Product Overview
IC2 IKH01 Rev F
Ingeteam Proprietary – All Rights Reserved Pag. 2
Table of Contents
Table of Contents
1 Introduction 5
2 Hardware Description 7
2.1 Power Supply ................................................................................................................. 9
2.1.1 24Vdc .................................................................................................................................................... 9
2.1.2 72-110Vdc ............................................................................................................................................. 9
2.2 Processor Module ........................................................................................................ 10
2.3 Header Module ............................................................................................................. 13
2.3.1 Header module CAN ........................................................................................................................... 13
2.3.2 Header module RTSX ......................................................................................................................... 14
2.4 Communications Modules .......................................................................................... 14
2.4.1 Fieldbuses interfaces ......................................................................................................................... 15
2.4.1.1 CAN interface module ........................................................................................................... 15
2.4.1.1.1 Cable interface ......................................................................................................... 15
2.4.1.1.2 Fiber optic interface ................................................................................................ 16
2.4.1.2 MVB interface module ........................................................................................................... 17
2.4.1.2.1 MVB ESD+ interface module ................................................................................... 17
2.4.1.2.2 MVB EMD interface module .................................................................................... 18
2.4.1.2.3 MVB EMD-R module ................................................................................................ 19
2.4.1.2.4 MVB EMD SNFR module ......................................................................................... 20
2.4.1.3 PROFIBUS DP interface module ........................................................................................... 21
2.4.1.4 PROFINET I/O interface module ........................................................................................... 22
2.4.2 SERIAL communications module .................................................................................................... 23
2.4.3 ETHERNET communications module ............................................................................................... 24
2.4.4 SERIAL RS485-T communications module ..................................................................................... 25
2.4.5 WIRELESS interfaces ......................................................................................................................... 26
2.4.5.1 GSM interface module ........................................................................................................... 26
2.4.5.2 WiFi interface module ........................................................................................................... 26
2.5 User Interface Modules ............................................................................................... 27
2.5.1 Rotary Swich ....................................................................................................................................... 27
2.5.2 LCD ...................................................................................................................................................... 27
2.6 Input /Output´s Modules .............................................................................................. 28
2.6.1 Digital Modules ................................................................................................................................... 29
2.6.1.1 16 Digital Input module ......................................................................................................... 29
2.6.1.2 4 Digital Input 2 Fast Digital Input module .......................................................................... 30
2.6.1.3 16 NPN Digital Input module ................................................................................................. 32
2.6.1.4 16 Digital Output module ...................................................................................................... 33
3 Software Description 59
4 Mechanical Solution 61
4.1 System Configuration .................................................................................................. 62
4.2 Mechanical Data ........................................................................................................... 63
5 Certifications 65
5.1 Electromagnetic Compatibility ................................................................................... 66
5.2 Climatic Conditions ..................................................................................................... 66
5.3 Vibration and Shock Tests .......................................................................................... 67
5.4 Fire Protection ( EN45545-2 ) ...................................................................................... 68
5.5 Storage and Transport Conditions ............................................................................. 68
1 Introduction
INGESYS™ IC2 is a standalone Controller with an internal modular and expandable design,
oriented to fulfill the requirements of control applications demanding a reduced number of
digital/analog I/Os, IEC61131 standard based programmable languages, wide range of
communication interfaces and remote monitoring features based on an embedded Web server.
INGESYS™ IC2 offers two variants each one with specific characteristics for the target application
sector:
Easy integration in control networks is possible thanks to its wide range of communication
interfaces, for integration in LAN networks via ETHERNET with protocols as MODBUS TCP/IP,
ETHERNET IP/CIP, TRDP and in fieldbuses like CAN, MVB, PROFIBUS DP, RS485, PROFINET
I/O-Device RT.
2 Hardware Description
INGESYS™ IC2 has a modular and expandable design that permits to achieve an optimal
hardware solution for each application.
- Centralized topology
In this topology the Controller is integrated by a single central system that incoporates a processor
module and up to 10 I/O modules in a compact mechanical enclosure
- Distributed topology
In this topology the Controller is integrated by the central system expanded with up to 16 Remote
I/Os units connected by a CAN fieldbus.
Remote I/O units are integrated by a header module and up to 8 I/O modules in a compact
mechanical enclosure.
Based on application requirements, the user determines the specific components that will
constitute the automation system, considering the most general architecture, central units
(Processor+Power supply+ Communications+I/Os) and Remote I/O units (Headers+Power
Supply+I/Os). After having defined exactly the components for the Central and Remote I/O units a
compact mechanical enclosure with a unique reference is assigned to each of these units.
2.1.1 24Vdc
Power Supply
Electrical
24Vdc (-30%/+25%)
Power Supply Voltage 24Vdc (-30%/+25%)
Class S1 (EN50155:2007)
2.1.2 72-110Vdc
Power Supply
Electrical
72-110Vdc (-30%/+25%)
Power Supply Voltage 72-110Vdc (-30%/+25%)
Class S1 (EN50155:2007)
Note:
(A1-B1), (A2- B2), (A3- B3) internally tied.
Common and specific characteristics of these processor modules are described in following table:
Memory %Q 200Kbyte
Memory %I 12Kbyte
Memory %M 1Kbyte
Programming Tools
IEC61131 Yes
C , C++ Yes
MATLAB®/Simulink® No Yes
Datalogger
Consecutive recordings 8 32
Simultaneous recordings 1 2
WEB Interface
Historical Data
Communication ports
Communication Interfaces
ETHERNET Protocols
TRDP Yes
Storage Memory
Internal 32Mbyte
Programming Tools
IEC61131 Yes
C , C++ Yes
MATLAB®/Simulink® No Yes
Communication Ports
Communication Interfaces
ETHERNET Protocols
Status LED:
Controller ON Green
ON
Controller without FW Green Blinking ( T=3" )
Controller OK Green
OK
No User Application OFF
Parameter configuration and EDS file generation is made by the internal Web server included in
the header module.
Fieldbus CAN
CAN ports 1
Tbl 7. CAN Header module characteristics.
------------------------------------------------------------
1 System configuration via WEB Server
Parameter configuration is made in the main program, similar to parameter configuration of local
I/Os, adding a configuration file provided for each header module reference.
Fieldbus RTSX
PROFIBUS DP module
In the case of C type processors up to two fieldbus interfaces can be integrated, for HC/HCS type
processors up to four fieldbus interfaces can be integrated.
Communications
Communication Protocol CANopen (Master/Slave)
Number of channels 1
CAN
1 R_Term*
2 CANL
3 GND
6 R_Term*
7 CANH
9
Tbl 13. CAN cable interface connector pinout.
Note:
(*) short circuit for connecting bus end resistor
Communications
Communication Protocol CANopen (Master/Slave)
Number of channels 1
CAN FO
Left Tx
Right Rx
Tbl 15. CAN fiber optic interface connector pinout.
Main characteristics:
Communications
Communication Protocol MVB
Number of channels 2
Main characteristics:
Communications
Communication Protocol MVB
Number of channels 2
Main characteristics:
Communications
Communication Protocol MVB
Number of channels 2
Main characteristics:
Communications
Communication Protocol MVB
Number of channels 2
Functionality Sniffer
Tbl 19. MVB EMD SNFR interface module characteristics.
Main characteristics:
Communications
Communication Protocol PROFIBUS DP Slave
Number of channels 1
Communications
Communication Protocol PROFINET I/O-Device RT (class B)
Status LEDs.
Main characteristics:
Communications
Protocols MODBUS RTU, Transparent protocol
Number of ports 1
Signals/Diagnosis Yes
Tbl 23. RS232/RS485 characteristics.
Note:
To enable terminating resistor integrated in the card 1 or 2 bridges are needed depending on
whether it is 2 wire (Half Duplex) or 4 wire (Full Duplex) connection.
HALF
1–4
6–7
FULL
7-9
(*) indicates pins for bus end resistor
Available ETHERNET protocols are the following: MODBUS TCP/IP, ETHERNET IP/CIP, TRDP.
Status LEDs.
Main characteristics:
Communications
Protocols MODBUS RTU, Transparent protocol
Signals/Diagnosis Yes
Tbl 26. RS485 characteristics.
Note:
When this equipment is the first or the last one in the bus, there is a series terminating resistor
integrated in the card that can be connected. 1 or 2 bridges are needed on the spare connector
depending on whether it is 2 wire (Half Duplex) or 4 wire (Full Duplex) connection.
HALF (These bridges should be done in free connector)
1–4
6–7
FULL (This bridge should be done in free connector)
7-9
Main characteristics:
Communications
Functional
UMTS/HSPA+ (3G)
Standards
GSM/EDGE (2G)
UMTS: -110dBm
Sensitivity
GSM850/EGSM900: -108.5dBm
DCS1800/PCS1900: -108dBm
Main characteristics:
Communications
Functional
Client mode
Working mode
AP mode
Communications
Number of Rotary switch 2
Connector is as follows:
2.5.2 LCD
Main characteristics:
Characters 16
Backlight Yes
LCD is as follows:
Mixed Digital Inputs / Outputs 12 x 24Vdc digital inputs + 4 0.5A x 24Vdc digital outputs module
Main characteristics:
Digital Inputs
Functional
Number of inputs 16
Electrical
Main characteristics:
Digital Inputs
Functional
Electrical
Electrical
Counting Features
Functional
A, B Incremental Encoder
Configuration One signal pulse counting
Pulses per time counting
Note:
All signals can be used as simple digital inputs or configured as inputs to the counter.
Main characteristics:
Digital Inputs
Functional
Number of inputs 16
Electrical
Main characteristics:
Digital Outputs
Functional
Number of outputs 16
Electrical
Max. short circuit current per output 1.7A, limited by SSR protection
Tbl 37. Digital Outputs. Technical Data.
Main characteristics:
Digital Outputs
Functional
Number of outputs 8
Connection mode High side drive with particular power to each signal and negative common to all
Electrical
The DOxx ON signaling light up (red) to indicate that the corresponding output has the activation
command registered.
The DOxx OK signaling light up (green) to indicate that there is power in the corresponding output
and the module status is OK. Diagnosis indications are activated once the processor unit is
accessing this module (CPU is ON RUN status and I/O transactions are active)
Main characteristics:
Digital Outputs
Functional
Number of outputs 16
Electrical
Max. short circuit current per output 900mA, limited by SSR protection
Tbl 39. Digital Outputs. Technical Data.
Main characteristics:
Digital Inputs
Functional
Number of inputs 8
Electrical
Digital Outputs
Functional
Number of outputs 8
Electrical
Max. short circuit current per output 1.7A, limited by SSR protection
Tbl 41. Digital Outputs. Technical Data.
Main characteristics:
Digital Inputs
Functional
Number of inputs 12
Electrical
Digital Outputs
Functional
Number of outputs 4
Electrical
Max. short circuit current per output 1.7A, limited by SSR protection
Tbl 43. Digital Outputs. Technical Data.
Main characteristics:
Digital Inputs
Functional
Number of inputs 4
Electrical
Digital Outputs
Functional
Number of outputs 12
Electrical
Max. short circuit current per output 1.7A, limited by SSR protection
Tbl 45. Digital Outputs. Technical Data.
Main characteristics:
Number of outputs 3
Electrical
Main characteristics:
Analog Inputs
Functional
Number of inputs 8
Electrical
Note:
There are no signaling elements.
Main characteristics:
IEPE Inputs
Functional
Number of inputs 4
Electrical
Isolation
Max Input voltage +/- 15V from any AIn(+/-) input to M point
Input Impedance
Analog Inputs
Functional
Number of inputs 4
Electrical
Note:
There are no signaling elements.
Main characteristics:
IEPE Inputs
Functional
Number of inputs 6
Electrical
Isolation
Max Input voltage +/- 15V from any AIn(+/-) input to M point
Input Impedance
Analog Inputs
Functional
Number of inputs 2
Electrical
Note:
There are no signaling elements.
Analog Inputs
Functional
Number of inputs 1
Electrical
IEPE Inputs
Functional
Number of inputs 4
Diagnostic
Electrical
Isolation
Encoder Input
Functional
Electrical
Main characteristics:
Temperature Inputs
Functional
Measurement ranges
Electrical
Internally the module is divided in 5 signal blocks (each block has 4 terminals). Each block contains
two possible input channels (TX-TY):
In following figures, the connection diagram for the different types of sensors is represented:
b) NTC + PT100 (2-wires) / PT100 (2-wires) + NTC. Both sensors share a common electrical point
formed by B(n)b y B(n)d.
Fig 41. NTC + PT100 (2-wires) // PT100 (2-wires) + NTC connection diagram.
Note:
In all cases both sensors share a common electrical point formed by B(n)b y B(n)d.
There are no signaling elements.
Main characteristics:
Analog Outputs
Functional
Number of outputs 4
Electrical
Note:
There are no signaling elements.
Main characteristics:
Digital Inputs
Functional
Voltage 24VDC
Electrical
Encoder Input
Functional
Incremental Encoder
Encoders supported
A, B signals
Electrical
Voltage 24VDC
Motor Output
Functional
Electrical
Signals:
DI00-DI03: Digital Inputs
A+/A-, B+/B-: Encoder Inputs
MOTORa, MOTORb: Output to Motor
PWRMOT+, PWRMOT- Power Supply
Main characteristics:
Digital Inputs
Functional
Electrical
Encoder Input
Functional
Incremental Encoder
Encoders supported
A, B signals
Electrical
Voltage 24VDC
Motor Output
Functional
Electrical
Signals:
DI00-DI03: Digital Inputs
A+/A-, B+/B-: Encoder Inputs
MOTORa, MOTORb: Output to Motor
PWRMOT+, PWRMOT- Power Supply
Main characteristics:
Audio Outputs
Functional
Electrical
Note:
There are no signaling elements.
3 Software Description
The INGESYS™ IC2 Controller offers powerful software tools for system programming, monitoring
and diagnosis based on standards.
q Application development environment based on CoDeSys, software tool based on the standard
IEC61131 with 5 programming languages (IL - Instruction List, ST - Structured Text, FBD -
Function Block Diagram, LD - Ladder Diagram, SFC - Sequential Function Chart).
Refer to:
· "INGESYS™ IC Development Environment User Manual".
· "INGESYS™ IC IEC61131 programing manual".
q Control function library with the most standard functions for automation tasks.
Refer to:
· "Library manager on CoDeSys".
q Communication function library, specifically designed to facilitate the user the management of
communication protocols.
Refer to:
· "INGESYS™ IC MODBUSTCP".
· "INGESYS™ IC CANopen solution".
· "Library manager on CoDeSys".
q Remote I/O monitoring and system management based on an embedded web server, with a
panel designer tool to enable the user the design of customized data panels.
Refer to:
· "INGESYS™ IC WEB Application Manual"
· "INGESYS™ IC Panel Designer Tool Manual".
q Besides the languages defined by the IEC61131 standard, IC2-HCS-xxx system gives
additionally the possibility to use MATLAB®/Simulink® (Simulink® Coder) to develop advanced
regulation algorithms.
Refer to:
· “INGESYS™ IC MATLAB®/Simulink® User Manual”
4 Mechanical Solution
4.1 System Configuration
INGESYS™ IC2 presents an internal modular and expandable design that enables its
customization to application´s I/Os and communication requirements.
INGESYS™ IC2 is formed by the integration of user defined processor, communication and I/O
modules, that are asembled in a compact mechanical solution. Up to 4 fieldbuses and 10 I/O
modules can be selected and integrated in a compact mechanical enclosure.
Once the modules are selected, a customized mechanical enclosure to contain the whole set is
designed and a unique reference code is assigned to the set. This reference is used to define
precisely the new customized system for further manufacturing and commercial purposes.
In the following figure, an example of a customized final system is shown:
The processor or header modules are always requested and both have a width of 149mm. Each
additional I/O module increase the width in 37,5mm. (Max.: 10 x I/O modules for Controller, 8 x I/O
modules for Remote I/O)
Mounting Panel
5 Certifications
The INGESYS™ IC2 presents two variants differentiated in the fulfillment of specific sector
standards.
The INGESYS™ IC2 variant for Rolling stock control, designed by the code R in the product
reference (IC2-X-R-XXX-X-XXXXXXXXXX), is compliant with railway standard EN50155.
The INGESYS™ IC2 variant for Industrial sector, designed by the code I in the product reference
(IC2-X-I-XXX-X-XXXXXXXXXX), is compliant with European directives CE and with the railway
standard EN50155, except in the compliance of power supply voltage range defined by this
standard.
EN 61000-4-2
Electric Shock Immunity Tests Shock on contact: ±6kV Shock in the air: ±8Kv
EN 50121-3-2:2007
Climatic Conditions
Temperature Range -40ºC to +70ºC (EN50155:2007 TX)
Relative Humidity Range 30% to 95% (EN50155:2007 Damp Heat Cyclic Test)
Tbl 69. Climatic Environment Conditions.
Vibrations Test
Frequency 15Hz
Constant frequency Severity 28,9m/s2
Duration 4,5hours on each axis (x,y,z)
Shocks Test
Shock type 1/2 sinusoidal wave cycle
Acceleration peak/pulse
15g / 11ms
duration
Number of pulses 3 successive pulses in each direction (+ & -) and per axis (x,y,z) = 3x2x3 = 18pulses
Tbl 71. Shocks Test.
INGESYS™ IC2 system has also been designed to conform to the following vibration tests as
stated in EN50155 (IEC 61373:2010):
Vibrations Test
Frequency 5 to 150Hz
Duration 10min on each axis (x,y,z)
Random vibration tests
Severity:
ASD Level ((m/s2)2/Hz) Vertical :0,0301;Transversal 0,0144;Longitudinal 0,0144
RMS Value (m/s2) Vertical: 1,01; Transversal: 1,01; Longitudinal: 1,01
Frequency 5 to 150Hz
Duration 5h on each axis (x,y,z)
Simulated long-life testing Severity:
ASD Level ((m/s2)2/Hz) Vertical: 0,964;Transversal: 0,461;Longitudinal: 0,461
RMS Value (m/s2) ) Vertical: 5,72;Transversal: 5,72; Longitudinal: 5,72
Special Treatments:
COATING
.- Industrial version ( add " -2C " to the commercial reference )
.- Railway version ( is coated by default )