-6. Connecting with External Fuel Tank
CAUTION : FIRE
Always make sure that the engine is stopped when working on piping.
Always be sure to wipe up any spilled fuel.
After working on the piping, check that there is no fuel leakage.
■Capacity of the external tank should be less than 185 gal (700 liters).
When refueling the external fuel tank, supply DEF to the internal DEF tank.
1 Turn the 3way fuel valve lever to the “B”
side. 3Way Fuel Valve
(Position for using the internal tank.)
2 Remove the plugs(R1/2”) from both the
External Fuel Return
external fuel inlet and the external fuel
External Fuel Inlet
return.
3 Connect the hoses from an external fuel
tank, as shown below.
Return Side
4 Turn the 3way fuel valve lever to the “A”
side.
(Position for using the external tank.)
5 Bleed air from the external tank
connecting hose. Fuel can be supplied
from the external tank after completing
the above procedures.
Position A Position B
Inlet Side
< Note >
If using a hose for the piping, use oil-resistant hose
External Tank (capacity less than 185 gal)
with an internal diameter of 0.31 to 0.35 in (8 to 9
mm).
Set the fuel level of the external fuel tank from 0 to
0.6 ~ 0.8 in
39
10. Inspection/Maintenance
California Proposition 65
WARNING
Batteries, battery posts, terminals and related accessories contain lead and lead
compounds, and other chemicals known to the State of California to cause cancer and
birth defects or other reproductive harm. WASH HANDS AFTER HANDLING.
CAUTION : FIRE
Always be sure to wipe up any spilled fuel or oil.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
Do not open the radiator cap immediately after stopping the engine. Do so will result
in steam gushing out.
Hot steam gushes out from the coolant sub-tank if the generator overheats. Do not
touch the coolant sub-tank.
Do not touch the SCR system and surrounding components immediately after
stopping the engine as they are still extremely hot.
CAUTION : INJURY
Personnel performing suspension work must wear protective gear such as helmets,
safety shoes and gloves.
Always be sure to use lifting hooks when suspending the generator, and raise it slowly
at a completely vertical angle.
Perform periodic inspection and maintenance according to the following table in order to
constantly maintain this generator in good working condition. Use the hour meter as a
reference for the operating time.
40
< Note >
All procedures except for pre-operation inspection should be performed by specialized
technicians.
Request authorized distributor where the generator was purchased to perform the procedures
in the table with a “”.
Always be sure to use genuine parts or those indicated specifically for replacement parts.
Use a container to catch fluid bled from this generator that is large enough to prevent the fluid
from spilling on the ground.Dispose of oil, fuel, coolant (LLC), filter, battery, DEF and other
hazardous materials according to laws and regulations concerning industrial waste.Contact
authorized distributor where the generator was purchased if you have any inquiries regarding
proper disposal.
When check doors are open during maintenance, take measures so that unrelated personnel
cannot accidentally come close to the generator. Close all doors and covers if you are going
to be away from this generator.
Please be careful about a strong wind and the opening and shutting of the door at the sloping
place enough. When door is opened or closed suddenly, a finger might be sandwiched.
Each parts
(Clean/Tightening)
Exhaust color (Check)
Coolant (Check/Add)
Coolant
(Replace/Radiator Flush)
Fuel filter
(Check/Drain excess
Water and sediments)
Electromagnetic pump
filter
(Clean/Replace)
Air cleaner element
(Clean/Replace) (Clean) (Replace)
Intercooler (Drain)
Fuel/Coolant/Oil Hoses
and Anti-Vibration Every
Rubber (Replace) 2 years
41
Every Every Every Every Every
Description Daily Remarks
250 hrs 500 hrs 750 hrs 1000 hrs 4500 hrs
Air Hose(Engine/
Intercooler/Air Creaner) Every
SCR system LLC hose 2 years
Radiator and Intercooler
(Clean)
Valve clearance
(Check/Adjust)
Fuel injector
Engine
(Check)
Elimination of carbon in
the exhaust pipe line
and muffler
DEF leakage
Dosing module
inspection
(SCR system)
Indicators,
Generator
Gauges
Alarms (Check)
Insulation test
Spill containment
(Check/Clean) (Clean)
Cleaning the Rear Cover
(Check/Clean)
42
< Note > Open Close
Refer to section “8-1. Checking Engine Oil” for
engine oil replacement amounts and types.
After reinserting the oil drain plug and shortly after
starting the engine, be sure to always check that there
is no oil leakage. Oil Drain Valve
Always be sure to wipe up any spilled engine oil.
Oil Drain Plug
43
(3) Air Filter Element Cleaning/Replacement Air Cleaner
Clean (Outer element) Every 250 hours
Replace (Inner / Outer element) Every 500 hours
Clip
1 Remove the air cleaner clips and cleaner cap.
2 Remove the outer element.
3 Clean or replace the outer element. Replace by
performing the above procedures in reverse order.
< Note > Air Cleaner Cap Vacuator Valve
Inner air element must not be reused even if it is cleaned.
Outer Element
Replace the inner element when replacing the outer element.
Always be sure to turn the cleaner cap in the direction
indicated by the arrow.
Replace the elements earlier if using in an excessively dusty
location. Inner Element
Do not add oil as this generator uses a dry element.
Clear foreign material by pinching the vacuator valve once a week in normal operating
conditions or daily if operating in a location that is excessively dirty or dusty. Wipe away any
dirt or moisture that has adhered to the parts.
Never touch the elements for any reason except cleaning.
The mass air flow (MAF) sensor is installed to the air cleaner inlet duct. Refrain from using
commercially available cleaning agent to remove dust clinging to the sensor; otherwise the
engine output will be reduced.
Outer Element part no.: P826889 (Isuzu part no.)
Inner Element part no.: P829333 (Isuzu part no.)
44
< Note >
After drainage, start the engine and check that there is no fuel leakage.
When the water is accumulate in the cup, drain water from the fuel tank.
Be careful not to over-tighten the drain plug and air bleeder plug.
Always be sure to wipe up any spilled fuel.
(5) Main Fuel Filter Replacement
Replace Every 500 hours
Main
1 Place a container under Fuel Filter to catch fuel spilling
out of the filter.
2 Remove the filter element (main) using the wrench.
3 Before installing the Element, lightly apply engine oil to
the Element gasket.
4 Screw the new filter into place and tighten it by hand
until the gasket contacts the seat. Then, give it
additional 2/3 turn or a specified fastening torque to seat Fuel Filter Element
(Main)
the filter.
45
(6) Pre Fuel Filter Replacement
Replace Every 500 hours
Pre
1 Place a container under Fuel Filter to catch fuel spilling out
of the filter.
Air Bleeder
2 Loosen the air bleeder plug of the fuel filter sufficiently. Plug
3 Loosen the drain plug on the bottom to drain the fuel.
4 Remove the outer case of the filter using the specified filter
wrench.
Outer Case
5 Remove the fuel filter element.
6 Install a new fuel filter element.
7 Replace the O-ring of the outer case. Fuel Filter Element
8 Apply fuel to the each O-ring thinly. (Pre) Drain Plug
9 Screw the outer case into the filter by hand until O-ring
contacts to the sealed surface. Fully screw the filter by
special filter wrench.
10 Tighten the drain plug on the bottom and the air-bleeding plug.
Drain plug tightening torque
2 ~ 3 N・m
Air bleeding plug tightening torque
8 ~ 12 N・m
46
< Note >
After attaching, be sure to always start the engine and check that there is no fuel leakage.
Always be sure to wipe up any spilled fuel.
After replacing the filter, always air out the fuel system.
(Refer to section “9-3. Procedures during Operation”.)
When a damage is found on the filter and gasket, replace with new parts.
Filter kit ( Without Gasket ) part no .: 8980714010 (Isuzu part no.)
Gasket kit ( Without Filter ) part no .: 8980714040 (Isuzu part no.)
Repair kit ( Including Gasket/Filter kit ) part no .: 8981731650 (Isuzu part no.)
(8) Supply Module Filter Replacement
Supply Module Filter Element
Replace Every 4500 hours
1 Place a container under Supply Module to catch
spilled DEF.
2 Remove the filter cover using the socket wrench.
3 Pull out the Filter element and Equalizing element
together.
4 Install the new Filter element and Equalizing
element.
5 Tighten the Filter cover.
Filter cover tightening torque
Equalizing
20 ~ 25 N・m
Element
< Note > Filter Cover
Be careful not to screw the Filter Cover too tightly.
Socket wrench size 27mm
After replacement, start the engine and check if there (width of two sides)
is no DEF leakage.
Always be sure to wipe up any spilled DEF.
The SCR continues to operate for approximately 3 minutes even after the starter switch is set
to the “OFF” position. Wait for 3 minutes or more until the supply module stops operating.
Discharged DEF is not reusable. Reuse may result in failure of the SCR.
When disposing of discharged DEF, comply with regulations.
Clean the filter by wiping it with clean cloth. Refrain from using high-pressure air to avoid
foreign material blown by air coming in DEF pipe, which results in SCR failure.
Supply Module filter element (Including equalizing element) part no.: 8983507160 (Isuzu part no.)
Socket wrench complies with ISO 2725-1
(9) Draining Water from the Fuel Tank
Drain Water Every 250 hours
47
(10) Coolant Replacement
Replace Every 1000 hours or every year
1 Set a container to catch spilled coolant. Radiator Plate
2 Remove the radiator plate.
3 Remove the radiator cap. Radiator Cap
4 Remove the coolant drain plug. &
Filler Neck
5 Apply sealant coating to the plug or wrap it in seal tape.
6 After the coolant has been drained, tighten the coolant drain
Sub-Tank
plug.
7 Remove the subtank and flush the coolant from the subtank.
8 Reattach the subtank to its original position and fill with coolant FULL
3 Close the valve lever after the liquid has been flushed, and apply sealant coating to the
plug or wrap it by seal tape.
48
Drain Valve Lever Drain Valve Drain Valve
Loosen
WARNING : INJURY
Do not lift up the unit using tie down. Use of such could result in the generator falling.
No persons should ever be under a lifted generator.
Do not use the fuel tank lifting hook to lift up when the fuel tank that contains fuel, and
also do not lift up with the fuel tank and spill containment as a single unit. Doing so
could result in the tank falling.
CAUTION : INJURY
Always be sure to use lifting hooks when lifting up the generator, and raise it slowly at
a completely vertical angle.
Personnel performing lifting work must wear protective gear such as helmets, safety
shoes and gloves.
Do not move the generator during operation.
5 Lift the generator, separate the spill containment and set the generator on a flat surface.
6 After cleaning and inspecting the inside of the spill containment, reassemble the spill
container with this generator by performing the above procedures in the reverse order.
7 Reassemble the fuel piping and wiring connector to their original positions.
8 Turn the 3way fuel valve lever to the “B” side.
49
< Note >
Connect the fuel hose supply route and return route
correctly.
After reassembling, bleed air from the fuel system.
(Refer to section “9-3. Procedures during Operation”.)
After reassembling, check that there is no fuel leakage.
Position A Position B
50
Lifting Hook
Wire Connector
Bolt
Washer
Position A
Washer
Fuel Tank
Wire Connector
Fuel Line (Inlet Side)
Spill Containment Fuel Line (Return Side)
51
(14) Elimination of excessive carbon in the exhaust system by extensive light load
WARNING : INJURY
Always be sure to check that the breakers on load side and switches for any
equipment using the generator are at OFF before turning the breaker to ON. Also be
sure to advise personnel on the load side that power will be turned on before
operating the breaker.
Close all doors and lock them during operation.
CAUTION : FIRE
Do not carry flammable items (such as fuel, gas and paint) or items that are highly
combustible near the generator as the muffler, exhaust gas and other parts become
extremely hot.
Position this generator 3 ft. (1 m) or more from walls or other hindrances, and on a
level surface.
CAUTION : INJURY
Do not operate the generator if it has been modified or any parts have been removed.
Position the generator on a level stable surface so that it cannot slide or move in any
manner.
Before starting operation, always be sure to turn off all switches of equipment being
used and all breakers to OFF.
52
(15) Cleaning the Rear Cover
CAUTION : BURNS
Do not touch the SCR system and surrounding components immediately after
stopping the engine as they are still extremely hot.
CAUTION : INJURY
Position the generator on a level stable surface so that it cannot slide or move in any
manner.
Before starting operation, always be sure to turn off all switches of equipment being
used and all breakers to OFF.
Electronic
Control Device
Wiring Connector
53
11. Long-Term Storage
WARNING : INJURY
Always be sure to stop the engine and remove the starter key when performing
inspection or maintenance.
CAUTION : FIRE
Always be sure to wipe up any spilled fuel or oil.
Allow the generator to cool before covering with the protective cover.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
54
(2) Double-Stacking Storage Procedures
WARNING : INJURY
Always be sure to observe the following items when double stacking this generator in a
warehouse or similar location.
Check that the hood of this generator is not dented, and
that bolts are not loose or missing.
Set in a location with a flat hard floor capable of
withstanding the double-stacking weight.
Always be sure to use lifting hooks when lifting this
generator.
Insert wood ties of the same size and that are wider than
this generator between each generator, and set another
generator on top of the ties.
Never stack more than two levels, and do not set a
generator on top that is larger in weight/size than that on
the bottom.
Do not operate the generator when it is double stacked.
12. Troubleshooting
CAUTION : FIRE
Never allow flame to come closer to the generator.
CAUTION : BURNS
Do not touch the engine and muffler after stopping the engine as they are still
extremely hot.
55
Problem Suspected cause Action
Starter motor 1. Battery output is weak 1. Check battery fluid or charge
does not drive 2. Battery is deteriorated 2. Replace Battery
or speed is low 3. Battery terminal is OFF or loose 3. Fix/Tighten terminal
4. Battery terminal is corroded 4. Clean terminal
5. Starter switch or relay is defective 5. Contact distributor or dealer for repair
6. Starter motor is defective 6. Contact distributor or dealer for repair
7. ECM (Engine Controller) is defective 7. Contact distributor or dealer for repair
Engine does not start
Black smoke 1. Air filter element is clogged 1. Check/Change air filter element
comes out from Muffler 2. Fuel injection nozzle is defective 2. Contact distributor or dealer for repair
3. Improper fuel is used 3. Change to clean fuel
4.SCR system is faulty 4. Contact distributor or dealer for repair
56
Problem Suspected cause Action
White smoke 1. Too much or too little oil to cylinder 1. Contact distributor or dealer for repair
comes out from 2. Water is interfused in fuel line 2. Drain water in fuel filter or fuel tank
Muffler 3. Fuel injection nozzle is defective 3. Contact distributor or dealer for repair
4. Coolant temperature is too low 4. Warm-up driving is needed
5. Engine thermostat is defective 5. Contact distributor or dealer for repair
Pointer (hand) does not 1. Voltage meter is defective 1. Contact distributor or dealer for repair
move in voltage meter 2. AVR is defective 2. Contact distributor or dealer for repair
3. Disconnected circuit,loose terminal or 3. Contact distributor or dealer for repair
departed
4. Initial exciter is defective 4. Contact distributor or dealer for repair
5. Alternator is defective 5. Contact distributor or dealer for repair
6. AVR protective device operation 6. Replace AVR fuse
Pointer (hand) 1. Voltage meter is defective 1. Contact distributor or dealer for repair
does not goes up 2. AVR is defective 2. Contact distributor or dealer for repair
to the rated 3. Voltage regulator dial is defective 3. Contact distributor or dealer for repair
voltage
Pointer exceeds 1. Voltage meter is defective 1. Contact distributor or dealer for repair
the rated voltage 2. AVR is defective 2. Contact distributor or dealer for repair
3. Improper load cable connection 3. Correctly set the connection location to
the receptacle
4.Voltage switch is set to 480 V 4. Set the voltage switch to 240 V
The voltage drops 1. AVR is defective 1. Contact distributor or dealer for repair
drastically when 2. Unbalanced loads sharing to each 2. Balance the loads sharing to each
connecting to load terminal terminal
3. The current of the used equipment 3. Change to a device with an available
exceeds the rated current capacity
4. Over load 4. Decrease the loads to meet the rated
output
5. AVR protective device operation 5. Replace AVR fuse
Cannot turn the 1. The Main breaker positions at between 1. Once turning the lever to OFF, turn it to
breaker to ON ON and OFF ON
2. Short circuit on the load 2. Check the load circuit
57
13. Generator Circuit Diagram
58
14. Engine Electrical Circuit Diagram
59
60
©2019