10-6 - Chilled Water System
10-6 - Chilled Water System
10-6 - Chilled Water System
Sample Computation :
1. What is the cooling load of chiller if the chilled water flow is 363.24 CMH and ΔT=5°C?
Load = 363.24 CMH x 5°C x 0.33036
Load = 599.99 or 600 TR
Note: a. This 599.99 computation is the gross capacity of the ROHM chiller/ 1-unit
b. 1 TR = 3.516 kW
FUNDAMENTAL FORMULA
COP – Coefficient of Performance
It is the measurement of system efficiency in Air
Conditioning
The higher the COP means the higher the efficiency
Example:
Compute Chiller COP with gross capacity of 2,109.6 kW and absorbed power of 351.6 kW
Answer: COP = 2,109.6 kW/ 351.6kW = 6
HEAT TRANSFER FLOW
EXAMPLE if ROHM Building - H is in maximum load that chiller units can only handle.
Constant Volume Chilled Water Distribution System – Full Load at Design Condition ( ΔT=5°C)
( ΔT=5°C)
CHWS = 1,452.96 CMH 100% SYSTEM LOAD ( ΔT=5°C)
14°C 363.24CMH 600 TR
9°C
363.24CMH 600 TR
14°C 600 TR 9°C
CP-1-2
CH-1-2
14°C 600 TR
363.24CMH 9°C
Constant Volume Chilled Water Distribution System – Part Load at Design Condition
( ΔT=3.5°C)
CHWS = 1089.72 CMH 85% CHILLER LOAD ( ΔT=5°C)
12.5°C 363.24CMH 600 TR
9°C
CP-1-2
CH-1-2
12.5°C 600 TR
363.24CMH 9°C
Constant Volume Chilled Water Distribution System – Part Load at ΔT=2.5°C- Valves Manually Open
( ΔT=2.5°C)
CHWS = 1089.72 CMH 50% CHILLER LOAD ( ΔT=2.5°C)
11.5°C 363.24CMH 600 TR
9°C
CP-1-2
CH-1-2
11.5°C 600 TR
363.24CMH 9°C
700 TR HEAT
COMPRESSOR HEAT
ABSORBED BY
100 TR
CONDENSING
WATER
700TR CWP-1-3
600TR 37°C
426.24 CMH 32°C 426.24 CMH
700TR CWP-1-4
426.24 CMH 600TR 426.24 CMH
32°C 37°C
Ensure first that there will be cooling load. This is necessary so that
chiller unit can load-up
Run AHUs, OACs, FCUs, supply fan
Run exhaust fans, for good air balance
Check the chilled/cooling water pumps
Check pressure and valve position
Run the system thru paramatrix control and ensure that cp & cwp are
running.
isolate valve of the stand-by chillers if necessary.
Observe if chiller runs according to the control system sequence.
FLOW CHART
Start in BMS Mode
In BMS mode, starting down and shutting-down are made on computer’s Graphic
User Interface which will be broadly discussed on December 3 & 4.
REGULAR CHECK
Check all valves position in proper order,
Check circuit breakers and panels, check the torque marks.
Monitor pressure and temperature conditions of chilled and cooling water,
Monitor cooling space parameters like temperature and humidity, including outdoor
condition
Check pump vibrations, unusual vibration and noise means something wrong
Check routine maintenance schedule of equipment like chillers
Check all filters of OAC’s, AHU’s and FCU’s if they need cleaning or replacement
Any alarm on BMS should be acknowledged and make action
Make record and report any incident immediately, big or small
Once a day, make a routine check on all system piping for any possible condensation
someday, leak on drain valves, irregularity and etc.
LOW ΔT SYNDROME
If the system is in Automatic Mode and delta -
T is low, probable cause is:
Dirty chilled water coils
Reduces system efficiency
Less Heat Transfer
Area may hard to reach desired temperature
Malfunctioned motorized valve or mis-calibration
SAFETY
AS OPERATOR, THINK SAFE TY ALL THE TIME
1. When dealing with valves like opening, adjusting and closing it, make it slowly to
avoid sudden increase and decrease in pressure. Sudden change in pressure
and flow, depend on situation, will result cavitations in the piping system.
Cavitations will reduce the life of the system.
2. Keep distance from unprotected parts of rotating equipment like fan or pump.
Thus, always check its condition
3. Maintain cleanliness everywhere
4. Always follow check list
5. When encountered trouble and not sure what to do, call for help of
knowledgeable person or trained personnel for their advice.
Questions?
What is condenser and evaporator approach?
It is the variation between the refrigerant temp and water temp on
evaporator or condenser
condenser approach 3°C and below is good
above 4 °C means dirty coils
Why motorized valve needs to close when one AHU unit is
shutdown?
To avoid mixing of supply temp back to return temp
delta T will become low and cooling energy is wasted
Questions?
What is the use of open-type expansion tank?
when chilled water temperature changes for example from 7°C to
25°C, due to long shutdown there will be a thermal expansion. It means
water volume will increase – that’s why it is called expansion tank
it also serves as make-up water should in case system piping is drained
because of maintenance
Any more questions?