DORMITORY COMPUTATIONS (Simula)
DORMITORY COMPUTATIONS (Simula)
DORMITORY COMPUTATIONS (Simula)
DESIGN COMPUTATIONS
Wind Load Analysis of Female and Male Dormitory (based on NSCP 2015)
Using Table 207E.4-1, NSCP 2015, Determining MWFRS Wind Loads for Enclosed
Building
Occupancy Category:
Location: Laguna, V = 250 kilometers per hour (Figure 207A.5-1A, NSCP 2015)
Exposure Category:
Exposure B, for buildings with a mean roof height of less than or equal to 9m where
upwind direction for a distance greater than 450 m. (Section 207A.7.3, NSCP 2015)
Topographic Factor:
Kzt = 1.0, site conditions and locations do not meet all the conditions specified in the
Wind Speed-Up over Hills, Ridges and Escarpments (Section 207A.8.2, NSCP 2015)
Enclosure Classification:
G = 0.85, permitted value of gust effect factor for a rigid building or other structure
7.5−6 0.66−0.62
(Interpolation) = Kz = 0.6566666667
7.375−6 K z−0.62
Velocity Pressure:
At z= 3m:
250× 1000 2
qz = 0.613(0.57) (1.0) (0.85) ( ¿ qz = 1432.284433 N/m2
3600
At z= 6m:
250× 1000 2
qz = 0.613(0.62) (1.0) (0.85) ( ¿ qz = 1557.923418 N/m2
3600
250× 1000 2
qz = 0.613(0.6566666667) (1.0) (0.85) ( ¿ qz = 1650.058674
3600
N/m2
2.75
θ = tan-1( )θ = 10.38885782°
15
θ ≥ 10
Angle, θ(degrees)
h/L 10 10.38885782 15
-0.7 -0.6844456872 -0.5
≤0.25
-0.18 -0.1660011185 0.0
-0.6951593737
0.2633928571
-0.1667611251
-0.9 0.8844456872 -0.7
0.5
-0.18 -0.18 -0.18
Cp= -0.6951593737
Cp= -0.1667611251
Angle, θ(degrees)
h/L 10 10.38885782 15
≤0.25 -0.3 -0.3155543128 -0.5
0.2633928571 -0.3254353317
Cp= -0.3254353317
Wind Pressure:
Walls
Windward:
p = 716.1422165 N/m2
p= 1231.764612 N/m2
Leeward:
p= -866.532082 N/m2
p= -350.9096861 N/m2
Windward:
p= 778.961709 N/m2
p= 1339.8141139 N/m2
Leeward:
p= -942.5436679 N/m2
p= -381.6912374 N/m2
Roof
Windward:
p= -1272.006253 N/m2
p= -677.9851299 N/m2
p= -530.901356 N/m2
p= 63.11976665 N/m2
Leeward:
p= -753.4498444N/m2
At z= 7.375 m (roof mean height): Cp= -0.3254353317 and GCpi = -0.18
p= -159.4287281 N/m2
Roof Overhang
Windward
p= 825.029337 N/m2
Walls
At z =3 m
Leeward, p= -866.532082N/m2
At z= 6 m
Roof
At z= 7.375 m
Roof Overhangs
At z= 7.375 m