Portable equipment for insulation fault location for unearthed


and earthed systems (IT and TN systems) to be used in conjunction
with or without an equipment for insulation fault location

EDS309x_D00012_02_D_XXEN/11.2018
EDS309… Portable insulation fault location system for unearthed and earthed systems (IT and
TN systems) to be used in conjunction with or without an insulation fault location
system

Product description
The EDS309… is a portable insulation fault location system for localising insulation faults in
unearthed systems (IT systems). All essential components are housed in a robust aluminium
case which is convenient to carry.

Application
IT systems without a permanently installed insulation fault location system
• EDS3090PG
for main circuits up to AC 20…575 V 42…460 Hz, DC 20…504 V with AGE185 up to
AC 500…790 V 42…460 Hz, DC 400…960 V
• EDS3091PG
EDS309… for control circuits up to AC 20…265 V 42…460 Hz, DC 20…308 V
• EDS3092PG
Device features for main circuits in conjunction with PGH185 up to AC 20…575 V 42…460 Hz, DC 20…504 V
with AGE185 up to AC 500…790 V 42…460 Hz, DC 400…960 V
• Portable insulation fault location systems
for control circuits in conjunction with PGH183 up to AC 20…265 V 42…460 Hz, DC 20…308 V
for IT systems AC 0…790 V, 42…460 Hz/
DC 0…960 V or de-energised systems • EDS3096PG
for main circuits in IT systems with all poles disconnected up to AC 0…575 V 42…460 Hz,
• Residual current measurement in TN/TT
DC 0…504 V
systems
• Use in main and control circuits, • EDS3096PV
photovoltaic systems for photovoltaic systems with PGH186 up to 20…575 V 42…460 Hz, DC 20…504 V
with AGE185 up to AC 500…790 V 42…460 Hz, DC 400…960 V
• Measuring clamps 20/52 mm
(115 mm optional) IT systems with a permanently installed insulation fault location system
• Robust aluminium case, convenient to carry • EDS3090
for main circuits with a permanently installed insulation fault location system
• Locating current injectors PGH18… with
with EDS460/490
variable locating current 1…25 mA
• EDS3091
• Integrated locating voltage for de-ener-
for control circuits with a permanently installed insulation fault location system
gised systems (PGH186)
with EDS460/491
Insulation fault locator EDS195PM Function
• Backlit LC display, 3 x 16 characters
Locating current injector PGH18…
• Measuring clamps 20/52 mm included in The PGH18… generates the relevant locating current signal. The locating current generated in
the scope of delivery this manner depends on the value of the insulation fault that is present and the system voltage.
• Accumulator • Depending on the switch position, the PGH185 or PGH186 limit the locating current is
(delivered with a power supply unit) to a maximum of 25 mA respectively 10 mA.
• Response value insulation fault location • The PGH183 limits the locating current to a maximum of 2.5 mA or 1 mA respectively.
2…10 mA for main circuits
In de-energised IT systems or in IT systems with a system voltage of < 50 V, the PGH186 drives
• Response value insulation fault location the locating current generated by an integrated voltage source (DC 50 V). In IT systems with a
0.2…1 mA for control circuits system voltage of > 50 V, the system voltage itself drives the locating current.
• Response value residual current measure-
Insulation fault locator EDS195PM
ment 10 mA…10 A
The insulation fault locator EDS195PM provides the following measuring functions:
• Selectable operating mode insulation
• Insulation fault location IΔL (EDS mode) for use in IT AC or DC systems. The response value
fault location/residual current measurement
is determined by the sensitivity of the EDS195PM insulation fault locator. In DC, AC and
Approvals 3AC IT systems, this is an arithmetic average value that can be set according to an arith-
metic average value. System interferences and excessively high system leakage capaci-
tances may have a negative influence on the accuracy
– within the portable EDS309…insulation fault location system or
– within a permanently installed insulation fault location system in conjunction with
EDS15…/46…/49…
• Residual current measurement IΔn (RCM mode) for use in TN or TT AC systems. The response
range for the alarm message is 10 mA…10 A.

2 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Displays Standards
The LC display indicates the measured residual current, the type The portable insulation fault location systems have been designed
of the connected measuring clamp resp. measuring current trans- in accordance with the following standards: DIN EN 61557-8 (VDE
former, the accumulator capacity, the activation of the alarm memory, 0413-8), EN 61557-8, IEC 61557-8, IEC 61326-2-4, DIN EN 60664-1
the activation of the buzzer, and the set nominal frequency. (VDE 0110-1), DIN EN 60664-3, DIN EN 61557-9, VDE 0413-9, IEC
61557-9, ASTM F1669M-96 (2007), ASTM F1207M-96 (2007)

Note: Electrical interferences during operation may result in false


tripping and indication errors.

Application example

EDS195PM
ISOSCAN®

RF

Equipment for insulation fault location EDS3096PG in de-energised systems (IT systems) (Note: TN-S system with all poles disconnected)

EDS195PM
ISOSCAN®

RF

Residual current measurement with EDS309… in earthed systems (TN-S systems)

EDS309x_D00012_02_D_XXEN/11.2018 3
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Application example

Central inverter
IT system
Junction box transformer
Strings =

PSA30..
PSA30..

BNC
BNC
EDS
195PM EDS
195PM

EDS195PM
ISOSCAN®

PSA30.. PGH186

Insulation
fault
PSA30..

EDS-
SET L2(-)

BNC
L1(+)
EDS
195PM E

AGE185
PE

Insulation fault location system EDS3096PV in unearthed photovoltaic systems (IT systems)

4 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Application example

EDS195PM
ISOSCAN®

PGH18x

RF

 quipment for insulation fault location EDS3090/3091PG for use in unearthed systems (IT systems) without a permanently installed equipment
E
for insulation fault location

EDS195PM
ISOSCAN®

EDS195PM

 quipment for insulation fault location EDS3090/3091 in unearthed systems (IT systems) with permanently installed equipment for insulation
E
fault location EDS

EDS309x_D00012_02_D_XXEN/11.2018 5
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Operating elements of the PGH18…


1 - On/off switch “ON” to activate the locating current
2 - S elector switch for the maximum locating current 25/10 mA or 1
2.5/1 mA
3 - Not visible: Magnetic adhesive strip at the back of the enclo-
sure for fixing to metal parts (e.g. switchboard cabinet)
8
4 - 3 sockets for system coupling
5 - Socket for PE connection 2
6 - LED indicators: 7
Power On LED “ON”
Indication of the positive test pulse of the locating current
6
Indication of the negative test pulse of the locating current
7 - Microfuse 100 mA
8 - Panel plug for supply voltage
3

5 4

Display and operating elements of the EDS195PM

1 - M
 icro USB connection for charging the device‘s rechargeable
battery
2 - BNC connection for the measuring clamp
1
3 - L C display, backlit
3 lines à 16 characters
4 - LED “ALARM”, lights when the response value is exceeded
2
5 - B
 utton for the selection of the operating mode:
IΔL = Insulation fault location in IT systems (EDS mode)
IΔn = Residual current measurement in TN-S systems (RCM mode)
EDS195PM
6 - B
 utton for transformer selection ISOSCAN®
for ITmax = 50 mA: for ITmax = 5 mA:
P20 = PSA3020 = PSA3320 3
P52 = PSA3052 = PSA3352
P165 = PSA3165 ---------------
W/WR = W…/WR… = W…-8000 4
WS = WS… = W…-8000
7 - “INFO” button:
– Device type
– Software version
– Current response values IΔL and IΔn
– Setup status
ESC button:
to exit the menu function without changing parameters
8 - “MENU” button 5 6
to toggle between the standard display and the menu selection
9 - On/Off switch 10 7
10 - “HOLD” button OK

to store the currently indicated measured value 11 8


Arrow up button: Parameter changes, scroll
11 - “RESET” button
fault memory acknowledgement
12 9
Arrow down button: Parameter changes, scroll
12 - Illumination button:
to switch on the display lighting

6 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Technical data EDS309…system Technical data EDS195PM


The technical data listed in this chapter apply to the components:
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
PGH18…, EDS195PM, AGH185.
Rated insulation voltage 50 V
Environment/EMC Rated impulse withstand voltage/pollution degree  0.8 kV/3
EMC  IEC 61326-2-4 Supply voltage
Operating temperature -10…+ 55 °C
Supply voltage US accumulators, batteries or USB power supply unit
Classification of climatic conditions acc. to IEC 60721:
Accumulators 3 x NiMh ≥ 2000 mAh
Stationary use (IEC 60721-3-3) 3K5 (except condensation and formation of ice)
Hours of operation (without display illumination) ≥ 150 h
Transport (IEC 60721-3-2) 2K3 (except condensation and formation of ice)
Charging time ≤5h
Storage (IEC 60721-3-1) 1K4 (except condensation and formation of ice)
Size AA R6
Classification of mechanical conditions acc. to IEC 60721:
Batteries 3 x LR6 AA – 1.5 V
Stationary use (IEC 60721-3-3)  3M4
USB power supply unit:
Transport (IEC 60721-3-2)  2M2
Primary :  100…240 V, 50…60 Hz
Long-term storage (IEC 60721-3-1)  1M3
Secondary:  DC 5 V, +/- 10 %,
Other Power consumption ≤ 0.5 W
Operating mode continuous operation Measuring circuit insulation fault location
Position of normal use any
Nominal system voltage conductors uninsulated, including measuring clamp up to 600 V
Weight EDS309…  ≤ 7000 g
Rated frequency DC, 42…2000 Hz
Weight EDS309… with PSA3165  ≤ 8500 g
Weight EDS3092  ≤ 9000 g Main circuit (ILmax = 50 mA):
Dimensions, case W x H x D  430 x 340 x 155 mm Measuring range 2 mA…50 m A
Documentation number D00012 Measuring clamps PSA3020, PSA3052, PSA3165
Response sensitivity IΔL adjustable 2… 10 mA (5 mA)*
Relative uncertainty ±30 %/±2 mA of the reference value
Technical data PGH18…
Control circuit: (ILmax = 5 mA)
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Measuring range 0.2 mA…5 m A
Measuring clamps PSA3320, PSA3352
Rated insulation voltage AC 500 V
Response sensitivity IΔL adjustable 0.2…1.0 mA (0.5 mA)*
Rated impulse voltage/pollution degree  4 kV/3
Relative uncertainty 0.2…0.9 mA  ±30 %/± 0.2 mA of the reference value
Nominal system voltage Un Relative uncertainty 1…5 mA  ±30 %/± 2 mA of the reference value
PGH183 AC 20…265 V 42…460 Hz, DC 20…308 V Measuring circuit residual current
PGH185 3AC/AC 20…575 V 42…460 Hz, DC 20…504 V
with measuring clamps PSA3020, PSA3052, PSA3165
PGH186 3AC/AC 0…575 V 42…460 Hz, DC 0…504 V
Measuring range 5 mA … 10 A (crest factor up to 3)
Supply voltage Response sensitivity IΔn adjustable 10 mA…10 A (100 mA)*
Supply voltage US  AC 230 V 50…60 Hz Measuring clamps PSA3320, PSA3352
Operating range of US  0.85…1.15 x US Measuring range 2 mA … 2 A (crest factor up to 3)
Supply voltage US version -13 AC 90…132 V/50…60 Hz Response sensitivityIΔn adjustable 5 mA…1 A (100 mA)*
Frequency range  42…1000 Hz
PGH 183, PGH 185:
Relative uncertainty, 42…60 Hz  ±5 %
Power consumption ≤ 3 VA
Relative uncertainty, 61…1000 Hz  ±20 %
PGH 186: Hysteresis20%
Power consumption  ≤ 6 VA Harmonics, indication can be switched off 1st to 8th harmonic component
Locating current Inputs
PGH183: Connection for measuring clamp BNC socket
Locating current, selectable, max.  1/2,5 mA Connection for power supply unit (DC 5 V)  μUSB socket
PGH185/186: Displays
Locating current, selectable, max.  10/25 mA
LCD 3 x 16 characters, selectable illumination
PGH183/185/186 LED  alarm
Test pulse 2s
Idle time  4s Other
Locating voltage Degree of protection, internal components DIN EN 60529 (VDE 0470-1) IP40
Protection class acc. to IEC 60947-1, DIN EN 60947-1 (VDE 0660-100) Class III
PGH186 DC 50 V Enclosure material ABS plastic
Other Flammability class UL94V-0
Degree of protection, internal components DIN EN 60529 (VDE 0470-1) IP40 Weight ≤ 350 g
Enclosure material ABS plastic Software version  D399 V1.2
Flammability class UL94V-0 Dimensions WxHxD 84x197x30 mm
Weight ≤ 700 g ( )* = Factory settings
Dimensions 160 x 148 x 81 mm

EDS309x_D00012_02_D_XXEN/11.2018 7
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Technical data measuring clamps Technical data AGE185

Electrical safety Insulation coordination acc. to IEC 60664-1


Standard  IEC 61010-2-030 Rated insulation voltage AC 1000 V
Pollution degree 2 Rated impulse voltage/pollution degree  4 kV/3
Installation category III Nominal system voltage Un 3AC, AC 500…790 V, DC 400…960 V, 42…460 Hz
Operating voltage 600 V
Other
Nominal insulation voltage AC 600 V CAT III bzw. AC 300 V CAT IV
Degree of protection, internal components DIN EN 60529 (VDE 0470-1) IP30
Transformation ratio Type of connection/cable:  safety plug with green-yellow connecting wire 1 mm2
PSA30…  10 A/10 mA Weight ≤ 400 g
PSA33…  1 A/0.1 mA Dimensions W x H x D 84 x 197 x 30 mm
PSA3165  10 A/10 mA Weight ≤ 200 g
Dimensions W x H x D 88.5 x 42 x 21 mm
Other
Degree of protection, internal components DIN EN 60529 (VDE 0470-1) IP40
Protection class acc. to IEC 60947-1, DIN EN 60947-1 (VDE 0660-100) Class III
Test port  BNC plug
Dimensions PSA3052/3352 216 x 111 x 45 mm
Dimensions PSA3020/3320 135 x 65 x 30 mm
Dimensions PSA3165  285 x 179 x 45 mm
Permissible cable diameter PSA3052/3352 52 mm
Permissible cable diameter PSA3052/3320 20 mm
Permissible cable diameter PSA3165  115 mm
Weight PSA3052/3352 ≤ 700 g
PSA3020/3320 ≤ 300 g
PSA3165  ≤ 1300 g

Dimension diagram PSA3020/3320 Dimension diagram PSA3052/3352 Dimension diagram PSA3165

135 216 285


43,5
50

ø52
99
54,5

132
101
111

43

5
ø11
179

170
21

max. opening: 110mm

shielded cable
BNC plug shielded cable BNC plug
2m
2m shielded cable BNC plug
2m
18,5

30
35
45
30

33
45
35

Dimension diagram aluminium case

8 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Ordering information

Main circuits Control circuits Nominal voltage Un Supply voltage US


Type Art. No.
with EDS without EDS with EDS without EDS AC DC AC
EDS460/490 – – – 20…575 V, 42…460 Hz 20…504 V – EDS3090 B91082026
230 V, 50…60 Hz EDS3090PG B91082021
20…575 V, 42…460 Hz 20…504 V
90…132 V, 50…60 Hz EDS3090PG-13 B91082022
– – –
230 V, 50…60 Hz EDS3096PG B91082025
0…575 V, 42…460 Hz 0…504 V
90…132 V, 50…60 Hz EDS3096PG-13 B91082029
– – EDS461/491 – 20…265 V, 42…460 Hz 20…308 V – EDS3091 B91082027
230 V, 50…60 Hz EDS3091PG B91082023
– – – 20…265 V, 42…460 Hz 20…308 V
90…132 V, 50…60 Hz EDS3091PG-13 B91082024
– – 20…265 V, 42…460 Hz 20…308 V 230 V, 50…60 Hz
EDS3092PG B91082030
– – 20…575 V, 42…460 Hz 20…504 V 230 V, 50…60 Hz
– – – 20…575 V, 42…460 Hz 20…504 V 230 V, 50…60 Hz EDS3096PV B91082031

Suitable system components Scope of delivery

Measuring
Nominal voltage Un Insulation fault Locating Measuring clamps
Designation Type Art. No. clamps Type
locator current injector 20 mm
AC DC 52 mm
Measuring clamp 115 mm for EDS195PM – PSA3020 PSA3052 EDS3090
– – PSA3165 B980852
EDS3090… and EDS3096… EDS195PM PGH185 PSA3020 PSA3052 EDS3090PG
EDS195PM PGH185-13 PSA3020 PSA3052 EDS3090PG-13
Coupling device to extend the 500…790 V/
400…960 V AGE185 B980305 EDS195PM PGH186 PSA3020 PSA3052 EDS3096PG
voltage range of the PGH185/186 42…460 Hz
EDS195PM PGH186-13 PSA3020 PSA3052 EDS3096PG-13
Accessories for fault location in EDS195PM – PSA3320 PSA3352 EDS3091
– – EDS165-SET B91082007
diode-decoupled systems EDS195PM PGH183 PSA3320 PSA3352 EDS3091PG
EDS195PM PGH183-13 PSA3320 PSA3352 EDS3091PG-13
PGH183 PSA3320 PSA3352
EDS195PM EDS3092PG
PGH185 PSA3020 PSA3052
EDS195PM PGH186 – 2 x PSA3052 EDS3096PV

Standards
Observe the applicable national and international standards. The EDS309… series meets the requirements of the following standards
for the erection of electrical installations:
• IEC 60364-4-41 (modified): Low-voltage electrical installations - Part 4-41: Protection for safety - Protection against electric shock;
German implementation HD 60364-4-41
The EDS309… type range complies with the device standards:
• DIN EN 61557-9 (VDE 0413-9): IEC 61557-9: Electrical safety in low-voltage distribution systems up to 1000 V a.c. and 1500 V d.c. -
Equipment for testing, measuring or monitoring of protective measures - Part 9: Equipment for insulation fault location in IT systems;
German version EN 61557-9
• IEC 61010-1:2001 Safety requirements for electrical equipment for measurement, control, and laboratory use -
Part 1: General requirements German version EN 61010-1

EDS309x_D00012_02_D_XXEN/11.2018 9
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Device selection for IT systems


with integrated equipment for insulation fault location

Type of distribution system AC, DC, AC/DC (mixed systems)


Application range Main circuits Control circuits Main circuits or Control circuits

Insulation monitoring device ISOMETER®/Locating current injector PGH

Type IRDH575 IRDH575 iso685-x-P isoxx1685xP


-B1: 3AC, AC 20…575 V, DC 20…504 V isoLR1685DP: AC 0…690, DC 0…690 V
Nominal system voltage Un 3AC, AC 20…150 V, DC 20…150 V AC 0…690 V, DC 0…1000 V
-B2: 3AC, AC 340…760 V, DC 340…575 V iso1685DP: AC 0…1000 V, DC 0…1500 V
US DC 19,2…72 V IRDH575B1-427 IRDH575B1-4227 – –
US AC 88…264 V/DC 77…286 V IRDH575B1-435, IRDH575B2-435 IRDH575B1-4235 – –
US AC/DC 24…240 V – – iso685-x-P –
US DC 18…30 V – – – isoxx1685xP
Locating current IL 10/25/50 mA 1/2,5 mA 1/1.8/2.5/5/10/25/50 mA 1/2.5/5/10/25/50 mA
isoLR1685DP: 20 Ω …. 100 kΩ
Response values 1 kΩ …. 10 MΩ 1 kΩ …. 10 MΩ 1 kΩ …. 10 MΩ
iso1685DP: 200 Ω …. 1 MΩ
LC display 4 x 20 characters 4 x 20 characters graphic display graphic display
Alarm relay 3 changeover contacts 3 changeover contacts 2 changeover contacts 3 changeover contacts
Interface/protocol RS-485 (BMS) RS-485 (BMS) RS-485 (BS) RS-485 (BS)
Address range 1…30 1…30 1…90 1…90

Insulation fault locator

Type EDS195PM
LC display 3 x 16 characters
Evaluating current IΔL 0.2…50 mA
Response value 0.2…1/2…10 mA selectable

Messzangen
Application range Main circuits Control circuits

Type PSA3020 PSA3052 PSA3165 (optional) PSA3320 PSA3352


20 mm
52 mm
115 mm

Complete systems
Type EDS3090 EDS3091
Aluminium case, EDS195PM, Aluminium case, EDS195PM,
Aluminium case, EDS195PM, PSA3320,
Comprising PSA3020, PSA3052, PSA3020, PSA3052,
PSA3352, power supply unit
power supply unit power supply unit

10 EDS309x_D00012_02_D_XXEN/11.2018
Portable insulation fault location system for unearthed and earthed systems (IT and TN systems)

Device selection for IT systems


without a permanently installed equipment for insulation fault location

Application Main circuit Control circuit


energised offline energised

Locating current injector PGH

3AC, AC 20…575 V 3AC, AC 0…575 V AC 20…265 V, DC 20…308 V


Nominal system voltage Un
DC 20…504 V DC 0…504 V
US AC 230 V PGH185 PGH186 PGH183
US AC 90…132 V PGH185-13 PGH186-13 PGH183-13
Locating current IL max. 10/25 mA 10/25 mA 1/2.5 mA

Insulation fault locator

Type EDS195PM
LC display 3 x 16 characters
Evaluating current IΔL 0.2…50 mA
Response value 0.2…1/2…10 mA selectable

Measuring clamps

Type PSA3020 PSA3052 PSA3165 (optional) PSA3320 PSA3352


20 mm
52 mm
115 mm

Components EDS309...
EDS195PM with Accessories PGH18... with accessories for Measuring clamps
Safety measuring cable, green/
Adapter BNC/4mm connector for

Safety claw grip, green/yellow

(EDS3096PV only: in the scope


Aluminium case with carrying

Safety measuring cable, black


Clamping connector on 4 mm

Adapter BNC-PS2 for WF-CT,

Measuring clamps 115 mm,


Measuring clamps 20 mm

Measuring clamps 52 mm
Coupling device, optional
Supply cable for PGH18...
Locating current injector
Insulation fault locator

Safety claw grip, black


Plug power supply for
Operating manual

EDS-Set, optional
curr. transform
Device type

of delivery)
EDS195PM
optional

optional
handle

yellow

EDS3090 1 1 EDS195PM 1 1 1 1 PSA3020 PSA3052 PSA3165 1


EDS3090PG 1 1 EDS195PM 1 1 1 1 PGH185 1 3 1 3 1 AGE185 PSA3020 PSA3052 PSA3165 1
EDS3090PG-13 1 1 EDS195PM 1 1 1 1 PGH185-13 1 3 1 3 1 AGE185 PSA3020 PSA3052 PSA3165 1
EDS3091 1 1 EDS195PM 1 1 1 1 PSA3320 PSA3352 1
EDS3091PG 1 1 EDS195PM 1 1 1 1 PGH183 1 3 1 3 1 PSA3320 PSA3352 1
EDS3091PG-13 1 1 EDS195PM 1 1 1 1 PGH183-13 1 3 1 3 1 PSA3320 PSA3352 1
PGH183 PSA3320 PSA3352
EDS3092PG 1 1 EDS195PM 1 1 1 1 2 6 2 6 2 1
PGH185 PSA3020 PSA3052
EDS3096PG 1 1 EDS195PM 1 1 1 1 PGH186 1 3 1 3 1 AGE185 PSA3020 PSA3052 PSA3165 1
EDS3096PG-13 1 1 EDS195PM 1 1 1 1 PGH186-13 1 3 1 3 1 AGE185 PSA3020 PSA3052 PSA3165 1

EDS309x_D00012_02_D_XXEN/11.2018 11