34 Samss 821
34 Samss 821
34 Samss 821
1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 General Requirements................................... 3
5 Design............................................................ 5
6 Nameplates.................................................... 6
7 Piping............................................................. 7
8 Documentation……………………………….... 9
9 Testing………………………………….…...... 10
10 Shipping………………………………….…… 10
1 Scope
This specification defines the minimum requirements for instrument control panels and
cabinets for location in outdoor areas.
Excluded from this specification are control panels provided in packaged equipment
and field instrument junction boxes and RTU Cabinets except as referenced in 23-
SAMSS-030.
2.1 Any conflicts between this specification and other applicable Saudi Aramco
Materials System Specifications (SAMSSs), Engineering Standards (SAESs),
Standard Drawings (SASDs), or Industry Standards, Codes, and Forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Process & Control Systems Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this specification in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Process & Control Systems
Department of Saudi Aramco, Dhahran.
3 References
Material or equipment supplied to this specification shall comply with the latest edition
of the references listed below, unless otherwise noted.
Page 2 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
4 General Requirements
4.1 Environmental
Page 3 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
Temperature:
Notes:
1) "Sheltered" refers to permanent, ventilated enclosures or buildings, or permanently
fixed sunshades with a top and three sides.
2) For semiconductors and any other instrumentation devices which dissipate internal
heat, an additional 15°C shall be added to the above temperatures. An example,
for "Outdoor Sheltered" installation, the equipment must perform at 55 + 15 = 70°C.
Similarly, for the "outdoor unsheltered" case, the equipment shall be designed for a
maximum operating temperature of 65 + 15 = 80°C.
3) The designer can take credit for forced or passive cooling to eliminate or reduce the
15°C heat rise. For example, if vortex coolers are used, the heat removal capacity
of the coolers may be subtracted from the generated heat. No more than 15°C
reduction in temperature will be given as credit. The designer shall substantiate his
claim by providing the support data and calculations. In addition, the use of cabinet
air conditioner that is suitable for the area classification may be explored depending
on the applications.
For offshore and nearshore (within one kilometer from the shoreline of the
Arabian Gulf and within three kilometers from the shoreline of the Red Sea), the
cabinet and its integral parts shall be protected against corrosion and operational
failure due to wind-borne sea water spray and the accumulation of wetted salt
(NaCl).
Page 4 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
Other pollutants present in the atmosphere under the most extreme conditions are:
H2S 20 ppm (vol/vol)
Hydrocarbon 150 ppm (vol/vol)
SO2 10 ppm (vol/vol)
CO 100 ppm (vol/vol)
NOx 5 ppm (vol/vol)
O3 1 ppm (vol/vol)
5 Design
5.1 Enclosures
5.1.1 In outdoor plant areas, the panel/cabinet shall be NEMA 250 / NEMA
ICS 6 Type 4 or IEC 60529, Type IP65.
5.1.2 In outdoor plant and other industrial areas located in severe corrosive
environments as defined in Paragraph 4.2, enclosures shall be NEMA
Type 4X or IEC 60529 Type IP66, manufactured of 316L stainless steel.
Galvanized and/or painted or coated carbon steel sheet metal enclosures
are not permitted.
Commentary Note:
5.2 Electrical
The panel/cabinet and all components within the panel shall be suitable
for the electrical area classification where the panel will be installed.
Page 5 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
The classification of the area in which the panel will be used, shall be
specified in the Purchase Order.
5.2.3 Relays
Pushbuttons, pilot lights and switches shall be heavy duty, oil-tight, and
shall meet the area classification of the installed location. Shutdown and
other critical pushbuttons shall have protective guards to prevent
accidental actuation. Lamp test function shall be provided for all
indicating lights.
For control panels, the Vendor shall arrange all instruments on the panel
front so that they are readable and operable by the operators in standing
position. The vendor shall also minimize the effects of glare from
sunlight and/or artificial lighting.
The noise level from the panel shall not exceed 85 dB at 3 meters.
Page 6 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
6 Nameplates
Nameplates shall be attached to the cabinets using stainless steel screws. The nameplate
shall be made of corrosion resistant material. The lettering shall be clearly legible.
Internal nameplates (within the cabinet) shall also be installed using stainless steel screws.
Using adhesive nameplates is not acceptable.
7 Piping
No process piping of any kind shall be allowed in a control cabinet. The only fluid
allowed is instrument air.
7.1.2 Pneumatic piping which does not have a pressure indication on the
instruments it connects shall be provided with a plugged tee for testing.
7.1.4 All open fittings and bulkhead connections shall be plugged or capped
during transportation.
7.2.1 Air headers shall be sized for the capacity of all instruments plus 20%
spare for future additions.
7.2.3 Stainless steel take-off nipples shall be provided at the top of the air
header for connection of the instruments. Each take-off nipple shall have
a ¼-inch isolating valve with a tag for connected instrument
identification. The isolating valve shall be rated at 3000 psi, stainless
steel construction, with ¼" female NPT connections. Packing type
valves shall have stainless steel stems. 20% spare take-off stainless steel
nipples with plugged isolating valves shall be installed for future
requirements.
7.2.4 The air header shall be sloped 1 to 100 downstream and have a ½-inch
drain valve with plug on the bottom at the lower end of the header.
Page 7 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
The end of the air header shall be capped with a 2-inch plugged valve.
Vertical headers shall have a blowdown valve at the lower end.
7.3.2 Each filter and regulator shall have adequate capacity to serve the entire
panel. It shall be suitable for an air-supply pressure between 400 and
860 kPa and a regulated header pressure of 170 kPa. The filter shall be
of the metal bowl type.
7.3.3 The station shall be equipped with suitable valving and coupling for
removal of each filter and regulator during normal operation without
service interruption.
7.4.1 Tubing
Page 8 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
7.4.2 Tube fittings shall be 316 stainless steel and shall be high pressure,
double compression type Crawford Fitting Swagelok, Parker Hannifin
CPI or A-lok, Hoke Gyrolok or equivalent to the above as approved by
the proponent. Interchange of tube fitting component parts from different
manufacturers is not allowed.
7.4.4 Bulkhead fittings and 20% spares, as a minimum, shall be installed with
adequate spacing to ensure that any connection can be removed without
the need to remove other fittings.
7.4.5 Tubing runs and Bulkhead fitting layouts shall be included in the
documentation provided to the Proponent.
7.4.6 All metal tubing runs shall be rigidly supported by being attached to the
panel framework.
8 Documentation
Page 9 of 10
Document Responsibility: Instrumentation Standards Committee 34-SAMSS-821
Issue Date: 22 July 2012
Next Planned Update: 1 November 2014 Instrument Control Cabinets – Outdoor
8.2.1 piping diagrams shall show the outline of the panels, relative position of
all instruments, and schematic of piping, including:
a. Piping connections on instruments
b. Interconnecting piping between instruments
c. Valving and test connections
d. Air header and individual supply connections
e. Miscellaneous accessories such as pressure gages, snap connectors,
etc.
8.2.2 Piping diagrams shall show tubing terminal layout including location of
terminal rack or block. Each terminal point on the rack or block shall be
identified with its instrument identification number.
Cabinet wiring diagrams and documentation for instruments installed within the
cabinet shall be provided as specified in GSO 07/DS1/……./2009, Instrument
Control Cabinets-Indoor.
9 Testing
10 Shipping
Revision Summary
1 November 2010 Minor revision to adopt GSO comments.
Revised the "Next Planned Update".
22 July 2012 Minor revision to exclude remote termainal units of the scope of this document
Page 10 of 10