Abb Drive Library Export
Abb Drive Library Export
Abb Drive Library Export
LOW VO LTAG E AC D R I V E S
06 – 07 Easily take full control of your processes to comprehensively manage your plant
16 Technical data
18 – 19 Dimensions
28 – 29 Higher enclosure class for cabinet-free installations even in harsh conditions
48 Circuit breakers
49 du/dt filters
50 Sine filters
51 ACS580 drives are compatible with the wide ABB product offering
—
The all-compatible ACS580 series
Effortless process automation
The ACS580 is an all-compatible ABB general purpose drive, offered in a range of
wall-mounted drives, drive modules and cabinet-built drives. It turns complicated
to simple and controls processes productively and efficiently.
Compressors
Material Automotive
handling Mixers
Conveyors
Fans
Agriculture Pumps
5
6 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Easily take full control of your processes to
comprehensively manage your plant
ACS580 drives are equipped with built-in features that simplify ordering and delivery,
and reduce commissioning costs. Everything is provided in a single, compact and
ready-to-use package for you to take full control of your processes.
Scalable performance
The ACS580 is a perfect match not only for energy-aware
applications, but also for applications where sophisticated
speed and torque control are needed.
7
—
Effortless automation and productivity
for your success
Adaptive programming
Adaptive programming is ideal for
creating simple programs for various
applications to further optimize the
process control. It does not require
expertise in programming.
Remote monitoring
A built-in web server and stand-alone
datalogger NETA-21 module enable
worldwide and secure access to drives.
8 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Typical industries and applications
— — — —
01 02 03 04
— — — —
05 06 07 08
— — —
01 Food and beverage 04 Rubber and plastics 07 Water handling
— — —
02 Material handling 05 Textile 08 Agriculture
— — —
03 Printing 06 Sawmill 09 Automotive
—
09
T Y P I C A L I N D U S T R I E S A N D A P P L I C AT I O N S 9
—
Streamline your processes
for profitable growth
Material Conveyors • Accurate and precise speed and torque control increase production uptime even when
handling the load varies.
• Safe torque off (SIL 3) function ensures machine and personnel safety.
• Minimized downtime with robust and reliable design.
• Swinging choke technology to mitigate harmonics.
• External +24 V supply to keep the communication up when the mains supply is disconnected.
Rubber and Extruders, injection • Smooth acceleration to prevent breaking the web of plastic film.
plastics molding machines, pumps • The scalable all-compatible platform allows easy process and component optimization with
different drive types that share the same user interface and tools.
• Wide range of supported fieldbus protocols for easy PLC integration.
Textile Bleaching machines, • Precise speed or torque control for high stretching accuracy and better quality of the end product.
compressors, conveyors, • Adjustable torque limit to prevent damage to mechanical equipment.
drum washers, extruders, • Adjustable acceleration/deceleration ramps to improve pump control.
fans, jet dyeing machines, • Real-time clock and timed functions for process optimization.
pumps, stenter machines, • Increased productivity and faster payback times with multiple setups, allowing production of
stretchers, winders two different products.
• Built-in counters for additional energy savings and preventive maintenance.
Sawmill Chippers, conveyors, • IP55/UL type 12 available up to 250 kW for harsh environments.
feeders, dryers, pickers, • Cabinet-built drive IP54 up to 500 kW.
drying kilns • Safe torque off (SIL 3) function ensures machine and personnel safety.
• External +24 V supply to keep the communications "alive" when the mains supply is turned off.
• ATEX-certified thermistor protection module, Ex II (2) GD.
Water handling Compressors, • Additional energy savings with energy optimizer function.
pump stations • Adjustable acceleration/deceleration ramps to improve pump control.
• Minimized downtime with robust and reliable design.
• ABB’s extensive product and service offering for comprehensive process optimization.
Automotive Conveyors, fans, pumps • ATEX-certified thermistor protection module, Ex II (2) GD.
• Increased productivity and faster payback times with multiple setups.
• Enhanced quality of end products with smooth control of the motor and process.
• Safe torque off (SIL 3) function ensures machine and personnel safety.
• Wide range of fieldbus networks supported, including PROFIBUS and PROFINET IO.
• P55/UL Type 12 available up to 250 kW 400 V and high enclosure rating for harsh environments.
• The robust design of the drive reduces mechanical stress on process line equipment, lowering
maintenance costs and ensuring high production quality.
10 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Complete offering, from wall-mounted drives
to cabinet installations
Powerful, rugged and robust ACS580 drives ensure ease of use, scalability and
quality. A wide power range and various mounting options and enclosure classes
ensure you will find a drive for your installation and environment needs.
—
01 Wall-mounted Wall-mounted IP21 drives, standard —
ACS580 IP21 drive 01
Wall-mounted IP21 drives are available in a power
—
02 Wall-mounted and voltage range from 0.75 to 250 kW and 3-phase
ACS580 IP55 drive
380-480 V. Side-by-side mounting, flange mounting
—
03 Flange-mounted and horizontal mounting are all available for
ACS580 IP21 drive
wall-mounted ACS580 drives.
—
04 ACS580 drive
module with IP00
—
05 Cabinet-built
ACS580 drive
with IP42
Wall-mounted IP55 drives, +B056
The IP55 drive is designed for applications
exposed to dust, moisture, vibrations and other
harsh environments. It is similar in size to the
compact IP21 drives, which provides significant —
02
savings in space, maintenance, engineering,
and material costs, as well as in setup and
commissioning time.
—
Common features throughout the
whole ACS580 product family
—
Standard ACS580 drives software
with versatile features
Analyze and resolve issues with the control panel's diagnostics menu. You can quickly analyze
why the drive is performing as it is, whether running, stopped or running at the present speed.
14 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Standard interface and extensions
for plug-in connectivity
—
ACS580 drives offer a wide range of standard interfaces. Default factory I/O connection diagram: Macro ABB standard
In addition, the drive has two option slots that can be
Terminal Meaning Default macro connections
used for extensions, including fieldbus adapters and
XI Reference voltage and analog inputs and outputs
input/output extension modules that allow an
1 SCR Signal cable shield (screen)
external +24 V supply with frame sizes R1 to R5.
2 AI1 External frequency reference 1: 0 to 10 V
For frames R6-R11 external +24 V terminals
3 AGND Analog input circuit common
are already integrated on the control
4 +10 V Output reference voltage 10 V DC
board. For further information, please 1 to 10 kohm
5 AI2 Not used
see the ACS580 user manual.
6 AGND Analog input circuit common
7 AO1 Output frequency: 0 to 20 mA
1 2
8 AO2 Output current: 0 to 20 mA
9 AGND Analog output circuit common
Max. 500 ohm
X2 & X3 Aux. voltage output and programmable digital inputs
10 +24 V Auxiliary voltage output +24 V DC
3
11 DGND Auxiliary voltage output common
4 12 DCOM Digital input common for all DI
—
How to select a drive
The right drive is extremely easy to select. The following instructions show you
how to order the right drive for your application.
power rating.
— ACS580-04-505A-4 R10
(kW)
250
(A)
505
(A)
485
(kW)
250
(A)
361
(kW)
200
(A)
560
(A)
483
(hp)
400
(A)
361
(hp)
300
(A)
560
ACS580-01-206A-4 R7 110 206 196 110 169 90 287 180 150 156 125 287 IN Rated current available continuously without overloadability at 40 °C.
ACS580-01-246A-4 R8 132 246 234 132 206 110 350 240 200 180 150 350 PN Typical motor power in no-overload use.
ACS580-01-293A-4 R8 160 293 278 160 246 *) 132 418 260 200 240 150 418 Maximum output current
ACS580-01-363A-4 R9 200 363 345 200 293 160 498 361 300 302 250 542 I max Maximum output current. Available for 2 seconds at start.
ACS580-01-430A-4 R9 250 430 400 200 363 **) 200 545 414 350 361 300 542 Light-overload use
I Ld Continuous current allowing 110% I Ld for 1 minute every 10 minutes at 40 °C.
P Ld Typical motor power in light-duty use.
Heavy-duty use
I Hd Continuous current allowing 150% I Hd for 1 minute every 10 minutes at 40 °C.
*) Continuous current allowing 140% I Hd for 1 minute every 10 minutes at 40 °C.
**) Continuous current allowing 130% I Hd for 1 minute every 10 minutes at 40 °C.
***) Continuous current allowing 125% I Hd for 1 minute every 10 minutes at 40 °C.
P Hd Typical motor power in heavy-duty use.
Nominal ratings, ACS580-01
The ratings apply for the frames R6 to R9 up to +40 °C in enclosed IP class 21.
IN Rated current available continuously without overloadability at 40 °C. The ratings apply for the frames R10 to R11 up to +40 °C in enclosed IP00/IP20.
PN Typical motor power in no-overload use. For derating at higher altitudes, temperatures or switching frequencies, see the HW manuals, document codes: 3AXD50000018826,
3AXD50000015497, 3AXD50000045815 and 3AXD50000032622.
Maximum output current
I max Maximum output current. Available for 2 seconds at start.
Light-overload use
I Ld Continuous current allowing 110% I Ld for 1 minute every 10 minutes at 40 °C.
P Ld Typical motor power in light-duty use.
Heavy-duty use
I Hd Continuous current allowing 150% I Hd for 1 minute every 10 minutes at 40 °C.
*) Continuous current allowing 130% I Hd for 1 minute every 10 minutes at 40 °C.
Pages 20, 21 and 22
**) Continuous current allowing 125% I Hd for 1 minute every 10 minutes at 40 °C.
P Hd Typical motor power in heavy-duty use.
The ratings apply for the frames R1 to R9 up to +40 °C in enclosure class 21.
The ratings apply for the frames R10 to R11 up to +40 °C in enclosure class IP00/IP20.
For derating at higher altitudes, temperatures, switching frequencies or enclosure classes, see the HW manuals, document codes:
3AXD50000018826 and 3AXD50000015497.
—
Communication and connectivity
Options
Choose your options (on pages 26, 28 and 35) Fieldbus adapter modules
The ACS580 comes with Modbus RTU fieldbus
Input/output extension modules
Standard input and output can be extended by
interface as standard and it is also compatible using optional analog and digital input/output
3 4 +K491
+K492
3AXD50000049964
3AXD50000192779
Two port Modbus/TCP
Two port PROFINET IO
FMBT-21
FPNO-21
— —
04 —
CHDI-01
—
CPTC-02
—
CBAI-01
07 Plus code
+L501
MRP code
3AXD50000004420
Description
External 24 V AC and DC 2 x RO and 1 x DO
Type designation
CMOD-01
Rating
*) For further information please see pages 40-41.
**) No additional analog input/output is offered
Voltage
Pages 26, 28 and 35
Options
16 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Technical data
Mains connection Environmental limits
Input voltage and 3-phase, U N 200 to 240 V, +10%/-15% Ambient temperature
output power range ACS580-01: from 0.75 up to 75 kW Transport -40 to +70 °C
3-phase, U N 380 to 480 V, +10%/-15% Storage -40 to +70 °C
ACS580-01: from 0.75 up to 250 kW
ACS580-04: from 250 up to 500 kW Operation area ACS580-01: -15 to +50 °C. No frost allowed
ACS580-07: from 75 up to 500 kW R1 to R9 from +40 to +50 °C with derating
Auto-identification of supply voltage ACS580-04: -15 to +55 °C. No frost allowed
R10 to R11 from +40 to +55 °C with derating
Frequency from 47 to 63 Hz ACS580-07: 0 to +40 °C. No frost allowed
Power factor cosϕ = 0.98 R6 to R11 from +40 to +50 °C with derating
Efficiency 98% Cooling method
(at nominal power) Air-cooled Dry clean air
Motor connection Altitude 0 to 1,000 m Without derating
Voltage 3-phase, from 0 to supply voltage 1,000 to 4,000 m With derating of 1%/100 m
Frequency 0 to 500 Hz For more detailed information please see
the ACS580 hardware manual
Motor control Scalar and vector control
Relative humidity 5 to 95%, no condensation allowed
Torque control Torque step rise time:
<10 ms with nominal torque Degree of protection ACS580-01:
Non-linearity: IP21 as standard. IP55 as option
± 5% with nominal torque (frames R1 to R9)
Speed control Static accuracy: ACS580-04:
20% of motor nominal slip IP00 as standard. IP20 as option
Dynamic accuracy: (frames R10 to R11)
1% seconds with 100% torque step
ACS580-07:
Maximum R1: 100 m
Cabinet-built frames R6 to R11:
recommended motor R2: 200 m
IP21 as standard. IP42 and IP54 as options
cable length R3-R11: 300 m
Functional safety Safe torque off
Product compliance (STO according EN 61800-5-2)
CE IEC 61508 ed2: SIL 3. IEC 61511: SIL 3.
Low Voltage Directive 2014/34/EU, EN 61800-5-1: 2007 IEC 62061: SIL CL 3. EN ISO 13849-1: PL e
Machinery Directive 2006/42/EC, EN 61800-5-2: 2007
Contamination levels No conductive dust allowed
EMC Directive 2014/30/EU, EN 61800-3: 2004 + A1: 2012
RoHS directive 2011/65/EU Storage IEC 60721-3-1. Class 1C2 (chemical gases).
Quality assurance system ISO 9001 and Environmental system Class 1S2 (solid particles) *)
ISO 14001 Operation IEC 60721-3-3. Class 3C2 (chemical
Waste electrical and electronic equipment directive gases). Class 3S2 (solid particles) *)
(WEEE) 2002/96/EC
Transportation IEC 60721-3-2. Class 2C2 (chemical gases)
RoHS directive 2011/65/EU
Class 2S2 (solid particles) *)
UL, EAC, RCM, UL, cUL
TÜV Nord (safety functions) External power supply
Harmonics compliance Standard:
ACS580-01 frames R6-R9,
Built-in optimized DC choke as standard in AC580-01 meets the
ACS580-04 all frames and
requirements of IEC 61000-3-12:2011.
ACS580-07 all frames 1.5 A at 24 V AC/DC ±10%
EMC according to EN 61800-3:2004 + A1:2012
Frames R1 to R9 with built-in C2 category filter as standard With option:
Frames R10 and R11 with preconfigured built-in C3 category filter option ACS580-01 frames R1-R5 1.04 A at 24 V AC/DC ±10%
Inputs and outputs (standard configuration) Communication
2 analog inputs Selection of Current/Voltage input mode is Protocol as standard (EIA-485): Modbus RTU. Protocols available as
user programmable. option: EtherNet/IP, EtherNet POWERLINK, Modbus/TCP, EtherCAT,
PROFINET IO, PROFISafe (for STO and SS1-t functions), CANopen,
Voltage signal 0 (2) to 10 V, R in >200 k Ω ControlNet, DeviceNet and Profibus DP.
Current signal 0 (4) to 20 mA, R in = 100 Ω Protection functions
Potentiometer 10 V ±1% max. 20 mA Overvoltage controller
reference value Undervoltage controller
2 analog outputs AO1 is user programmable for current or Motor and motor cable earth-leakage monitoring
voltage. AO2 current Motor and motor cable short-circuit protection
Voltage signal 0 to 10 V, R load: >100 kΩ Motor overtemperature protection
Output and input switch supervision
Current signal 0 to 20 mA, R load: <500 Ω Motor overload protection
Internal auxiliary voltage 24 V DC ±10%, max. 250 mA Phase-loss detection (both motor and supply)
Under load supervision (belt loss detection)
6 digital inputs 12 to 24 V DC, 24 V AC, Connectivity of PTC Overload supervision
sensors supported by a single digital input. Stall protection
PNP or NPN connection (5 DIs with NPN Loss of control reference
connection).
*) C = Chemically active substances
3 relay outputs Maximum switching voltage 250 V AC/30 V S = Mechanically active substances
DC Maximum continuous current 2 A rms
Supported thermistors Any of the analog inputs, or digital input 6,
are configurable for PTC with up to 6 sensors.
Both analog outputs can be used to feed
the PT100, PT1000, KTY83, KTY84 or
Ni1000 sensors.
For more detailed information please see
the ACS580 hardware manual.
17
18 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Dimensions
ACS580-01 flange mounting dimensions, with +C135 or a loose option kit for IP21
Height Width Offs. Out Offs. In Weight
Frames (mm) (in) (mm) (in) (mm) (in) (mm) (in) (kg) (lb)
Offs. Out Offs. In
R1 461 18.2 206 8.1 133 5.2 109 4.3 4.6 10.1
R2 551 21.7 206 8.1 130 5.1 114 4.5 6.5 14.6
R3 613 24.1 290 11.4 118 4.6 116 4.6 11.8 26.0
R4 776 30.6 290 11.4 120 4.7 137 5.4 19 41.9
R5 776 30.6 290 11.4 124 4.9 173 6.8 28.3 62.4
R6 672 26.5 374 14.7 193 7.6 167 6.6 42.4 93.5
R7 722 28.4 406 16.0 194 7.6 169 6.7 54 119.1
R8 814 32.1 433 17.0 202 8.0 184 7.2 69 152.2 H
D
W
DIMENSIONS 19
—
Ratings, types and voltages
—
Ratings, types and voltages
3-phase, U N = 230 V (range 200 to 240 V). The power ratings are valid at nominal voltage 230 V (0.75 to 75 kW)
Drive type Frame Nominal ratings Light-duty use Heavy-duty use Maximum
size output current
IN I Ld PLd I Hd PHd I Max
(A) (kW) (A) (kW) (A) (kW) (A)
Nominal ratings
IN Rated current available continuously without overloadability at 40 °C.
PN Typical motor power in no-overload use.
Maximum output current
I max Maximum output current. Available for 2 seconds at start, then as long as allowed by drive temperature.
Light-overload use
I Ld Continuous current allowing 110% I Ld for 1 minute every 10 minutes at 40 °C.
P Ld Typical motor power in light-overload use.
The ratings apply for the frames R1 to R9 up to +40 °C in enclosed IP21/IP55.
For derating at high altitudes, temperatures or switching frequencies, see the user’s HW manual, document code: 3AXD50000035866.
—
Overloadability and output current illustration
1.5 × I hd
Definition ACS580
No overload In
1.1 × I ld
110% overload 1 min / 10 minutes I ld
150% overload 1 min / 10 minutes I hd
In
I ld
I hd
Time
23
24 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Easiness on a whole new level
Commission
without a hassle
Select language, set time
and date, name the drive,
enter motor values, test
rotating the motor.
Primary settings
Select ready-made macros,
perform ID-run, fine-tune
settings related to e.g.
ramps, limits, PIDs,
fieldbuses, reset to defaults.
Input/output menu
Set and monitor your input/
output (I/O) connections for
real-time diagnostics
Help button
The help button provides
more information about
your selection and it can be
pressed in any view.
A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G 25
—
Control panel options and mounting kits
The standard delivery of the ACS580 includes the assistant control panel
(requires the +J400 code), but it can be also replaced by other control panels.
—
Door mounting and daisy chaining
Improve safety and leverage the full potential of the ACS580 control panel options
with a door mounting kit and panel bus adapter.
Door mounting fosters easy operation and control panel for even easier and quicker
safety. It enables you to operate the drive without operation. When daisy chaining the drives,
opening the cabinet door, saving time and you need only one assistant control panel.
keeping all the electronics behind the closed The rest of the drives can be equipped with
door. Up to 32 drives can be connected to one panel bus adapters.
Cabinet door
Cabinet, inside
—
Control panel options
The ACS-AP-S assistant control panel (plus code +J400) is included as standard in the delivery.
If no code is mentioned in the ACS580 order, the assistant control panel is automatically added to the delivery.
It can be replaced by one of the other +Jxxx options listed below.
—
Higher enclosure class for cabinet-free installations
even in harsh conditions
Donʼt let dust, moisture or dirt interrupt your processes and drag down productivity.
ACS580 IP55/UL Type 12 units keep your systems running even in tough conditions.
Maintain productivity in
harsh conditions
Compact units for rough environments Be productive, save money and keep it simple
The ACS580 IP55 and UL Type 12 units are an ideal If there's a job assignment to build an outdoor
choice for harsh environments, where impurities, swimming pool, the construction employees need
such as dust or dirt waft in the air. Typical harsh to have the right tools and equipment to be
environments include textile, cement, metal and successful and productive. A shovel and garden
wood processing industries and harsh outdoor hose are obviously not the right choice for
conditions in desert and tropical environments. the job. The same applies to your processes:
Higher protection class ensures smooth in order to perform the job well, you need to
processes by reducing downtime. have the right equipment for it.
These units can be installed directly on the wall If the environment around your processes
closer to the motor, which provides flexibility includes impurities, drives with lesser enclosure
and simplifies installation. The robust, protective ratings are more likely to fail because they are
design ensures that no additional enclosures not designed for harsh environments. A failure
or components, such as dust filters and fans, causes an interruption and instantly cuts down
are needed. productivity and adds costs. Coated control
boards of the ACS580 IP55/UL Type 12 units,
Ordering Description increased use of plastics with smart design,
codes and fully gasketed control panel section that
+B056 IP55/UL Type 12 unit (R1-R9) maintains the IP rating even if the control panel
+F278 Integrated main switch (R1-R5) *) is removed help keep your processes up and
+E223 Integrated C1 filter (R1-R5) *) running in tough environments.
+F316 Integrated main switch and C1 filter (R1-R5 *)
*) Integrated into the R1 and R2, external box for
the R3, R4 and R5.
H I G H E R E N C LO S U R E C L A S S F O R C A B I N E T- F R E E I N S TA L L AT I O N S E V E N I N H A R S H C O N D I T I O N S 29
Installing the drive closer to the motor allows Exploring the root cause is extra work and an
shorter motor cables to be used. Shorter cables open cabinet door instantly decreases safety,
not only cost less and are easier to handle, but exposes all the components to the impurities and
they make it easier to fulfill EMC requirements interrupts your processes. All these costs can be
and reduce the need for additional filters. avoided with cabinet-free installation.
Cost reductions take place also by eliminating Integrated main switch and EMC C1 filter for
the need for a cabinet. IP55/UL Type 12 enclosure further safety improvements and cost reductions
provides protection from dust and jetting water The ACS580 IP55/UL Type 12 units can be ordered
from any direction. Speed-controlled main with an integrated main switch and/or EMC C1
cooling fans maintain optimal drive operating filter (R1-R5). The integrated main switch further
temperatures without a need for external cooling. simplifies the installation and improves safety as
Keeping the drive at optimal temperature it ensures a correct drive is being disconnected
increases the lifetime of the drive. instead of another one. The switch can be
padlocked with three padlocks and in case all
In addition, the IP55/UL Type 12 units reduce padlocks are used, three people need to agree and
maintenance costs compared to cabinet-mounted observe together whether it is safe to connect
drives because of the elimination of air filters. the drive before the drive can be connected.
The cabinet air filters need to be replaced on
a regular basis and if they're not cleaned or taken Having the EMC C1 filter embedded to the drive,
care of properly, the cabinet temperature may there is no need to order, install and test it
rise and cause issues in the process. In these separately. The integrated filter is already tested
situations a maintenance engineer may need to with the drive and it is prewired so there is no
open the cabinet door to identify the root cause. need for additional cabling.
30 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
ACS580-07 cabinet-built drives
Effortless process automation in a ready-made cabinet
For many purposes: The ACS580-07 is ready to control many applications including,
mixers, extruders, compressors, centrifuges, and fans, also installed in
potentially explosive environment.
1 1 B
8 E
6 7 6 A
5 5
3 3
4
2 2
F
Cooling
system
E
1
F F
4
7 6 C
F
A E
8 F
D
Cooling system
—
Commissioning, programming
and customization tools
setup, commissioning and monitoring for all-compatible Parameter setting Networked drives
drives. The free version of the tool provides startup and Point-to-point Control diagrams
connection
maintenance capabilities and gathers all drive information,
Simple monitoring Data logger(s)
such as parameter loggers, faults, backups and lists, into
Supports adaptive Graphical safety
a support diagnostics file. Drive composer pro provides
programming setup
additional features such as custom parameter windows,
Adaptive Adaptive (block)
graphical control diagrams of the driveʼs configuration, programming programming
and improved monitoring and diagnostics. in Demo mode
– Multiple backup and
restore
– Drive configuration by
using virtual drive
Link/MRP codes Description Type designation
new.abb.com/ Link to –
drives/software-tools/ download free
drive-composer Drive composer entry
9AKK105408A3415 Drive composer entry –
PC tool (document)
3AUA0000108087 Drive composer pro DCPT-01
PC tool
(single user license)
3AUA0000145150 Drive composer pro DCPT-01
PC tool
(10 users license)
3AUA0000145151 Drive composer pro DCPT-01
PC tool
(20 users license)
C O M M I S S I O N I N G , P R O G R A M M I N G A N D C U S TO M I Z AT I O N TO O L S 33
a productive way. Combining the tools required for The common engineering tool Automation
Builder is used for drive and PLC
configuring, programming, debugging and maintaining programming and configuration.
automation projects in a common, intuitive interface, Automation Builder is available in Basic,
Automation Builder addresses the largest single cost Standard and Premium editions, fitting the
element of most of todayʼs industrial automation needs of small projects and managing the
challenges of many and large projects for
projects: software. OEM and system integrators.
Adaptive programming
Adaptive programming
Adaptive programming software, embedded inside
the drive, is especially handy when there is a need to
distribute some of the machine’s control logic to the drive.
Adaptive programming brings energy savings when the
drive is adjusted to control the application optimally. You
can use our Drive composer PC tool to set up the adaptive
programming. The drive also offers sequence programming
capabilities. Adaptive programming makes it possible to
enhance the existing application control program to
precisely fit users’ application needs. The program is also
handy for ensuring that the drive’s electrical design is
connected as it should be with working drive signals.
—
Communication and connectivity
Fast and reliable communication
The F-series fieldbus adapter modules are flexible, plug-in • Reduces mechanical and electrical cost
adapters that provide fast and simple universal connectivity • Decrease in downtime
to all major controllers. Universal connectivity means ABB • Increase in productivity
low voltage drives connect to automation controllers and • Diminished start-up costs
communication networks, allowing users to choose the • Lower maintenance and diagnostic costs
best network to meet their needs. • Quick access to networked drives with PC-based
start-up and maintenance software tools
• Reductions in wiring costs compared to traditional
I/O connections
—
Industrial automation plant – different network possibilities and their secure deployment
Trusted network
My ABB NETA-21 Untrusted network
customer webpage Connection between devices
portal access
Remote desktop connection
(Drive composer)
Remote access 6
Local PC
either through own Gateway
connection or via mode
NETA-21
plant access
HTTPS
Automation 3 PLC 5
builder and NETA-21 Local PC Local PC
Drive Manager
Drive Composer
(or MODBUS/TCP
4
master) 2
Local PC
Drive IEC
programming
using Automation
Builder
1
USB
Local PC / Drive
Composer
—
Communication and connectivity
Options
Fieldbus options
Plus code MRP code Fieldbus protocol Adapter
+K451 68469341 DeviceNet™ FDNA-01
+K454 68469325 PROFIBUS DP. DPV0/DPV1 FPBA-01
+K457 68469376 CANopen® FCAN-01
+K458 3AUA0000031336 Modbus RTU FSCA-01
+K462 3AUA0000094512 ControlNet FCNA-01
+K469 3AUA0000072069 EtherCAT® FECA-01
+K470 3AUA0000072120 POWERLINK FEPL-02
+K490 3AXD50000192786 Two port Ethernet/IP FEIP-21
+K491 3AXD50000049964 Two port Modbus/TCP FMBT-21
+K492 3AXD50000192779 Two port PROFINET IO FPNO-21
+Q986 3AXD50000112821 Safety functions fieldbus Profisafe module FSPS-21
— —
CMOD-01 CMOD-02
— — —
CHDI-01 CPTC-02 CBAI-01
Options
Plus code MRP code Description Type designation
+L501 3AXD50000004420 External 24 V AC and DC 2 x RO and 1 x DO CMOD-01
+L523 3AXD50000004418 External 24 V and isolated PTC interface CMOD-02
+L512 3AXD50000004431 115/230 V digital input 6 x DI and 2 x RO CHDI-01
+L537 3AXD50000033578 ATEX-certified PTC interface, Ex II (2) GD and external 24 V *) CPTC-02
+L500 3AXD50000137954 Bipolar analog I/O adapter module **) CBAI-01
* For further information please see pages 44-45.
)
—
Safety options
PROFIsafe safety functions module FSPS-21 Safe stop 1, time controlled (SS1-t)
The FSPS-21 module has integrated PROFIsafe, safety
functions and PROFINET IO connection. The ready-made STO activated
|n|
safety functions make safety configuration in the drive
unnecessary. The module supports STO and SS1-t safety
functions. It is used together with a safety PLC that 0
Time limit t
supports PROFIsafe over PROFINET communication. Function
requested
For more information see FSPS-21 PROFIsafe safety Safe stop 1 stops the motor safely with a controlled ramp
functions module web page at new.abb.com/drives/ stop and stop time monitoring. SS1-t initiates the ramp stop
functional-safety from the drive and activates STO when speed reaches zero.
If the drive is not decelerating to zero speed within the time
limit, the STO function is activated. SS1-t is typically used in
applications where motion must be stopped quickly and
safely before switching to a no-torque state.
—
Example: SS1-t
Safety function module FSPS-21, functionality cycle
1
ABB drive *) Start ABB drive *) Start
Speed
RUN RUN
STO STO
M M
Reset Reset
Time 1 Time
2. SS1-t, safety functions request / start of monitoring 3. Transition and time monitoring of the SS1-t
Speed
2 3 3
RUN
RAMP STOP
STO STO
M M
Reset Reset
2 Time 3 Time
4. Zero speed or SS1-t time limit reached / STO is opened 5. Safe state / STO is open
Speed
STOP STOP
4 STO 5 STO
M
Reset
M
Reset
Time 4 Time 5
6. Safety function request removed / reset / STO is closed 7. Start – return to normal operation
I 6
ABB drive *) Start 7 ABB drive *) Start
Speed
STOP RUN
II 6
6 STO STO
M M
Reset
Time 6
Time
Reset
—
ABB Ability™ Condition Monitoring for drives
Condition Monitoring gives you fact-based insight into your drives, via KPIs and
signal data, to keep your processes moving smoothly. Remote monitoring of your
drives lets you identify irregularities before they become problems. This helps you
make proactive decisions, built on real-time information – and saves you money!
Solid fact-based decision making Find the root cause of process issues
Get the facts, and the history, to help run Remotely access data from ABB drives built-in
your operations better and more safely. sensors to track the cause of problems. Get back
to smooth operation quickly with data back-ups.
Always stay one step ahead of problems Remotely analyze and optimize drives
Recognize early signs of possible failures Get critical drive information anywhere anytime
and assess the risks, before they turn into – even in difficult to access sites, or when a site
serious operational issues. visit is impossible.
—
Tailor your drive monitoring to perfectly fit your needs
Our standard package gives you industry leading Optional services include digitally enabled remote
monitoring capabilities to fit your needs – whether you want assistance by ABB technical support, advanced analytics
to view the drive status through ABB’s internet portal or and reporting, and a range of other features to make your
integrate this data with your existing monitoring systems. maintenance operations more effective.
Get these benefits from the standard package of And select from these options,
ABB Ability™ Condition Monitoring for drives based on your situation
• Condition Monitoring – Continuously monitor your Powertrain Monitoring – Combine Condition Monitoring
drive performance remotely through ABB portal, for drives with our Smart Sensors for motors and
without need for on-site presence, or through your bearings, to monitor your complete powertrain
own monitoring system using data transfer via
Condition-Based Maintenance – Assess the risk profiles
Cloud Interface
of your drives to do efficient, proactive maintenance,
• Alarm Management – Create flexible alerts and based on condition rather than routines
warning notifications, and have them sent to the
Offline Data Collection – Upload and analyze data
right people for rapid action
from your drives without using on-line connectivity
• Asset Health – Generate professional maintenance to the internet
reports, tailored to your needs, about the state of
Expert Reports – Get our drive professionals to review
your drives
your data and advise on maintenance planning, with our
• Team Support – Wherever you are, you can access ABB Expert Report service option
and analyze drive signal data and information, and
Remote Assistance – Connect to ABB’s helpdesk, to get
then provide valuable support to your team
expert support and problem solving, with full visibility of
• Backup Management – Back up and safely protect your drives online
your drive parameters
A B B A B I L I T Y ™ C O N D I T I O N M O N I TO R I N G F O R D R I V E S 39
—
Make decisions based on accurate, real-time information
—
The connectivity devices that enable
remote viewing and monitoring
NETA-21
NETA-21 connects the drive to the cloud via the Internet
or local Ethernet network.
• The module comes with a built-in web server and
requires no Flash/Java plugins
• In the absence of a customer local area network,
it can be connected via a mobile network router
(either Ethernet or USB network adapter)
—
• One module can be connected to several drives Monitor your drives condition from anywhere at anytime
and identify potential problems before they occur
at the same time
40 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
EMC – electromagnetic compatibility
What is EMC? —
Immunity and emission compatibility
EMC stands for electromagnetic compatibility. It is the
ability of electrical/electronic equipment to operate without
Disturbance level
problems in an electromagnetic environment. Immunity level
Immunity limit
Likewise, the equipment must not disturb or interfere with
any other product or system in its locality. This is a legal Compatibility
requirement for all equipment taken into service within margin
Installation environments
Independent variable e.g. frequency
A power drive system (PDS) can be connected to
either industrial or public power distribution networks.
The environment class depends on the way the PDS is
connected to power supply. —
Installation environments
—
The product standard EN 61800-3 divides PDSs into four categories according to the intended use
—
Every ACS580 drive is equipped EMC product standard (EN 61800-3) category C2 is
fulfilled in wall-mounted drives and in cabinet-built
with a built-in filter to reduce drives up to frame size R9. Category C3 is fulfilled in
high-frequency emissions. drive modules and cabinet-built drives (frames R10
and R11) with no external filters.
—
Harmonic mitigation
—
Where do the harmonics come from?
Converter
—
The effects of harmonic distortions
Mainly affect the power distribution system up to the rectifier: Can affect other equipment connected to the electrical system:
• Additional losses in wires and cables • Erratic operation of telecommunication systems, computers, video
• Extra heating of transformers monitors, electronic test equipment, etc.
• Circuit breaker malfunctioning • Resonance with power factor correction capacitors
H A R M O N I C M I T I G AT I O N 43
—
ACS580 drives are compliant with EN 61000-3-12. They are equipped with:
• optimized DC choke (R1-R9)
• AC chokes (R10-R11)
—
Drive system features affecting harmonics
Medium voltage
grid Harmonics reduction can be achieved either
by structural modifications in the drive system
or by using external filtering. The structural
modifications may be to strengthen the
supply, or to use 12 or more pulse drives,
Short circuit power MVA to use a controlled rectifier, or to improve
the internal filtering in the drive.
Transformer MVA The image to the left shows the factors in the
Rated power
AC drive system that have some influence
and impedance % on harmonics. The current harmonics
depend on the drive construction, and
the voltage harmonics are the current
harmonics multiplied by the supply
impedances.
6-pulse
Type of rectifier
Diode/thyristor
Inverter
Type of inverter PWM, VSI
kW
Load Motor Rated power and load
%
44 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
For explosive atmospheres
ATEX certified
ATEX provides similar guidelines to the IECEx System, Zones 2 (for gas) and
22 (for dust), where
with a few exceptions, and with certification of protective
potentially explosive
devices (e.g. drive-integrated safety functions). Zone 2 (gas) atmospheres can
/ 22 (dust) occur by accident,
not during normal
operation.
—
Cooling and fuses
Cooling
ACS580 drives are fitted with variable-speed cooling air fans. The cooling air must be free from corrosive
materials and not exceed the maximum ambient temperature of 40 °C for frames R1 to R9 (50 °C with derating).
The speed-controlled fans cool the drive only when needed, which reduces overall noise level and
energy consumption.
Fuse connections
Standard fuses can be used with ABB general purpose drives. For input fuses, see the table below.
—
Circuit breakers
ACS580-01
Type Frame Aux. Miniature Tmax moulded case circuit breaker Switch-disconnector Main
designation size Contr. circuit Main Main contactor
ACS580-01- Volt.: breaker Switch Switch UL (≤40 °C)
ABB type ABB type ABB type ABB type ABB type
3-phase, U N = 400 or 480 V (380…415 V. 440…480 V)
02A7-4 R1 230/115 S 203P-B/C/Z 10 – OT16F3 OT16F3 AF09-30-22-13
03A4-4 R1 230/115 S 203P-B/C/Z 10 – OT16F3 OT16F3 AF09-30-22-13
04A1-4 R1 230/115 S 203P-B/C/Z 10 – OT16F3 OT16F3 AF09-30-22-13
05A7-4 R1 230/115 S 203P-B/C/Z 10 – OT16F3 OT16F3 AF09-30-22-13
07A3-4 R1 230/115 S 203P-B/C/Z 10 – OT16F3 OT16F3 AF09-30-22-13
09A5-4 R1 230/115 S 203P-B/C/Z 10 – OT16F3 OT16F3 AF09-30-22-13
12A7-4 R1 230/115 S 203P-B/C/Z 16 – OT16F3 OT16F3 AF09-30-22-13
018A-4 R2 230/115 S 203P-B/C/Z 20 – OT25F3 OT25F3 AF09-30-22-13
026A-4 R2 230/115 S 203P-B/C/Z 25 – OT25F3 OT25F3 AF12-30-22-13
033A-4 R3 230/115 S 203P-B/C/Z 32 – OT63F3 OT63F3 AF26-30-22-13
039A-4 R3 230/115 S 203P-B/C/Z 40 – OT63F3 OT63F3 AF52-30-22-13
046A-4 R3 230/115 S 203P-B/C/Z 50 – OT63F3 OT63F3 AF52-30-22-13
062A-4 R4 230/115 S 803 S-B/C 75 – OT100F OT100F AF52-30-22-13
073A-4 R4 230/115 – 1SDA067918R1 Prospective SC current 65kA OT100F OT100F AF52-30-22-13
088A-4 R5 230/115 – 1SDA067918R1 Prospective SC current 65kA OT160EV OT200U AF65-30-22-13
106A-4 R5 230/115 – 1SDA068555R1 Prospective SC current 65kA OT160EV OT200U AF146-30-22-13
145A-4 R6 230/115 – 1SDA068555R1 Prospective SC current 65kA OT160EV OT200U AF146-30-22-13
169A-4 R7 230/115 – 1SDA068555R1 Prospective SC current 65kA OT250E OT400U AF146-30-22-13
206A-4 R7 230/115 – 1SDA054141R1 Prospective SC current 65kA OT250E OT400U AF146-30-22-13
246A-4 R8 230/115 – 1SDA054365R1 Prospective SC current 65kA OT400E OT400U AF265-30-22-13
293A-4 R8 230/115 – 1SDA054420R1 Prospective SC current 65kA OT400E OT400U AF265-30-22-13
363A-4 R9 230/115 – 1SDA054420R1 Prospective SC current 65kA OT630E OT600U AF400-30-22-70
430A-4 R9 230/115 – 1SDA054420R1 Prospective SC current 65kA OT630E OT600U AF400-30-22-70
ACS580-04
Type Frame Aux. Miniature Tmax moulded case circuit breaker Switch-disconnector Main
designation size Contr. circuit Main Main contactor
ACS580-04- Volt.: breaker Switch Switch UL (≤40 °C)
ABB type ABB type ABB type ABB type ABB type
U N = 380…480 V (380, 400, 415 V)
505A-4 R10 230/115 – 1SDA054412R1 (T5H 630 PR221DS-LS/I I n = 630 3p F F) OT630E OT600U –
585A-4 R10 230/115 – 1SDA069428R1 (T6V 800 PR221DS-LS/I I n = 800 3p F F) OT630E OT600U –
650A-4 R10 230/115 – 1SDA069428R1 (T6V 800 PR221DS-LS/I I n = 800 3p F F) OT800E OT800U –
725A-4 R11 230/115 – 1SDA062770R1 (T7H 1000 PR231/P LS/I In = 1000A 3p F F) OT800E OT800U –
820A-4 R11 230/115 – 1SDA062770R1 (T7H 1000 PR231/P LS/I In = 1000A 3p F F) OT1000E OT1200U –
880A-4 R11 230/115 – 1SDA062770R1 (T7H 1000 PR231/P LS/I In = 1000A 3p F F) OT1000E OT1200U –
A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G 49
—
du/dt filters
du/dt filtering suppresses inverter output voltage spikes and rapid voltage changes that stress
motor insulation. Additionally, du/dt filtering reduces capacitive leakage currents and high-frequency
emissions from the motor cable as well as high-frequency losses and bearing currents in the motor.
The need for du/dt filtering depends on the motor insulation. For information on the construction
of the motor insulation, consult the manufacturer. More information on the du/dt filters can be
found in the ACS580 hardware manual.
External du/dt filter for ACS580-01 and ACS580-04 External du/dt filters for ACS580-07
du/dt filter type du/dt filter type
* 3 filters included, dimensions apply to one filter. * 3 filters included, dimensions
Unprotected Protected Protected apply to one filter.
(IP00) to IP22 to IP54 Protected
to IP54
NOCH0120-60*
BOCH-0880A-7
BOCH-0880A-7
NOCH0030-60
NOCH0070-60
NOCH0030-62
NOCH0030-65
NOCH0070-62
NOCH0070-65
NOCH0016-60
NOCH0016-62
NOCH0016-65
NOCH0120-62
NOCH0120-65
FOCH0320-50
FOCH0260-70
FOCH0610-70
FOCH0875-70
COF-02
COF-01
ACS580 ACS580
400 V 400 V
ACS580 - 01- 02A7- 4 ACS580 - 07- 0145A-4
ACS580-01-03A4-4 ACS580 - 07- 0169A-4
ACS580-01-04A1-4 ACS580 -07-0206A-4
ACS580 - 01- 05A7- 4 ACS580 -07-0246A-4
ACS580-01-07A3-4 ACS580 - 07- 0293A-4
ACS580-01-09A5-4 ACS580 - 07- 0363A-4
ACS580 - 01-12 A7- 4 ACS580-07-0430A-4
ACS580-01-018A-4 ACS580 -07-0505A-4
ACS580-01-026A-4 ACS580 -07-0585A-4
ACS580-01-033A-4 ACS580 -07-0650A-4
ACS580-01-039A-4 ACS580 - 07- 0725A-4
ACS580-01-046A-4 ACS580 -07-0820A-4
ACS580-01-062A-4 ACS580-07-0880A-4
ACS580-01-073A-4
ACS580-01-088A-4
Dimensions and weights of the du/dt filters
ACS580 - 01-106A- 4
du/dt filter Height Width Depth Weight
ACS580 - 01-145A- 4 (mm) (mm) (mm) (kg)
ACS580 - 01-169A- 4 NOCH0016-60 195 140 115 2.4
ACS580-01-206A-4 NOCH0016-62/65 323 199 154 6
ACS580-01-246A-4 NOCH0030-60 215 165 130 4.7
ACS580-01-293A-4 NOCH0030-62/65 348 249 172 9
ACS580-01-363A- 4 NOCH0070-60 261 180 150 9.5
ACS580-01-430A-4 NOCH0070-62/65 433 279 202 15.5
ACS580-04-505A-4 NOCH0120-60 3) 200 154 106 7
ACS580-04-585A-4 NOCH0120-62/65 765 308 256 45
ACS580-04-650A-4 FOCH0260-70 382 340 254 47
ACS580-04-725A-4 FOCH0320-50 662 319 293 65
ACS580-04-820A-4 FOCH0610-70 662 319 293 65
ACS580-04-880A-4 FOCH0875-70 662 319 293 65
BOCH-0880A-7 400 248 456 18
COF-01 570 296 360 23
COF-02 570 360 301 23
50 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Sine filters
Sine filters are low-pass filters that suppress the high frequency components of the drive output.
A sine filter consists of single- or three-phase reactors and delta- or star-connected capacitors.
The sine filter provides true sinusoidal voltage waveform at the drive output by suppressing the
high frequency voltage components of the drive output. Suppression of the high frequency voltage
components is needed when extra-long motor cables are used, there is a step-up transformer
between the drive and a motor, or when a drive is installed with an old direct-on-line motor.
—
ACS580 drives are compatible with
the wide ABB product offering
—
ABB Ability™ smartphone apps
Easy and fast access to product information Search for support documents and contacts
and support
Start up, commission and tune Instantly access drive status and Access your product and service View your drives installed base and
your drive and application configuration with a information in the cloud plan service activities
simplified user guidance from anywhere
Optimize performance via drive Create and share backups and Use dynamic QR code to Report service events
troubleshooting features support packages troubleshoot your drive
Drivetune for commissioning and managing drives Drivebase for ensured reliability and reduced downtime on production sites
53
54 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
We keep your world turning
Whatever your needs are, we offer the most extensive
service offering for drives, motors and generators from
spare parts and technical support to cloud-based condition
monitoring solutions to keep your equipment running.
When you’ve decided on the right product, ABB and its global network of Value End-of-life services
Providers can help with installation and commissioning. They are also on hand Responsible dismantling,
recycling and reusing of
to support you throughout the operation and maintenance phases of the products products, according to local
life cycle, providing maintenance programs tailored to your facility’s needs. laws and industrial standards.
ABB will ensure you are aware of any service opportunities. If you’ve registered
your drives and motors with ABB, then its engineers will proactively contact you
advising on your most effective service options. All of which helps maximize
performance, uptime and efficiency throughout the lifetime of your powertrain.
Maintenance
Systematic and organized
maintenance and support over
the life cycle of your assets.
W E K E E P YO U R W O R L D T U R N I N G 55
Extensions, upgrades
& retrofits
Up-to-date systems and devices
Advanced services with the best possible
Gain the unique ABB Ability™ performance level.
digital advantage through data
collection and analytics with
advanced services.
Engineering & consulting
Ways to identify and improve the
reliability, usability, maintainability
and safety of your production
processes.
—
“I need operational excellence,
rapid response, improved
performance and life cycle Technical support & repairs
management.” Quick and accurate response
during emergencies and efficient
support during planned
production breaks.
Installation &
commissioning
Highly-trained and reliable
installation and commissioning
experts at your service.
Training
Comprehensive and
professional training either at
Agreements ABB premises or your own.
Comprehensive bundling of
relevant services into one
contract to suit your needs.
56 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
A lifetime of peak performance
Full range of life cycle services and support Limited range of life cycle Replacement and
services and support end-of-life services
Full range of life cycle Full range of life cycle Limited range of life Replacement and
services is available. services is available. cycle services is end-of-life services
Services
—
Ordering information
How do I build an ordering code?
ACS580-01 Segment A D E F
ACS580 - 01 - 12A7 - 4 + Option codes
Basic codes
Segment Option Description
A Construction 01 = When no options are selected: Wall mounted, IP21 (UL Type 1),
assistant control panel with a USB port, choke, EMC C2 filter (internal EMC filter),
safe torque off, braking chopper in frames R1, R2, R3, coated boards,
cable lead through entry from the bottom, cable box or the conduit plate with
cable entries, quick installation and start-up guide multilingual)
D Current rating Refer to the rating table
E Voltage rating 4 = 400/480 V (380…480 V)
Option codes
Segment Option Code Description
F Control panel and panel +J400 ACS-AP-S Assistant control panel (as standard)
options +J425 ACS-AP-I Assistant control panel
+J429 ACS-AP-W Assistant control panel with a Bluetooth interface
+J404 ACS-BP-S Basic control panel
+J424 CDUM-01 Blank control panel cover (no control panel)
I/O (one slot available +L501 CMOD-01 External 24 V AC/DC and digital I/O extension (2×RO and 1×DO)
for I/O options) +L523 CMOD-02 External 24 V AC/DC and isolated PTC interface
+L537 CPTC-02 ATEX-certified PTC interface, Ex II (2) GD and external 24 V. Requires also option +Q971.
+L512 CHDI-01 115/230 V Digital input extension (6×DI and 2×RO)
+L500 CBAI-01 Bipolar analog I/O adapter module
Safety +Q971 ATEX-certified Safe Disconnection Function, Ex II (2) GD. Sold only with option +L537.
Fieldbus +K451 FDNA-01 DeviceNet™
+K454 FPBA-01 PROFIBUS DP
+K457 FCAN-01 CANopen
+K458 FSCA-01 Modbus/RTU
+K462 FCNA-01 ControlNet
+K469 FECA-01 EtherCAT
+K470 FEPL-02 Ethernet POWERLINK
+K490 Two port FEIP-21 EtherNet/IP™
+K491 Two port FMBT-21 Modbus TCP
+K492 Two port FPNO-21 PROFINET IO
+Q986 Safety functions fieldbus module FSPS-21
Embedded fieldbus +CEIA-01 Embedded Modbus RTU adapter
+EIA-485 (as standard)
IP enclosure +B056 IP55 (UL type 12). Factory option, retrofit not possible.
Constructon +C135 Flange mounting kit. (Only available for 400V IP21 drives)
+H358 Cable conduit plate, blank
Complementary options +P931 Extended warranty up to 36 months
+P932 Extended warranty up to 60 months
+P952 European Union Country of origin
58 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Ordering information
How do I build an ordering code?
ACS580-04 Segment A D E F
ACS580 - 04 - 505A - 4 + Option codes
Basic codes
Segment Option Description
A Construction 04 = Drive with coated circuit boards, integrated control unit (inside drive module), control panel door
mounting kit, embedded Modbus RTU adapter, EIA-485 (standard), assistant control panel with USB-port,
quick guides with default set of languages, web links to basic PC tool and manuals in quick guide
D Current rating Refer to the rating table
E Voltage rating 4 = 380…480 V
Option codes
Segment Option Code Description
F Control panel and panel +J400 Assistant control panel (standard) / ACS-AP-S (+J400 is included in the standard delivery)
options
+J425 Assistant control panel /ACS-AP-I (+J425 and +J404 replaces +J400 / ACS-AP-S)
+J404 Basic control panel / ACS-BP-S (+J425 and +J404 replaces +J400 / ACS-AP-S)
+0J427 No control panel holder and no control panel
(3AXD50000016230 = Control panel mounting platform / DPMP-03)
I/O (one slot available +L500 CBAI-01 Bipolar analog I/O adapter module
for I/O options)
(L501, L523 and L512 +L501 External 24 V DC/AC and Digital I/O extension (2xRO and 1xDO) / CMOD-01
available as retrofit +L512 115/230V Digital input (6xDI and 2xRO) / CHDI-01
options)
+L523 External 24 V and isolated PTC interface / CMOD-02
+L537 ATEX-certified PTC interface, Ex II (2) GD and external 24 V / CPTC-02. Requires also +Q971 option.
Safety +Q971 ATEX-certified Safe Disconnection Function, Ex II (2) GD / CPTC-02 (+Q971
option sold only together with +L537 option)
Fieldbus +K451 FDNA-01 DeviceNet™
(One fieldbus adapter
+K454 FPBA-01 PROFIBUS DP
supported.
Fieldbus adapters +K457 FCAN-01 CANopen
available as loose +K458 FSCA-01 Modbus/RTU
options for retrofit.)
+K462 FCNA-01 ControlNet
+K469 FECA-01 EtherCAT
+K470 FEPL-02 Ethernet POWERLINK
+K490 Two port FEIP-21 EtherNet/IPTM
+K491 Two port FMBT-21 Modbus TCP
+K492 Two port FPNO-21 PROFINET IO
+Q986 Safety functions fieldbus module FSPS-21
IP enclosure +B051 IP20 Finger safe
Construction +J410 Control panel door mounting kit (+J410 Includes DPMP-03)
+H370 Full-size input terminals
+P906 Remote control board
+0H371 No full size output terminals
+0H534 No pedestal
+0P919 No cabinet installation ramp
Filters +E210 EMC/RFI-filter, C3, 2nd Environment, Unrestricted (Earthed & Unearthed Networks)
+E208 Common mode filter
Complementary +P931 Extended warranty up to 36 months
options
+P932 Extended warranty up to 60 months
+P952 European Union Country of origin
O R D E R I N G I N F O R M AT I O N 59
ACS580-07 Segment A D E F
ACS580 - 07 - 145A - 4 + Option codes
Basic codes
Segment Option Description
A Construction 07 = Cabinet-built, IP21, Main switch and aR fuses, Assistant control panel (ACS-AP-S), EMC filter C2 (R6-R9)/
C3 (R10-R11), Common mode filter (R10-R11), ACS580 standard control program, Safe torque-off, Boards with coating,
Bottom entry and exit of cables, Cable lead through entry, One set of default electric documents in USB stick
D Current rating Refer to the rating table
E Voltage rating 4 = 380…480 V
Option codes
Segment Option Code Description
F Control panel and panel options +J429 ACS-AP-W Assistant control panel with Bluetooth interface
I/O (one slot available for I/O +L500 CBAI-01 Bipolar analog I/O adapter module
options) +L501 External 24 V DC/AC and Digital I/O extension (2xRO and 1xDO)
+L504 Additional I/O-Terminal Block
+L512 115/230V Digital input (6xDI and 2xRO)
+L523 External 24 V and isolated PTC interface
+L537 ATEX-certified thermistor protection module, Ex II (2) GD
(requires ATEX-certified Safe Disconnection Function, Ex II (2) GD, add +Q971 to code)
Safety +Q971 ATEX-certified Safe Disconnection Function, Ex II (2) GD
(+Q971 option sold only together with +L537 option. Not available with +Q951)
+Q951 Safety option of emergency stop where Main breaker is opened during emergency
+Q963 Safety option of emergency stop where main breaker is not opened during emergency
Fieldbus +K451 FDNA-01 DeviceNet™
(One fieldbus adapter +K454 FPBA-01 PROFIBUS DP
supported.
+K457 FCAN-01 CANopen
Note:
Embedded fieldbus interface +K458 FSCA-01 Modbus/RTU
can't be used at the same time +K462 FCNA-01 ControlNet
with fieldbus adapter. +K469 FECA-01 EtherCAT
Fieldbus adapters available as +K470 FEPL-02 Ethernet POWERLINK
loose options for retrofit.)
+K490 Two port FEIP-21 EtherNet/IPTM
+K491 Two port FMBT-21 Modbus TCP
+K492 Two port FPNO-21 PROFINET IO
+Q986 Safety functions fieldbus module FSPS-21
ABB Ability™ Condion +K496 NETA-21 Wired remote monitoring system (Not released)
Monitoring for drives +K497 K496 option with Wireless modem for wireless connectivity(Not released)
IP enclusre +B054 IP42 enclosure class(Type 1 in case of UL certification)
+B055 IP54 enclosure class(Type 12 in case of UL certification)
Construction +C129 Cabinet drive is UL listed
+C180 (not released yet)
Enhanced stiffness for cabinet according to International building code 2012.
Filters +F250 Line contactor
+F289 Main case circuit breaker (UL listed, requires C129 option)
Cabling +H351 Top entry (additional channel for frames R6-R9, +125 mm the drive cabinet width)
Top entry through roof (frames R10-R11)
+H353 Top exit (additional channel for frames R6-R9, +125mm the drive cabinet width)
Top exit (frames R10-R11) – additional 150 mm channel
+H358 Cable conduit entry (Default in US, anywhere else specify in order)
+C164 Plinth 100 mm (separate in package)
+C179 Plinth 200 mm (separate in package)
Cabinet options +G300 Cabinet heater (External supply)
+G327 Ready Pilot light, white
+G328 Run Pilot light, green
+G329 Fault Pilot light, red
Starter for auxiliary motor fan +M600 1…1.6 A; 1PC-s, dimensioned by fan size, Includes protective devices
+M601 1.6…2.5 A; 1PC-s, dimensioned by fan size, Includes protective devices
+M602 2.5…4 A; 1PC-s, dimensioned by fan size, Includes protective devices
+M603 4…6.3 A; 1PC-s, dimensioned by fan size, Includes protective devices
+M604 6.3…10 A;1PC-s, dimensioned by fan size, Includes protective devices
+M605 10…16 A;1PC-s, dimensioned by fan size, Includes protective devices
Complementary options +P931 Extended warranty up to 36 months
+P932 Extended warranty up to 60 months
60 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
61
—
Notes
62 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G
—
Notes
Additional information
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not
accept any responsibility whatsoever for
potential errors or possible lack of infor-
mation in this document.
new.abb.com/drives/ACS580
new.abb.com/drives
new.abb.com/drives/drivespartners
new.abb.com/motors-generators
Online manuals
for the ACS580 drives
Video playlist:
ACS580 how-to videos
3AUA0000145061 REV L EN 9.10.2020