Constructional & Electrical Performance Data LUL S1108 (Formerly 1-108 & EME-SP-14-025 A2) - 500sqmm Trackfeeder

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Constructional & Electrical Performance Data

LUL S1108 (formerly 1-108 & EME-SP-14-025 A2) – 500sqmm Trackfeeder

Construction Stranded tinned annealed copper conductors,


Ethylene Propylene Rubber (EPR) insulation, Low Smoke Zero Halogen (LSZH) sheath

Specification S1108 (formerly 1-108 & LUL EME-SP-14-025 A2)

Voltage Rating 750V (dc)

Operating Temperature -25C to +85C

Standard Colour Black

Approvals London Underground Limited

Conductor diameter 29.15mm (Nom)

Radial thickness of insulation 5.00mm (Min)

Radial thickness of sheath 7.50mm (Min)

Overall diameter 54.0mm (Min) – 56.50mm (Max)

Nett Weight 7300 Kg/Km

High Voltage test 5000V for 5 minutes

Conductor resistance 0.0361 Ω/Km @ 20°C (Max)

Insulation resistance 535 MΩ/Km @ 20°C (Min)

Current Ratings

Calculated from first principles using IEC287 and based on an ambient temperature of 20°C and a maximum conductor
temperature of 85°C.

Derating factor 0.96 for 25°C ambient


0.92 for 30°C ambient

One cable laid on ballast 1160 Amps


Two cables laid on ballast 1160 Amps (one cable spacing – no derating)

One cable laid in a duct 770 Amps


Two cables laid in a duct 615 Amps

Short Circuit Current Ratings

72.90 kA for 1 second


42.10 kA for 3 seconds
32.60 kA for 5 seconds

General Note
AEI Cables reserves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.

© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA

Telephone: +44 (0) 191 410 3111 Facsimile: +44 (0) 191 410 8312
Email: sales@aeicables.co.uk or technical@aeicables.co.uk
Website: www.aeicables.co.uk
Constructional & Electrical Performance Data
LUL S1108 (formerly 1-108 & EME-SP-14-025 A2) – 630sqmm Trackfeeder

Construction Stranded tinned annealed copper conductors,


Ethylene Propylene Rubber (EPR) insulation, Low Smoke Zero Halogen (LSZH) sheath

Specification Generally to LUL 1-108 A2

Voltage Rating 750V (dc)

Standard Colour Black

Harmonised Code N/A

Conductor diameter 32.76mm (Nom)

Radial thickness of insulation 5.00mm (Min)

Radial thickness of sheath 7.50mm (Min)

Overall diameter 57.70mm (Min) – 60.2mm (Max)

Nett Weight 8601 Kg/Km

High Voltage test 5000V for 5 minutes

Conductor resistance 0.0286 Ω/Km @ 20°C (Max)

Insulation resistance 486 MΩ/Km @ 20°C (Min)

Current Ratings

Calculated from first principles using IEC287 and based on an ambient temperature of 20°C and a maximum conductor
temperature of 85°C.

Derating factor 0.96 for 25°C ambient


0.92 for 30°C ambient

One cable laid on ballast 1440 Amps


Two cables laid on ballast 1440 Amps (one cable spacing – no derating)

One cable laid in a duct 950 Amps


Two cables laid in a duct 760 Amps

Short Circuit Current Ratings

Short circuit temp 160°C Short circuit temp 250°C

51.90 kA for 1 second 72.90 kA for 1 second


30.00 kA for 3 seconds 42.10 kA for 3 second
23.20 kA for 5 seconds 32.60 kA for 5 second

General Note
AEI Cables reserves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.

© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA

Telephone: +44 (0) 191 410 3111 Facsimile: +44 (0) 191 410 8312
Email: sales@aeicables.co.uk or technical@aeicables.co.uk
Website: www.aeicables.co.uk
Constructional & Electrical Performance Data
LUL S1108 (formerly 1-108 & EME-SP-14-025 A2) – 935sqmm Trackfeeder

Construction Stranded tinned annealed copper conductors,


Ethylene Propylene Rubber (EPR) insulation, Low Smoke Zero Halogen (LSZH) sheath

Specification S1108 (formerly 1-108 &LUL EME-SP-14-025 A2)

Voltage Rating 750V (dc)

Operating Temperature -25C to +85C

Standard Colour Black

Approvals London Underground Limited

Conductor diameter 38.70mm (Nom)

Radial thickness of insulation 5.00mm (Min)

Radial thickness of sheath 7.50mm (Min)

Overall diameter 65.0mm (Min) – 67.50mm (Max)

Nett Weight 11,400 Kg/Km

Minimum Bending Radius 540mm

High Voltage test 5000V for 5 minutes

Conductor resistance 0.0194 Ω/Km @ 20°C (Max)

Insulation resistance 420 MΩ/Km @ 20°C (Min)

Current Ratings

Calculated from first principles using IEC287 and based on an ambient temperature of 20°C and a maximum conductor
temperature of 85°C.

Derating factor 0.96 for 25°C ambient


0.92 for 30°C ambient

One cable laid on ballast 1770 Amps


Two cables laid on ballast 1770 Amps (one cable spacing – no derating)

One cable laid in a duct 1170 Amps


Two cables laid in a duct 935 Amps

Short Circuit Current Ratings

97.20 kA for 1 second


56.10 kA for 3 seconds
43.50 kA for 5 seconds

General Note
AEI Cables reserves the right to amend the product information without notice or liability.
The information is considered accurate at the time of going to print.

© AEI Cables Limited Durham Road, Birtley, Chester-le-Street, County Durham DH3 2RA

Telephone: +44 (0) 191 410 3111 Facsimile: +44 (0) 191 410 8312
Email: sales@aeicables.co.uk or technical@aeicables.co.uk
Website: www.aeicables.co.uk

You might also like