Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Building Technologies

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

7 782

Flame safeguard LFS1...


Flame safeguard with approval for continuous operation for the supervision of oil
flames and gas flames in applications with an ionization probe and a photocell
detector RAR9.
Flame safeguard for intermittent operating mode with UV flame detectors QRA2 /
QRA2M / QRA4 / QRA4M / QRA10 / QRA10M.

LFS1 and this Data Sheet are intended for OEMs using the LFS1 in or on their
products.

Use, features
Use LFS1 units are designed for the supervision of oil burners and gas burners in
combination with control unit LEC1, burner control LME39.xxxRP, or with
programmable logic controllers.
Typical fields of application range from industrial burners up to the highest security level
SIL3 and in the field of ship burners.

Flame supervision:
- Takes place with photocell detector RAR9 with approval for continuous operation,
in the case of LFS1.1 (firing on oil).
- Takes place with an ionization probe with approval for continuous operation or with
UV flame detector QRA2 / QRA2M / QRA4 / QRA4M / QRA10 / QRA10M in
intermittent operation, in the case of LFS1.2 (firing on gas).

Building Technologies
CC1N7782en
18.04.2018
Use, features
The flame detectors are used in conjunction with control unit LEC1 or with freely
programmable controllers in the following applications:
- Dual supervision of burners / supervision of the main flame or of the ignition and
main flame by 2 flame safeguards with the same or different flame detectors
- Multiflame supervision / plants with several burners whose flames must be
supervised individually by one or several flame detectors, but whose startup and
supervision is carried out centrally and simultaneously by only one control unit
- The flame safeguards are also used as flame indication units in combustion
plants with manual startup

Features - Flame signal display via multicolor LED signal lamp


- Flame signal display via DC 0...10 V output signal (display only)
- Can be parameterized via BCI communication interface
- Potential-free signal contacts with double insulation
- Undervoltage detection

Supplementary documentation
ASN Title Documentation Document type
number
LEC1 Control unit CC1N7761 Data Sheet
Connection accessories for small
AGK11.7 CC1N7201 Data Sheet
burner controls
AZL21 / AZL23 Display and operating units CC1N7542 Data Sheet
LFS1 Flame safeguard CC1A7782 User documentation
PC software for microprocessor
Installation and Operating
ACS410 controlled burner controls and CC1J7352
Instructions
flame safeguards
BCI interface between flame
OCI410 CC1N7616 Data Sheet
safeguard and PC
QRA4 / QRA4M UV flame detector CC1N7711 Data Sheet
QRA2 / QRA2M
UV flame detector CC1N7712 Data Sheet
QRA10 / QRA10M
RAR9 Photocell detector CC1N7713 Data Sheet

2/40

Building Technologies CC1N7782en


18.04.2018
Warning notes
To avoid personal injury or damage to property or the environment, the following
warning notes must be observed.

Do not open, interfere with, or modify the unit.

∂ All activities (mounting, installation, service, etc.) must be performed by qualified


staff.
∂ Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If this is not observed,
there is a risk of electric shock
∂ Take suitable measures to provide protection against accidental contact at the
electrical connections. If this is not observed, there is a risk of electric shock
∂ Press the lockout reset button / operation button of the LFS1 or the AGK20 lockout
reset button extension only manually (applying a force of ′10 N) without using any
tools or pointed objects. If this is not observed, there is a risk of loss of safety
functions and a risk of electric shock
∂ Units must not be put into operation after a fall or shock, as this can adversely affect
the safety functions even if the units do not exhibit any external signs of damage. If
this is not observed, there is a risk of loss of safety functions and a risk of electric
shock
∂ Each time work has been carried out (mounting, installation, service, etc.), check
that the wiring is correct. If this is not observed, there is a risk of loss of safety
functions and a risk of electric shock
∂ The mains-powered ionization probe does not offer protection against electric shock
hazards. Protection against accidental contact must be ensured. If this is not
observed, there is a risk of electric shock
∂ An ignited UV tube is a source of UV radiation.
If the flame is supervised by optical flame detectors, both detectors must be placed
in a way that ensures there is no direct visual contact between them. If this is not
observed, there is a risk of loss of safety functions
∂ Connection of UV flame detectors QRA2M and QRA10M is only permitted if
additional module AGK30 is used. Additional module AGK30 must always be
connected within plug-in base AGK11.7 in terminal areas 1…7. If this is not
observed, there is a risk of loss of safety functions and a risk of electric shock
∂ The data line for the AZL2 or other accessories, such as the OCI410 (plugs into the
BCI interface), must only be connected or disconnected when the unit is dead (all-
polar disconnection), since the BCI interface does not ensure safe separation from
the mains voltage. If this is not observed, there is a risk of electric shock
∂ Intermittent operation: For safety reasons – self-test of the flame supervision circuit,
etc. – at least one controlled shutdown must take place every 24 hours for
applications with LFS1.2... and UV flame detectors QRA2 / QRA2M / QRA4 /
QRA4M / QRA10 / QRA10M. If this is not observed, there is a risk of loss of safety
functions
∂ The separating element supplied can be installed in the area between connection
terminals 9, 10, 11, and 12, and the other terminals (1...7) as a means of achieving
double insulation; refer to the Installation notes chapter. It is particularly important
that the wiring is handled and installed correctly and as specified in the area around
the terminals. If this is not observed, there is a risk of loss of safety functions and a
risk of electric shock
∂ The 0...10 V voltage output terminal 7 is not double-insulated from the mains
voltage. It is important to bear this in mind when selecting measuring equipment (at
least CAT III). If this is not observed, there is a risk of electric shock

3/40

Building Technologies CC1N7782en


18.04.2018
Standards and certificates
Only in conjunction with Applied directives:
the flame detectors ∂ Low Voltage Directive 2014/35/EU
∂ Pressure Equipment Directive 2014/68/EC
∂ Gas Appliances Regulation (EU) (EU) 2016/426
∂ Electromagnetic Compatibility EMC (immunity) *) 2014/30/EU
*) The compliance with EMC emission requirements must be checked after the flame safeguard is
installed in equipment

Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
∂ Automatic burner control systems for burners and DIN EN 298
appliances burning gaseous or liquid fuels
∂ Safety and control devices for burners and appliances DIN EN 13611
burning gaseous and/or liquid fuels — General
requirements
∂ Automatic electrical controls for household and similar use DIN EN 60730-2-5
Part 2-5:
Particular requirements for automatic electrical burner
control systems

The edition of the standards that applies in each case can be found in the
declaration of conformity.

Β Note on DIN EN 60335-2-102


Household and similar electrical appliances - Safety - Part 2-102:
Particular requirements for gas, oil and solid-fuel burning appliances having electrical
connections.
The electrical connections of the LFS1 and the AGK11.7 comply with the requirements of
EN 60335-2-102.

EAC Conformity (Eurasian Conformity)

ISO 9001:2015
ISO 14001:2015
OHSAS 18001:2007

China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536

Marine approval (in preparation):

with LEC1
LFS1.11Ax ● ● ● ● --- ● ---
LFS1.21Ax ● ● ● ● ● ● ●
Marine approvals:
Det Norske Veritas: Classification A A A A
Germanischer Lloyd: Classification A
Bureau Veritas EC Code: 31

SIL3 classification to EN 13611:2014:

Suitable for use in safety-related, industrial applications up to safety level SIL3 (safety
integrity level 3).

4/40

Building Technologies CC1N7782en


18.04.2018
Standards and certificates (continued)
The following parameters apply:

Safety
Operating PFHD MTTFD
ASN Flame detector integrity SFF
mode [1/h] [y]
level up to
LFS1.11A1 Continuous
RAR9 SIL3 1.80E-08 6500 ≥99%
LFS1.11A2 operation
LFS1.21A1 Continuous
Ionization probe SIL3 1.80E-08 6500 ≥99%
LFS1.21A2 operation
LFS1.21A1 QRA2 / QRA2M, QRA4 / QRA4M,
Intermittent SIL2 2.30E-07 510 ≥99%
LFS1.21A2 QRA10 / QRA10M
LFS1.21A1 Ionization probe + QRA2 / QRA2M,
Intermittent SIL2 2.30E-07 510 ≥99%
LFS1.21A2 QRA4 / QRA4M, QRA10 / QRA10M

Life cycle
The flame safeguard has a designed life cycle* of 250,000 burner startup cycles which,
under normal operating conditions in heating mode and nominal switching loads,
corresponds to approx. 10 years of service (starting from the date of manufacture on
the nameplate). For industrial applications with reduced switching loads of a maximum
of 0.1 A, the flame safeguard has an increased designed life cycle* of up to 1,000,000
burner startup cycles.

This life cycle is based on the endurance tests specified in standards EN 13611 and EN
298. A summary of the conditions has been published by the European Control
Manufacturers Association (Afecor) (www.afecor.org).

* The designed life cycle is based on use of the flame safeguard according to the
manufacturer’s data sheet. In this case, it is advisable to perform a safety check or
replace the unit. The designed life cycle is not the warranty time specified in the
Terms of Delivery.

Commissioning notes
Concerning connection diagram 7782a06, connection example of two manually
operated burners: Ensure that the drop-out delay time of external relay d is not greater
than 50 ms.

5/40

Building Technologies CC1N7782en


18.04.2018
Mounting notes
∂ Ensure that the relevant national safety regulations are complied with
∂ The flame safeguards can be mounted in any position on the burner, in the control
cabinets, or on the control panels
∂ The plug-in base AGK11.7 is available for mounting and is designed for cable entry
from the front, the side, or below.
4 earth terminals provide connections for the earth conductors of burner plant
components such as the ignition transformer. The flame safeguards themselves
are double-insulated; refer to the Installation notes chapter
∂ The separating plate must be connected so that it is flat / level with the plug-in base;
refer to red hatched area

7782
z07/1
115

∂ The separating plate must only be plugged into terminal 8

6 7 8 9 10 11 2

7782
z06/
1115

6/40

Building Technologies CC1N7782en


18.04.2018
Installation notes
∂ Always run the high-voltage ignition cables separately from the unit and other
cables while observing the greatest possible distances
∂ When wiring, ensure that there is enough free space for the BCI connection jack
∂ Do not mix up phase and neutral conductors

Note!
For use in power supply systems with non-grounded neutral conductors!
Power supply systems with earthed neutral conductors form the basis of the
diagrams and circuit diagrams of the LFS1 in this Data Sheet. In power supply
Β systems with non-earthed neutral conductors, terminal 2 of the LFS1 must be
connected to the earth conductor via the RC unit ARC 4 668 9066 0 for ionization
current supervision. It must be made certain that local regulations are complied with
(e.g., protection against electric shock) since 120 V AC (50 / 60 Hz) or 230 V AC (50
/ 60 Hz) mains voltage produces peak leakage currents of 2.7 mA.

Note!
Double insulation.
The flame safeguards LFS1 and the terminal bases AGK11.7 including separating
plate element are double-insulated between the terminal areas 1...7 and 9...12. This
means that they feature strengthened insulation; refer also to the Technical data
chapter.
Β If the double insulation needs to be present up to the connected components, the
separating plate element included in the scope of delivery of the AGK11.7 must be
installed in all cases (marked with an arrow in the figure below). As an alternative,
other suitable measures can also be put in place. Safe separation can only be
ensured if all connected components are fitted with a safe separation facility and the
components have been wired as specified. In particular, compliance with the relevant
warning notes must be ensured.

Separating plate element

7782z04en/1215

Note!
When using QRA2M and QRA10M!
Connect additional module AGK30 in accordance with connection diagram 7782a14.

Β The ground terminal of plug-in base AGK11.7 (symbol ) must be permanently


connected to the burner ground. Additional module AGK30 must always be
connected within plug-in base AGK11.7 in terminal areas 1…7.
If this is not observed, there is a risk of loss of safety functions and a risk of electric
shock.

7/40

Building Technologies CC1N7782en


18.04.2018
Electrical connection of the flame detectors
It is important to achieve practically disturbance-free and loss-free signal transmission:
∂ Never run detector cables together with other cables
– Line capacitance has an impact on the flame signal
– Use a separate cable
∂ The ionization probe does not offer protection against electric shock
∂ Position the ignition electrode and the ionization probe so that the ignition spark
cannot arc over to the ionization probe; risk of electrical overloads
∂ Observe the permissible detector cable lengths; refer to the Technical data
∂ Mount and adjust the flame detector so that it only detects the flame to be
supervised in each case
∂ Connection of UV flame detectors QRA2M and QRA10M is only permitted if
additional module AGK30 is used
∂ Protect the UV cell adequately against the following UV sources: halogen lamps,
welding equipment, special lamps, ignition sparks, as well as high-energy X-rays
and gamma rays
∂ Polarity or short circuit at the connection terminals of the RAR9 does not lead to a
flame signal
∂ Polarity at the connection terminals of UV flame detectors QRA2 / QRA2M / QRA4
/ QRA4M / QRA10 / QRA10M does not lead to a flame signal.
A short circuit at the connection terminals of UV flame detectors QRA2 / QRA2M /
QRA4 / QRA4M / QRA10 / QRA10M leads to:
- Fault code LOC10: at operating level (terminal 6 of the LFS1 active)
- No flame signal: test level (terminal 6 of the LFS1 inactive)
∂ In general the terminal 5 of LFS1 must not be grounded! When replacing a LFE10
by a LFS1.2 it is particularly important that the ground connection has to be
removed from terminal 10 at the terminal base of LFE10. The ground connection of
QRA10 has to remain unaltered in order to ensure the protection class 1.
∂ If the ionization electrode connected to the burner ground short-circuits, there is no
flame signal

Disposal notes
The flame safeguard contains electrical and electronic components and must not be
disposed of together with domestic waste.
Local and currently valid legislation must be complied with.

8/40

Building Technologies CC1N7782en


18.04.2018
Design
Microprocessor-based flame safeguards LFS1 have a plug-in design and consist of the
LFS1 features
power supply section, flame signal amplifier, and flame relay with potential-free
contacts.
There is also an operating button with an integrated LED signal lamp, which is located
under a viewing window. The LED is used to provide a multicolor indication of error
status and operational status messages, concerning flame signal strength, for instance.
The flame signal strength can also be measured as a 0...10 V DC signal using a
commercially available voltmeter (at least CAT III) at terminal 7.

Communicating via the BCI interface:


On the underside of the LFS1 in the base area, there is a communication interface (BCI
interface), which is used to change parameters or provide a numerical indication of the
flame signal. When the display and operating unit AZL2 is connected, it is possible to
change parameters such as the flame signal flame-on and flame-out response times. In
addition, the flame signal strength can also be displayed permanently during
continuous burner operation.

Using with the control unit LEC1:


The electrical circuit of the LFS1 is intrinsically safe and, in conjunction with the control
unit LEC1, is tested for proper functioning each time the burner is started up. An
automatic extraneous light test is performed by increasing the sensitivity of the amplifier
during the burner off and purging times of the control unit LEC1. An automatic flame
detector test is performed by increasing the operating voltage of the UV tubes during
the burner off and purging times of the control unit LEC1.
In the case of applications with other control units – such as programmable logic
controllers – the extraneous light test can be activated via the control input at terminal
6. This is not required for ionization supervision.

Undervoltage ∂ Flame OFF signal: From operating position if mains voltage drops lower than
approx. 80 V AC (at UN = 120 V AC)
∂ Flame ON signal: Restart is initiated if mains voltage exceeds approx. 85 V AC (at
UN = 120 V AC)
∂ Flame OFF signal: From operating position if mains voltage drops lower than
approx. 165 V AC (at UN = 230 V AC)
∂ Flame ON signal: Restart is initiated if mains voltage exceeds approx. 170 V AC (at
UN = 230 V AC)

Overvoltage No shutdown if the voltage limit exceeds UN +10%.

9/40

Building Technologies CC1N7782en


18.04.2018
Design (continued)
Flame supervision Flame detector Data Sheet
QRA2 / QRA2M, QRA10 / QRA10M N7712
QRA4 / QRA4M N7711
RAR9 N7713
Ionization probe (must be supplied by customer) ---

Using an ionization Flame supervision by making use of the electrical conductivity of the flame in
probe conjunction with the rectifying effect is only possible with gas and blue-flame burners.
Since the flame signal amplifier responds only to the DC component of the flame signal
(ionization current), a short circuit between the flame detector and functional earth
cannot simulate a flame signal.
Single-electrode operation, i.e., ignition and supervision with a single electrode, is not
possible. Do not activate the test mode switchover using terminal 6 during flame
supervision with ionization probes. Terminal 6 must be connected directly to the phase
conductor at terminal 1 in this case.

Using an ionization It is possible to connect an ionization probe and a UV flame detector QRA to the
probe and a UV flame LFS1.2... at the same time. The flame assessment behaves as follows:
detector QRA
Ionization probe UV flame detector QRA LFS1.2 flame assessment
OFF OFF OFF
ON OFF ON
OFF ON ON
ON ON ON

10/40

Building Technologies CC1N7782en


18.04.2018
Type summary and ordering information

The type references given below apply to the LFS1 without plug-in base and without flame detector.
For ordering information for plug-in bases and other accessories; refer to Accessories.

Part no. Type Nominal Use Flame detector BCI Output 0...10 Times Comparison
2)
voltage connection V tw tan
1)
tab
1) types
max. min. max.
BPZ:LFS1.11A2 LFS1.11A2 AC 230 V Oil RAR9... ∂ ∂ 5s 0,3 s 1s LAE10
BPZ:LFS1.21A2 LFS1.21A2 AC 230 V Gas / oil ION ∂ ∂ 5s 0,3 s 1s LFE10
QRA2 / QRA2M
QRA4 / QRA4M
QRA10 / QRA10M
BPZ:LFS1.11A1 LFS1.11A1 AC 120 V Oil RAR9... ∂ ∂ 5s 0,3 s 1s LAE10-110V
BPZ:LFS1.21A1 LFS1.21A1 AC 120 V Gas / oil ION ∂ ∂ 5s 0,3 s 1s LFE10-110V
QRA2 / QRA2M
QRA4 / QRA4M
QRA10 /
QRA10M)
Range adjustment for times From (Parameter 217.00) (Parameter 217.01)
(those are added up to the hours indicated above) 0s 0s
To (Parameter 217.00) (Parameter 217.01)
11.907 s 11.907 s
Increment --- 0.147 s 0.147 s
Factory setting --- 0s 0s

Key
tw Waiting time
tan Flame signal flame-on response time
tab Flame signal flame-out response time
Corresponds to the detection time in the event of a loss of flame (FFDT) EN 298
¹) Factory setting: Refer to note on parameterization
²) Flame safeguards LFS1 are intended to replace the relevant comparison types

11/40

Building Technologies CC1N7782en


18.04.2018
Type summary and ordering information (cont’d)

Note on parameterization:
Use the display and operating unit (display) AZL2 to ensure that the exact value of the required time is
always set as multiples of increments of 0.147 seconds. When parameterizing minimum or maximum
times, a potential tolerance of ±7% must be taken into consideration.

The following applies to minimum values: At least one value which is 7% greater must be
parameterized.
The following applies to maximum values: At least one value which is 7% smaller must be
parameterized.

Example 1: The flame signal flame-out response time tab must not be set above 5 seconds
Calculation: (5 seconds – 1 second) – 7% = 3.65 seconds

Value to be parameterized
(parameter 217.01): Must be the same as or smaller than the calculated value (e.g., 3.528 seconds)

Example 2: The flame signal flame-on response time tan must be set to at least 5 seconds
Calculation: (5 seconds – 0.3 seconds) + 7% = 5.05 seconds

Value to be parameterized
(parameter 217.00): Must be the same as or greater than the calculated value (e.g., 5.145 seconds)

12/40

Building Technologies CC1N7782en


18.04.2018
Accessories
To be ordered
separately:
Flame detector
UV flame detector QRA2…
Refer to Data Sheet N7712

UV flame detector QRA4…


Refer to Data Sheet N7711

UV flame detector QRA10…


Refer to Data Sheet N7712.

Photocell detector RAR9


Refer to Data Sheet N7713

Ionization probe
Supplied by customer

Connection accessories Plug-in base AGK11.7


for small burner controls Article no.: BPZ:AGK11.7
∂ To connect the flame safeguard LFS1 to the burner plant
∂ 11-pole screw terminals
∂ With enclosed plastic separating plate to ensure safe
separation between terminals 9...12 and terminals 1...7
∂ Black plastic
Refer to Data Sheet N7201

Cable gland holder AGK65


Article no.: BPZ:AGK65
For up to 5 PG11 cable glands
Refer to Data Sheet N7201

Cable gland holder AGK65.1


Article no.: BPZ:AGK65.1
For up to 5 M16 x 1.5 cable glands
Refer to Data Sheet N7201

13/40

Building Technologies CC1N7782en


18.04.2018
Accessories (continued)
To be ordered
separately:
Others RC unit ARC46689066 0
Article no.: BPZ:ARC466890660
For the supervision of ionization currents in networks with
non-earthed neutral conductor

Mounting clip for support rail


(The suitability for the particular application has to be
ensured by the user)
Order no. 2309.000
Rittal GmbH & Co. KG
Auf dem Stützelberg
35745 Herborn, Germany
Phone: +49 (0) 2772 / 505-0
Fax: +49 (0) 2772 / 505-2319
www.rittal.de

Reset button extension AGK20


Article no.: BPZ:AGK20

Adapter KF8896
Article no.: BPZ:KF8896
∂ Adapter for replacing LAE10 and LFE10 with LFS1.
∂ Ensures mechanical height adjustment and correct
terminal assignment
Refer to dimensions

Signal cable AGV50.100


Article no.: BPZ:AGV50.100
Signal cable for AZL2, with RJ11 connector, cable length 1
m, pack of 10

Signal cable AGV50.300


Article no.: BPZ:AGV50.300
Signal cable for AZL2, with RJ11 connector, cable length
3 m, pack of 10

Additional module AGK30


Article no.: S55856-Z301-A100
∂ For establishing compatibility of the LFS1.2 with QRA2M
and QRA10M
∂ With 4 connecting wires for connection in plug-in base
AGK11.7

14/40

Building Technologies CC1N7782en


18.04.2018
Accessories (continued)
To be ordered
separately:
Service tools Optical interface OCI400
Article no.: BPZ:OCI400
∂ Optical interface between flame safeguard and PC
∂ Facilitates viewing and recording setting parameters on
site using the ACS410 software
Refer to Data Sheet N7614

OCI410...
Article no.: BPZ:OCI410
BCI interface module between flame safeguard and PC
Facilitates viewing, processing, and recording setting
parameters on site using the ACS410 software
Refer to Data Sheet CC1N7616

Modbus converter or BCI interface converter OCI412.11


Article no.: BPZ:OCI412.11
The unit is used as an interface converter...
∂ …between flame safeguard LFS1 in the proprietary BCI
communication protocol for building automation systems
or PLC systems
The interface on the outlet side is based on the RS-485
standard.

PC software ACS410
Article no.: BPZ:ACS410
For setting the parameters and for visualizing the flame
safeguards
Refer to Software Documentation J7352

Display and operating Display and operating unit AZL21.00A9


unit Article no.: BPZ:AZL21.00A9
Display and operating unit, choice of mounting methods, 8-
digit LCD, 5 buttons, BCI interface for LFS1, degree of
protection IP40
Refer to Data Sheet N7542

Display and operating unit AZL23.00A9


Article no.: BPZ:AZL23.00A9
Display and operating unit, choice of mounting methods, 8-
digit LCD, 5 buttons, BCI interface for LFS1, degree of
protection IP54
Refer to Data Sheet N7542

15/40

Building Technologies CC1N7782en


18.04.2018
Technical data
General unit data Mains voltage (rated voltage) For grounded and non-grounded networks
∂ LFSx.xxA1 120 V AC
(also suitable for 100 V AC networks).
∂ LFSx.xxA2 230 V AC
Mains frequency 50...60 Hz
Internal consumption 5 VA
Rated surge voltage Overvoltage category III:
4 kV for the entire LFS1 unit
2.5 kV for the creepage distances or air gaps
due to voltage limitation measures
Basis of calculation for air gaps and Overvoltage category III and degree of
creepage distances contamination 2 for 230 V AC in accordance
with
DIN EN 60730-1:
- Reinforced insulation between terminal
areas 1...7 and 9...12
- Normal insulation between terminal areas
9...10 and 11...12
External fuse (optional) Max. T6.3H250V to IEC 60127-2
Internal fuse for terminals 11 / 12 (fuse T1.6L250V to IEC 60127-4
cannot be replaced)
External current limitation for terminals 9 / Example: External fuse T1.6A
10
Permissible mounting position Optional
Weight
∂ LFS1.11A1 115 g
∂ LFS1.11A2 115 g
∂ LFS1.21A1 148 g
∂ LFS1.21A2 144 g
Safety class To DIN EN 60730-1:
∂ Safety class I For applications without safe separation.
Protection against electric shock is achieved
through double or reinforced insulation.
Provision for the protective earth connection
is made in the plug-in base AGK11.7. When
replacing LAE10 / LFE10 with KF8896 and
LFS1, the maximum safety class that can be
achieved is I.
∂ Safety class II For applications with safe separation.
Protection against electric shock is achieved
through double or reinforced insulation.
Degree of protection IP40, to be ensured through mounting
Degree of contamination Degree of contamination 2 to DIN EN 60730-1
Software class Class C to DIN EN 60730-2-5
2-channel structure
Minimum flame safeguard self-test frequency2 x per second for continuous operation with
ionization probe or RAR9
Detection time in the event of loss of flame Max. 1 s for LFS1 (including flame detector)
Reaction time in the event of loss of flame Max. 1 s for LFS1 with LEC1
Voltage output at terminal 7 DC 0…10 V
Increment DC 40 mV

16/40

Building Technologies CC1N7782en


18.04.2018
Technical data (continued)
Permissible cable lengths ¹) At a line capacitance of 100 pF/m, unshielded
∂ Terminals 3 to 5 Max. 20 m ²)
∂ Terminal 6 Max. 20 m
∂ Terminal 7 Max. 3 m
∂ Terminals 9 to 12 Max. 20 m
Max. 300 m ¹)
In the event of reduced current rating of max.
0.01 A, 24 V DC / 24 V AC and cosφ = 1.
The Ölflex Smart cable type 108 / 4 x 0.75
mm² is ideal
∂ BCI connection Max. 3 m
Connectable cross-sectional areas
AGK11.7
∂ Terminals 1...7 and 9...12 Min. 0.5 mm² and max. 1.5 mm²
Solid or stranded wire with ferrule
∂ Auxiliary terminals N, PE, 31 Min. 0.50 mm² and max. 1.5 mm²
Solid or stranded wire with ferrule (when
connecting 2 solid or stranded wires per
terminal, the same cross-sectional areas must
be used for each terminal)
Specifications as per EN 60730-1:
Type of shutdown or interruption of each Shutdown with micro switch, 1-pole
circuit Mode of operation type 2 B

Perm. current rating


Terminals 3 and 5 (flame detectors) Refer to Flame detectors chapter
Terminal 6 (test mode switchover) Max. 1 mA
Terminal 7 (voltage output 0...10 V) Max. 0.1 mA
Terminals 11 and 12 (NO switching output) Max. 1 A, cosι ″0.6
For a maximum of 250,000 burner startup
cycles
Max. 0.1 A, cosι = 1
For a maximum of 1,000,000 burner startup
cycles
Terminals 9 and 10 (NC switching output) Max. 0.1 A, cosι ″0.6
For a maximum of 250,000 burner startup
cycles
Max. 0.1 A, cosι = 1
For a maximum of 1,000,000 burner startup
cycles
¹) For longer distances, use low-capacitance cables, maximum 2 nF total, unshielded
²) Run detector cables separately, at least 5 cm away from other cables

Permissible switching voltage


Terminal 6 (test mode switchover) Mains voltage +10%
DC 125 V
Terminals 11 and 12 (NO switching output)
AC 250 V
DC 125 V
Terminals 9 and 10 (NC switching output)
AC 250 V

17/40

Building Technologies CC1N7782en


18.04.2018
Technical data (continued)
Environmental Storage DIN EN 60721-3-1
conditions Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60°C
Humidity <95% r.h.
Transport DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...+60°C
Humidity <95% r.h.
Operation DIN EN 60721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M2
Temperature range -20...+60°C
Humidity <95% r.h.
Installation altitude Max. 2,000 m above sea level

Attention!
Condensation, formation of ice, and ingress of water are not permitted. If this is
not observed, there is a risk of loss of safety functions and a risk of electric
shock.

Signal cable AGV50 Signal cable To connect display and operating unit
Display ↑ BCI AZL2
White, unshielded cable
Internal conductor 4 x 0.141 mm²
Each cable with 2 RJ11 connectors
Cable length AGV50.100 1m
Cable length AGV50.300 3m
Place of installation for signal cable with Under the burner hood (additional
connector measures for SKII to EN 60730-1)

18/40

Building Technologies CC1N7782en


18.04.2018
Technical data (continued)

Measuring circuits for


detector current
measurement
Ionization probe UV flame detector Photocell detector
QRA2 / QRA4 / QRA4M / QRA10 RAR9

QRA... RAR9...

ION

UV flame detector
QRA2M / QRA10M

QRA...
AGK11.7 31
PE N

GN/YE BU BN BK
AGK30

Key A Incidence of light from the flame


C Electrolytic capacitor 100 µF, 10 V DC
ION Ionization probe
M Microammeter
QRA UV flame detector
RAR9 Photocell detector

Attention!
High-voltage ignition may affect the ionization current.
Possible remedy: Swap the ignition transformer's primary connection.

19/40

Building Technologies CC1N7782en


18.04.2018
Technical data (continued)
Flame supervision with ionization probe At mains voltage
Values apply to factory setting of parameters 182 = 0 120 V AC 230 V AC
Detector voltage between ionization probe and ground Approx. 270 V AC Approx. 270 V AC
(AC voltmeter Ri ″10 Mς)
Switching threshold (limit values):
Switching on (flame ON) (DC ammeter Ri ′5 kς) ″DC 1.5 µA ″DC 1.5 µA
Switching off (flame OFF) (DC ammeter Ri ′5 kς) ′DC 0.5 µA ′DC 0.5 µA
Detector current required for reliable operation ″DC 3 µA ″DC 3 µA
Switching threshold in the event of poor flame during operation Approx. DC 2 µA Approx. DC 2 µA
(LED flashes green)
Possible detector current with flame (typical) 20 µA DC 20 µA DC

Flame supervision with UV flame detector QRA2 / QRA2M / At mains voltage


QRA4 / QRA4M / QRA10 / QRA10M
Values apply to factory setting of parameters 182 = 0 120 V AC 230 V AC
Detector voltage at QRA2 / QRA2M / QRA4 / QRA4M / QRA10 /
QRA10M (with no load)
Terminal 6 OFF (test mode) Approx. 290 V AC Approx. 290 V AC
Terminal 6 ON (operating mode) Approx. 250 V AC Approx. 250 V AC
Switching threshold (limit values):
Switching on (flame ON) ″20 µA DC ″20 µA DC
Switching off (flame OFF) ′5 µA DC ′5 µA DC
Detector current required for reliable operation ″24 µA DC ″24 µA DC
Switching threshold in the event of poor flame during operation Approx. 24 µA DC Approx. 24 µA DC
(LED flashes green)
Possible detector current with flame (typical):
Test mode 700 µA 700 µA
Operating mode 550 µA 550 µA

Flame supervision with photocell detector RAR9 At mains voltage


Values apply to factory setting of parameters 182 = 0 120 V AC 230 V AC
Switching threshold (limit values):
- Switching on (flame ON) ″6.5 µA DC ″6.5 µA DC
- Switching off (flame OFF) ′3.5 µA DC ′3.5 µA DC
Detector current required for reliable operation ″10 µA DC ″10 µA DC
Switching threshold in the event of poor flame during operation Approx. 10 µA DC Approx. 10 µA DC
(LED flashes green)
Possible detector current with flame (typical) 65 µA DC 65 µA DC
Possible detector current in the event of glare, e.g., with artificial 70 µA DC 70 µA DC
light (leads to lockout with error message LOC10)

The detector current values specified in the table only apply to the factory settings and under the
following conditions:
- Mains voltage 120 V AC / 60 Hz or 230 V AC / 50 Hz, depending on type
- Ambient temperature 23 °C
- Parameter 182 in accordance with the factory setting from the following table

20/40

Building Technologies CC1N7782en


18.04.2018
Technical data (continued)
Range adjustment for flame sensitivity using Switching threshold for switching on flame ON signal /
parameter 182: Test level switching threshold for flame detector
ION QRA2 / QRA2M / RAR9
QRA4 / QRA4M /
QRA10 / QRA10M
Parameter 182 = 0 1 µA / 1 µA ¹) 12 µA / 12 µA ¹) 5 µA / 5 µA ¹)
Parameter 182 = 1 2 µA / 2 µA 12 µA / 12 µA 10 µA / 8 µA
Parameter 182 = 2 4 µA / 4 µA 12 µA / 12 µA 20 µA / 18 µA
Parameter 182 = 3 8 µA / 8 µA 12 µA / 12 µA 30 µA / 28 µA
¹) Values printed in bold are the same as the factory settings

21/40

Building Technologies CC1N7782en


18.04.2018
Technical data (continued)

7782d01en/0216
LFS1.2 terminal 7 10
voltage output for flame 9
supervision with 8
ionization probe 7

Volts DC
6
5 Parameter 699.00 = 5
4
Parameter 699.00 = 13 *)
3
2 Parameter 699.00 = 35
1
0
0 10 20 30
Detector current µA
*) Factory setting

LFS1.2 terminal 7 10

7782d02en/0416
voltage output for flame 9
supervision with QRA2 / 8
QRA2M / QRA4 / 7
Volts DC

QRA4M / QRA10 / 6
QRA10M 5 Parameter 699.01 = 5
4
Parameter 699.01 = 16 *)
3
2 Parameter 699.01 = 35
1
0
0 20 40 60 80 100
Detector current µA
*) Factory setting

LFS1.1 terminal 7 10
voltage output for flame 9
supervision with RAR9
8
7
6
5
Volts DC

4 Parameter 699.01 = 5
3
Parameter 699.01 = 16 *)
2
Parameter 699.01 = 35
1
0
0 20 40 60
Detector current µA

*) Factory setting

The information applies under the following conditions:


- Mains voltage 230 V AC / 50 Hz or 120 V AC / 60 Hz, depending on type
- Ambient temperature 23 °C

22/40

Building Technologies CC1N7782en


18.04.2018
Connection diagram and internal diagram
LFS1.1 with RAR9 HS
L
N
T/B
12 10 6 1 L

7782a07/0415
EK LFS1.1...
FR

fr1 fr2
HR LED

hr1

Si

11 9 7 BCI 2 N 3 4 5

RAR9...
0...10 V

Note!

Β The test mode switchover (T/B) is only required in conjunction with the control unit
LEC1. Otherwise terminal 6 of the LFS1 must be connected directly to the phase
conductor «L» at terminal 1 in this case.

Key

BCI Communication interface HS All-polar main switch


(Burner Communication Interface) ION Ionization probe
EK Lockout reset button (internal) LED Internal LED (three-colored)
FS Flame signal QRA UV flame detector
FSV Flame signal amplifier RAR9 Photocell detector
FR Internal flame relay Si Internal fuse
fr1 Flame relay NO contact T/B Flame signal amplifier test mode switchover
fr2 Flame relay NC contact (QRA, RAR9: Only required in case of replacement by
HR Internal auxiliary relay (test mode switchover) LEC1
hr1 Auxiliary relay NO contact 0...10 V Voltage output for outputting flame signal strength
+ Terminal labeling on QRA

23/40

Building Technologies CC1N7782en


18.04.2018
Connection diagram and internal diagram
LFS1.2 with QRA2 / HS
L
QRA4 / QRA4M /
QRA10 N
T/B
12 10 6 1 L
LFS1.2...

7782a08/1215
EK
FR

fr1 fr2
HR LED

hr1

Si

11 9 7 BCI 2 N 3 4 5

QRA...
0...10 V
ION

Key

BCI Communication interface HS All-polar main switch


(Burner Communication Interface) ION Ionization probe
EK Lockout reset button (internal) LED Internal LED (three-colored)
FS Flame signal QRA UV flame detector
FSV Flame signal amplifier RAR9 Photocell detector
FR Internal flame relay Si Internal fuse
fr1 Flame relay NO contact T/B Flame signal amplifier test mode switchover
fr2 Flame relay NC contact (QRA, RAR9: Only required in case of replacement by
HR Internal auxiliary relay (test mode switchover) LEC1
hr1 Auxiliary relay NO contact 0...10 V Voltage output for outputting flame signal strength
+ Terminal labeling on QRA

24/40

Building Technologies CC1N7782en


18.04.2018
Connection diagram and internal diagram

LFS1.2 with QRA2M / HS


L
QRA10M
N
T/B
PE 12 10 6 1
LFS1.2...

7782a14/0418
EK
FR

fr1 fr2
HR LED

hr1

Si

11 9 7 BCI 2 3 4 5

QRA10M
QRA2M
0...10 V
ION

31

GN/YE BU BN BK
AGK30

Key

BCI Communication interface HS All-polar main switch


(Burner Communication Interface) ION Ionization probe
EK Lockout reset button (internal) LED Internal LED (three-colored)
FR Internal flame relay QRA UV flame detector
fr1 Flame relay NO contact Si Internal fuse
fr2 Flame relay NC contact T/B Flame signal amplifier test mode switchover
HR Internal auxiliary relay (test mode switchover) (QRA, RAR9: only required when replacing with
hr1 Auxiliary relay NO contact LEC1)
0...10 V Voltage output for outputting flame signal strength
1…31 Number of terminals in plug-in base AGK11.7 + Terminal marking on QRA

Connecting wire colors of AGK30


BU Blue
BN Brown
GN/YE Green/yellow
BK Black

25/40

Building Technologies CC1N7782en


18.04.2018
LFS1 program sequence

Wait for standby Operation Test

Program time tw tan tab

Phase number AZL2 oP:P2 oP:P1 oP:P2

217.01
217.00
Parameter number AZL2

LED steady on

LED flashing

Terminal Function / inputs

No. 1

No. 6 * T/B hr1

No. 3 FS
No. 4 / 5

Terminal Function / outputs


T/B

No. 11 / 12 hr1 fr1

No. 9 / 10 fr2

No. 7 0...10 V

7782d08en/0718

Key

FS Flame signal tw Waiting time


fr1 Flame relay NO contact tan Flame signal flame-on response time
fr2 Flame relay NC contact tab Flame signal flame-out response time
hr1 Auxiliary relay NO contact 0...10 V Voltage output for outputting flame signal strength
LED Internal LED (three-colored) oP:P1 Flame signal OFF
T/B Flame signal amplifier test mode switchover oP:P2 Flame signal ON
(QRA2 / QRA2M / QRA4 / QRA4M / QRA10 / Input / output signal 1 (ON)
QRA10M)
* Extraneous light test for flame detectors QRA Input / output signal 0 (OFF)
(not required for RAR and ionization probe flame Input permissible signal 1 (ON) or 0 (OFF)
supervision)

26/40

Building Technologies CC1N7782en


18.04.2018
Function
Basic mode of operation of the flame safeguards in conjunction with control unit
LEC1.

When used with the LEC1, the flame safeguard feeds the flame signal into the burner
control’s control program in essentially the same way as if the flame safeguard were a
component of the burner control (as in the case of an oil or gas burner control). In the
event of non-ignition, loss of flame during burner operation, or a faulty flame signal
during burner off or purging times, the burner will always be shut down and the burner
control will initiate lockout. The switching functions needed to feed the flame signal into
the burner control’s control circuit are provided by the flame relay (FR) of the flame
safeguard and the 2 auxiliary relays (HR1 / HR2) of the control unit LEC1; refer to Data
Sheet N7761.

In conjunction with the flame safeguard LFS1, the control unit LEC1 provides the
sequence control for the flame simulation test and the flame detector test on the LFS1.

The test is controlled via the connecting line between terminal 15 of the control unit
LEC1 and terminal 6 of the flame safeguard LFS1.

Both tests
∂ start about 7 seconds after a controlled shutdown
∂ are continued during burner off periods
∂ are continued during the ensuing prepurge time
∂ end 3 seconds before the start of the safety time

The following flame signals during this test time lead to lockout with interlocking of the
control unit LEC1:
- Extraneous light
- Aging flame detectors
- Other defects in the flame supervision equipment

In the flame safeguard, the switching functions required for testing are performed by the
auxiliary relay (HR).
Since it is not necessary to carry out a test in the case of flame supervision with an
ionization probe, the connecting line between terminal 15 of the burner control and
terminal 6 of the flame safeguard is not required here.
Instead, terminal 6 must be connected to the phase.

Example:
By making a connection to terminal 1 of the LEC1

Any flame signal – be it a normal flame signal during operation or a faulty signal – is
indicated by the signal lamp (3-colored LED) in the housing of the flame safeguard;
refer to Indication and diagnostics chapter.

27/40

Building Technologies CC1N7782en


18.04.2018
Mode of operation of the flame safeguards with dual supervision (detailed connection diagram, e.g., for oil
burners)
With this type of supervision, 1 flame is supervised by 2
independently operating flame safeguards. The aim is to
reduce the possibility of loss of flame during operation, in
the case of a simultaneous failure of both flame
safeguards, to an unlikely coincidence. With dual
supervision, the control contacts of the flame relays of
both flame safeguards are connected in series so that
loss of the flame signal of either of the flame
safeguards is sufficient to cause lockout of the burner.
A faulty flame signal by only 1 of the 2 flame safeguards
during burner off times or purging times also leads to
lockout.

Key FR Internal flame relay


fr1 Flame relay NO contact
fr2 Flame relay NC contact
HR Internal auxiliary relay (test mode switchover)
hr1 Auxiliary relay NO contact
BV1 1st fuel valve
BV2 2nd fuel valve
RAR9... Photocell detector
Si Internal fuse
Z Ignition transformer

28/40

Building Technologies CC1N7782en


18.04.2018
Mode of operation of the flame safeguards when used for the supervision of 2 manually controlled burners
With this type of supervision, too, the burner can be
started only if the flame detector test or flame simulation
test has been successful. This means that neither of the
2 flame safeguards may detect a flame signal during
0 burner off times. When the burner is started up, the
detector test will automatically be interrupted. When
button (I) is pressed, relay (d) is energized via circuit path
10 12 1
Burner A 9...10 of the flame relays, which is still closed, thus
3
FR 4
switching on the ignition of both burners.
fr1
5 At the same time, fuel is released.
hr1 HR The duration of the start pulse given by pressing button
6 9 11 2 (I) should be limited by a time relay – in the sense of a
10 12 1
safety time.
If a flame is established on both burners – indicated by
FR 4
fr1
5 the signal lamps in the housing of the flame safeguards –
hr1 HR relay (d) is now maintained in its energized condition via
6 9 11 2 circuit path 11...12 of the 2 flame relays.
d When the button (I) is released, the ignition will be
switched off, thus completing the startup sequence.
If the event of loss of flame on 1 of the burners, the
L2
respective flame relay is deenergized, thereby
neutralizing the holding circuit for relay (d). This means
7782a10en/0416
that the fuel valves of both burners will immediately be
shut.
The burners are switched off manually be pressing the
button (0), or automatically by the control thermostat or
pressurestat / pressure switch in the phase wire
connection.
In the case of flame supervision with ionization probes,
terminal 6 of the flame safeguards must be connected
directly to the phase since no detector test is required
here.

Example:
With a connection to terminal 1.

Note!
Β Ensure that the drop-out delay time of relay d does not exceed 50 ms; refer to
connection example 7782a06.

Key BV... Fuel valve


FR Internal flame relay
fr1 Flame relay NO contact
fr2 Flame relay NC contact
HR Internal auxiliary relay (test mode switchover)
hr1 Auxiliary relay NO contact
L2 Lockout warning lamp, external
LP Air pressure switch
R... Control thermostat or pressurestat
Si Internal fuse
W Limit thermostat or pressure switch
Z Ignition transformer

29/40

Building Technologies CC1N7782en


18.04.2018
Mode of operation of the flame safeguards in the case of multiflame supervision with LEC1 (detailed
connection diagram, e.g., for gas burners)

As with dual supervision, the control contacts of


the flame relays of all flame safeguards must
be connected in series in the case of multiflame
supervision.
FR
A burner causes all other burners to go to
lockout if:
LFS1.2 - The flame is not established during the
safety time, or
- The flame is lost during operation.

FR After the burner control has been reset,


correctly operating burners can only be
restarted once the faulty burner has been shut
LFS1.2
down.
In that case, the operating switch must not only
bridge the control contacts of the relevant flame
safeguard, thus closing the control chain again,
FR but must also break the phase wire connection
to the ignition transformer and the fuel valves.
Likewise, after rectification of the error, the
LFS1.2
burner can only be restarted together with the
other burners; that is, only after all burners
7782a11/1115 have previously been shut down.

Attention!
An ignited UV tube is a source of UV radiation. In the case of flame supervision by
means of flame detectors, the detectors must be placed in a way that ensures there is
no direct visual contact between them. If this is not observed, there is a risk of loss
of safety functions.

Attention!
When replacing the LFE10 with the LFS1.2, the earth connection at terminal 10
in the LFE10 terminal base must be removed; terminal 5 of the LFS1.2 must not
have an earth connection. Earth connection of QRA10 remains unchanged to
ensure the protection class 1.

Key BS Operating switch OFF / ON ↑ for each burner


FR Internal flame relay
BV1 / BV2 Fuel valves for 1st and 2nd stage
fr1 Flame relay NO contact
fr2 Flame relay NC contact
HR Internal auxiliary relay (test mode switchover)
hr1 Auxiliary relay NO contact
ION Ionization probe
QRA UV flame detector
Si Internal fuse
Z Ignition transformer

30/40

Building Technologies CC1N7782en


18.04.2018
Mode of operation of the flame safeguards in the case of multiflame supervision with a PLC, intermittent
operating mode
In the case of multiflame supervision, a fail-safe
PLC performs the central control function (the
example shown uses a Simatic ET200SP F-CPU
and input / output modules ET200SP F-I/O).
Each burner has its own ignition equipment, its
own fuel valve, and its own flame supervision
system (made up of a flame safeguard LFS1.2
and a flame detector).
The control contacts for all the flame safeguards'
flame relays are connected in parallel. In other
words, each burner can be switched on and off
independently of the other burner.
The flame signal is evaluated in the PLC on a
non-equivalent basis in line with the evaluation
principle 1oo2 (1-OFF-2). This means that the 2-
way start pulse is tested at terminals Dix and
Diy.
QRA In the event of a flame ON signal, the fr1 (NO)
contact closes and the fr2 (NC) contact opens at
the same time.
In the event of a flame OFF signal, the fr2 (NC)
contact closes and the fr1 (NO) contact opens at
the same time.

Wait for standby


Test for prematurely aged UV cell The test mode switchover for the burner 1 flame
safeguard is inactive (terminal 6 is permanently
Program time tw tan
connected to phase conductor L).
Phase number AZL2 oP:P2
The test mode switchover for the burner 2 flame
safeguard is active. This means that terminal 6
217.00

Parameter number AZL2


is switched off by the PLC via a fail-safe relay
LED steady on output (Ro3) at set intervals or after 24 hours of
LED flashes uninterrupted burner operation at the very latest;
Terminal Function / inputs refer to the adjacent control sequence.
The PLC must prevent further burner operation
until the cause of the error has been rectified.
Ro3 T/B hr1

No. 4 / 5 FS
(LFS1)

Ro2 V2 Safety shutdown V2 = OFF

Terminal Function / outputs


If the fr2 signal disappears due to extraneous
light (e.g., from an aged UV cell), burner startup
T /B

must be prevented.

Dix hr1 fr1


Burner 2)
Diy fr2
Burner 2)

7782d05en/1215

31/40

Building Technologies CC1N7782en


18.04.2018
Mode of operation of the flame safeguards in the case of multiflame supervision with pilot burner and a PLC,
intermittent operating mode
In the case multiflame supervision with a pilot
burner, a fail-safe PLC performs the central
control function (the example shown uses a
Simatic ET200SP F-CPU and input / output
modules ET200SP F-I/O).
The pilot burner has its own ignition equipment
(Z1), its own fuel valve (V1), and its own flame
supervision system made up of a flame
safeguard LFS1.2 and an ionization probe
(ION).
The main burner has its own fuel valve (V2)
and its own flame supervision system made up
of a flame safeguard LFS1 and a UV flame
detector QRA.
The main burner does not have its own ignition
equipment (Z1) as its flame is safely ignited by
the pilot burner. The flame relay control
contacts for both flame safeguards LFS1.2 are
connected in series.
This means that both burners can only be
switched on and off together with the other
burner in each case. The flame ON signal at
terminals Dix / Diy on the digital input module
F-DI can therefore only occur when both flame
signals are present.
Extinguishing 1 of the 2 flames, or even both
flames, leads to a flame OFF signal. The flame
signal is evaluated in the PLC on a non-
equivalent basis in line with the evaluation
principle 1oo2 (1-OFF-2).
Wait for standby Test for prematurely aged UV cell This means that the 2-way start pulse is tested
at terminals Dix and Diy. In the event of a
Program time tw tan flame ON signal, the fr1 (NO) contact closes
Phase number AZL2 oP:P2 and the fr2 (NC) contact opens at the same
time.
217.00

Parameter number AZL2


In the event of a flame OFF signal, the fr2 (NC)
contact closes and the fr1 (NO) contact opens
LED steady on
at the same time.
LED flashes

Terminal Function / inputs The test mode switchover for the pilot burner
flame safeguard is inactive (terminal 6 is
permanently connected to phase conductor L).
Ro3 T/B hr1
The test mode switchover for the main burner
No. 4 / 5
(LFS1...)
FS flame safeguard is active.
Ro2 V2 Safety shutdown V2 = OFF This means terminal 6 is switched off by the
PLC via a fail-safe relay output (Ro3) at set
intervals or after 24 hours of uninterrupted
Terminal Function / outputs If the fr2 signal disappears due to extraneous
burner operation at the very latest; refer to the
light (e.g., from an aged UV cell), burner startup adjacent control sequence.
T/B

must be prevented.
The PLC must prevent further burner operation
until the cause of the error has been rectified.
Dix hr1 fr1
Burner 2)
Diy fr2
Burner 2)

7782d06en/1215

32/40

Building Technologies CC1N7782en


18.04.2018
Mode of operation of the flame safeguards in the case of multiflame supervision with pilot burner and a PLC,
intermittent operating mode (continued)

Attention!
A fail-safe PLC must be used!

Key F-CPU Fail-safe CPU (central processing unit) of PLC


F-DI PLC fail-safe digital input modules
F-RO PLC fail-safe digital relay output modules
ION Ionization probe
L/N Phase conductor / neutral conductor
FR / HR Flame relay / auxiliary relay
V1 / V2 Fuel valve for burner 1 / burner 2
QRA UV flame detector
PLC Programmable logic controller
Z1 Ignition transformer for pilot burner

33/40

Building Technologies CC1N7782en


18.04.2018
Operation, indication, diagnostics
Operation The lockout reset button (EK) is the key operating element for resetting

7101z01/0804
EK
the burner control and for activating / deactivating the diagnostics
functions.

7101z02e/0305
The multicolor signal lamp (LED) in the lockout reset button is the key
indicating element for both visual diagnostics and interface diagnostics.

Both elements (EK / LED) are located under the transparent cover of the lockout reset
button.

There are 2 diagnostics options:


1. Visual diagnostics: Operational status indication or diagnostics of the cause of
error.
2. Interface diagnostics: With the help of interface adapter OCI400 and PC software
ACS410 (in preparation).

A description of the visual diagnostics is provided below.

Operational status In normal operation, the different operating states are indicated in the form of color
indication codes according to the color code table below:

Color code table for the multicolor signal lamp (LED)


Status Color code Color
Waiting time (tw) or no operating ........................................ OFF
voltage
Waiting for flame signal ........................................ Yellow
Test mode active, no extraneous light Flashing yellow
signal available
Test mode active, extraneous light Yellow-green
signal available
Operation, flame OK ......................................... Green
Operation, flame not OK Flashing green
Undervoltage Yellow-red
Error, alarm ......................................... Red
Error code output; refer to Error code Flashing red
table
Interface diagnostics Red flickering light
Warning message: 1 million switching x x x x x x Also flashes
cycles exceeded (switching cycle yellow in addition
counter) to the current
color “x”

Key ...... Permanent Red


OFF Yellow
Green

Service counter Press the lockout reset button (EK) for 10 seconds to activate a yellow flashing warning
signal when 1 million switching cycles have been performed. In this case, it is advisable
to carry out a safety test or to replace the unit.
If 1 million switching cycles have not yet been performed, there will be no yellow
flashing warning signal. Press the lockout reset button (EK) for 10 seconds again to
deactivate this function.

34/40

Building Technologies CC1N7782en


18.04.2018
Operation, indication, diagnostics (continued)
Diagnostics of cause of After lockout, the red signal lamp (LED) lights up. In this status, visual diagnostics of
error the cause of the error according to the error code table can be activated by pressing
the lockout reset button for more than 3 seconds. By pressing the lockout reset button
again for more than 3 seconds, the interface diagnostics will be activated. The interface
diagnostics only work if the AGK20 lockout reset button extension is not fitted.
If the interface diagnostics have been activated by accident – in which case the slightly
red light of the signal lamp (LED) flickers – it can be deactivated by pressing the lockout
reset button again for more than 3 seconds. The moment of switching over is indicated
by a yellow light pulse.

The following sequence activates diagnostics of the cause of the error:

OCI400
Lockout position Lockout position Lockout position
Visual diagnostics Interface diagnostics
Flashing PC / analyzer
On
Reset

7130z04e/0602
Error code table
>3s >3s <3s

Signal lamp (LED) Possible cause


flashing code
1...9 flashes Free
10 flashes Wiring error or internal error, output contact error, other errors.
Flame detector RAR9 current outside permissible range
(defective flame detector RAR9 or glare).
Short circuit at the connection terminals of the UV flame
detectors QRA at the operating level (terminal 6 of the LFS1
active)
15 flashes Manual locking active (LOC167)

When diagnosing the cause of errors, the built-in relays FR and HR are in the no-load
position.

Reset to quit the diagnostics of the cause of the error and switch the flame safeguard
on again. Press the lockout reset button for about 1 second (less than 3 seconds).

35/40

Building Technologies CC1N7782en


18.04.2018
Communication, BCI interface
BCI interface
The BCI interface connection jacks are located on the underside in the LFS1 base
area; refer to the figure. Parameters can be set in accordance with the parameter list
below using the display and operating unit AZL2 and signal cable AGV50.
The signal cable AGV50 is preassembled and fitted with a RJ11 connector.
When connecting, ensure that the orientation is correct – the clip on the RJ11
connector must inserted into the notch on the connection jack. A click sound indicates
that the clip has locked into place. To disconnect the connection, open the clip by
gently tilting it towards the cable using your finger before pulling out the RJ11
connector.

BCI interface
connection jack

7782z05en/1215

The display and operating unit AZL2 with LCD display enables simple operation,
parameterization, and targeted diagnostics via menu-driven operation. When
performing diagnostics, the display shows the operating statuses, the type of error, and
the startup counter (IBZ). Passwords protect the different parameter levels for OEM
(burner / boiler manufacturer) and heating engineers (HF) against unauthorized access.
Simple settings that the plant operator can make on site do not require a password.

For detailed information on parameterization; refer to User Documentation A7782,


Operation via AZL2 chapter.

For the parameters, their default settings, and their range adjustments at the different
access levels, refer to the following parameter list.

36/40

Building Technologies CC1N7782en


18.04.2018
Dimensions
Dimensions in mm

LFS1 Ø22

5
59.1
53.9
63
9
Plug-in base AGK11.7 and 88 41.6
AGK65.1 91

47.2
62.5
Plug-in base AGK11.7 with separating plate element (shown in green)

28,5

62,5
4
17

,4
23,5

Ø5 6,2
Ø1

7782m02/0415

10,5
24 24
30 30
88

37/40

Building Technologies CC1N7782en


18.04.2018
Dimensions (continued)
Dimensions in mm

62,7
Adapter KF8896

7782m01/0416

PE
LAE 1 2 3 4 5 6 7
LFE

KF8896
LFS1 1 2 3 4 5 6 7 8 9

48,5
88

When replacing LAE10 and LFE10 with LFS1, adapter KF8896 ensures that the height
can be adjusted mechanically and that the terminals are assigned correctly.

LFS1 with adapter

5
KF8896 and plug-in
base for LAE10 / low
plug-in base for LFE10
AGK410413450
63

89
26
13

47,2
62,5

38/40

Building Technologies CC1N7782en


18.04.2018
Dimensions (continued)
Dimensions in mm

LFS1 with adapter

5
KF8896 and plug-in
base for LAE10 / high
plug-in base for LFE10
AGK410490250

63

109
46
13

47,2
62,5

39/40

Building Technologies CC1N7782en


18.04.2018
Dimensions (continued)
Dimensions in mm

LFS1 with lockout reset


button extension
AGK20

7101m03/1108
Designation Length (L) in mm
AGK20.19 19
AGK20.43 43
AGK20.55 55

 2018 Siemens AG Building Technologies, Berliner Ring 23, D-76437 Rastatt,


Subject to change!
40/40

Building Technologies CC1N7782en


18.04.2018

You might also like