An Introduction To Earthquake
An Introduction To Earthquake
Chapter one
Introduction
1.1 Effects of earthquakes (on buildings)
An earthquake event can create different hazards for a structure. The effect that is of
primary interest to a designer is the inertial response of structures to ground acceleration that
occurs during an earthquake.
Ground shaking during an earthquake generates inertial forces in the structure. This
inertial force is in response to the self weight of the structure undergoing acceleration from an
initially rest position. (Newton's second law of motion).
Earthquake induced ground motions create inertial forces significantly in the lateral
direction by shaking the structures back and forth.
The vertical acceleration during ground shaking either adds to or subtracts from the
acceleration due to gravity. Since factors of safety are used in the design of structures
to resist the gravity loads, usually most structures tend to be adequate against vertical
shaking.
III. The design lateral forces specified in the code shall be considered in each of the two
orthogonal directions of the structure. For structures which have lateral force resisting
elements in the two orthogonal directions only, the design lateral force shall be
considered along one direction at a time, and not in both directions simultaneously.
load without failure. These are extremely important properties for structures designed to
sustain damage without collapse.
Chapter 2.0
Fundamental of Earthquake Engineering
Causes of Earthquakes
Ground motion generated by sudden displacement within the earth's crust is called an
earthquake.
However, the vast majority of damaging earthquakes originate at, or adjacent to, the
boundaries of crustal tectonic plates, due to relative deformations at the boundaries.
Plate tectonics: According to the widely accepted theory of plate tectonics, the crust and
upper part of the mantle of the earth, called the lithosphere, is about 50Km thick under the
deepest oceans and 150Km thick under the highest mountains. The lithosphere is subdivided
into tectonic plates, which moves as rigid bodies on a relatively soft asthenosphere due to the
convection currents that circulate as a result of the temperature and pressure difference
between the core and the crust.
Tectonic plates
Because of the relative displacements between the two adjoining plates, high stresses
are induced in the bedrock materials within the affected zones. In the case where the stresses
exceed the material strength, or the frictional capacity at the plate interface, the accumulated
strain energy is released in the form of earthquake shock waves.
1. Divergent (constructive)
2. Convergent (destructive)
3. Transform(conservative)
Faults: A fault is defined as a fracture or crack in the rock along which some definite
movement has taken place. Earthquakes are mainly caused due to sudden slip at faults which
results in shaking of earth. This sudden slip results in release of large amount of energy.
Based on fault movement, faults can be classified into four main categories,
Epicenter: The point on the earth's surface that lies vertically above the focus is called the
Epicenter.
Seismic Waves: The large amount of energy released during an earthquake causes radial
propagation of waves within the earth. These waves are called seismic waves which transmit
energy from one point to another through different layers of soil and rock. The waves reflect
and refract on their way to the earth's surface.
Seismic waves can be classified into two main categories:
1. Body wave
2. Surface wave
Body waves: Body waves are generated at the rupture zone and they propagate within the
earth's interior. There are two types of body waves;
i. Primary waves(P-waves)
ii. Secondary Waves (S-waves)
Primary waves: These are longitudinal waves which vibrate in the same direction as the
propagation of the wave. They travel in a push-pull manner similar to sound waves. The
main characteristics of P-waves are ;
P-waves travel faster than S-waves and are thus first to arrive at a recording
station
They travel through all forms of matter (Solid, liquid, and gas)
The velocity of P-waves depend on the density and compressibility of the
medium
Secondary waves (S-waves): These are transverse or shear waves which cause particles to
vibrate in perpendicular direction to the propagation of the wave. They are slower than P-
waves and hence arrive at a recording station after P-waves. Other important characteristics
of S-waves are;
S-waves travel only through solids and not through fluids (liquid and gas)
since fluids do not have any shear resistance.
Their velocity depends on the density and shear strength of material through
which they pass.
Surface waves: Surface waves are the result of reflection and refraction of P and S-waves
during propagation in stratified formation of the earth's crust. They travel along the surface of
the earth and are of two types;
i. Love waves
ii. Rayleigh waves
Love waves: They vibrate in a horizontal plane parallel to the earth's surface and
perpendicular to the direction of wave propagation.
Love waves travel faster than Rayleigh waves and cannot travel through fluids
Love waves along with S-waves cause more damage to structures
Rayleigh waves: These are surface waves that vibrate in an elliptical orbit in the vertical
plane.
Intensity: An earthquake can also be measured based on its effect on people, built
environment, and the natural environment. This observed effect on the surface of the earth's
crust during and after an earthquake event is known as intensity of an earthquake.
Hence, Intensity is a qualitative measure of an earthquake.
For the same magnitude earthquake, the intensity can vary widely at different
locations.
One of the most widely used intensity scale is the Modified Mercalli Intensity scale
(MMI). Other Intensity scales include European Macroseismic scale(EMS),
Medvedev-Sponheuer-Karnik (MSK).
Modified Mercalli Intensity scale (MMI scale)
Intensity Acceleration(cm/s2) Damage Potential
I Less than 1 only instruments can record
II Over 1 felt only on upper floors
III Over 2.5 felt by people at rest and indoor
IV Over 5 felt by people in motion, glass panes of window rattle.
V Over 10 (0.01g) cracking of plaster, people are disturbed
people panic and run outdoors, perceptible damage to
VI Over 30
buildings
VII Over 100 (0.1g) well-designed and well constructed structures are affected
well-designed and well constructed buildings are badly
IX Over 300
damaged
destruction of large number of well-designed and well-
X Over 650 constructed buildings, damage to roads and rails, cracks in
grounds, sliding of slopes, liquefactions
most of the buildings are destroyed, damage to bridges and
XI Over 1000 (g)
dams
total destruction, waves seen on ground surface, rivers
XII Over 3000
courses altered, large amount of rocks may move
3. Based on location:
Inter-plate - earthquakes that occur along the tectonic plate boundaries
I. Richter magnitude (ML) : The Richter magnitude is also known as local magnitude.
The scale was defined by Charles Richter in 1935. According to Richter, the
magnitude of an earthquake M is given by a logarithm of a maximum displacement
amplitude A (in µm), recorded on a Wood-Anderson seismograph located at exactly
100Km from the Epicenter.
The standard Wood-Anderson seismograph has a natural frequency of 1.25
Hz, a critical damping ratio of 0.8 and amplification factor of 2800.
𝑀𝐿 = 𝑙𝑜𝑔10 𝐴 − 𝑙𝑜𝑔10 𝐴0
𝐴
= 𝑙𝑜𝑔10 ( )
𝐴0
II. Body Wave Magnitude (mB): The body wave magnitude is based on amplitude of P-
waves and can be expressed as;
𝐴
𝑚𝐵 = 𝑙𝑜𝑔10 ( ) + 𝜎(∆, ℎ)
𝑇 𝑚𝑎𝑥
III. Surface wave magnitude (Ms): The Ms scale is used to quantify stronger
earthquakes. It is based on the recordings of amplitudes of surface waves with a
period T of 20±2 seconds.
A commonly used equation for computing Ms of a shallow focus (<50km) earthquake
from seismograph records between epicentral distances (20° < ∆< 160°) can be
given as;
𝐴
𝑀𝑠 = 𝑙𝑜𝑔10 ( 𝑠 ) + 1.66 𝑙𝑜𝑔10 ∆ + 3.3
𝑇 𝑚𝑎𝑥
IV. Moment magnitude scale (MW): The ML, mB,and MS scales are all based on using
the maximum recorded amplitude of seismic waves to determine the magnitude of an
earthquake event. These three scales have been found to under-estimate the energy
released during a very large earthquake event. Hence, seismologists have developed a
standard magnitude scale, known as the moment magnitude scale, which can be more
accurate for large earthquakes. The moment magnitude of an earthquake is calculated
using the amount of moment released during an earthquake.
The moment magnitude, MW, can be determined using the following equation;
2
𝑀𝑊 = [ 𝑙𝑜𝑔10 𝑀0 (𝑑𝑦𝑛𝑒. 𝑐𝑚) − 16.0 ]
3
# An earthquake causes an average of 2.6m strike-slip displacement over a 75km long, 22km
deep portion of a transform fault. Assuming the rock along the fault has an average rupture
strength of 180KPa, estimate the seismic moment released and hence the moment magnitude
of the earthquake.
Solution:
Length of fault, L = 75 Km
Depth of fault, D = 22 Km
= 7.72×1014 Nm = (7.72×1014)×107
= 7.72×1021 dyne-cm
2
Hence, Moment magnitude, 𝑀𝑊 = [ 𝑙𝑜𝑔10 𝑀0 − 16.0 ]
3
2
= [ 𝑙𝑜𝑔10 (7.72 × 1021 ) − 16.0 ]
3
= 3.93
∴ 𝑀𝑊 = 3.93
Solution:
𝐴
Surface magnitude, 𝑀𝑠 = 𝑙𝑜𝑔10 ( 𝑠 ) + 1.66 𝑙𝑜𝑔10 ∆ + 3.3
𝑇 𝑚𝑎𝑥
15.6×103
𝑀𝑠 = 𝑙𝑜𝑔10 ( ) + 1.66 𝑙𝑜𝑔10 (10.78°) + 3.3
20
∴ 𝑀𝑆 = 7.9
The time history is the ground motion record that is, plot of the acceleration, velocity, and
displacement, of a point on the ground surface as a function of time for the entire duration of
earthquake.
The maximum amplitude of the recorded acceleration is termed as the peak response
acceleration. Similarly the peak response velocity, and the peak response displacement, are
the maximum amplitude of the recorded velocity and displacement respectively.
Response Spectra
Hence, the response spectrum is a plot of peak value of a response quantity such as
acceleration, velocity, or displacement of an SDOF system as a function of natural vibration
period Tn of the system with a particular damping ratio. Several such plots for different
values of damping ratios can be included to cover the range of damping values included in
actual structures.
the response spectrum of any particular ground motion, but it represents the average of
response spectra of several ground motions.
The design response spectrum is supposed to cover the wide range of natural periods
and the practical range of damping values so that it provides the peak response of all possible
structures. The design response spectrum is presented in the seismic standards. In the Indian
standard, the acceleration response spectrum is presented for 5% damping with the
modification factors for other values of damping.
The peak values of ground acceleration, velocity, and displacement, are known as
amplitude parameters. These amplitude parameters give an idea of the severity of shaking at
a site.
Attenuation
The reduction in vibration of earthquake waves as they travel further away from their
Epicenter is called attenuation.
Esteva (1969) proposed the following attenuation law for earthquake effect at a site with firm
ground,
5600.𝑒 0.8𝑀
𝑎̃ = where, 𝑎̃ is PGA in cm/sec2
(𝑅+40)2
32.𝑒 𝑀
𝑉̃ = where, 𝑉̃ is PGV in cm/sec2
(𝑅+25)2
200 𝑉 ̃2
𝑑̃ = (1 + 0.6 ) . ̃ where, 𝑑̃ is PGD in cm
𝑅 𝑎
# Find the maximum possible PGA at a site 29Km from an earthquake source that is capable
of producing a maximum of 7.6 magnitude earthquake in Richter scale. Use the attenuation
law proposed by Cornell et.al.
ln[PGA] = 6.088
440.64
PGA = = 0.449g cm/sec2
981
Seismicity is the geographic and historic distribution of earthquake as recorded from different
Epicenter location on the earth's surface.
A seismic zone is designated where areas with similar seismicity are classified in the same
zone. Hence a seismic zone can be an area of similar seismicity sharing a common factor, e.g.
the Himalayan belt that lies between the convergence of the Indian and Eurasian Plate.
The goal of seismic zoning is to mark and separate regions of similar probable
intensity of ground motion in a country. This helps in providing a guideline for
earthquake resistance design in constructed facilities.
Hence, a seismic zoning map provides the probable PGA in a region based on
the history of earthquakes within an area. The map can also indicate the
magnitude, intensity, and recurrence interval or frequency of earthquakes in
the area where a structure is to be designed.
Seismic hazard: It is the probability that an earthquake will occur in a given geographical
area, within a given window of time, and with ground motion intensity exceeding a given
threshold.
Seismic Risk: It is estimated based on the seismic hazard in a given area and the risk factor
calculated can be used in building codes, planning infrastructure projects, and determining
insurance rates. In addition, seismic risk also depends on susceptibility of the structure to
damage and the consequences of damage.
Earthquake hazards: Earthquakes pose several hazards to our natural and built environment
such as;
Liquefaction: The phenomenon in which the soil liquefies and the strength of soil is
drastically reduced to the point where the soil is unable to support the structure. Liquefaction
mainly occurs in sandy soil with high water table.
Chapter3
Introduction to Structural dynamics
Dynamic loading: A loading which changes in direction and/or magnitude with respect to
time is a dynamic loading. Hence, earthquake loads, blast impacts, mechanical vibrations, all
have to be considered as dynamic loads in order for their effects on structures to be
understood.
Response of structures to vibration: Structural responses are the effects due to the dynamic
loading on the structure. The structural responses such as displacements and velocities for a
structure under dynamic loading will also be dynamic, i.e. they will vary with time.
Hence structural dynamics involves finding the responses of a structure to dynamic
loading. Two different approaches can be used to carry out dynamic analysis. The choice of
method used depends upon how the loading is defined.
1. Deterministic approach: The analysis of the response of any specified
structural system to a prescribed dynamic loading is defined as a deterministic
analysis.
Prescribed dynamic loading: A loading for which the time
variation is fully known, even though the load may be highly
oscillatory or irregular in character, is known as a prescribed
dynamic load.
Simple Harmonic motion: A motion for which the acceleration of the system is directly
proportional to its displacement from a mean position and is directed to that mean position
can be said to be in simple harmonic motion. e.g. a pendulum.
Damping: The property of a structural system primarily due to its material and structural
arrangement, by which free vibration steadily diminishes in amplitude is called damping. The
simplest model of damping in a system is the viscous damping model.
For viscous damping, the velocity of the system is directly proportional to the
damping force. The proportionality constant is the damping coefficient 'C'.
Hence, damping force,
𝐹𝐷 = 𝐶. 𝑉
where, 𝐹𝐷 is the damping force acting on the system
C is the damping coefficient
V is the velocity of the system
Degree of freedom: The number of independent co-ordinates required to fully describe the
motion of a structural system is known as its degree of freedom.
For instance, the motion of a single pendulum shown below can be described using the
deflection angle 𝜃. Hence it is a single degree of freedom (SDOF) system.
SDOF system
On the other hand, the double pendulum shown below requires at least two deflection angles
𝜃1 and 𝜃2 to describe its motion. Hence the system has two DOF's.
𝜃1
𝜃2
MDOF system
Free vibration: A structure is said to be undergoing free vibration when it is disturbed from
its static equilibrium position and then allowed to vibrate without any external dynamic
excitation (force).
Hence a free vibration is initiated by giving the system some initial displacement u(0) and
velocity v(0) when time t is zero.
C is damping coefficient
m is mass
For e.g. an equivalent single storey model that can be represented by the mass-spring-
damper system given above is shown below. (Note: k = k1 + k2 )
𝑃(𝑡) − 𝐹𝐷 − 𝐹𝑆 = 𝑚. 𝑎
𝑃(𝑡) = 𝑚. 𝑎 + 𝐹𝐷 + 𝐹𝑆
𝑑2𝑢 𝑑𝑢
𝑚. + 𝑐. + 𝑘. 𝑢 = 𝑃(𝑡)
𝑑𝑡 2 𝑑𝑡
𝑚. 𝑢̈ + 𝑐. 𝑢̇ + 𝑘. 𝑢 = 𝑃(𝑡) ..........(i)
𝐹𝐷 is damping force
𝐹𝑆 is elastic spring force
a is acceleration of mass m
Also, free vibration is initiated by disturbing the system from its static equilibrium
position by imparting the mass some displacement u(0) and velocity 𝑢̇ (0) at time zero.
Hence, the undamped free vibration equation can be formulated and solved as follows;
𝑚. 𝑢̈ + 𝑐. 𝑢̇ + 𝑘. 𝑢 = 𝑃(𝑡)
The solution to equation (ii) has the form, 𝑢 = 𝑒 𝑠𝑡 , where the constant s is unknown
𝑚𝑠 2 + 𝑘 = 0
−𝑘
𝑠2 =
𝑚
𝑘
𝑠 2 = −𝜔𝑛2 (∵ 𝜔𝑛2 = )
𝑚
∴ The general solution of the equation of motion is, 𝑢(𝑡) = 𝐴1 𝑒 𝑠1.𝑡 + 𝐴2 𝑒 𝑠2.𝑡
𝑒 𝑖𝑥 +𝑒 −𝑖𝑥 𝑒 𝑖𝑥 −𝑒 −𝑖𝑥
Using de Moivre's theorem, 𝑥 = , s𝑖𝑛𝑥 =
2 2𝑖
Evaluating eq(ii) and eq(iii) at time t=0, we can determine constants A and B,
25 Downloaded from http://www.masenzworld.com
An introduction to Earthquake engineering
∴ 𝐴 = 𝑢(0)
The motion described by equation (iv) is shown in the figure above and is known as a
simple harmonic motion.
The undamped system oscillates back and forth between the maximum displacement
𝑢0 and minimum displacement −𝑢0 . The magnitude 𝑢0 is called the amplitude of the motion,
is given by;
𝑢̇ (0) 2
𝑢0 = √[𝑢(0)]2 + [ ]
𝜔𝑛
Hence the amplitude 𝑢0 depends on the initial displacement u(0) and the initial
velocity 𝑢̇ (0) given to the system at time t=0.
𝑚. 𝑢̈ + 𝑐. 𝑢̇ + 𝑘. 𝑢 = 0
𝑢̈ + 2𝜉𝜔𝑛 𝑢̇ + 𝜔𝑛2 𝑢 = 0
26 Downloaded from http://www.masenzworld.com
An introduction to Earthquake engineering
𝜉 𝑖𝑠 𝑑𝑎𝑚𝑝𝑖𝑛𝑔 𝑟𝑎𝑡𝑖𝑜
Based on the damping ratio 𝜉 acting on a system there can be three types of systems,
1. Critically-damped systems (𝜉 = 1)
2. over-critically damped systems (𝜉 > 1)
3. Under-critically damped systems (𝜉 < 1)
Free vibration response for systems with critical and overcritical damping
Majority of structures such as buildings, bridges, dams, nuclear power plants, offshore
structures etc are underdamped (𝜉<1), with their damping ratio typically less than
10% or 𝜉<0.10.
The response for an undercritically (underdamped) free vibration system can be determined
as follows;
The equation is satisfied for all values of t if, 𝑠 2 + 2𝜉𝜔𝑛 𝑠 + 𝜔𝑛2 = 0 (characteristic
equation)
Equation (iv) gives the response u(t) for an underdamped free vibration system
Damping lowers the natural frequency from 𝜔𝑛 to 𝜔𝐷 , hence lengthens the natural period
from 𝑇𝑛 to 𝑇𝐷 .
2𝜋 2𝜋 𝑇𝑛
𝑇𝑛 = , 𝑇𝐷 = , 𝑇𝐷 =
𝜔𝑛 𝜔𝐷 √1−𝜉 2
𝑇𝐷 is damped natural period
𝜔𝐷 is damped natural frequency
eq(iv) indicates that the displacement amplitude decays exponentially with time. The
𝑢̇ (0)+ 𝜉𝜔𝑛 𝑢(0) 2
envelope curve is ±𝜌𝑒 −𝜉𝜔𝑛 𝑡 as shown in figure above. 𝜌 = √(𝑢(0))2 + ( )
𝜔𝐷
Logarithmic decrement
The damping in a system can be evaluated from the record of free vibration. The decay of
successive amplitudes of motion which is expressed by the logarithmic decrement is related
to the damping ratio.
The logarithmic decrement for a system is defined as the natural logarithm of any two
successive amplitudes in free vibration.
From the equation to the exponential curve above,
𝑢1 = 𝜌𝑒 −𝜉𝜔𝑛 𝑡
𝑢2 = 𝜌𝑒 −𝜉𝜔𝑛 (𝑡+𝑇𝐷)
𝑢
The logarithmic decrement is given by, 𝛿 = 𝑙𝑛 ( 1 )
𝑢2
𝑢1
𝑙𝑛 ( ) = (−𝜔𝑛 𝜉𝑡) − [− 𝜔𝑛 𝜉(𝑡 + 𝑇𝐷 )]
𝑢2
2𝜋
= 𝜔𝑛 𝜉𝑇𝐷 = 𝜔𝑛 𝜉 ( )
𝜔𝐷
2𝜋𝜉
∴𝛿=
√1 − 𝜉 2
If 𝜉 is very small (0.02-0.2) then √1 − 𝜉 2 ≅ 1
MDOF modelling
For most civil engineering structures, the dynamic response cannot be described accurately
using a SDOF model. Instead, MDOF modelling has to be carried out to obtain a more
accurate response of the structural system to a dynamic loading.
One of the most common models used for a multi-storey building is the shear building model.
The assumptions made in constructing a shear building model are;
1) The total mass of the structure is concentrated at the levels of the floors.
2) The girders on the floors are infinitely rigid as compared to the columns. Hence
the floors only undergo only rigid lateral displacement.
3) The deformation of the structure is independent of the axial forces present in the
columns.
SDOF MDOF
1. Modelling cost is low 1. Modelling cost can be high
2. SDOF models are not 2. More accurate than SDOF models
accurate for most structures
3. Difficult to assess the 3. Greater number of DOF's provide better approximation but
reliability of results obtained using two to three DOF's can also give good results
The equations of motion for a MDOF system can be formulated using dynamic equilibrium
condition. The four types of forces that need to be considered for dynamic equilibrium at any
point are;
Therefore for each degree of freedom (DOF) the dynamic equilibrium can be expressed as;
The equilibrium equations can be expressed more conveniently in matrix form as,
Also, we have, [𝑭𝑰 ] = [𝒎]. {𝒖̈ } where, [𝒎] is the mass matrix, {𝒖̈ } is the acceleration
vector
[𝑭𝑫 ] = [𝒄]. {𝒖̇ } [𝒄] is the damping matrix, {𝒖̇ } is the velocity vector
[𝑭𝒔 ] = [𝒌]. {𝒖} [𝒌] is the stiffness matrix, {𝒖} is the displacement
vector
Equation (ii) is the equation of motion for MDOF systems in matrix format
The three storey shear building (see fig.1) can also be represented using the MDOF mass-
spring system as shown below;
The equations of motion can be derived for each mass using Newton's law.
𝑚1 𝑢1̈ + 𝑘1 𝑢1 − 𝑘2 𝑢2 + 𝑘2 𝑢1 = 𝑃1 (𝑡)
For mass 𝑚2 ,
𝑚2 𝑢2̈ + 𝑘2 𝑢2 − 𝑘2 𝑢1 − 𝑘3 𝑢3 + 𝑘3 𝑢2 = 𝑃2 (𝑡)
For mass 𝑚3 ,
𝑚3 𝑢3̈ − 𝑘3 𝑢2 + 𝑘3 𝑢3 = 𝑃3 (𝑡)
eq(i) can be expressed as, ([𝒌]. −𝜔2 [𝒎]). {𝝓} = {𝟎} ........(ii)
Expanding the determinant will give an algebraic equation of nth degree for the frequency
parameter 𝜔2 for a system having n degrees of freedom. The n roots of this equation
(𝜔1 , 𝜔2 , 𝜔3 , … . . , 𝜔𝑛 ) represent the frequencies of n modes of vibration which are possible in
the system. The mode having the lowest frequency is called the first mode or fundamental
mode. The next higher frequency is second mode etc.
The vector made of the entire set of modal frequencies, arranged in sequence, is called
the frequency vector {𝜔}
𝜔1
𝜔2
{𝜔} = .
.
{𝜔𝑛 }
The mode shape vector {𝝓} represents the shape of the vibrating system for various
modes. {𝝓} is a dimensionless vector which is expressed for mode n as ;
𝜙1𝑛
𝜙2𝑛
{𝝓} = . where, n is mode number, N is no of DOF's
.
{𝜙𝑁𝑛 }
Chapter 4
Lateral load resisting systems for buildings
Lateral force-resisting systems
A structural system must be selected by the designer to resist the lateral loading that
my act on the building. Aspects of structural configuration, symmetry, mass distribution, and
vertical regularity may need to be discussed between the architect and the structural engineer.
Important criteria such as adequate strength, stiffness, and ductility must also be considered
for the building to have satisfactory response during an earthquake.
The lateral load in a building is transferred as follows;
Horizontal seismic inertia forces are developed in the structure when subjected to
earthquake loading. These inertial forces are generated at the various floor levels.
The floor and roof slabs are also called diaphragms and have high in-plane rigidity
when made of concrete (RCC)
The diaphragms transfer the inertial load to the vertical load resisting elements.
In the case of wall systems, the shear walls are the primary vertical members
which resist most of the lateral loading from the diaphragms.
In the case of RC frame the columns resist the lateral loading.
The vertical elements transfer the loads to the foundation and hence the load path is
completed at the bearing soil underneath the foundation.
Hence, the floor and roof diaphragms, along with the shear walls and columns together
work as the lateral load resisting system in a building. A well-designed and well-built
building has a reliable load path, established by design. This load path transfers the lateral
forces over the full height of the building from the roof to the foundation.
Lateral force resisting systems can generally be divided on the basis of structural systems
1) Structural frame system
2) Structural wall system
3) Dual frame-wall systems
These three categories can be further subdivided as given in table 7 of IS1893:part1 (2002).
joints. Such frames are capable of carrying gravity loads while providing adequate resistance
to horizontal forces, acting in any direction.
3. Dual System
This system consists of reinforced concrete frames and RC or masonry walls,
interacting together to provide the required resistance to lateral forces. Each structural system
also carries its appropriate share of gravity load in proportion to its lateral stiffness. Dual
system is also known as hybrid or wall-frame system. A dual system is also designed so that
the moment frame independently resists at least 25% of the design base shear due to the
earthquake. A dual system is more redundant and hence has a higher value for response
reduction factor 'R' in IS1893.
2. Plan irregularities:
Torsional irregularity
Re-entrant corners
Non-parallel systems
diaphragm discontinuity
36 Downloaded from http://www.masenzworld.com
An introduction to Earthquake engineering
Vertical irregularity
Vertical irregularity occurs due to sudden and significant change of strength, stiffness,
geometry, and mass over the height of a building.
Stiffness irregularity: According to IS-1893(2002) a soft storey is that in which the lateral
stiffness is less than 70% the lateral stiffness of the storey above or less than 80% of the
average lateral stiffness of the three stories above.
Extreme soft storey is defined as having a lateral stiffness less than 60% the lateral
stiffness of the storey above or less than 70% of the average lateral stiffness of the
three storeys above.
The upper storey moves as a single rigid unit and hence accumulative deformation due to
earthquake lateral loading occurs mainly in the ground storey. The soft storey can fail if
plastic hinges are formed on the soft storey columns.
Mass irregularity
From IS 1893(2002) mass irregularity can be said to exist where the seismic weight of
any storey is more than 200% of that of its adjacent storeys. The seismic weight a floor is its
full dead load plus a percentage of its imposed load as specified in the code.
Lateral strength irregularity: A weak storey is one in which the storey lateral strength is
less than 80% if that in the storey above. The storey lateral strength is the total strength of all
seismic force-resisting elements sharing the storey shear in considered direction.
Rigid diaphragm distributes the horizontal forces to the vertical resisting elements in
direct distribution to their relative rigidities (stiffness). This is based on the
assumption that the diaphragm does not deform itself and will cause each vertical
element to deflect the same amount.
Reinforced concrete slabs and composite steel deck are rigid diaphragms, whereas
timber flooring is a flexible diaphragm.
Center of mass: It is the point where the entire mass of a system can be thought to be
concentrated. The resultant of the earthquake force acts through the center of mass. For a
system with uniform density the center of mass is located at its geometric center (centroid).
Center of rigidity ( center of stiffness): It is the point through which the resultant of the
resisting forces developed in the system passes. Hence, center of rigidity is also the point on
the diaphragm where the application of lateral force will cause only rigid body translation and
no rigid body rotation.
This rigid joint ensures that the ends of beams and columns meeting joints must rotate
by same amount. However, since the beam is infinitely rigid, it cannot deform and
hence, the joint itself is not allowed to rotate. In this case, the bending moment in the
column is reduced to half of that frame without rigid (flexible) joint.
Inelastic deformability is achieved by specially detailing the beams, columns, and the
beam-column joints. The structural detailing in moment resisting frames must ensure
that ductile failure of frame members occur before shear or brittle failure.
The lateral stiffness of moment frames are comparatively less than the shear wall and
braced systems. Hence, the lateral deflections can be relatively large for the frame
system.
The main advantages of moment resistant frames over frames with flexible joints are;
i. Some of the overturning moment caused by the lateral load is transferred to the
ground by means of axial force couple in columns. This helps to significantly reduce
bending moment in the columns.
ii. The lateral storey displacements reduces significantly.
iii. In case of multi-storey buildings both of the above advantages are very significant
which reduces the cost of structure. As the number of storey increases it is more
effective to design special moment resisting frames with ductile detailing.
Portal frame method: The basic assumptions for the portal frame analysis are:
i. The degree of static indeterminacy is 3mn where m is the number of bays and n is the
no of storey.
ii. The point of contra flexure in the column is at mid height of column.
iii. The point of contra flexure in the beam is at mid span of the beam
iv. The axial forces in the internal column in zero.
Cantilever method: assumptions (i) and (ii) are same as that for portal frame method.
iii. The axial force in the column is approximated by assuming that the frame behaves as
a cantilever beam.
iv. The axial stress in columns is assumed to vary linearly from the neutral axis.
Shear Wall
Shear walls are vertical elements of the lateral load resisting systems. A well-designed shear
wall starts at foundation level and is continuous throughout the height of the building. Shear
walls are equivalent to columns with a large depth and a small width. Hence shear walls are
very rigid in their own plane and flexible in the perpendicular plane. Due to the high rigidity
shear walls can help limit lateral displacement of floors during earthquakes.
A shear wall can transfer the lateral forces in its own plane by developing both bending
moment and shear resistance. Since the moment of inertia of a wall section is large for force
acting parallel to its plane, the reinforcement required to resist the moment and shear is not
excessive. Depending on the height to length ratio of a wall (H/L) the following behavior can
occur;