Eds309x en
Eds309x en
Eds309x en
EDS309x_D00012_02_D_XXEN/11.2018
EDS309… Portable insulation fault location system for unearthed and earthed systems (IT and
TN systems) to be used in conjunction with or without an insulation fault location
system
Product description
The EDS309… is a portable insulation fault location system for localising insulation faults in
unearthed systems (IT systems). All essential components are housed in a robust aluminium
case which is convenient to carry.
Application
IT systems without a permanently installed insulation fault location system
• EDS3090PG
for main circuits up to AC 20…575 V 42…460 Hz, DC 20…504 V with AGE185 up to
AC 500…790 V 42…460 Hz, DC 400…960 V
• EDS3091PG
EDS309… for control circuits up to AC 20…265 V 42…460 Hz, DC 20…308 V
• EDS3092PG
Device features for main circuits in conjunction with PGH185 up to AC 20…575 V 42…460 Hz, DC 20…504 V
with AGE185 up to AC 500…790 V 42…460 Hz, DC 400…960 V
• Portable insulation fault location systems
for control circuits in conjunction with PGH183 up to AC 20…265 V 42…460 Hz, DC 20…308 V
for IT systems AC 0…790 V, 42…460 Hz/
DC 0…960 V or de-energised systems • EDS3096PG
for main circuits in IT systems with all poles disconnected up to AC 0…575 V 42…460 Hz,
• Residual current measurement in TN/TT
DC 0…504 V
systems
• Use in main and control circuits, • EDS3096PV
photovoltaic systems for photovoltaic systems with PGH186 up to 20…575 V 42…460 Hz, DC 20…504 V
with AGE185 up to AC 500…790 V 42…460 Hz, DC 400…960 V
• Measuring clamps 20/52 mm
(115 mm optional) IT systems with a permanently installed insulation fault location system
• Robust aluminium case, convenient to carry • EDS3090
for main circuits with a permanently installed insulation fault location system
• Locating current injectors PGH18… with
with EDS460/490
variable locating current 1…25 mA
• EDS3091
• Integrated locating voltage for de-ener-
for control circuits with a permanently installed insulation fault location system
gised systems (PGH186)
with EDS460/491
Insulation fault locator EDS195PM Function
• Backlit LC display, 3 x 16 characters
Locating current injector PGH18…
• Measuring clamps 20/52 mm included in The PGH18… generates the relevant locating current signal. The locating current generated in
the scope of delivery this manner depends on the value of the insulation fault that is present and the system voltage.
• Accumulator • Depending on the switch position, the PGH185 or PGH186 limit the locating current is
(delivered with a power supply unit) to a maximum of 25 mA respectively 10 mA.
• Response value insulation fault location • The PGH183 limits the locating current to a maximum of 2.5 mA or 1 mA respectively.
2…10 mA for main circuits
In de-energised IT systems or in IT systems with a system voltage of < 50 V, the PGH186 drives
• Response value insulation fault location the locating current generated by an integrated voltage source (DC 50 V). In IT systems with a
0.2…1 mA for control circuits system voltage of > 50 V, the system voltage itself drives the locating current.
• Response value residual current measure-
Insulation fault locator EDS195PM
ment 10 mA…10 A
The insulation fault locator EDS195PM provides the following measuring functions:
• Selectable operating mode insulation
• Insulation fault location IΔL (EDS mode) for use in IT AC or DC systems. The response value
fault location/residual current measurement
is determined by the sensitivity of the EDS195PM insulation fault locator. In DC, AC and
Approvals 3AC IT systems, this is an arithmetic average value that can be set according to an arith-
metic average value. System interferences and excessively high system leakage capaci-
tances may have a negative influence on the accuracy
– within the portable EDS309…insulation fault location system or
– within a permanently installed insulation fault location system in conjunction with
EDS15…/46…/49…
• Residual current measurement IΔn (RCM mode) for use in TN or TT AC systems. The response
range for the alarm message is 10 mA…10 A.
2 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
Displays Standards
The LC display indicates the measured residual current, the type The portable insulation fault location systems have been designed
of the connected measuring clamp resp. measuring current trans- in accordance with the following standards: DIN EN 61557-8 (VDE
former, the accumulator capacity, the activation of the alarm memory, 0413-8), EN 61557-8, IEC 61557-8, IEC 61326-2-4, DIN EN 60664-1
the activation of the buzzer, and the set nominal frequency. (VDE 0110-1), DIN EN 60664-3, DIN EN 61557-9, VDE 0413-9, IEC
61557-9, ASTM F1669M-96 (2007), ASTM F1207M-96 (2007)
Application example
EDS195PM
ISOSCAN®
RF
Equipment for insulation fault location EDS3096PG in de-energised systems (IT systems) (Note: TN-S system with all poles disconnected)
EDS195PM
ISOSCAN®
RF
EDS309x_D00012_02_D_XXEN/11.2018 3
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
Application example
Central inverter
IT system
Junction box transformer
Strings =
PSA30..
PSA30..
BNC
BNC
EDS
195PM EDS
195PM
EDS195PM
ISOSCAN®
PSA30.. PGH186
Insulation
fault
PSA30..
EDS-
SET L2(-)
BNC
L1(+)
EDS
195PM E
AGE185
PE
Insulation fault location system EDS3096PV in unearthed photovoltaic systems (IT systems)
4 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
Application example
EDS195PM
ISOSCAN®
PGH18x
RF
quipment for insulation fault location EDS3090/3091PG for use in unearthed systems (IT systems) without a permanently installed equipment
E
for insulation fault location
EDS195PM
ISOSCAN®
EDS195PM
quipment for insulation fault location EDS3090/3091 in unearthed systems (IT systems) with permanently installed equipment for insulation
E
fault location EDS
EDS309x_D00012_02_D_XXEN/11.2018 5
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
5 4
1 - M
icro USB connection for charging the device‘s rechargeable
battery
2 - BNC connection for the measuring clamp
1
3 - L C display, backlit
3 lines à 16 characters
4 - LED “ALARM”, lights when the response value is exceeded
2
5 - B
utton for the selection of the operating mode:
IΔL = Insulation fault location in IT systems (EDS mode)
IΔn = Residual current measurement in TN-S systems (RCM mode)
EDS195PM
6 - B
utton for transformer selection ISOSCAN®
for ITmax = 50 mA: for ITmax = 5 mA:
P20 = PSA3020 = PSA3320 3
P52 = PSA3052 = PSA3352
P165 = PSA3165 ---------------
W/WR = W…/WR… = W…-8000 4
WS = WS… = W…-8000
7 - “INFO” button:
– Device type
– Software version
– Current response values IΔL and IΔn
– Setup status
ESC button:
to exit the menu function without changing parameters
8 - “MENU” button 5 6
to toggle between the standard display and the menu selection
9 - On/Off switch 10 7
10 - “HOLD” button OK
6 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
EDS309x_D00012_02_D_XXEN/11.2018 7
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
ø52
99
54,5
132
101
111
43
5
ø11
179
170
21
shielded cable
BNC plug shielded cable BNC plug
2m
2m shielded cable BNC plug
2m
18,5
30
35
45
30
33
45
35
8 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
Ordering information
Measuring
Nominal voltage Un Insulation fault Locating Measuring clamps
Designation Type Art. No. clamps Type
locator current injector 20 mm
AC DC 52 mm
Measuring clamp 115 mm for EDS195PM – PSA3020 PSA3052 EDS3090
– – PSA3165 B980852
EDS3090… and EDS3096… EDS195PM PGH185 PSA3020 PSA3052 EDS3090PG
EDS195PM PGH185-13 PSA3020 PSA3052 EDS3090PG-13
Coupling device to extend the 500…790 V/
400…960 V AGE185 B980305 EDS195PM PGH186 PSA3020 PSA3052 EDS3096PG
voltage range of the PGH185/186 42…460 Hz
EDS195PM PGH186-13 PSA3020 PSA3052 EDS3096PG-13
Accessories for fault location in EDS195PM – PSA3320 PSA3352 EDS3091
– – EDS165-SET B91082007
diode-decoupled systems EDS195PM PGH183 PSA3320 PSA3352 EDS3091PG
EDS195PM PGH183-13 PSA3320 PSA3352 EDS3091PG-13
PGH183 PSA3320 PSA3352
EDS195PM EDS3092PG
PGH185 PSA3020 PSA3052
EDS195PM PGH186 – 2 x PSA3052 EDS3096PV
Standards
Observe the applicable national and international standards. The EDS309… series meets the requirements of the following standards
for the erection of electrical installations:
• IEC 60364-4-41 (modified): Low-voltage electrical installations - Part 4-41: Protection for safety - Protection against electric shock;
German implementation HD 60364-4-41
The EDS309… type range complies with the device standards:
• DIN EN 61557-9 (VDE 0413-9): IEC 61557-9: Electrical safety in low-voltage distribution systems up to 1000 V a.c. and 1500 V d.c. -
Equipment for testing, measuring or monitoring of protective measures - Part 9: Equipment for insulation fault location in IT systems;
German version EN 61557-9
• IEC 61010-1:2001 Safety requirements for electrical equipment for measurement, control, and laboratory use -
Part 1: General requirements German version EN 61010-1
EDS309x_D00012_02_D_XXEN/11.2018 9
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
Type EDS195PM
LC display 3 x 16 characters
Evaluating current IΔL 0.2…50 mA
Response value 0.2…1/2…10 mA selectable
Messzangen
Application range Main circuits Control circuits
Complete systems
Type EDS3090 EDS3091
Aluminium case, EDS195PM, Aluminium case, EDS195PM,
Aluminium case, EDS195PM, PSA3320,
Comprising PSA3020, PSA3052, PSA3020, PSA3052,
PSA3352, power supply unit
power supply unit power supply unit
10 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)
Type EDS195PM
LC display 3 x 16 characters
Evaluating current IΔL 0.2…50 mA
Response value 0.2…1/2…10 mA selectable
Measuring clamps
Components EDS309...
EDS195PM with Accessories PGH18... with accessories for Measuring clamps
Safety measuring cable, green/
Adapter BNC/4mm connector for
Measuring clamps 52 mm
Coupling device, optional
Supply cable for PGH18...
Locating current injector
Insulation fault locator
EDS-Set, optional
curr. transform
Device type
of delivery)
EDS195PM
optional
optional
handle
yellow
EDS309x_D00012_02_D_XXEN/11.2018 11