Mtu 12V4000: Standby Power: 1550 Kwel 60 Hz/Water Charge Air Cooling/Fuel Consumption Optimized

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

MTU 12V4000

Standby power: 1550 kWel


380V/60
60 Hz/water
Hz/water chargecharge air cooling/fuel
air cooling/fuel consumption
consumption optimized
optimized

Optional equipment shown. Standard equipment may vary.

Product highlights
Bene�ts Performance Assurance Certi�cation (PAC)
— Low fuel consumption — Engine-generator set tested to ISO 8528-5 for transient response
— Optimized system integration ability — 85% load factor
— High reliability — Verified product design, quality and performance integrity
— High availability of power — All engine systems are prototype and factory tested
— Long maintenance intervals
Complete range of accessories available
Support — Control panel
— Global product support — Fuel system
— Fuel connections with shut-off valve mounted to base frame
Standards — Starting/charging system
— Engine-generator set is designed and manufactured in
facilities certified to standards ISO 2008:9001 and Emissions
ISO 2004:14001 — Fuel consumption optimized
— Generator set complies to ISO 8528
— Generator meets NEMA MG1, BS5000, ISO, DIN EN and Certi�cations
IEC standards — CE certification option
— NFPA 110

Power rating
— System rating: 650 kVA - 1700 kVA
— Accepts rated load in one step per NFPA 110
— Generator set complies to G3 according to ISO 8528-5
— Generator set exceeds load steps according to ISO 8528-5
Application data 1)
Engine Liquid Capacity (Lubrication)
Manufacturer MTU Total oil system capacity: l 260
Model 12V4000G43 Engine jacket water capacity: l 160
Type 4-cycle Intercooler coolant capacity: l 40
Arrangement 12V
Displacement: l 57.2 Combustion air requirements
Bore: mm 170 Combustion air volume: m3/s 2.3
Stroke: mm 210 Max. air intake restriction: mbar 50
Compression ratio 16.4
Rated rpm 1800 Cooling/radiator System
Engine governor ADEC (ECU 7) Coolant flow rate (HT circuit): m3/hr 67
Max power: kWm 1736 Coolant flow rate (LT circuit): m3/hr 35
Air cleaner dry Heat rejection to coolant: kW 640
Heat radiated to charge air cooling: kW 410
Fuel system Heat radiated to ambient: kW 75
Maximum fuel lift: m 5
Total fuel flow: l/min 16
Exhaust system
Fuel consumption2) l/hr g/kWh Exhaust gas temp. (after turbocharger): °C 430
At 100% of power rating: 420.4 201 Exhaust gas volume: m3/s 5.4
At 75% of power rating: 312.4 199 Maximum allowable back pressure: mbar 85
At 50% of power rating: 221.7 212 Minimum allowable back pressure: mbar 30

Engine

4-cycle Closed crankcase ventilation Fuel consumption optimized engine


Standard single stage air filter Governor-electronic isochronous
Oil drain extension & shut-off valve Common rail fuel injection

Cooling system

Jacket water pump Water charge air cooling Jacket water heater
Thermostat(s)

Fuel system

Flexible fuel connectors mounted to Fuel filter with water separator Separate fuel cooler
base frame Switchable fuel filter with water separator

Starting/charging system

24V starter Battery rack & cables


Starter batteries Battery charger

Mounting system

Welded base frame Resilient engine and generator mounting Modular base frame design

Exhaust system

Exhaust bellows with connection flange Y-connection-pipe

1 All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
2 Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
Sound data Emissions data
—— Consult your local MTU distributor for sound data. —— Consult your local MTU distributor for emissions data.

Rating definitions and conditions


—— Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for
the duration of a power outage. No overload capability for this
rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1,
BS 5514 and AS 2789. Average load factor: ≤ 85%.
Operating hours/year: max. 500.
—— Consult your local MTU distributor for derating information.

Rated power is available up to 40°C and 400m above sea level.

Subject to change. | 32310221 | Edition 01/19 | ESM 2019-09.