LF505-S Lem
LF505-S Lem
LF505-S Lem
Features
Electrical data
●● Closed loop (compensated)
IPN Primary nominal rms current 500 A current transducer using the Hall
IPM Primary current, measuring range 0 … ±1480 A effect
RM Measuring resistance RM min RM max ●● Insulating plastic case recognized
with ±24 V @ ±500 A max 0 148.5 Ω according to UL 94-V0.
@ ±1480 A max 0 2.5 Ω
ISN Secondary nominal rms current 100 mA Special features
KN Conversion ratio 1 : 5000
●● IPM = 0 … ±1480 A
UC Supply voltage (±5 %) ±24 V
●● UC = ±24 V (±5 %)
IC Current consumption IP 33 + IS mA
UC ●● Connection to secondary circuit
IS
RM
on JST BH03B-XASK-BN
Accuracy - Dynamic performance data
connector
UC
X Accuracy @ IPN, TA = 25 °C ±0.6 % ●● 2D Datamatrix Barcode-label
@ IPN, TA = −10 °C … +70 °C ±0.9 % ●● Improved dynamic performance
εL Linearity error < 0.1 % ●● Extended temperature range.
Typ Max
Advantages
IO Offset current @ IP = 0, TA = 25 °C ±0.4 mA
IOM Magnetic offset current @ IP = 0, and specified RM, ●● Excellent accuracy
after an overload of 3 × IPN ±0.2 mA ●● Very good linearity
IOT Temperature variation of IO −10 °C … +70 °C ±0.1 ±0.3 mA ●● Low temperature drift
−40 °C … −10 °C ±0.3 ±0.8 mA ●● Optimized response time
tr Step response time 1) to 90 % of IPN < 1 µs ●● Wide frequency bandwidth
di/dt di/dt accurately followed > 200 A/µs ●● No insertion losses
BW Frequency bandwidth (−1 dB) DC … 100 kHz ●● High immunity to external
interference
General data ●● Current overload capability.
TA Ambient operating temperature −40 … +70 °C Applications
TS Ambient storage temperature −40 … +85 °C
RS Resistance of secondary winding @ TA = 70 °C 68 Ω ●● AC variable speed drives and
m Mass 230 g servo motor drives
Standards EN 50178: 1997 ●● Static converters for DC motor
IEC 61800-5-1 drives
UL 508: 200 ●● Battery supplied applications
●● Uninterruptible Power Supplies
Note: 1)
With a di/dt of 100 A/µs. (UPS)
●● Switched Mode Power Supplies
(SMPS)
●● Power supplies for welding
applications.
Application domain
N° 97.14.50.027.0 ●● Industrial.
Page 1/3
9December2015/version 8 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer LF 505-S/SP27
Insulation coordination
Ud Rms voltage for AC insulation test, 50 Hz, 1 min 3.8 kV
ÛW Impulse withstand voltage 1.2/50 µs 17.3 kV
Min
dCp Creepage distance 1) 39 mm
dCI Clearance 1) 23 mm
CTI Comparative tracking index (group IIIa) 175
Note: 1)
Without cable length.
Applications examples
Safety
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
9December2015/version 8 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Dimensions LF 505-S/SP27 (in mm)
dCl dCp
Connection
IP
UC
IS
RM
UC
9December2015/version 8 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com