Chiller Safety

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

Chiller safety

Operation
1. Avoiding copper tubes frozen in evaporator
① Operating steps Incorrect

Start Stop
Frozen
1.Start chilled water 1.Staop cooling
pump water pump

2.Start cooling 2.Stop chilled


water pump water pump
Operation
1. Avoiding copper tubes frozen in evaporator
② Don’t by-pass flow switch or adjust their setting

NC COM
NO

Always connect NO and COM


Operation
1. Avoiding copper tubes frozen in evaporator
③ Check the filter of chilled water when annual
maintenance
Operation
2. In heating mode, confirm angle valve is100%
closed.

Checking: HTG
temperature >
Diluted Steam 100℃,check the
solution angle angle valve
pipes
valve
temperature at
main-shell side
Concentrated
solution angle valve
Operation
3. When the chiller is in cooling operation, the
heating water discharge valve must be opened
and its handle removed. The handle should be
well kept during heating operation.
Operation
4. Without BROAD’s permission, the concentration
regulating valve is forbidden to be adjusted at
random otherwise crystallization may happen or
the capacity will reduce
Operation
5. Close steam heat source manual valve when
turning chiller in dilution or stop, avoid
crystallization due to the valve leakage.
Burner system
1.Ensure good ventilation
Chiller Bad ventilation
room

Good ventilation, Bad burning due to less O2


good burning

Damp, electrical insulation

Even cause bodily injury

9
Burner system

2.Gas leakage

Forbidden
Gas leakage checking device Abnormal
to start

Linkage with powerful


Normal
exhaust fan

Start chiller

10
Burner system
3.Exhaust leakage
Bad leak-tightness Leak to chiller
Burning exhaust
room

Vent to air CO poisoning


Good
leak-tightness

11
Burner system
4.Clean or change fuel filter regularly

Fuel filter Blocked

Cleaning Smoking or burner stop


regularly

Damage

May cause deflagration

12
Burner system
5. Forbidden to run burner with smoking
Burning less O2 smoking

Air pollution, even


Excess O2 cause fire

Raise
Deflagration fuel consumption

Fuel waste
13
Burner system
6.Gas pressure and heat value should be
stable
Exhaust tube
Gas pressure Unstable
scaling

Raise
Stable Heat value fuel consumption

Normal Deflagration

14
Burner system
7.Confirm exhaust damper is fully open
before chiller start
Exhaust Closed or
damper partial opened Fire stop and
pressure escape
door acts

Full opened
Exhaust
damper
Pressure
escape door

15
Vacuum And Life-span
1. Ensure good vacuum in the chiller according to
“Vacuum Management regulation”.

2. Forbidden to operate vacuum valve by un-


trained person, remove the valve handle after
operating the valve.
Vacuum And Life-span
3. Valves must be closed carefully. The canned
cover and plug must be closed soon after valve
operation.

Cover

Plug
Vacuum And Life-span
4.Forbidden to use LiBr solution from other
suppliers, solution is the blood of the chiller,
unqualified solution will damage the chiller.

Solution analysis Unfit


Turbid solution
every year standard

Composition fit Regenerate


Add Li2CrO4
standard solution
Vacuum And Life-span
5. Management of idle machine: if the chiller will
stay idle for 8 months, high purity nitrogen
(>99.999%) of 0.01-0.02 MPa must be charged
for avoiding air leakage and chiller corrosion.

6. Without BROAD’s written permission, copper


tubes and water pipe system are
forbidden to be washed with chemicals. Copper
tubes may be corroded seriously
without controlling.
Electricity
1. Internet cable must be used to network
monitoring. The control cabinet must be always
power on (Internet cable must be 24 hours
connected) no matter the chiller is on/off,
otherwise BROAD Monitoring Center cannot
trace the chiller situation.
Electricity
2.The power supply must meet local standards.
The fluctuation range of voltage must be at
≤10% rated value. A dedicated grounding is
available in the machine room. Grounding
cable≥2.5mm2 and grounding resistance ≤10Ω.

3. The safety devices are forbidden to be short-


circuited, and their settings can not be changed.

10
Others
1. Forbidden to vibrate the piping system or to
bear any external shock on the chiller, it may
affect the chiller’s life-span, or even damage
the chiller.
2. It is forbidden to put heavy objects on the
pressure escape door.

Pressure
escape door
Others
3. The chiller must be well kept.
The door and windows of the machine room must be
installed with lock. No entrance for unrelated person.
The tool box and documents should be well kept.

4. Humidity of machine room should be less than 85% with


the temperature ranging from 5℃to 43℃.

5. Heating source pressure should be stable.


Fluctuation should be within ±0.02 MPa. Working
pressure and temperature should not be 10% higher than
the rated.
Safety indicator on chillers
15
20
25
35
40
45