Abb LMT100 200 Nivel
Abb LMT100 200 Nivel
Abb LMT100 200 Nivel
A B B M E A S U R E M E N T & A N A LY T I C S | O P E R AT I N G I N S T R U C T I O N
Table of Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
General safety information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Improper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical limit values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Warranty provision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Use of instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operator liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Qualified personnel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
RoHS Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Returning devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Information on WEEE Directive 2012/19/EU
(Waste Electrical and Electronic Equipment). . . . . . . . . . . . . . . . . . . . 7
Safety information for electrical installation. . . . . . . . . . . . . . . . . . . . . 7
Safety information for inspection and maintenance. . . . . . . . . . . . . . . . 8
Explosive atmospheres installation. . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Transmitter overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Transmitter components overview. . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Optional wired on SST plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unpacking and handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
All installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Hazardous area considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
IP protection and designation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mounting the transmitters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mounting the LMT100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mounting the LMT200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
LMT200 valve positioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Pressure Equipment Directive (PED) (2014/68/EU). . . . . . . . . . . . . . . . 17
Transmitter housing rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installing / removing the external push buttons. . . . . . . . . . . . . . . . . . 17
Installing / removing the HMI display . . . . . . . . . . . . . . . . . . . . . . . . 18
Integral display rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Securing the housing in flame-proof areas. . . . . . . . . . . . . . . . . . . . . 18
6 Transmitter wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cable connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Supply requirement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Integrated lightning protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 3
7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Transmitter factory configuration consideration. . . . . . . . . . . . . . . . . 22
Preliminary checks prior to start-up. . . . . . . . . . . . . . . . . . . . . . . . . 22
Local push buttons functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Write protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Hardware write protection activation via external switch. . . . . . . . . . . . 22
Write-protection activation via device software. . . . . . . . . . . . . . . . . . . . . 23
Range and span consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Configuration types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Configuring the transmitter without an integral HMI . . . . . . . . . . . . . . 23
Configuring the transmitter using the optional integral
HMI - Through the Glass (TTG) (L2 option) . . . . . . . . . . . . . . . . . . . . . 23
Commissioning using the Easy Setup menu . . . . . . . . . . . . . . . . . . . . 24
Configuration with a handheld terminal . . . . . . . . . . . . . . . . . . . . . . 25
8 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Menu navigation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Control button functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
HMI menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Easy Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Device Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Calibrate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Device Info. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Menu levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Product display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Switching to operator menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Switching to the configuration level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Selecting and changing parameters. . . . . . . . . . . . . . . . . . . . . . . . . 30
Selecting a parameter value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Setting a numerical parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Exiting the setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Menu: Easy Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Menu: Device Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Overview of the linearization/strapping tables. . . . . . . . . . . . . . . . . . . . . . 38
Menu: Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Menu: Calibrate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Level Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Menu: Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Waveform display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Menu: Device Info. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Menu: Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Cyber security and access level . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Setting passwords. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Access Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Write protect switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Password recovery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
4 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
10 Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Personnel qualifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Required tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Electronic replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Safety Inspection and test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Float inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Sensor inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Transmitter testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Fieldbus communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
1 Introduction
This manual is designed to provide information on installing,
operating and troubleshooting the LMT Series of level
transmitters. This LMT Series is comprised of the LMT100 and
LMT200 models.
Magnetic float
Every section of this manual is dedicated to the specific phases
assembly
of the LMT lifecycle. The start of the lifecycle begins with the
receipt of the transmitter and its identification and continues Sensor
through installation, the connection of all electrical
components, the configuration of the device and finally ends
with the troubleshooting and maintenance operations.
Product description
Current
The LMT Series of level transmitters is a modular range of field pulse
mounted, microprocessor-based electronic transmitters, Sensor
utilizing multiple sensor technologies. Accurate and reliable tube Gauge (KM26)
measurement of liquid levels is provided in even the most
difficult and hazardous industrial environments. The LMT Sensor
Series can be configured to provide specific industrial output wire
signals, according to Fieldbus digital communication. The LMT
Series consists of two models (LMT100 & LMT200): Figure 2 LMT200 mounted on gauge (KM26)
Sensor 3 The interaction of the magnetic field around the wire and the
magnetic float causes a torsional stress wave to be induced
Current in the wire. This torsion propagates along the wire at a
pulse known velocity, from the position of the magnetic float and
Sensor Tube toward both ends of the wire.
2 Safety
General safety information
The following Safety section provides an overview of the safety For reasons of safety, ABB recommends that only sufficiently
aspects that must be observed for operation of the device. For insulated tools, conforming to IEC EN 60900, be used.
the detailed safety guidelines, refer to the LMT Series Safety
Since the transmitter may form a link within a safety chain,
Manual (SM LMT100200-EN A).
it is recommended that the device be replaced immediately
if defects are detected. In the event of use in a hazardous
The device is constructed in accordance with international and
area, only non-sparking tools are to be used.
local regulations and is deemed to be operationally safe.
Additionally, the device is tested and shipped from the factory
in perfect working condition. The information contained within In addition, the user must observe all relevant safety
this manual, as well as all applicable documentation and regulations regarding the installation and operation of
certification, must be observed and adhered to in order to electrical systems and the relevant standards, regulations and
maintain the factory-deployed condition throughout the LMT guidelines concerning explosion protection.
Series period of operation.
Only by observing all of the safety information can the user Improper use
minimize the risk of hazards to personnel and / or the
The LMT Series magnetostrictive transmitters are designed for
environment. The provided instructions are intended as an
reliable and accurate measurement of liquid levels in the
overview only and do not contain detailed information on all
industrial applications. Use the LMT for this purpose only. The
available models or every conceivable scenario that may arise
manufacturer accepts no liability for any form of damage
during setup, operation and / or maintenance work.
resulting from improper use!
Use of instruction
DANGER - Serious damage to health / risk to life to ABB must be free of any hazardous materials (for example,
This symbol in conjunction with the signal word “DANGER”
acids, alkalis and solvents).
indicates an imminent electrical hazard. Failure to observe
this safety information will result in death or severe injury.
WARNING - Bodily injury
This symbol in conjunction with the signal word “WARNING”
Disposal
indicates a potentially dangerous situation. Failure to observe ABB actively promotes environmental awareness and has an
this safety information may result in death or severe injury.
operational management system that meets the requirements
CAUTION - Minor Injuries
This symbol in conjunction with the signal word “CAUTION”
of DIN EN ISO 9001:2000, EN ISO 14001:2004 and OHSAS 18001.
indicates a potentially dangerous situation. Failure to observe ABB products are intended to have minimal impact on the
this safety information may result in minor or moderate injury. environment and individuals during their manufacture, storage,
This symbol may also be used for property damage warnings.
transport, use and disposal.
NOTICE - Property Damage
This symbol indicates a potentially damaging situation.
Failure to observe this safety information may result in This adherence to environmental standards includes the use of
damage to or destruction of the product and / or other natural resources. In this endeavor, ABB maintains an open
system components.
dialog with the public through its publications.
IMPORTANT (NOTE)
This symbol indicates operator tips, particularly useful
information or important information about the product or its The product / solution is manufactured from materials that can
further uses. The signal word “IMPORTANT (NOTE)” does not be reused by specialized recycling companies.
indicate a dangerous or harmful situation.
WARNING
There are electric circuits within the housing which are
dangerous if touched. Therefore, the auxiliary power must
be switched off before opening the housing cover.
WARNING
The device can be operated at high pressure and with
aggressive media. Any process media released may cause
severe injuries. Depressurize the pipeline / tank before
opening the transmitter process connection.
For specific conditions for safe use of the LMT100 and LMT200,
refer to the LMT Series Safety Manual (SM LMT100200-EN).
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 9
3 Transmitter overview
Transmitter components overview
The following represents an exploded view of the components
comprising the LMT Series level transmitter (see Figure 3).
4 Unpacking
Identification
The transmitter is identified by the name plates. A The Please refer to the serial number when speaking to ABB service
nameplate provides information (see figure 4) concerning the department personnel.
model number, probe length, sensor material, process
connection type, process connection material, maximum IMPORTANT (NOTE)
pressure ratings, power supply, output signal, serial number, The name plates shown here are only examples. The name
maximum processed temperature limits and Maximum ambient plates attached to the device may be different to what you see
temperature limits. B The certification plate contains the below.
certification-related parameters for use in a hazardous area.
WARNING
Transmitter probes with a W3 or W7 option have a flexible
sensor tube. When removing the sensor from the sensor
well, do not expose the sensor to moisture. Additionally, it is
important to prevent water from entering the sensor well.
12 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
5 Mounting
General
Read the following installation instructions carefully before
proceeding. Failure to observe the warnings and instructions
CAUTION
may cause a malfunction or personal hazard. Before installing When the certification plate label is not identified the type
the transmitter, ensure the device design meets the of protection, the user shall, on installation,mark the label
requirements of the measurement point from both a measure with the type of protection. The certification will be void If
technology and safety point of view. there are more than one type of protection marked on the
label.
This applies in respect to:
• Explosion-protection certification
• Measuring range IP protection and designation
• Pressure
The housing for the LMT Series transmitters is certified as
• Temperature
conforming to protection type IP66 (according to IEC 60529) or
• Operating voltage
NEMA 4X (according to NEMA 250).
CAUTION
Do not run an external magnet on the outside of the sensor
and then take the magnet off. This leaves residual magnetic
properties on the wire, causing a false echo. if a magnet is
Figure 6 Floats
used, be sure to run the magnet from the sensor elbow to
the probe tip to ensure no residual magnetic field is
IMPORTANT (NOTE)
present.
During installation, take care not to bend the probe tube, and
protect the float from shock and impact loads.If the float is
Compression fittings removed during installation, it must be slid back onto the probe
When fitted with a compression fitting as the process tube afterwords for LMT100 with the “TOP” marking oriented
connection, the sensor tube is shipped with a set of TEFLON® towards the sensor head end, to enable correct measurements
ferrules and a set of metal ferrules in a separate bag. The to be made. For LMT200, the float must be installed in the
TEFLON® ferrules are only intended for use in applications with chamber in proper orientation.
operating pressures at or below 3.4 bar (50 psig) and process
temperatures at or below 204°C (400°F). For higher operating Sensor wells
pressures or temperatures or for permanent installation, Certain transmitter options have the sensor tube inserted into
replace the TEFLON® ferrules with metal ferrules. a sensor well. These options allow the sensor tube and housing
to be removed for service without breaking the seal on the
Floats vessel. These options include (consult model number) W1, W2,
The float is a key component of the LMT Series transmitter that W3, W4, W5, W6, C3, C4, W7, J4 and J5.
must be matched to the medium in respect of density, pressure
resistance and material durability. Every LMT float is precisely
engineered to customer application, ensuring optimal accuracy
and performance. Precisely spaced magnets create a 360°
magnetic field coverage, safeguarding level transmitter and
gauge performance, even the most challenging applications.
Several materials of construction available including Titanium,
14 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Sensor Wells 2 Lower the bottom tube section with the float stop and float
Model Sensor Type Sensor Well into tank.
W1, W2, ½ in. rigid 5/8 in. tube
3 Insert the top of the tube assembly through the mounting
W4, W5, W6, 5/8 in. rigid ¾ in. pipe (typical)
flange.
C3, C4
W3, ½ in. flexible stainless 5/8 in. tube 4 Add the next section of tube and thread together using
W7 5/8 in. flexible plastic 1 in. sectioned tube thread locking fluid (Loctite® 242®) to secure joints.
J4, J5 ½ in. rigid 5/8 in. tube with TEFLON® jacket
5 Repeat step 4 for each middle tube section.
6 Add the last section (TOP) of the tube with 1 in. compression
The compression fittings that hold the sensor inside the sensor
fitting, and thread into the assembly using thread locking
well contain TEFLON® ferrules. It is not necessary to change the
fluid (Loctite® 242®) to secure the joint.
TEFLON® ferrules to metal. This connection will not be required
to retain process pressure. 7 Thread the tube compression fitting into the mounting
flange using thread sealant.
IMPORTANT (NOTE)
8 Lower the tube assembly until it hits the bottom of the tank.
When installing/removing a sensor into/from a sensor well, a
Raise the sensor well back up 12mm (½in) and secure the
wrench shall be used on both the sensor, and the sensor well.
assembly in place by tightening the tube compression
The sensor installation torque shall not be transferred to the
fitting.
sensor well.
WARNING
When handling flexible tubing, do not bend any section of
the tube into a diameter of less than 4 feet. This could
permanently damage the internal assembly and prevent
proper operation.
Hose / Gear
Clamp Transmitter
Clamp
Top Mount
Factory
Zero Mark
Bottom Mount
Figure 9 LMT200 Mounting
90° Probes
Select LMT Series of transmitters are manufactured with a 90°
bend near the housing to distance the electronics housing from
the temperature of the process, to remote the sensor from the
chamber or to allow access to the electronics when the sensor
mounted under cryogenic insulation. These are identified by
Bottom Mount
Top Mount
Elbow
Retaining
Screw
Sensor
tube
IMPORTANT (NOTE)
With an Ex d / flame-proof design, please refer to the securing
the housing cover in flame-proof areas section.
IMPORTANT (NOTE)
Retighten the housing cover until it is hand-tight.
Default 90°
180° 270°
6 Transmitter wiring
• F
ield wiring should be rated at least 10°C above the device
DANGER maximum ambient temperature
Observe all applicable regulations governing electrical
installation. Connections must be established only in a zero-
voltage state. Since the transmitter does not switch-off
elements, overvoltage protection devices, lightning
protection and / or voltage separation capacity must be
provided at the plant. (overvoltage / lightning protection is
optional). Check that the existing operating voltage
corresponds to the voltage indicated on the name plate. The
same wires are used for both the power supply and output
signal. In case the surge protection option is present and
the transmitter is installed in a hazardous area, the
transmitter has to be supplied power from a voltage source
isolated from mains (galvanic separation). Furthermore, the
potential equalization for the entire powering cable must be
guaranteed since the intrinsic safety circuit of the
transmitter is grounded.
Depending on the design supplied, the electrical connection is 2 Internal ground terminal
established via a cable entry, M20 x 1.5 or ½” NPT thread. The 3 Fieldbus line (polarity independent)
screw terminals are suitable for wire cross sections up to
2.5mm2 (AWG 14). Figure 17 LMT Foundation Fieldbus terminal scheme
IMPORTANT (NOTE)
Supply requirement
With transmitters for use in “Zone 2”, a qualified cable gland for
this type of protection must be installed by the customer. Refer For signal / power connections, use twisted, stranded pairs of
to the LMT Series Safety Manual (SM LMT100200-EN A). M20 x wiring, 18 to 22 AWG / 0.8 to 0.35mm2 Ø up to 1500m (5,000ft).
1.5 threads are located in the electronics housing for this Longer loops require lower gauge wire. If a shielded wire is
purpose. For transmitters with a flame-proof enclosure (Ex db) used, the shield should be grounded only at one end, not both
type of protection, the housing cover must be secured using the ends. In case of wiring at the transmitter end, use the terminal
locking screw. The screw plug that may have been supplied with located inside the housing marked with the appropriate
the transmitter must be sealed at the plant using Molykote DX. symbol.
The installer assumes responsibility for any other type of
sealing medium used. Increased force is required to unscrew The supply voltage range is 9 VDC to 32 VDC.
the housing cover after an interval of several weeks. This is not
caused by the threads but is due to the type of gasket. For Exia approval power supply must not exceed 24 VDC (FF -
816 certification) or 17.5 V DC (FISCO certification).
CAUTION Avoid routing cables with other electrical cables (with inductive
• T
he cable entry device shall comply with the requirements load) or near large electrical equipment.
of EN 60079-0 and maintain IP 54 or better as required by
the installation conditions.
20 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Wiring procedure
Follow these steps to wire transmitter:
• Remove the terminal cap from one of the two electrical
WARNING
connection ports located at both sides of the transmitter General risks. Cable, cable gland and unused port plug must
housing. be in accordance with the intended type of protection (for
• The connection ports may have a ½-inch internal NPT or M20 example, intrinsically safe and explosion-proof) and the
threads. Various adapters and bushings can be fitted to these degree of protection (for example, IP6x according to IEC EN
threads to comply with plant wiring (conduit) standards. 60529 or NEMA 4x). See also the addendum for Ex Safety
• For Foundation Fieldbus version, the terminal without surge Aspects and IP Protection. In particular, for explosion-proof
protection is as below: installation, remove the red, temporary plastic cap and plug
the unused opening with a plug certified for explosion
containment.
Grounding
A terminal is available on both the outside of the housing and in
the plug for grounding (PE) the transmitter. Both terminals are
electrically connected to one another (see Figure 19).
Figure 18 FF Terminal board without surge option
WARNING
In an explosion-proof / flame-proof installation, do not
Figure 19 Ground connection on transmitter housing
remove the transmitter covers when power is supplied to
the unit.
All transmitters are supplied with an external ground
connection for protective grounding. Wire this ground
• Run the cable through cable gland and the open port. connection to a suitable earth ground. For a transmitter
• Connect the positive lead to the + terminal and the negative measuring loop, an earth ground should maintain a resistance
lead to the – terminal. of 5 ohms or less. Use a heavy-duty conductor, at least 15 AWG /
• Plug and seal the electrical ports. Ensure that upon 1.6mm2 Ø.
completion of the installation, the electrical ports are
properly sealed against entry from rain and / or corrosive
vapors and gases.
WARNING
The LMT provides internal and external grounding terminals
for use in installations in accordance to the applicable
regional regulations governing electrical installations.
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 21
A Measuring sensor
Remote version: Connection to remote
mount design B Transmitter
The signal cable connects the measuring sensor to the
transmitter. The cable is fixed to the transmitter, however, it 1 Heat-shrink tube Ø 4 mm, 10 mm long 2 Forked cable lug
can be separated as needed.
3 Heat-shrink tube Ø 2.3 mm, 40 mm long (shielding)
When laying the signal cable, observe the following points:
–– Install the signal cable in the shortest path between the
The signal cable can also be cut to any
measuring sensor and the transmitter. Shorten the signal
cable accordingly as needed. length. Then the cable ends must be
–– The maximum permissible signal cable length is 30 m prepared as below.
(99 ft).
–– Twist the shield, shorten and insulate with heat-shrink
–– Avoid installing the signal cable in the vicinity of electrical
tube 3. Crimp a matching forked cable lug 2 and insulate the
equipment or switching elements that can create stray
crimping with a heat-shrink tube 1.
fields, switching pulses and induction. If this is not possible,
–– Provide the wires on the measuring sensor side with wire-
run the signal cable through a metal pipe and connect this
end ferrules (0.75 mm2).
to operational ground.
–– Twist the wires to the transmitter side and solder.
–– Carry out all terminal connections carefully.
–– Lay the wires in the terminal box in such a way that they are
not affected by vibrations. Remote version: Connecting the signal cable
• Switch off the power supply and wait for t > 2 minutes
before opening.
NOTICE
The shielding of the signal cable also serves as a functional
ground and must be connected to the sensor and to the
transmitter on both sides.
4 Insert the cable through the cable gland into the terminal
box.
7 Connect the shield of the signal cable to the forked cable lug
to the ground terminal.
7 Commissioning
Transmitter factory configuration
consideration 1 Identification nameplate
The LMT Series level transmitters have been factory-calibrated
2 “Z” Zero push button
to reflect the published performance specification; no further
calibration is required under normal conditions. ABB typically 3 “S” Span push button
configures the LMT Series level transmitters according to user
4 Write-protection button
requirements. A typical configuration includes:
• Tag number
• Calibrated span
• Display configuration Write protection
Write protection prevents the configuration data from being
Preliminary checks prior to start-up overwritten by unauthorized users.
NOTICE
Operating the control buttons with a magnetic screwdriver
is not permitted.
Figure 23 Push Button Functionalities Figure 24 Write Protection Push Button
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 25
Write-protection activation via device software The lower range value and span parameters can be set directly
Write-protection via device software is possible. Please refer to on the transmitter, using the external push buttons.
Section 8 “Operation” of this manual, under “Menu: Device
Setup”. The transmitter is calibrated by the manufacturer, based on the
order information. The tag plate contains information on the
IMPORTANT (NOTE) “lower range value” and the “upper range value” set. In general,
A brief interruption in the power supply results in initialization the following applies:
of the electronics (program restarts).
WARNING
Range and span consideration Operating the control buttons with a magnetic screwdriver
The LMT Series data sheets provide all the information is not permitted.
concerning the range and span limits in relation to the model
and sensor codes.
LRV and URV configuration using local push buttons
• Apply the level for the lower range value and wait until the
URL Upper Range Limit of a specific sensor. This represents
signal has stabilized.
the measured value’s highest set point that the
• Press the “Z” button. This sets the zero level position.
transmitter can be adjusted to.
• Apply the level for the upper range value and wait until the
LRL Lower Range Limit of a specific sensor. This represents
signal has stabilized.
the lowest value of the measured value that the
• Press the “S” button. This sets the span level position. If
transmitter can be adjusted to measure.
required, reset the damping to its original value.
URV Upper Range Value. The measured value’s highest value
by which the transmitter is calibrated.
Record the new settings. The respective parameter is stored in
LRV Lower Range Value. The lowest value of the measured
the non-volatile memory 10 seconds after the “Z” or “S” button
value to which the transmitter is calibrated.
is pressed.
SPAN The algebraic difference between the Upper and Lower
Range Values. The minimum span is the minimum value
IMPORTANT (NOTE)
that can be used without degradation of the specified
This configuration does not affect the physical process level
performance.
(PV value), also shown on the digital display or user interface.
After performing a change, check the device configuration.
The transmitter can be calibrated with any range between the
LRL and the URL with the following limitations:
LRL < LRV < (URL – CAL SPAN) Configuring the transmitter using the
CAL SPAN > MIN SPAN optional integral HMI - Through the Glass
URV < URL (TTG) (L2 option)
The integral HMI is connected on the LMT Series
Configuration types
communication board. It can be used to visualize the process-
Level transmitters can be configured as follows: measured variables as well as to configure the display and the
• Configuration of the parameters for the lower and upper transmitter.
range values (via Zero and Span push buttons), without an
integral HMI using the local push buttons. The TTG technology allows the user to activate the keypad on
• Configuration of the level transmitter using the integral HMI the HMI without the need of opening the windowed cover of
with keypad (menu-controlled) the transmitter. The capacitive pickups detect the presence of
• Configuration with a handheld terminal the user’s finger in front of the respective button, activating
the specific command. At the transmitter power-on, the HMI
automatically calibrates its sensitivity. It is mandatory for the
Configuring the transmitter without an
proper functioning of the TTG HMI that the cover is sufficiently
integral HMI tightened at power-on.
LMT Series level transmitters allow local adjustments via the
onboard non-intrusive push buttons, when selected. The push In case the cover has been removed to access the
buttons are located under the identification nameplate. To gain communication board, it is recommended to power off and
access to the local adjustments, release the attaching screws power on the transmitter once the windowed cover has been
on the nameplate and rotate the identification plate clockwise. set in place and properly tightened.
26 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Figure 25 HMI Display Keyboard Note that depending on the device configuration, Level Unit
may display as Volume Unit or Flow Unit
The keys (1), (4), (2) and (3) are available for the menu-controlled
configuration.
IMPORTANT (NOTE)
If the device is configured with two levels, the interface
2 Select Easy Setup in the main menu parameters will be set up at this point in the procedure.
Depending on device configurations, these two parameters will
be one of the following combinations:
• Interface Level LRV and Interface Level URV
• Volume Interface LRV and Volume Interface URV
7 Select Level Damping Time in the Easy Setup menu and press Configuration with a handheld terminal
The user can utilize a hand-held terminal to read out or
configure / calibrate the transmitter.
Damping allows for smoothing of the device output step
response.
Hand-held terminals such as Emerson Process 375, 475 and
AMS (provided the LMT Series EDD is downloaded and enabled
in the terminal).
8 Select Display 1 Line 1 View in the Easy Setup menu and press
8 Operation
The HMI display is provided with optional capacitive control 4 Marker for indicating relative position within the menu
buttons. When this option is selected, device control through
5 Function currently assigned to the and control
the glass of the closed cover is enabled.
buttons
IMPORTANT (NOTE)
When the capacitive control button option is selected, the Control button functions
transmitter automatically calibrates the buttons on a regular
basis. If the cover should be opened during operation, the Function Meaning
button sensitivity is increased at first. As a result, operating Exit Exit the menu
errors may occur. The button sensitivity returns to normal Back Go back to the upper level menu
during the next automatic calibration. Cancel Cancel a parameter entry
Next Select the next position for entering numerical and
Menu navigation alphanumeric values
Function Meaning
Select Select a submenu or parameter
Edit Edit a parameter
OK Save the entry
3 Menu number
Easy Setup
Device Setup
Display
Calibrate
Main Access
Diagnostics
Device Info
Communication
Service
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 29
This menu allows the verification and the setting of parameters The Calibrate menu allows the local calibration of the
for the basic configuration of the LMT Series level transmitters. instrument. This includes setting calibration points and the
Easy Setup guides the user to the choice of interface language, offset value for the level, liquid interface (for two liquids) and
the tag number configuration, the engineering units, the upper temperature.
range value and the lower range value (URV and LRV) and the
display visualization mode (the value that needs to be Diagnostics
visualized on the HMI).
Device Setup
Display
The Device Info menu enables the user to retrieve all device
information. The menu-driven structure shows the user the
sensor type, the hardware and software revisions, the high and
low sensor limits, and the minimum applicable span.
Communication
Menu levels
Product display
Product Display
Symbol Description
Call up information level
Service access
IMPORTANT (NOTE)
The HMI display automatically returns to the product display, 5
minutes after the last button is actuated
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 31
The first line indicates where the error occurred. The second
line shows the unique ID. The next lines give a brief description
of the error and its remedy.
32 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
The Easy Setup menu has multiple options that are available to
the user. These options are detailed below:
Language
Setting a numerical parameter
1 Select the parameter you want to set in the menu
Level Unit The interface LRV and URV define the lower and upper values at
which LMT transmitters will generate interface measurement
output
The Level Unit option allows the user to select the unit of
measurement for the level measurement. This unit of
measurement then provides a basis for all setup functions.
Selectable engineering units include: inches, feet, meters,
centimeters and millimeters. Note that depending on device Damping is a setting designed to delay the output response to
settings, Level Unit may also display as Volume Unit or Flow a change in the measured level. If the process is agitated or
Unit. splashing of the liquid is a possibility, a higher damping value
may be required. If the process changes rapidly, a lower
Level LRV damping value may be needed to improve the response time to
a level change. The highest damping value allowable is 60
seconds.
The Level LRV (lower range value) is the configuration for the
lowest value, measured in engineering units, at which LMT
transmitters will generate output. LRV is also referred to as the
zero point. LRV is set to zero from the factory. Note that
depending on device settings, Level LRV may also display as The display line can be set to Raw Level, Distance/Ullage and
Volume Level LRV or Flow LRV. Level. If the device is configured for two levels, it can also be set
to Interface. The graph can be set to display % span or % mA
Level URV value.
Tag
The Level URV (upper range value) is the configuration for the
highest value, measured in engineering units, at which LMT
transmitters will generate output. This is generally known as The tag parameter is the final step in Easy Setup. It allows the
the span point. Note that depending on device settings, Level operator to add the device tag or another memo in the device
URV may also display as Volume Level URV or Flow URV. tag menu
IMPORTANT (NOTE)
If the device is configured with two levels, two further
parameters will be included in the Easy Setup menu. Depending
on the device configuration, these will be one of the following
combinations:
• Interface Level LRV and Interface Level URV
• Volume Interface LRV and Volume Interface URV
34 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Software WP
Write Protect
Hardware WP
Level Unit
Unit Setup Flow Unit
Volume Unit
Level Damping
Time
Level Units
Lower Range
Device Variables Level
Upper Range
Level Offset
Lower Range
Interface Upper Range
Interface Offset
Lower Range
Distance/Ullage Upper Range
Ullage Ref. Point
Units
Lower Range
Upper Range
Temperature
Temperature
Offset
Lower Temp Limit
Upper Temp Limit
Damping Time
Units
Volume Level Lower Range
Upper Range
Units
Volume Interface Lower Range
Upper Range
Units
... Flow Lower Range
Upper Range
36 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
...
Table State
Input Units
Output Type
Linearization Setup
Output Units
Minimum
Maximum
Device Points
Configuration
Clear
Mount Configure Tables Restore
Orientation Save
Standard
Password
Advanced
Access Control
Password
Service Password
Reset to Defaults
Save as default
Reset to factory
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 37
A(τ) = A*(1-2.71828-t/τ)
0.8
linearization were not used in these cases, the resulting level
calculation would not meet the expected accuracy due to the
0.6
non-linear function between the level in the tank and the
calculated level.
0.4
Figure 30 shows the chart for the plot of Level (mm) vs. Volume
(m3) for the tank in figure 29
The below is an example linearization table for the tank in Configuring Setup
Figure 29, where the Diameter is 1000 mm, Length is 2500 mm, STEP 1:
Input Unit is mm, Output Type is Volume, and Output Unit is Press to navigate to Setup
liters.
Press to enter the Linearization Setup menu
Point 00 01 02 03 04 20
Input Value 0 100 200 800 900 1000
<In> (mm)
Output 0 102.19 279.56 1683.94 1861.31 1963.5
Value
<Out> (lit)
STEP 2:
STEP 1:
Press to enter the Table State menu
STEP 3:
Press to edit the Table State
STEP 2:
Press to navigate to Device Setup menu
STEP 4:
Press or to navigate to Enabled
IMPORTANT (NOTE)
All parameters in the following section are edited in the same
way unless otherwise stated
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 43
You can now configure the Input Units, Output Type, Output Press to go back to the Linearization Setup root menu
Units, and the Minimum and Maximum output values from the
Linearization Setup menu
IMPORTANT (NOTE)
The options for Output Type are Level, Volume, and Flow
IMPORTANT (NOTE) depending on the device configuration
There is no need to go back to the Linearization Setup root
menu each time to navigate between the submenus. After you STEP 7:
enter one of the Linearization Setup submenus, it is possible to Press to navigate to the Output Units menu
navigate to the other submenus using the and
keys. Press to edit the output unit
For example, when inside the Table State submenu, pressing Press or to select the output unit
will jump directly to the Input Units submenu. Pressing
it again will take you to the Output Type submenu. Press to confirm the selection
STEP 8:
Press to navigate to the Minimum menu
STEP 6:
Press to navigate to the Output Type menu
Editing Points
STEP 1:
STEP 3:
From the Linearization menu, press or to
Press to scroll to the Input value <In>
navigate to the Points submenu
STEP 4:
Press to scroll to the Output value <Out>
IMPORTANT (NOTE)
1 Current linearization point number (00 – 20)
STEP 5:
Press to edit the output value of the point
Repeat Step 2-5 to enable and assign input and output values
for other points.
IMPORTANT (NOTE)
At least 2 points must be used, but 2 points will be the same as
standard calibration unless the Output Type is set to Volume or
Flow.
46 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Menu: Display
Language
Contrast
Display Mode
Operator Pages
Operator Page 1...4
Autoscroll
Autoscroll Timer
Distance Format
Linearization
Format
Temperature
Format
Display Test
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 47
Menu: Calibrate
Calibration Points
Level Calibration
Reset Calibration
Process
Temperature Offset
Temperature
Reset Calibration
Calibration
Level LRV
Level URV
Interface LRV
Interface URV
Distance/Ullage
LRV
Distance/Ullage
URV
Volume Interface
LRV
Volume Interface
URV
Flow LRV
Flow URV
...
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 49
...
Level Offset
Interface Offset
Temperature
Offset
Level Calibration
The LMT Series is a digital transmitter with no routine
calibration or reconfiguration required. If a recalibration is
required, this can be done using the menu driven HMI display,
push button and Hand-held terminals.
By default, after the trim the SVL and LVL are aligned at the
calibration points 00 and 01 matching each other values, but
during the Level Calibration SVL can be mapped to different
Level Values (LVL) that don’t violate the validation rule for Level
calibration: The LVL span must be within ±5% the SVL span.
STEP 2:
Press or to navigate to Advanced
Press Select
In other words, the SVL can be seen as the level output of the
instrument based only on the factory trim. After the factory
trim the SVL at any given point on the probe will remain
unchanged for the life of the instrument (unless trimmed again
at later time). It is not affected by any level calibration, offset or
linearization applied by the user.
STEP 3: STEP 5:
Press or to navigate to the Calibrate menu Press to scroll to <In>, which corresponds to the input
value of point 00
Press Select to enter the menu
For wet calibration, the float must be at the position where the
cal. Point 00 is wanted
STEP 4:
Press or to navigate to the Level Calibration
menu
STEP 6:
For dry calibration, when the float or level cannot be moved to
the desired position for point 00, press <right> to edit the
input value
IMPORTANT (NOTE)
Calibration points menu description
Menu: Diagnostics
Level Sim
Interface Sim
Ullage Sim
Temperature Sim
Simulation
Volume Level Sim
Volume Interface
Sim
Flow Sim
Diagnostic History
Clear Diag History
Electronics Temp
History Process Temp
Process Temp Min
Process Temp Max
Proc Temp Reset
Maintenance
Required
Group Masking Check Function
Off Specification
Info/None
LVL – Level
INT – Interface
PV% – Process Value in percentage
SVL – Sensor Value for Level
SVI – Sensor Value for Interface
STEP 2: • At Level displays the signal with the Level position centered
Press or to navigate to Advanced on the screen, unless other limiting factors apply. Typically,
the Level position should be visible on the screen.
Press Select • At Distance displays the signal starting from the distance
specified by the user. The Level position must be centered in
the screen, unless other limiting factors apply. Typically, the
level position should be visible on the screen.
• End of Probe displays the signal at the tip of the probe.
STEP 3:
Press or to select THD (threshold)
Press or to navigate to the Diagnostic menu
STEP 4:
Press or to navigate to the Waveform menu
PULSE WIDTH:
Press and to select PLS (pulse width)
Press and to edit each digit Managing the horizontal offset of the waveform
STEP 1:
Press to complete this operation and confirm the input Press to scroll to the offset setting
value
Press to increase the horizontal offset to start
displaying the signal from a point further down the length of
the probe
STEP 2:
Press to increase the horizontal scale or to
reduce it
IMPORTANT (NOTE)
• If with the selected offset the screen covers more than the
length of the probe then the navigation to larger offset will be
rejected, because the selected one already covers everything
that is to display.
IMPORTANT (NOTE)
• If the scale selected covers more than the length of the probe
then the navigation to larger scale will be rejected, because
the selected one already covers everything that is to display
• After reaching the upper scale, pressing will rollover to
the lowest scale
60 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Serial Number
1 Level
1 Level +
Device Temperature
Configuration 2 Level
2 Level +
Temperature
Mount Top
Orientation Bottom
Sensor ID
Type
Probe Length
SW Version
HW Version
Sensor
FPGA Version
Sensor Low Limit
Sensor High Limit
Sensor Offset (Lvl)
Sensor Offset (Int)
ITK Version
SW Version
Electronics
HW Version
SW Version
Display
HW Version
62 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
Menu: Communication
Node Address
Tag
Descriptor
Message
Manuf. ID
Device Type
Device Revision
IMPORTANT (NOTE)
When the transmitter is powered-up for the first time, the
Standard and Advanced levels can be accessed without
password protection. It is strongly recommended to set
passwords for these access levels.
Access Level
The Access Level is entered via the Operator menu / Enter
Registration details Communication between the DAP and CAP takes place using
channels. Each I/O function block in the CAP has exclusive use
All the Registration details are available from the Fieldbus
of exactly one channel. A channel may be bi-directional and it
Foundation webpage.
may have multiple values.
10 Maintenance
The LMT Series of level transmitters operate normally without Electronic replacement
the need for periodic maintenance or inspection. If the
If the electronic module needs to be replaced proceed as follows:
transmitter meets or exceeds the requirements of the
1 Disconnect the power supply and disconnect the wiring.
application, the transmitter can be expected to provide reliable
level indication for a minimum of ten years.
DANGER
If a transmitter fails an inspection or assistance is required for Explosion hazard. Do not open or disconnect equipment
inspection or troubleshooting, contact the ABB Service when a flammable or combustible atmosphere is present.
Department via email at ktek-service@us.abb.com. The Service
Department will answer questions, provide additional
2 Open the communication board compartment cover.
assistance and issue Return Authorization Numbers for
equipment in need of repair.
CAUTION
In the event a magnetostrictive transmitter has suffered a
failure in any component which is exposed to the process,
any other magnetostrictive transmitter installed in the
same or similar process should be inspected for the same
failure, regardless of its maintenance schedule. These
common cause failures include: 1) float collapse due to over
pressure; 2) damage due to material incompatibility; 3)
Figure 38 Open Housing Cover
damage of the sensor tube due to improper installation.
Personnel qualifications
Safety inspection, maintenance and troubleshooting should
only be performed by qualified personnel. These qualifications
include knowledge of information in this instruction manual,
knowledge of the product and its operating principles,
knowledge of the application in which the transmitter is being
applied and general experience as an instrument technician.
IMPORTANT (NOTE)
Failure to disconnect the power supply could result in damage
while removing the communication board electronics
68 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
1 Move the float up and down the length of the sensor tube. It
should move freely from the bottom of the sensor tube to
the process connection.
Figure 41 Communication Board
2 Remove the float from the sensor tube by removing the
6 Connect the sensor flat cable to the new electronic module retaining clip or bolt from the end of the transmitter. Inspect
with dip switch 1 in up position. the float for signs of excessive wear or damage.
7 Screw the new communication into the housing. 3 Submerge the float in a container of water to check for leaks
as air bubbles escaping from the float. The float is a sealed
8 Connect the transmitter to power supply, wait ten seconds
unit and any holes in the shell of the float could allow process
and lower dip-switch 1 to 0 position. LMT can reconfigure
fluid to seep inside.
itself with the previous configured parameters thanks to the
auto-configuration functionality.
IMPORTANT (NOTE)
9 Reset the dip switch position
ABB floats are designed for different specific gravity ranges.
10 Connect back the HMI board on top the communication The float may or may not float in the water. It may be necessary
board with the double male header connector removed in to hold the float under the water to perform this test.
step 3.
Upon completion of float inspection, place the float back on the
11 Place back the window cover removed during step 2.
sensor tube paying careful attention to float orientation. Some
LMT Series transmitters will be equipped with float spacers
designed to keep the float positioned in the measurable range
Safety Inspection and test
of the sensor tube. It is important that the spacer be replaced
An LMT Series transmitter can be divided up into four major when the transmitter is reassembled.
components the float, the sensor, the transmitter and the
output. All of these components and their subcomponents IMPORTANT (NOTE)
should be evaluated during each periodic inspection. This When handling the transmitter ensure the probe does not bend
inspection (and possible repair) should take less than 4 hours if during installation. A bend in the probe could prevent the float
the proper tools are made available. Prior to inspection, the from travelling freely up and down and it could damage the
transmitter should be removed from service following end user magnetostrictive wire fitted inside.
specified procedures regarding lockout, tagout, wiring and
cleaning. Once removed from service, the LMT Series Sensor inspection
transmitter should be laid on a flat even surface. For detailed The sensor of the LMT Series consists of a metal tube
safety guidelines, refer to the LMT Series Safety Manual (SM containing several wires. The sensor tube will measure the float
LMT100200- EN A) location properly if the tube is straight and the float can travel
freely up and down its length. Perform a visual inspection on
the sensor tube to make sure it is straight, free from pits or
gouges, and does not show excessive wear patterns.
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 69
1 Apply power to the transmitter using the typical power setup Window cover - stainless steel 3KQZ207030U0100
for the particular option. 2 HMI display assembly 3KQZ204001U0000
3 HMI connector 3KXL000273U0100
2 Move the float up and down the sensor tube.
4 Communication board 3KXL065055U0200
3 Monitor the indication of the level on the HMI to make sure 6 Terminal board without surge AU3066
the indication corresponds to the float position. Terminal board with surge AU3068
4 Remove the float to make sure the transmitter responds with 7 Blind cover - aluminum 3KQZ207035U0100
an Alarm Indication and a level indication of ----. Blind cover - stainless steel 3KQZ207110U0100
8 Agency approved plug (1/2” NPT) 3KXL000613U2600
5 Place the float back on the sensor tube with the correct
Agency approved plug (M20) 3KXL000614U1100
orientation.
9 Plastic plug (1/2” NPT) 3KXL000438U0100
Plastic plug (M20) 3KXL000289U0100
IMPORTANT (NOTE)
12 Standard mounting kit SPM200-1018-3
It is possible for the LMT Series to continue providing Fieldbus
Vibration isolator mounting kit VI-KIT
communication if the HMI display is not functioning properly. If
the HMI indicator on an electronics module fails to operate, it is
recommended that the electronics module be replaced at the
earliest convenience. It will not be necessary however to shut
down a transmitter or remove it from service based on an HMI
failure.
Fieldbus communication
1 Apply power to the transmitter using the typical loop wiring.
3 Move the float along the length of the probe and monitor the
PV indication on the handheld device.
11 Dimensional drawings
Enclosures
ML up to # of Kits
914.4mm (36in) 2
1828.8mm (72in) 3
2286.0mm (90in) 4
2743.2mm (108in) 4
3200.4mm (126in) 5
3657.6mm (144in) 5
4114.8mm (162in) 6
4572.0mm (180in) 6
> 4572.0mm (180in) consult factory
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 81
Transmitter
Magnet
Valve
Magnet Stem
Assembly Bracket
Valve Mounting
Brackets
82 L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A
*** IMPORTANT CUSTOMER NOTICE: PLEASE READ PRIOR TO RETURNING PRODUCTS TO ABB***
Be sure to include the Return Authorization (RA) number on the shipping label or package to the attention: Customer Service. A
copy of this document should also be included with the packing list. ABB wants to maintain a safe work environment for its
employees. In the event, the returned product or material has been in contact with a potentially hazardous chemical, per federal
regulations, the customer must provide evidence of decontamination and the related chemical composition and characteristics. In
order to expedite your return, please include the applicable Material Safety Data Sheets (MSDS) and decontamination tags by
affixing these documents in close proximity to the shipment label for identification purposes. (January 18, 2006)
Completed by Customer
Reason
Problem Found:
Action:
Requested:
Is expedited return shipping requested? Yes No
If yes, please provide a purchase order or your shipper’s account number (ex. FedEx or UPS). ABB pays return transport via standard ground shipments only.
If purchase order is issued, a copy of purchase order must be included with return documentation. Account #:
Is ABB authorized to repair items determined to be non-warranty? Yes No
If yes, a copy of purchase order must be included with return documentation.
Has product been in contact with any potentially hazardous chemical? Yes No
If yes, documentation product and forward MSDS to ABB, “ATTN: Customer Service”
Ship Via:
L M T 1 0 0 A N D L M T 2 0 0 | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R S | F F O I/ L M T 1 0 0/ 2 0 0/ F F - E N R E V. A 83
Note
—
ABB Inc.
Industrial Automation
125 E. County Line Road
Warminster PA 18974 USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
E-mail: quotes.ktek@us.abb.com
Service e-mail: ktek-service@us.abb.com
www.abb.com/level
—
We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained
therein. Any reproduction, disclosure to third parties or utilization of its contents - in
whole or in parts – is forbidden without prior written consent of ABB.
Copyright© 2016 ABB All rights reserved 3KXL141000R4201