Vmax/A: Medium Voltage Vacuum Circuit Breaker Ansi: 4.76kV-15 KV 1200-2000 A 31.5 Ka
Vmax/A: Medium Voltage Vacuum Circuit Breaker Ansi: 4.76kV-15 KV 1200-2000 A 31.5 Ka
Vmax/A: Medium Voltage Vacuum Circuit Breaker Ansi: 4.76kV-15 KV 1200-2000 A 31.5 Ka
Vmax/A
Medium voltage vacuum circuit breaker
ANSI: 4.76kV-15 kV; 1200-2000 A; 31.5 kA
Safe Practices
Vmax/A circuit breakers are equipped with high energy/high
speed mechanisms. The design includes several interlocks
and safety features which help ensure safe and proper
operating sequences. To ensure safety of personnel
associated with installation, operation and maintenance of
these breakers, the following recommendations must be
followed:
2
1.4 Information in this booklet
It follows that:
– at the rated service voltage the use of vacuum interrupters is
absolutely safe;
– application of the withstand voltage at industrial frequency,
according to the IEC 62271-100, VDE 0670 and IEEE C37.04
Standards, is safe;
– application of a voltage higher than the withstand voltage at
industrial frequency or of a direct current test voltage in direct
current, specified in the IEC, VDE and ANSI/IEEE Standards,
cannot be used;
– Limitation of the above-mentioned local phenomena, with
interrupters with open contacts, depends on keeping the
specified distance between the contacts.
3
2. Introduction and
safe practices
2.1. Introduction 2.2. Safe practices
The purpose of this manual is to provide instructions for Vmax/A circuit breakers are equipped with high energy / high
unpacking, storage, installation, operation, and maintenance for speed mechanisms. The design includes several interlocks and
Vmax/A vacuum circuit breakers. This manual should be safety features which help ensure safe and proper operating
carefully read and used as a guide during installation, initial sequences. To ensure safety of personnel associated with
operation, and maintenance. installation, operation, and maintenance of these circuit breakers,
the following recommendations must be followed.
The specific ratings of each model circuit breaker are listed on
the individual nameplates. The Vmax/A circuit breakers are Only qualified persons, as defined in the National Electric Safety
protective devices. As such, they are maximum rated devices. Code, who are familiar with the installation and maintenance of
In no event should they be applied outside of their nameplate medium voltage circuits and equipment should be permitted to work
ratings. on these circuit breakers
Read these instructions carefully before attempting any
installation, operation, or maintenance of these power circuit-
WARNING breakers.
CE
4
Ambient temperature
2.3. Standard and regulations Maximum + 40 °C / 104 °F
Average maximum over 24 hours + 35 °C / 95 °F
2.3.1. Fabrication
Minimum for indoor installation - 30 °C/ -22 °F
The Vmax/A circuit breakers conform to the following
standards:
Humidity
- IEEE C37.04
The average value of the relative humidity, measured for a period longer than
- DIN VDE 0670, part 104, and IEC 62271-100 24 hours, must not exceed 95%
- DIN VDE 0847, part 4, and IEC 61000-4
The average value of the pressure of the water vapor without condensation,
measured for a period longer than 24 hours, must not exceed 2.2 kPa.
2.3.2. Installation and operation
For assembly and operation, please refer to the relevant The average value of the relative humidity, measured for a period longer than
regulations, and in particular to: 1 month, must not exceed 90%.
- ANSI / NFPA70 The average value of the pressure of the water vapor, measured for a period
longer than 1 month, must not exceed 1.8 kPa.
- NEC
Altitude
2.3.3. Service conditions
< 1000 (3300 ft.) m above sea level.
Normal service conditions
For application above 1000m (3300 ft.) C37.20.2 is applicable
Follow the recommendations in the IEC 62271-1 and 62271-
100 Standards. In more detail: Climate
IEEE C37.09
To avoid the risk of corrosion or other damage in areas:
IEEE C37.54 – C37.20.2.
– with a high level of humidity, and/or
– with rapid and large temperature variations, take appropriate steps
(for example, by using suitable electric heaters) to prevent condensation
phenomena.
5
3. Receiving,
handling, and
storage
Vmax/A circuit breakers are subject to complete factory production tests and inspection prior to packaging and shipment. The shipping
package is designed to provide reasonable protection during shipment and to provide convenient handling. Accessories such as opening
handles and racking handles are shipped separately from the circuit breaker. The circuit breaker is shipped in special packing, in the open
position. Each piece of apparatus is protected by a plastic cover to prevent any infiltration of water during the loading and unloading stages
and to keep the dust off during storage.
3.1. Receiving
On receipt, check the state of the apparatus, integrity of the Immediately upon receipt of the circuit breaker(s), examine the
packing and correspondence with the nameplate data with what carton(s) to determine if any damage or loss was sustained during
is specified in the order confirmation and in the accompanying transit. If damage or indication of rough handling is evident, file a
shipping notes. damage claim at once with the carrier and promptly notify the
nearest district office. ABB is not responsible for damage to goods
Also make sure that all the materials described in the shipping which occur after delivery. However, ABB will lend assistance if
notes are included in the supply. notified of claims. Use care in unpacking the circuit breaker to
avoid damaging any circuit breaker parts.
Should any damage or irregularity be noted in the supply on
unpacking, notify ABB (directly or through the agent or supplier) Unpack circuit breakers as soon as possible after receipt. If
as soon as possible and in any case within five days of receipt. unpacking is delayed, difficulty may be experienced in making
The apparatus is only supplied with the accessories specified at a claim for damages not evident upon receipt. Check the
the time of ordering and validated in the order confirmation sent contents of each carton against the packing list before
by ABB. discarding any packing material. If any discrepancy is
discovered, promptly notify the nearest district office.
The accompanying documents inserted in the shipping packing Information specifying the purchase order number, carton
are: number, and part numbers of damaged or missing parts should
– Instruction manual (this document) accompany the claim.
– Test certification
– Identification label
– Copy of the shipping documents
– Electric wiring diagram.
6
Once removed from the shipping container, the circuit breaker
3.2. Handling wheels are designed to move the circuit breaker across a
smooth, paved surface.
Vmax/A circuit breaker shipping containers are designed to
be handled by fork lift (not supplied). To lift and handle the
Care must be taken not to damage the secondary plug (item 3,
circuit breaker, proceed as follows (Figure 1):
Figure 2) when transporting, rolling, or handling the Vmax/A
– use a special lifting tool (1) (supplied as accessory) fitted with a
circuit breakers.
safety chain and hooks (2);
– insert the hooks (2) in the special holes in the circuit breaker
frame and lift;
– Upon completion of the operation, (and in any case before putting
into service) unhook the lifting tool.
During handling, take great care not to stress the insulating parts
and the terminals of the circuit breaker.
DO NOT pull the circuit breaker by the front handles with the
circuit breaker in any position other than full Disconnect to
avoid injuries at the hands.
7
3.3. Storage
On receipt the apparatus must be carefully unpacked and CAUTION
checked as described in Checking on receipt. If immediate
installation is not possible, the packing must be replaced, using
the original material supplied. Insert special hygroscopic
substances inside the packing, using at least one standard
packet per piece of apparatus. Should the original packing not be
available and immediate installation is not possible, store in a
covered, well-ventilated, dry, dust-free, non-corrosive ambient,
away from any flammable materials and at a temperature
between – 30°C ( -22°F ) and + 45°C ( +113°F ).
8
4. Description
4.1. General 4.2. Reference Standards
The Vmax series of circuit breakers are pieces of The Vmax circuit breakers conform to the IEC 62271-100, IEEE
apparatus under vacuum for indoor installation; for the C37.04 – C37.54 – C37.09 – C37.55 standards and those of
electrical performances, please refer to the major industrialized countries.
corresponding technical catalogue. For special
installation requirements, please contact ABB. The
following version is available:
9
4.3. Withdrawable Circuit Breaker A lock prevents racking-in and racking-out with the circuit- breaker
closed. With the truck in an intermediate position between isolated
4.3.1. Vmax/A circuit breaker and racked-in, a further lock prevents circuit breaker closing (either
mechanical or electrical). The circuit breaker is completed with the
The withdrawable circuit breaker Vmax/A (see figure 3) is available primary contacts (4).
for ABB RELIAGEAR ND Switchgear.
It consists of a truck on which the supporting structure of the circuit
breaker is fixed.
The cord with the connector (2) (plug) for connection of the
operating mechanism electrical accessories comes out of the
connection (3).
The shutter actuators (5) for operating the shutters of the medium
voltage enclosure are fixed on the sides of the circuit breaker.
On the front part of the circuit breaker truck, the front channel is
mounted with the handles that actuate tabs (6) for inserting and
securing the circuit breaker.
1. RACKING TRUCK
2. CONNECTOR (PLUG)
3. CABLING CONNECTION
4. PRIMARY CONTACTS (CLUSTERS)
5. SHUTTER ACTUATOR
6. TRUCK FRONT CHANNEL TABS
7. ROF WHEELS (OPTIONAL)
8. RATING PLATE
9. CLOSE PUSHBUTTON
10. OPEN PUSHBUTTON
11. SPRING CHARGE INDICATOR
12. OPEN CLOSE INDICATOR
13. CHARGING LEVER
14. OPERATION COUNTER
15. UNDERVOLTAGE RELEASE MECHANICAL OVERRIDE
16. LIFTING PROVISION
10
4.3.2. General characteristics of withdrawable The basic versions of the withdrawable circuit breakers are
circuit breakers for RELIAGEAR ND three-pole and fitted with:
Switchgear - EL type manual operating mechanism
- Mechanical signaling device for closing springs
charged/ discharged
- Mechanical signaling device for circuit breaker
open/closed
- Closing and opening pushbutton
- Operation counter
- Auxiliary circuit breaker open/closed contacts
- Lever for manually charging the closing springs
- Isolating contacts
11
4.4. Characteristics of the electrical accessories
TRIP COIL (52TC1) Shunt opening release (-MBO1)
Note: Application of the shunt opening release and/or additional shunt operating
release foresees the use of one or two auxiliary make contacts (normally open),
thereby reducing the number of auxiliary contacts available.
12
REMOVAL
4.5. Preliminary operations (From Disconnect Position to Withdrawn Position)
Clean the insulating parts with clean dry cloth. 1. Visually check to see that the circuit breaker is racked
Check that the top and bottom terminals are clean and free of fully to the disconnect position and the connector plug is
disconnected.
any deformation caused by shocks received during transport
or storage. 2. In order to release the stored energy inside the circuit
breaker: push the CLOSE pushbutton and then push the
4.5.1. Insertion and removal of withdrawable circuit
OPEN pushbutton.
breaker
3. Pull handles to center (this withdraws cell interlock tabs;
This section describes the process for inserting the breaker
allowing breaker to be removed).
into the disconnect position of the switchgear and the removal
of the circuit breaker from the disconnect position. Racking of 4. Pull the breaker from circuit breaker compartment with
the circuit breaker to and from the connect and disconnect the handles onto the required transportation device.
position is covered in the following section.
13
4.6. Putting into service
- Check tightness of the power connections at the circuit-
4.6.1. General procedures breaker terminals.
- Check that the value of the power supply voltage of the
auxiliary circuits is within limits stated by IEEE C37.06.
- Check that no foreign bodies, such as bits of packing, have
got into the moving parts.
- Check that there is a sufficient exchange of air in the
installation place to avoid over temperatures.
- Supply the auxiliary circuits with power.
- Check the functionality and efficiency of the mechanical and
electrical locks.
- Carry out a few circuit breaker opening and closing operations by
means of the pushbuttons on the front of the circuit- breaker.
- Carry out the checks indicated in table below.
- Do not attempt to insert the circuit breaker into any
compartment prior to inspection.
- Compare the circuit breaker name plate rating with the
switchgear rating.
- Do not attempt to insert a closed circuit breaker.
- Always inspect the circuit breaker compartment to insure that it
is free of obstructions, tools, or other equipment.
1 Insulation resistance Medium voltage circuit The insulation resistance should be at least 50 Mohm
With a 2500 V megger, measure the insulation resistance between and in any case constant over time.
the phases and the exposed conductive part of the circuit.
2 Auxiliary circuits Check that the connections to the control circuit are correct: Operations and signals are normal.
proceed at the relative power supply.
3 Manual operating mechanism Carry out a few closing and opening operations (see cap. 6). The operations and the relative signals take place
N.B. Supply the undervoltage release and the locking magnet on normally.
the operating mechanism at the relative rated voltage
(if provided).
4 Motor o pera tor (8 8 M) Supply the spring charging geared motor at the relative rated The springs are charged normally. The
voltage. signals are normal.
With the springs charged, the geared motor stops.
Carry out a few closing and opening operations. The geared motor recharges the springs after each
N.B. Supply the undervoltage release and the locking magnet on closing operation.
the operating mechanism at the relative rated voltage (if provided).
5 Undervoltage Coil (27UV) (if Supply the undervoltage release at the relative rated voltage and The circuit breaker closes normally.
provided) carry out the circuit breaker closing operation. The signals are normal.
Cut off power to the release. The circuit breaker opens. The
signaling changes over.
6 Trip Coil (52TC1) and Close the circuit breaker and supply the shunt opening release at The circuit breaker opens normally. The
2nd Trip Coil (52TC2) (if provided) the relative rated voltage. signals are normal.
14
Item inspected Procedure Positive check
7 Close Coil (52X) With the circuit breaker open and charged supply the shunt closing The circuit breaker closes normally.
release at the relative rated voltage. The signals are normal.
8 Key lock (if provided) Open the circuit breaker, keep the opening pushbutton Neither manual nor electrical closing takes place.
depressed, then turn the key and remove it from the housing.
Attempt the circuit breaker closing operation.
Put the key back in and turn it 90°. Both electrical and manual closing takes place
Carry out the closing operation. normally; in this position the key cannot be
removed.
9 Auxiliary contacts in the operating Insert the auxiliary contacts in suitable signaling circuits. Signals take place normally.
mechanism. (52a and 52b) Carry out a few closing and opening operations.
10 Undervoltage override With the circuit breaker open, springs charged, override not Closing is not possible.
(33UVa) (if provided) connected and undervoltage release not supplied with power,
attempt circuit breaker closing.
11 Locking electromagnet on the With the circuit breaker open, in the isolated for test position Racking-in is not possible.
truck circuit breaker (52BM) and the locking electromagnet not supplied, attempt circuit-
(if provided) breaker racking-in.
Supply the locking electromagnet and carry out the racking-in Racking-in takes place correctly.
operation.
15
4.6.2. Safety indications
DISCONNECT POSITION
- In the disconnect position the shutters are closed
and the control plug is not connected.
- Only manual charging, manual closing and manual
opening operations are allowed.
- The circuit breaker is interlocked to not be able to
rack from the disconnect position.
TEST POSITION
- In order to rack the circuit breaker, the control plug
must be connected to the switchgear which puts
the circuit breaker into the test position. Figure 7: Circuit Breaker in Test Position
- In the test position, electrical operation of the circuit
breaker is allowed with control power supplied
through the secondary contacts with the shutters
closed.
- Racking is allowed from the test position to the
connect position.
CONNECT POSITION
- In the Connect position, the primary disconnects
are fully engaged and the shutters are open.
- Electrical operation of the circuit breaker through
the secondary contacts remains enabled.
- Racking to and from the connect position should
be done with the door closed.
16
4.6.5 Racking from Connect to Test
Perform a visual inspection of the circuit breaker: 1. Verify Close/Open indicator and signaling provisions show
OPEN. If not, OPEN the circuit breaker. Racking to test
1. Verify Close/Open indicator and signaling provisions show
position is prevented by interlocking when the breaker is
OPEN. If not, OPEN the circuit breaker. Racking to
closed.
connect position is prevented by interlocking when the
breaker is closed. 2. Verify switchgear door is closed.
17
Figure 9: Circuit Breaker Compartment
18
4.6.8. Circuit breaker closing and opening operations CIRCUIT BREAKER CLOSING
- This operation can only be carried out with the closing
spring completely charged.
Circuit breaker operation can be either manual or electrical - For manual closing, press the pushbutton (5).
(figure 11). - The circuit breaker must be in the test or disconnect
position to close.
MANUAL SPRING CHARGING OPERATION - The operation can also be carried out remotely by means
To manually charge the closing springs, it is necessary to of control circuit delivering power to the close coil.
repeatedly activate the charging lever (2) (maximum rotation angle - The closing operation is signaled by the OPEN/CLOSE
indicator.
of the lever: about 90°) until the yellow signaling device
(7) appears; indicating completion of charging. The maximum
CIRCUIT BREAKER OPENING
force which can normally be applied to the lever is < 250 N.
- This operation can be carried out with the closing spring
charged or discharged.
ELECTRICAL SPRING CHARGING OPERATION
- For manual opening, press the pushbutton (4).
The Vmax/A is equipped with an electric charging motor. When
the control plug is connected and power is supplied to the motor - The operation can also be carried out remotely by means
charging circuit (see electric circuit diagram section 9), the of control circuit delivering power to the trip coil or optional
charging motor will charge the closing spring until the yellow second trip coil.
signaling device appears. The circuit is designed such that the - The opening operation is signaled by the OPEN/CLOSE
charging motor will turn on whenever the closing spring is indicator.
discharged.
If the power is cut off during charging, the geared motor stops and
will automatically start recharging the springs when the power
returns. In any case, it is always possible to complete the
recharging operation manually.
19
5. Operation,
installation and
maintenance
5.1. Interlocks 5.1.3. Spring Charge Interlock
These interlocks are provided to prevent incorrect operations
and/or malfunctions. The interlocks are the following:
- When the circuit breaker is racked to the test position
and then the plug is disconnected, the handles in the
5.1.1. Interference blocking
front channel of the truck are blocked because the
A mechanical interference blocking in the circuit breaker
closing spring is charged.
compartment prevents under rated circuit breakers from being
- In order to remove the circuit breaker from the
inserted into higher rated compartments. The code plate rating
compartment, the closing spring must be discharged by
includes continuous current, interrupting current, and maximum
manually pushing the CLOSE pushbutton.
voltage.
- After closing, there is still stored energy in the opening
spring. So the breaker should be opened by pushing
5.1.2. Racking Interlocks
the OPEN pushbutton. Otherwise, the pulling of the
- The withdrawable truck can only be moved from the test/ handles will OPEN the circuit breaker.
- Isolated position to the connected position (and vice
versa) if the circuit breaker is open (this means that first
of all the circuit- breaker must be opened).
- The circuit breaker can only be closed if the
withdrawable truck is exactly in the defined
disconnected, test or in the connected position.
- The circuit breaker can only be racked when the
breaker is OPEN.
- The switchgear is provided with devices which
only allow connection and disconnection of the
plug connector in the test position.
- The circuit breaker can only be racked when the
control plug is connected.
- The handles in the front channel of the truck can
only be pulled in when the circuit breaker is in the
disconnect position.
20
5.2.1. General
5.2. Maintenance Vacuum circuit breakers are characterized by simple, sturdy
construction and long life.
Vmax circuit breakers are designed for a minimum amount of
maintenance. Circuit breakers in a clean, non-corrosive
The drive is maintenance-free for its whole operating life and
environment require only annual inspection. Dusty or
only requires functional inspections.
corrosive environments require inspection more often at the
discretion of the user. Following each interrupted fault
The vacuum interrupters are maintenance-free for their whole
inspection is required.
operating life.
DO NOT work on an energized circuit breaker.
Vacuum interruption does not produce harmful effects even
when there are frequent trips at the rated and short-circuit
DO NOT work on a circuit breaker unless all of the components
current.
are disconnected by means of a visible break and securely
grounded.
The servicing interventions and their aim depend on the
environmental conditions, on the sequence of operations and
DO NOT work on a circuit breaker with power supplied to the
on the trips under short-circuit.
secondary control circuit.
Note
DO NOT defeat safety interlocks. This may result in bodily injury,
For maintenance work, respect the following Standards:
death and/or equipment damage.
– the relative specifications indicated in the “Standards and
Specifications” chapter;
DO NOT work on a closed circuit breaker.
– regulations for safety in the workplace indicated in the
“Putting into service and operations” chapter;
DO NOT work on a circuit breaker with charged energy. (Springs)
– Regulations and specifications of the country where the
apparatus is installed.
DO NOT use a circuit breaker by itself as the sole means of
isolating a high voltage circuit.
The maintenance operations can only be carried out by trained
personnel who respect all the safety regulations. Furthermore, is
DO NOT leave a circuit breaker in an intermediate position in a
recommended that ABB service personnel should be called in, at
cell. Always have the circuit breaker in the Disconnect or
least to check the service performances, and for any repair work.
Connect position.
During maintenance work, turn the power supply off and put the
apparatus under safe conditions.
DO NOT put a circuit breaker of a lower rating into a
switchgear compartment of a higher rating.
21
5.2.2. Mechanism 5.2.3. Operating life
The mechanism requires visual inspection of hardware, All vacuum circuit breakers are characterized by simple, sturdy
lubrication and operation during routine inspection. construction and long useful life. Frequent operation of the service
and short-circuit currents does not negatively affect the degree of
Remove the front cover by unfastening the screws and set the vacuum of the interrupters.
front cover aside, securing the hardware.
Typical useful life expectancy of a Vmax vacuum circuit breaker
Always lubricate the working surface of the moving parts. Verify is determined by the following factors:
lubrication on the connections of the actuator and lever arm. - Vacuum interrupter, maintenance free up to 10,000 mechanical
Remove any grease on the circuit breaker frame. Use only operating cycles.
grease Isoflex Topas NB52 (ABB No GCE0007249P100 1Pt. - drive with mechanical actuator, maintenance free under
can). If the grease becomes caked and dirty, remove with a normal service conditions
clean cloth and reapply lubrication. - up to 10,000 operating cycles for all the circuit breakers with
breaking capacity up to 31.5 kA and rated current up to 2000A
Maintenance operations are aimed at ensuring trouble-free - indication of ON/OFF position up to 10,000 operating cycles
operation of the apparatus for the longest possible time. - Withdrawable truck: up to 500 handling operations can be
In accordance with what is specified in IEEE C37.04 - C37.54 - carried out in the case of normal activation and with regular
C37.09 - C37.55 Standards and NETA Standards, the following inspections.
operations must be carried out:
Inspection: Determination of the actual conditions The data on the useful life are in principle applied to all the
Servicing: Measures to be taken to maintain the specification components which are not directly affected by the operator.
conditions The useful life of the manually activated components (movement
Repairs: Measures to be taken to restore the specification of the withdrawable truck, etc.) can vary according to the type of
conditions. handling.
22
5.2.4. Inspections and functional tests Functional test
– With the circuit breaker in the test position or in a withdrawn
Interruption devices in general position with power supplied through a breaker test cabinet,
– Carry out regular inspections to check that the interruption carry out 3 closing and 3 opening operations by means of the
devices are in good condition. opening and closing coils and 3 closing and 3 opening
– Inspection at fixed intervals can be waived when the operations by means of the manual pushbuttons.
apparatus is permanently monitored by qualified personnel. – Verify that the CLOSE/OPEN indicator changes positions
– Above all, the checks must include a visual inspection to check with each operation.
for any contamination, traces of corrosion and electrical – Further tightening operations during the operating life of the
discharge phenomena. circuit breaker are not foreseen. However, if it should be
– Carry out more frequent inspections when there are unusual necessary to tighten the nuts or screws again following any trips,
operating conditions (including adverse climatic conditions) refer to the values indicated in figures 13 and 14.
and in the case of environmental pollution (e.g. heavy
contamination or an atmosphere with aggressive agents). Stored energy operating mechanism Carry out the functional
– Visual examination of the isolating contacts: test of the operating mechanism every 5,000 operations or every
Turning the system of contacts alternately is recommended, in 4 years.
order to keep the internal surface of the contact areas clean.
The contact areas must be cleaned if there are signs of Note: Insulate the working area and make it safe, following
overheating (discolored surface). the safety regulations specified in IEEE C37.04 – C37.54 –
C37.09 – C37.55 standards.
– If any conditions are found, appropriate servicing measures
must be taken (see the paragraph on “Servicing).
20 Nm
20 Nm
Figure 12: Terminals Torque Requirements Figure 13: Base Frame Torque Requirements
23
5.2.6. Actuator and transmission system
5.2.5. Servicing A functional test of the drive must be carried out:
If cleaning is found to be necessary during the inspections, as - when the number the number of operating cycles indicated
specified in par. “Operations before putting into service”, use has been exceeded, (after 10,000 operation) or
the following procedure: - During maintenance operations.
- Insulate the working area and make it safe by following the
safety regulations specified in the ANSI/NFPA70/NEC Before carrying out the functional test, open the circuit breaker
Standards. and
- General cleaning of the surfaces: - Take it to the test position
- Dry and eliminate any light deposits of dirt using a soft dry - Discharge the closing or opening springs
cloth; - Visually inspect the lubrication conditions of the tulip isolating
- More resistant deposits of dirt can be removed using a slightly contacts, of the sliding surfaces, etc.
alkaline household cleanser or Rivolta BWR 210 type - Check correct electrical and mechanical operation of the
detergent. various devices, with particular attention to the interlocks.
- Cleaning the insulating surfaces and conductive components: - The screws and nuts are tightened in the factory and correct
- Light dirt: with Rivolta BWR 210 detergent; tightening is marked with a collared sign. No further tightening
- Resistant dirt: with cold 716 type detergent. operations are foreseen during the operating life of the circuit-
breaker.
After cleaning, rinse thoroughly with clean water and dry
carefully Functional test:
- Connect the power supply voltage.
Note: Only use halogen-free detergents and never - Carry out several no-load operations. This test particularly
trichloroethane, trichloroethylene or carbon tetrachloride! applies to circuit breakers which are rarely activated under
normal conditions.
24
5.2.7. Servicing details 5.2.9. Repairs
- If provided, turn off the spring charging motor power supply Replacement of spare parts and accessories must only be
and manually discharge the operating mechanism springs by carried out by ABB personnel or suitably qualified and specially
closing and opening the circuit breaker. trained personnel.
- Replace parts subject to high climatic or mechanical stresses
(contact an ABB service center). Always work with the circuit breaker open and locked so that it
cannot be closed again, with the work area insulated and made
Note: These operations can only be carried out by ABB personnel safe.
or suitably qualified and specially trained personnel.
The drive springs must be discharged.
5.2.8. Vacuum interrupters
The vacuum interrupters are maintenance-free up to the All power supply sources must be disconnected and made safe
maximum number of electrical operations. against any reclosing during removal and installation work.
25
With the circuit breaker outside the cell, rotate the racking screw
5.3. Truck as though racking the circuit breaker to the Connect position.
This process will expose surfaces inside the truck that need to
The truck (figure 14) requires visual inspection of hardware,
be inspected and lubricated. Lubricate the exposed parts;
lubrication, and operation during routine maintenance.
specifically the entire racking screw. Inspect the circuit breaker
With the circuit breaker outside the cell, verify all visible
locking tabs for any damage. Return truck to the Disconnect
hardware tightness, including handles and wheels. Wheels
position. As a precaution, do not operate the circuit breaker
should rotate freely by hand movement. Replace or tighten
outside the cell unless the truck is in the full Disconnect position.
any missing or loose hardware.
26
DANCER
27
6. Spare parts and
accessories
To order circuit breaker spare parts/accessories, refer to
the ordering sales codes indicated in the technical 6.1. List of spare parts
catalogue and always state the following:
– Type of circuit breaker – Shunt opening release
– Rated voltage of the circuit breaker – Additional shunt opening release
– Rated normal current of the circuit breaker – Undervoltage release
– Breaking capacity of the circuit breaker – Time delay device for undervoltage release
– Serial number of the circuit breaker – Mechanical override for undervoltage release
– Rated voltage of any electrical spare parts. For – Shunt closing release
availability and to order spare parts, please contact our – Spring charging geared motor with electrical signaling of springs
service office. charged
WARNING – Contact signaling geared motor protection circuit breaker
open/closed
– Contact signaling closing springs charged/discharged
– Circuit breaker auxiliary contacts
– Locking electromagnet on the operating mechanism
– Position contact of the withdrawable truck
– Contacts signaling racked-in/isolated
– Key lock in open position
– Isolation interlock with the door
– Protection for opening pushbutton
– Protection for closing pushbutton
– Locking electromagnet on the withdrawable truck
– Set of six tulip contacts
28
7. Overall
dimensions
Vmax/A - Withdrawable circuit breaker for RELIAGEAR ND SWITCHGEAR
ANSI: 4.76kV – 15kV, 1200A, 25kA - 31.5kA
29
Vmax/A - Withdrawable circuit breaker for RELIAGEAR ND SWITCHGEAR
ANSI: 4.76kV – 15kV, 2000A, 25kA - 31.5kA
30
8. Electric circuit
diagram
Circuit-diagram of Vmax/A circuit breaker in
withdrawable and Roll on the Floor versions for
ReliaGear ND Switchgear.
31
9. Product
quality and
environmental
protection
The apparatus are produced in compliance with the requirements of international standards for the quality management
system and environmental management system. In these fields, the excellent level is proved by quality certificates according
to ISO 9001 and by the EMS according to ISO 14001.
Methods of disposal
Disposal can either be carried out thermally in an incineration plant or by storing on a waste site.
RAW MATERIAL RECOMMENDED METHOD OF DISPOSAL
Metal material (Fe, Cu, Al, Ag, Zn, W, others) Separation and recycling
Thermoplastics Recycling or disposal
Epoxy resin Separation of metal material and the disposal of rest
Rubber Disposal
Oil as dielectric (transformer oil) Draining from equipment and further recycling or disposal
Packing material Recycling or disposal
Packing material Recycling or disposal
32
ABB Inc.
Medium Voltage Apparatus
655 Century Point
Lake Mary, Florida 32746
ABB Inc.
Medium Voltage
Service
2300 Mechanicsville
Road Florence, South
Carolina 29501
www.abb.com/mediumvoltage
www.abb.us/mvservice