TWE-SVF41B-EN

Service Facts
Split System Air Handler
Convertible 20-Ton

Model:
TWE240B300F
TWE240B400F
TWE240BK00F
TWE240BW00F

October 2006
Optional Equipment

Table 1 - Trouble Shooting


W

"P

Th

Lo

Fu

Th tor

Lo

Ex

R
R ct
Lo

R
ig

on age ng

ea

irc ink

el

ap an)

ef

he e e ge

es alv
es io
ig

ef
ha

ow he

w
w

er ans

si

er

ce
h

ay ake

rig der
r ig

tri
ui

tri n i akin
tro

tin e fu

ac

ck
bl
tt

m
vo

in
vo

ss
er

vo

in
tb

ct d
e

.O
.U
(F
o

os orm

al

d
l

V
do flow
lta
lt

iv
lta

io c o g )
oo
su mo

tr

re
c

el
ta

cu

ve

n
g

or
g

em
pp

(F

ra
t
e

to

(T il
rc

e
ck

va
ai
an
ly

ir
w

ut
e

ha

XV
c
SYSTEM FAULTS

rfl

Le d
ir i

p.
se

nt

ha
iri

r
ow
ng

Lo

or
rg
er
de

C
AP
.)
REFRIGERANT CIRCUIT
Head Pressure Too High C P
H P S
Head Pressure Too Low C P P
H S
Suction Pressure Too High C P P P P
H S P
Suction Pressure Too Low C P P P P
H P
Indoor Coil Frosting C P P P P
H
Liquid Floodback (TXV) C P
H
Liquid Floodback (Cap. Tube) C P
H
ELECTRICAL
I.D. Motor Won't Start C P P P P P P P P P
H P P P P P P P P P
Heating Element Inoperative C
H P P P P P P P P P P P P P
C Cooling H Heating P Primary Causes S Secondary Causes

Optional Equipment Figure 1 - Refrigerant Circuit


Unit Subbase...................... BAYBASE005A
Return Grille........................ BAYGRLE005A
Low Static Drive Kit............ BAYLSDR001A
High Static Motor
230 & 240 Volt BAYHSMT029A
575 Volt BAYHSMT036A
Isolator
Floor Mounted Rubber....... BAYISLT010A
Suspended Rubber............. BAYISLT016B
Floor Mounted Spring........ BAYISLT021A
Suspended Spring.............. BAYISLT031B
Discharge Plenum & Grille
Discharge Plenum & Grille BAYPLNM019A
Discharge Plenum & Grille with Elect.
BAYPLNM029A
Heat Acc............
Hydronic Coil - Steam........ BAYWATR016A
Hydronic Coil - Hot Water.. BAYWATR021B
Drip Kit................................ BAYDRKT005A

WARNING: HAZARDOUS VOLTAGE-DISCONNECT POWER BEFORE SERVICING


SAFETY NOTICE
This information is intended for use by indi- RE-CONNECT
Failure to DISCONNECT viduals possessing adequate backgrounds of ALL GROUNDING DEVICES
POWER before servicing electrical and mechanical experience. Any at- All parts of this product capable of conduct-
tempt to repair a central air conditioning ing electrical current are grounded. If ground-
could lead to severe personal product may result in personal injury and/or ing wires, screws, straps, clips, nuts or
injury or death. property damage. The manufacturer of seller washers used to complete a path to ground
cannot be responsible for the interpretation are removed for service, they must be re-
of this information, nor can it assume any lia- turned to their original position and properly
bility in connection with its use. fastened.

© 2005 American Standard Inc. All rights reserved TWE-SVF41B-EN


Product Specifications

Table 2 - Product Specifications


MODEL TWE240B3 TWE240B4 TWE240BK TWE240BW
RATED Volts/PH/HZ 208-230/3/60 460/3/60 380/3/60 575/3/60
INDOOR COIL - TYPE Plate Fin
Rows - F.P.I 3-12
Face Area (sq. ft) 21.6
Tube Size (in.) O.D. 0.375
Refrigerant Control Expansion Valve
Drain Connection Size (in.) O.D. 1.0 PVC Pipe-Female
INDOOR FAN - TYPE FC Centrifugal
Dia. Width (in.) 15 x 15
No. Used 2
Drive Speeds Belt - 1
No. Motor - HP 1 - 5.0
Motor Speed R.P.M. 1750
Volts/PH/HZ 208-230/3/60 460/3/60 380/3/50 575/3/60
F.L. Amps - L.R. Amps 14.5 - 98.0 6.7 - 47.0 10.0 - 53.9 5.4 - 37.3
FILTER Furnished
Type Throwaway
Size (in.) Qty. 4 each - 16x25x2 & 16x20x2
REFRIGERANT (R-22) Shipped w/Nitrogen Holding Charge
Ref. Line Connections Braze
Suction Line Size - (in.) O.D. 1 3/8
Liquid Line Size - (in.) O.D. 1/2
DIMENSIONS LxWxH
Crated (in.) 95 x 34 x 77
Uncrated (in.) 94 x 32 x 72
WEIGHT
Shipping (lbs.) 886
Net lbs. 820

Table 3 - Evaporator Fan Performance


External Static Pressure (in. of water column)
0.10 0.20 0.30 .040 0.50 0.60 0.70 0.80 0.90 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40 2.60
RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM RPM
CFM
BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP BHP
486 528 570 612 654 696 743 781 808 835 883 930 976 1021 1066 1111 1156 1201
6400
1.08 1.24 1.41 1.57 1.70 1.83 2.06 2.25 2.40 2.55 2.86 3.16 3.52 3.89 4.26 4.62 4.99 5.36
509 551 593 635 677 722 762 794 820 846 894 941 986 1030 1075 1119 1164 1208
6800
1.24 1.41 1.58 1.74 1.90 2.08 2.29 2.46 2.61 2.76 3.07 3.40 3.78 4.16 4.55 4.93 5.36 5.69
531 573 615 657 700 747 781 806 831 856 904 951 995 1039 1083 1127 1171 1215
7200
1.40 1.58 1.75 1.92 2.09 2.33 2.52 2.66 2.81 2.96 3.29 3.65 4.04 4.44 4.84 5.23 5.63 6.02
558 603 651 694 731 766 795 819 844 869 919 963 1007 1050 1093 1136 1179 1222
7600
1.69 1.84 1.98 2.15 2.38 2.57 2.74 2.88 3.02 3.17 3.55 3.94 4.34 4.75 5.16 5.57 5.98 6.37
585 633 686 730 761 785 809 832 857 882 933 975 1018 1060 1103 1145 1187 1228
8000
1.97 2.11 2.21 2.39 2.66 2.81 2.95 3.09 3.23 3.37 3.80 4.23 4.65 5.07 5.49 5.91 6.34 6.72
619 657 710 752 778 801 823 848 873 899 947 989 1032 1074 1117 1159 1200 1237
8400
2.20 2.35 2.54 2.73 2.94 3.09 3.23 3.39 3.55 3.71 4.14 4.57 5.01 5.44 5.87 6.31 6.73 7.10
652 680 733 773 794 816 837 863 889 915 960 1002 1045 1087 1130 1172 1212 1246
8800
2.43 2.60 2.86 3.07 3.22 3.36 3.50 3.68 3.86 4.04 4.47 4.92 5.36 5.81 6.26 6.70 7.11 7.47
682 723 760 790 811 834 858 884 909 932 975 1016 1058 1099 1141 1182 1219 1252
9200
2.76 2.98 3.19 3.37 3.52 3.68 3.84 4.01 4.20 4.40 4.83 5.28 5.73 6.17 6.62 7.07 7.47 7.85
711 766 787 807 828 852 878 904 929 949 990 1030 1071 1111 1152 1192 1226 1258
9600
3.08 3.36 3.52 3.67 3.82 3.99 4.17 4.35 4.53 4.75 5.20 5.65 6.09 6.54 6.99 7.43 7.83 8.22
Low
Static Standard Static Drive
Low Static Drive II High Static Drive
Drive
I
Notes:
1. Evaporator fan performance is based on wet coil and 1-inch throwaway filters.
2. Tabulated brake horsepower (BHP) is the motor shaft output required.

TWE-SVF41B-EN 3
Product Specifications

Table 4 - Blower Speeds


Motor Sheave Turns Open
Drive Used with 6 5 4 3 2 1 0
Low Static I TWE240B3 557 583 609 634 660 686 712
Low Static II TWE240B4
TWE240BW 701 727 753 779 805 831 857
TWE240BK
Standard Static 862 894 926 958 990 1022 1054
High Static TWE240B3
TWE240B4 N/A 991 1040 1091 1140 1190 1239
TWE240BW

Table 5 - Supplementary Heaters


Heater Model Used With Power Supply kW Rating Nominal BTUH
BAYHTRM310A 7.50/10.00 25598/34130
BAYHTRM320A TWE240B3 208/240/3/60 14.96/19.92 51058/67987
BAYHTRM330A 22.50/29.92 76793/102117
BAYHTRM350A 37.42/49.84 127714/170104
BAYHTRM410A 10.00 34130
BAYHTRM420A TWE240B4 480/3/60 19.92 67987
BAYHTRM430A 29.92 102117
BAYHTRM450A 49.94 170104
BAYHTRMW10A 10.00 34130
BAYHTRMW20A TWE240BW 600/3/60 19.92 67987
BAYHTRMW30A 29.92 102117
BAYHTRMW50A 49.84 170104
All field wire must be rated at least 75 C.

Table 6 - Static Pressure Drop Through Electric Heaters Table 7 - Drive Components
Unit Standard Low Static I Low Static II High Static
Air Handler Airflow (CFM) Static Pressure Drop - Inches W.G.
Motor
Model Kilowatt Rating 10.00 19.92 29.92 49.84 HP 5 7.5
6800 0.06 0.06 0.13 0.19 Volts 208-230/460/575 208-230/460/575
Phase 3 3
7200 0.08 0.08 0.16 0.24 Hertz 60 60
RPM 1740 3470
TWE240B 8000 0.10 0.10 0.20 0.30 Frame 184T 184T
8800 0.12 0.12 0.24 0.36 Insul B B
Amb 40 C Max. 40 C Max.
9600 0.14 0.14 0.28 0.42 S.F. 1.15 1.15
Motor
Sheave See
P.D. 5.4 - 6.6 4.3 - 5.5 Standard 4.0 - 5.0
O.D. 7.10 6.00 Sheave 5.35
Bore 1.125 1.125 1.125
Blower
Sheave
P.D. 10.9 13.4 13.4 14.0
O.D. 11.25 13.75 13.75 14.25
Bore 1.4375 1.4375 1.4375 1.4375
Belt
Qty 1 1 1 2
Size B64 B67 B69 A68

Literature Order Number TWE-SVF41B-EN


File Number SV-UN-TWE-SVF41B-EN-10/06
Supersedes TWE-SVF41A-EN-04/05
Stocking Location Electronic Only

The manufacturer has a policy of continuous product and data improvement and reserves the right to