Lah 50-P-SP1
Lah 50-P-SP1
Lah 50-P-SP1
16004
Electrical data
IPN Primary nominal current rms 50 A Features
1)
IPM Primary current, measuring range 0 .. ± 90 A • Closed loop (compensated) current
RM Measuring resistance @ TA = 70°C TA = 85°C transducer using the Hall effect
RM min RM max RM min RM max • Printed circuit board mounting
with ± 15 V @ IPN [± A DC ] 22 163 58 159 Ω • Insulated plastic case recognized
@ IPN [A RMS ] 2) 22 93 58 89 Ω according to UL 94-V0.
@ IP IPN 2)
ISN Secondary nominal current rms 50 mA Special features
KN Conversion ratio 1 : 1000 • IPM = 0 .. ± 90 A
VC Supply voltage (± 5 %) ± 15 V • K N= 1 : 1000.
IC Current consumption 10 + IS mA
Advantages
Accuracy - Dynamic performance data • Excellent accuracy
X Accuracy 3) @ IPN, TA = 25°C ± 0.25 % • Very good linearity
ε L
Linearity error < 0.15 % • Low temperature drift
Typ Max • Optimized response time
IO Offset current @ TA = 25°C ± 0.3 mA • Wide frequency bandwidth
IOM Magnetic offset current @ IP = 0 and specified RM, • No insertion losses
after an overload of 5 x IPN ± 0.2 ± 0.3 mA • High immunity to external
IOT Temperature variation of IO 0°C .. + 70°C ± 0.2 ± 0.6 mA interference
- 25°C .. + 85°C ± 0.2 ± 0.8 mA • Current overload capability.
tr a Reaction time @ 10 % of IPN < 200 ns Applications
tr Response time 4) to 90 % of IPN step < 500 ns
di/dt di/dt accurately followed > 200 A/µs • AC variable speed drives and servo
BW Frequency bandwidth (- 1 dB) DC .. 200 kHz motor drives
• Static converters for DC motor drives
• Battery supplied applications
General data
• Uninterruptible Power Supplies
TA Ambient operating temperature - 25 .. + 85 °C (UPS)
TS Ambient storage temperature - 40 .. + 90 °C • Switched Mode Power Supplies
RS Secondary coil resistance @ TA = 70°C 72 Ω (SMPS)
@ TA = 85°C 76 Ω • Power supplies for welding
m Mass 22 g applications.
Standards EN 50178: 1997
Application domain
• Industrial.
Notes: 1)
During 10 s, with R M ≤ 53 Ω
2)
The measuring resistance RM min may be lower
(see "LAH Technical Information" leaflet or the "LAH Application Note")
3)
Without IO & IO M
4)
With a di/dt of 100 A/µs.
Page 1/3
071113/7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. w w w .lem.com
Current Transducer LAH 50-P/SP1
Isolation characteristics
Application examples
Note: 5)
On PCB with soldering pattern UTEC93-703.
Safety
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
071113/7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. w w w .lem.com
Dimensions LAH 50-P/SP1 (in mm. 1 mm = 0.0394 inch)
Connection
Bottom view
Left view
Front view
Page 3/3
071113/7 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice. w w w .lem.com