Cooling Tower Calculations
Cooling Tower Calculations
Cooling Tower Calculations
1 in a District
Cooling Plant and enters a cooling tower at 41°C. The water is cooled to 35°C in the
cooling tower by air that enters the tower at DB/WB =35/32.2°C and leaves at
DB/WB=40/39.7°C. determine (a) the condenser water flow rate (b) the volume flow
rate of air into the cooling tower in cfm and (c) the mass flow rate of the required
makeup water. (d) L/G ratio for the cooling tower
Solution:
Assumptions:
Cooling Load in kW
COP =
Work input in kW
12,619.82 𝑘𝑊
𝐻𝑒𝑎𝑡𝑜𝑢𝑡 = m∙w 𝐶𝑝 ∆𝑡 → m∙w =
4.18 𝑘𝐽/𝑘𝑔. °𝐶 × (41 − 35)℃
𝑚3∙ = 𝑚𝑤
∙ = 503.18 kg/s = 7,976 USgpm
(b)
𝑚̇ 3 (ℎ3 − ℎ4 ) 𝑚̇ 3 𝐶𝑝 (𝑇3 − 𝑇4 )
𝑚̇ 𝑎 = → 𝑚̇ 𝑎 =
(ℎ2 − ℎ1 ) − (𝜔2 − 𝜔1 ) ℎ4 (ℎ2 − ℎ1 ) − (𝜔2 − 𝜔1 ) 𝐶𝑝 𝑇4
0.914 + 0.954 3
𝑚𝑎∙ = 256.23 𝑘𝑔/𝑠 × 𝑚 /𝑘𝑔 = 239.3188 𝑚3 /𝑠
2
507,093 𝑐𝑓𝑚
𝑚𝑎∙ = 507,093 𝑐𝑓𝑚 → 𝑚𝑎∙ /𝑇𝑅 = → 𝑚𝑎∙ = 𝟏𝟔𝟗 𝒄𝒇𝒎/𝑻𝑹
3000 𝑇𝑅
(c)
The mass flow rate of the required makeup water is determined from:
The above reveals that make up water flow rate in the cooling tower is
approximately 0.92% of the condenser water flow.
(d)
∙
𝐿 𝑚𝑤 503.18
= ∙ = = 1.96
𝐺 𝑚𝑎 256.23