Numerical Over Flux Relay: Powering Innovation
Numerical Over Flux Relay: Powering Innovation
Numerical Over Flux Relay: Powering Innovation
FEATURES
Programmable V/F ra�o
History of 5 latest relay closing details
Applica�on
JNF 020 Over flux relay is used in power systems in order to
protect transformers and generators against insula�on failure
and core damage due to over hea�ng under prolonged over
fluxing condi�on. It protects the equipment against abnormal
V/F ra�os due to system disturbance which can occur during
star�ng, load sheding and shut down condi�ons.
PRINCIPLE OF OPERATION
Over fluxing of a transformer occurs when its flux density exceeds rated density, it is caused when
its V/F ra�o is greater than that which the manufacture deems it safe. This of course is the case
when it is connected directly to the generator i.e, without benefit of an intervening circuitbreaker
and the generators excita�on system is energized while accelera�ng to opera�ng speed JNF 020
monitors voltage & frequency ra�o, when it exceeds the set value it indicates fault and the output
relay operates a�er a set alarm �me delay.
TECHNICAL DATA
RATINGS
Rated Voltage : 110VAC
Frequency ra�ng : 50 Hz
Auxiliary supply : 1) 20 to 60V DC
2) 75 to 150V AC / DC 3) 175 to 300V DC / 185 to 250V AC
SETTINGS
Alarm se�ng Alarm Time delay : 1.1 - 1.30 V/Hz. In steps of 0.01
Alarm Time delay : 00.5 - 50.0 secs. In steps of 0.1
Inverse Time Pickup : 1.2 - 1.50 V/Hz. In steps of 0.01
TMS : 001 - 100 In steps of 1
Rated voltage : 105 - 125 V. In steps of IV
OVERLOAD RATING
Voltage input : 2 �mes Rated con�nuous
BURDEN
AC voltage input AUX Supply : Less than 0.1VA
Less than 4W (Non Operated)
Less than 10W (Operated)
bangalore@jvselectronics.in, www.jvselectronics.in
NUMERICAL OVER FLUX RELAY
JNF 020
ACCURACY:
Voltage : ±5% of reading
Frequency : ±0.02 Hz of reading
Opera�ng �me : ±5% of the value
CONTACT RATINGS
Trip / Alarm : 10A at 24V DC / 230V AC
CONTACT DURABILITY
Loaded contact : 10,000 opera�ons min.
Unloaded contact : 100,000 opera�ons min.
MECHANICAL DESIGN
Weight : 3500gms (approx)
Case Size : 152X296 sq mm, depth 250mm
Installa�on : Flush moun�ng
Panel cutout : 146 x 264 mm
STANDARD COMPLIANCE
Accuracy Test : IEC 60255-3
Insula�on Test : IEC 60255-5
TERMINAL DIAGRAM
ORDERING INFORMATION
Relay : JNF 020
Voltage ra�ng : 110VAC
Aux. Supply : 20 to 60V DC or
75 to 150V AC/ DC or
175 to 300V DC / 185 to 250V AC
bangalore@jvselectronics.in, www.jvselectronics.in