27KV 300 A Blade Cutout
27KV 300 A Blade Cutout
27KV 300 A Blade Cutout
®
Section
10A
10A-1
NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.
©Copyright 2004 Hubbell • 210 North Allen Street • Centralia, MO 65240
10A-2
Type C Cutouts
LOADBREAK cutout
with Arc-Chute interrupter,
pages 11-13
LINKBREAK cutout,
pages 8-10
STANDARD cutout,
pages 3-7
Application
The primary purpose of any cutout is to provide protection to the
lines of your system and the various apparatus on those lines
such as transformers and capacitor banks. Chance Type C
cutouts provide reliable protection from low-level overloads
that just melt the fuse link, intermediate faults, and very high
faults, through maximum interrupt capacity.
In addition, Type C cutouts can also be used as a sectionalizing
device. With the use of a portable loadbreak tool, Type C cutouts
can function much like an overhead disconnect switch. There
are 300 amp disconnect blade Type C cutouts available.
Ratings/Specifications
STANDARD Type C cutouts have maximum design voltage
ratings to simplify the confusing ratings of cutouts. There are
no restrictions on application to grounded wye, ungrounded
wye, or delta systems having maximum operating voltages CUTOUT-ARRESTER
(line-to-line) equal to or less than the cutout maximum design Combinations,
voltage rating. (See the LINKBREAK and LOADBREAK cut-
outs for their specifications.) Interruption tests have been
page 14
performed at full system line-to-line voltage. In each voltage
class, there are continuous current ratings of 100 amps, 200
amps and 300 amps. See the table on page 6 for other specifica- U.S. Patent 4,546,341; 6,392,526 and other Patents
tions. Pending
10A-4
Fusetube
The 1⁄2-inch inside diameter of the Type C cutout’s 100
ampere fusetube increases internal pressure giving superior
and reliable expulsion action. During frequently encoun-
tered intermediate fault ranges this diameter also permits
higher TRV (transient recovery voltage) values to be toler-
ated. This small bore design eliminates any concern related
to high impedance phase-to-phase faults on ungrounded wye
and delta systems.
Brackets
C cutouts come packed one per carton including a NEMA
Heavy Duty “B” bracket with captive 11⁄2" bolt for crossarm
mounting.
10A-5
GALVANIZED-STEEL CHANNEL
BIRD-PROOFED
ONE-PIECE
STAINLESS STEEL SOLID-PORCELAIN
BACKUP SPRING INSULATOR
TO MAINTAIN
CONTACT PRESSURE
SILVER-TO-SILVER
CONTACTS
SYNTHETIC
GALVANIZED STEEL HOOKS FUSE TUBE
FOR LOADBREAK TOOL LINER
LARGE NUT TO
FASTEN FUSELINK
WITHOUT BREAK-
ING STRANDS
CAST BRONZE
LOWER TUBE
CASTING
COPPER
CURRENT PATH
STAINLESS-STEEL
SPRING ENSURES
MECHANICAL ASSIST: PROPER TOGGLE ACTION
FUSEHOLDER IS AVAIL- OF FUSELINK EJECTOR SILVER-TO-SILVER
ABLE WITH A TORSIONAL (CAST-BRONZE ON ALL 200 CONTACTS
SPRING ON TRUNNION TO AND LINKBREAK FUSEHOLDERS; WITH STAINLESS STEEL
AID DROP OUT OPERATION STAINLESS-STEEL ON ALL 100A) BACKUP SPRINGS
IN CORROSIVE ENVIRON-
MENTS.
FUSEHOLDER TOGGLE LATCH CAST BRONZE HINGE
LIMITS TENSION OF FUSELINK FOR CORROSION RESISTANCE
No Restrictions
C710-313PB 27 kV thru 24.9 kV; 100 12,000 17.3" 440 mm 26.0 / 11.79 E700-1768P Yes‡
†26.4 thru 34.5 kV
No Restrictions
C710-342PB 27 kV thru 24.9 kV; 200 10,000 17.3" 440 mm 26.6 / 12.07 E700-2479P Yes‡
†26.4 thru 34.5 kV
No Restrictions
C710-333PB 27 kV thru 24.9 kV; 300 12,000** 17.3" 440 mm 26.2 / 11.88 P700-1535P N/A
†26.4 thru 34.5 kV
C710-633PB 36 kV Thru 34.5 kV 300 12,000** 26" 660 mm 28.6 / 12.97 P700-1535P N/A
NOTE: 26" fuse links are recommended.
36 kV (170 kV BIL) — RUS Listed
C710-713PB 36 kV Thru 34.5 kV 100 11,200 28.4" 720 mm 33.9 / 12.97 E700-1743P Yes‡
No Restrictions
C710-743PB 27 kV thru 24.9 kV; 200 12,000 28.4" 720 mm 34.3 / 15.55 E700-2117P Yes‡
†26.4 thru 34.5 kV
C710-733PB 36 kV Thru 34.5 kV 300 12,000** 28.4" 720 mm 33.9 / 15.37 P700-1535P N/A
NOTE: 26" fuse links are recommended.
*Suffix: P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt
Terminal variations:
P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
E = Small eyebolt [No. 8 solid through 2/0 stranded (7.7 - 90mm2)]
Change “P” to “E;” e.g., C710-112EB
L = Large eyebolt [No. 6 solid through 4/0 stranded (13.3 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
Change “P” to “L;” e.g., C710-112LB
Bracket variations:
B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt
X = Extended bracket (horizontal section 25⁄8" longer than NEMA Type B bracket)
Change “B” to “X;” e.g., C710-112PX
D = Pole mounting bracket Change “B” to “D;” e.g., C710-112PD
(Blank) = Without crossarm bracket Drop “B” from Catalog No.; e.g., C710-112P
**Momentary rating — Solid blade
†For application on single-phase to neutral or three-phase solidly-grounded wye-connected circuits where recovery voltage
does not exceed the maximum-design voltage of the device.
‡Must use removable buttonhead fuse links.
MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI
®
®
▼
15 kV
8.7" leakage
Catalog No.
T710-1MMPB
Mounting
Assembly
only
36 kV (170 kV BIL)
C710-613PB T710-613T 2.8lb. 1.27 kg.
C710-643PB T710-643T 3.2 lb. 1.45 kg. T710-6MMPB 23.4 lb. 10.61 kg.
C710-633PB T710-633T 2.8 lb. 1.27 kg.
NOTE: 26" fuse links are recommended.
36 kV (170 kV BIL)
C710-713PB T710-713T 2.8lb. 1.27 kg. 36 kV - 26" leakage 36 kV - 28.4" leakage
C710-743PB T710-743T 3.2 lb. 1.45 kg. T710-7MMPB 28.7 lb. 13.02 kg. T710-6MMPB T710-7MMPB
C710-733PB T710-733T 2.8 lb. 1.27 kg.
NOTE: 26" fuse links are recommended.
10A-8
Type C 100-Amp
LINKBREAK Cutout
15 kv - 110 kV BIL 22/36.4 kV - 150 kV BIL
15/27 kV - 125 kV BIL 22/36.4 kV - 170 kV BIL
changeable with any other manufacturer’s cutout.
All standard non-loadbreak fuseholders and the linkbreak
fuseholders are interchangeable and fit into both the non-
loadbreak and Type C LINKBREAK cutout mounting assem-
blies produced after January 1985. Mounting assemblies are
same as Type C STANDARD cutouts, shown on page 10A-7.
Ratings / Specifications
The 15 kV Type C LINKBREAK cutout has a maximum
design voltage rating of 15 kV. There are no voltage restric-
tions on application to grounded wye, ungrounded wye, or
delta systems having maximum operating voltages (line to
line) equal to or less than the cutout maximum design voltage
rating.
The 15/27 and 22/36.4 kV Type C LINKBREAK cutouts have
maximum design slant voltage ratings. These cutouts are to
be used on systems which have phase-to-ground voltages no
greater than the value listed to the left of the slant (/) and
which have phase-to-phase voltages no greater than the
value listed to the right of the slant.
The Type C LINKBREAK cutout is to be used with only
Chance, McGraw-Edison and Kearney fuselinks. S&C Elec-
tric fuselinks and other fuselinks which require more than 1
A sharp downward pull on the lever with a hookstick inch elongation before breaking must not be used with the
breaks the fuselink. Type C LINKBREAK cutout.
15 kV - 110 kV BIL unit
Application
The Chance Type C 100 amp LINKBREAK cutout provides
short circuit protection to utility lines with the added feature
of mechanical linkbreak capability in a loadbreaking func-
tion. Linkbreak cutouts provide reliable protection from
overloads that just melt the fuselink through the maximum
interrupt capacity of the fuseholder and also provide induc-
tive and capacitive loadbreak capability. For loadbreak rat-
ings see chart, next page.
The unit will also accept the Type C 200 amp non-loadbreak
fuseholder or a 300 amp disconnect blade. Each LINKBREAK
cutout includes standard loadbreak hooks to use with por-
table loadbreak tools. This method is particularly useful for
switching of the 200 amp fuseholder and 300 amp disconnect
blade.
Loadbreak Ratings
*Cutout kV,
Catalog Nominal Inductive Capacitive
Number System Voltage Amperes Amperes
C720-112PB 14.4 100 100
C720-114PB 14.4 100 100
C720-211PB† 24.9 100 100
C720-213PB† 24.9 100 100
C720-311PB† 34.5 100 50
C720-313PB† 34.5 100 50
C720-613PB† 34.5 100 50
loads.
*Suffix: P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
B = B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt
Terminal variations:
P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
E = Small eyebolt [No. 8 solid through 2/0 stranded (7.7 - 90mm2)]
Change “P” to “E;” e.g., C720-112EB
L = Large eyebolt [No. 6 solid through 4/0 stranded (13.3 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
Change “P” to “L;” e.g., C720-112LB
Bracket variations:
B = B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt
X = Extended bracket (horizontal section 25⁄8" longer than NEMA Type B bracket)
Change “B” to “X;” e.g., C720-112PX
D = Pole mounting bracket Change “B” to “D;” e.g., C720-112PD
(Blank) = Without crossarm bracket Drop “B” from Catalog No.; e.g., C720-112P
Extra corrosion resistance:
S = Available on only 150 kV and 170 kV BIL, e.g., C720-311PBS
†For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the left of the
slant; and for application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages
not exceeding the value to the right of the slant.
‡Must use removable buttonhead fuse links.
MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI
®
®
10A-11
Type C
LOADBREAK Cutout
with Arc Chute type interrupter
• 15 kv • 15/27 kV • 20/34.5 kV
Application
The Type C Loadbreak Cutout is available for application on
15, 25 and 35 kV distribution systems. The addition of the arc
chute expands the flexibility of the Chance protective devices
family by providing loadbreak capability for cutouts and
disconnect solid blade units. The loadbreak cutout provides
short circuit protection to utility lines with the added feature
of a loadbreaking function.
The loadbreak cutout is applicable for transformer and
capacitor bank switching or line sectionalizing.
Loadbreak cutouts provide protection from overloads that
just melt the fuselink through the maximum interrupt
capacity of the fuseholder. They also provide loadbreak
capability through 300 amperes.
Design
All design features and most components of the loadbreak
unit are identical to those incorporated in the Type C stan-
dard cutout. The loadbreak portion of the Type C Loadbreak
cutout is a heavy duty, reliable load interrupter that provides
a positive visible loadbreak. A common loadbreak mounting
assembly will accept the Chance Type C 100 amp and 200
amp loadbreak fuseholders or a 300 amp loadbreak discon-
nect blade.
Ratings/Specifications
The 15kV Type C loadbreak cutout has a maximum design
voltage rating of 15kV. There are no voltage restrictions on
applicaton to grounded wye, ungrounded wye, or delta sys-
tems having maximum operating voltages (line to line) equal
to or less than the cutout maximum design voltage rating.
The 15/27 and 20/34.5 kV Type C loadbreak cutouts have
maximum design slant voltage ratings. These cutouts are to
be used on systems which have phase-to-ground voltages no
greater than the value listed to the left of the slant (/) and
which have phase-to-phase voltages no greater than the
value listed to the right of the slant.
Fuseholders and mounting assemblies from other manufac-
turers' loadbreak cutouts are not interchangeable with
Chance loadbreak cutouts. Likewise, Chance fuseholders
and mountings are not interchangeable with other manufac-
turers' loadbreak cutouts.
Operation
Dimensions
The self-contained loadbreak device enables the lineman to
interrupt load current by means of a simple hookstick opera- kV BIL A B C D E
tion. To break the current, the lineman inserts a hookstick
into the operating ring and rapidly opens the device. Upon
110 251⁄4" 67⁄8" 103⁄4" 31⁄2" 255⁄8"
opening, a spring-loaded stainless steel blade mechanism
642 mm 175 mm 273 mm 89 mm 651 mm
snaps out through a gray arc chute and elongates, cools and
extinguishes the confined arc. The loadbreaking operation is
125 281⁄4" 85⁄8" 121⁄2" 31⁄8" 307⁄8"
independent of the operating speed of the lineman. The fuse
719 mm 219 mm 318 mm 79 mm 784 mm
remains undamaged. No special or portable tools are re-
quired to operate the unit. In the open position, the fuse-
150 281⁄4" 85⁄8" 121⁄2" 31⁄8" 307⁄8"
holder or blade hangs in an approximate vertical position for
719 mm 219 mm 318 mm 79 mm 784 mm
the visible-break.
10A-12 Type C
LOADBREAK Cutout
with Arc Chute Interrrupers
Specifications and Ordering Information See page 10A-17 for
All Type C Cutouts meet or exceed ANSI/NEMA specifications. Catalog Number System.
▼
▼ 15 kV, 110 kV BIL
15/27 kV,
125 kV BIL
▼
20/34.5 kV,
150 kV BIL
15/27 kV (125 kV BIL) — RUS Listed
C730-211PB 15/27 kV 100 200 8,000 12.6" 320 mm 25.1 / 11.4 P700-1535P No
No Restrictions
C730-213PB 15/27 kV 100 200 12,000 12.6" 320 mm 25.3 / 11.5 E700-1768P Yes‡
thru 14.4 kV;
C730-242PB 15/27 kV †20.8 thru 24.9 kV 200 200 10,000 12.6" 320 mm 26.0 / 11.8 E700-2479P Yes‡
C730-233PB 15/27 kV 300 50 12,000** 12.6" 320 mm 25.5 / 11.6 P700-1535P N/A
*Suffix: P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt
Terminal variations:
P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
E = Small eyebolt [No. 8 solid through 2/0 stranded (7.7 - 90mm2)]
Change “P” to “E;” e.g., C730-112EB
L = Large eyebolt [No. 6 solid through 4/0 stranded (13.3 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]
Change “P” to “L;” e.g., C730-112LB
Bracket variations:
B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt
X = Extended bracket (horizontal section 25⁄8" longer than NEMA Type B bracket)
Change “B” to “X;” e.g., C730-112PX
D = Pole mounting bracket Change “B” to “D;” e.g., C730-112PD
(Blank) = Without crossarm bracket Drop “B” from Catalog No.; e.g., C730-112P
Extra corrosion resistance:
Not Available
**Momentary rating — Solid blade
†For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the left of the
slant; and for application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltages
not exceeding the value to the right of the slant.
‡Must use removable buttonhead fuse links.
MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI
®
®
Type C 10A-13
LOADBREAK Cutout
Fuseholders and Mounting Assemblies
15 kV (110 kV BIL)
Cutout Fuseholder or Mounting
Catalog Blade only Weight Assembly only Weight
Number Catalog No. *Catalog No.
C730-112PB T730-112T 3.3 lb. 1.5 kg.
C730-114PB T730-114T 3.5 lb. 1.6 kg.
T730-1MMPB 18.6 lb. 8.4 kg.
C730-143PB T730-143T 4.1 lb. 1.9 kg.
C730-133PB T730-133T 3.6 lb. 1.6 kg.
Replacement Arc Chute Interrupter: Catalog No. T730-0080 (1.2 lb. / 0.54 kg.)
15 kV — T730-1MMPB
10A-14 Type C
CUTOUT-ARRESTER COMBINATIONS
Over-the-Arm Type only
Cutout-Arrester
13"
Dimensions
(330 mm)
kV BIL E G
110 22" (559 mm) 233⁄4" (603 mm)
125 263⁄4" (679 mm) 251⁄2" (648 mm)
15 kV cutout with direct-connected Ohio Brass large- 150 263⁄4" (679 mm) 251⁄2" (648 mm)
block, MOV, polymer 9 kV lightning arrester 170 321⁄2" (826 mm) 28" (711 mm)
Advantages of combination proven quality of both cutout and arrester assure consistent
Chance cutout-arrester combinations cost less than the total high performance for the combinations.
cost of separately purchased components. The combination These units include Chance cutouts fitted with only Ohio
units install faster, more economically and take up less space Brass® MOV arresters, superseding previous silicon-carbide
in storage, transit and service. Each combined unit takes up units. For easy conversion to the new arrester designation
a minimum of space on the crossarm and has a favorable system, refer to the Cutout Cross-Reference Guide, Bulletin
weight distribution for minimal off-center loading. The field- 10-0203.
Note:
Arresters can be combined with any Type C Cutout:
MCOV Duty Cycle
Polymer Housing
kV Rating
Arrester
Method
C 7
Positions 4 & 5: *Position 7: *Position 8: Position 9:
Continuous Interrupting or Momentary Terminal Variations
O No arrester Current Current (Amps) (tin plated)
1 = 100 Amps 1 = 8,000 P = Parallel-groove
For cutout-
(Accepts 1–100 Amp links) 2 = 10,000 (27kV must use clamps
arrester combinations,
see table below for two- removable buttonhead links) E = Small eyebolts
3 = 300 Amps solid blade
letter arrester codes. 3 = 12,000 (All must use L = Large eyebolts
4 = 200 Amps removable buttonhead links) T = Fuseholder only
(Accepts 140–200 Amp links) 4 = 16,000 (All must use (enter T in position 1
Arrester Manufacturer
Metal Oxide Varister Operating *Not all combinations of kV Rating, Continuous Current
(MOV) Design Rating and Interrupting Rating (Positions 6, 7 & 8) are
Connection
Polymer Housing
Arrester
5 kA
Large Block
Heavy Duty Direct EL EM EN EP
10 kA
Riser
Pole Direct FL FM FN FP Accessories
Terminal Connectors
Catalog No. Description Minimum Order Quantity
T700-1325 Parallel-Groove Clamp, tin-plated bronze forNo. 6 solid thru 4/0 ACSR or 250 kcmil stranded 10
T700-1326 Small Eyebolt for No. 8 solid thru 2/0 stranded 10
T700-1327 Large Eyebolt for No. 6 solid thru 4/0 ACSR or 250 kcmil stranded 10
Mounting Brackets
C206-0283 NEMA Heavy Duty “B” Bracket with 2" captive bolt for crossarm mounting —
C206-0280 Extended Crossarm Bracket (Horizontal section is 25⁄8" longer than NEMA “B” bracket) —
C206-0299 “D” Pole Mounting Bracket —
C206-0632 Cutout/Arrester Bracket complete with carriage bolts and backstrap —
HUBBELL POWER SYSTEMS, INC. HUBBELL CANADA LP HUBBELL DE MEXICO, S.A. DE. CV
210 N. Allen 870 Brock Road South Av. Coyoacan No. 1051
Centralia, Mo 65240-1395 Pickering, Ontario L1W 1Z8 Col. Del Valle
Phone: 573-682-5521 Phone: 905-839-1138 03100 Mexico, D.F.
Fax: 573-682-8714 Fax: 905-831-6353 Phone: 52-55-9151-9999
e-mail: hpsliterature@hps.hubbell.com e-mail: infohps@hubbellonline.com Fax: 52-55-9151-9988
e-mail: vtasdf@hubbell.com.mx
™ ® ® ® ®