Turbine Trip, Latch Judge: Breaker On Conditions

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 12

TURBINE TRIP ,LATCH JUDGE

BREAKER ON CONDITIONS

BREAKER 1 ON
&
BREAKER 2 ON

OR
BREAKER 2 ON
&
BREAKER 3 ON

OR
BREAKER 3 ON
&
BREAKER 1 ON

BREAKER OFF CONDITIONS

NOT(BREAKER ON CONDITIONS)

HP SAFE OIL SET UP CONDITIONS


HP SAFE OIL SET UP 1
&
HP SAFE OIL SET UP 2

OR
HP SAFE OIL SET UP 2
&
HP SAFE OIL SET UP 3

OR
HP SAFE OIL SET UP 3
&
HP SAFE OIL SET UP 1

TURBINE TRIPPED CONDITIONS

NOT(HP SAFE OIL SET UP CONDITIONS)


OR
EMERGENCY GOVERNOR TRIPPED POSITION
TURBINE LATCHED CONDITIONS

EMERGENCY GOVERNOR RESET POSITION IN THE SET BIT OF S-R FF


&
NOT(HP SAFE OIL SET UP)IN THE RESET BIT OF S-R FF

ACTUAL SPEED

>(SPEED 1,SPEED 2)

>(SPEED 2,SPEED 3)

>(SPEED 3,SPEED 1)
OUT OF THREE WHICHEVER IS LESS

SPEED 1 ERROR

DIFFERENCE BETWEEN SPEED 1 & ACTUAL SPEED(H:30,L:-30)


OR
SPEED 1 FAULT

SPEED 2 ERROR

DIFFERENCE BETWEEN SPEED 2 & ACTUAL SPEED(H:30,L:-30)


OR
SPEED 2 FAULT

SPEED 3 ERROR

DIFFERENCE BETWEEN SPEED 3 & ACTUAL SPEED(H:30,L:-30)


OR
SPEED 3 FAULT

SPEED ERROR TRIP

SPEED 1 ERROR
&
SPEED 2 ERROR

OR
SPEED 2 ERROR
&
SPEED 3 ERROR

OR
SPEED 3 ERROR
&
SPEED 1 ERROR

EHG MAJOR FAULT

SPEED ERR TRIP


OR
SYSTEM POWER FAULT

OVERSPEED TRIP

IF ACTUAL SPEED(H:3300,L:800)

ACCELERATION RATE LIMIT

ACTUAL SPEED(H:3060,L:100000)
&
DIFFERENTIATE ACTUAL SPEED(H:49,L:100000)

IP & HP OVERSPEED LIMITED SOLENOID VALVE OPEN CONDITIONS

ACTUAL SPEED(H:3060,L:100000)
&
DIFFERENTIATE ACTUAL SPEED(H:49,L:100000)
&
NO MECHANICAL/ELECTRICAL OSP TEST
OR
PLU ACTION
OR
TURBINE TRIP COMMAND

RSV TRIP SOLENOID VALVE ACTION

TURBINE TRIP COMMAND

RSV TEST SOLENOID VALVE ACTION

RSV TEST LOGIC


OR
TURBINE TRIP COMMAND
OR
LATCH COMMAND/TURBINE LATCHED & TURBINE NOT RUNNING
MSV TEST SOLENOID VALVE

MSV TEST LOGIC


OR
TURBINE TRIP COMMAND
OR
LATCH COMMAND/TURBINE LATCHED & TURBINE NOT RUNNING

MSV TRIP SOLENOID VALVE

TURBINE TRIP COMMAND

HPT SOLENOID VALVE DE-ENERGISE CONDITIONS

HPT SOLENOID TEST


OR
TURBINE NOT LATCHED
OR
TURBINE TRIP COMMAND

TURBINE TRIP COMMAND

SPEED ERR TRIP


OR
OVERSPEED TRIP
OR
ETS TRIP SIGNAL
OR
MANUAL TRIP
IN THE SET BIT OF S-R FF
&
TURBINE TRIPPED WITH DELAY 5s IN RESET BIT OF S-R FF

GENERATOR LOAD CONDITIONS

>(GENERATOR LOAD1,GENERATOR LOAD 2)

>(GENERATOR LOAD2,GENERATOR LOAD 3)

>(GENERATOR LOAD3,GENERATOR LOAD 1)


WHICHEVER IS LESS OUT OF THE THREE.
MAIN STEAM PRESSURE

MAIN STEAM PRESSURE LEFT

IP 1st PRESSURE
>(IP 1st PRESSURE ,IP 2nd PRESSURE)

>(IP 2nd PRESSURE ,IP 3rd PRESSURE)

>(IP 3rd PRESSURE ,IP 1st PRESSURE)


WHICHEVER IS LESS OUT OF THE THREE.

ACCELERATE RATE / LOAD RATE

IF BREAKER ON
CHECK FOR ATC RUN
IF ATC RUN
THEN
ATC LOAD RATE
ELSE
LOAD RATE SET BY OPERATOR

IF BREAKER OFF
CHECK FOR ATC RUN
IF ATC RUN
THEN
ATC SET ACCELERATE RATE
ELSE
CHECK FOR OPERATOR SET ACCELERATE RATE
IF OPERATOR SET ACCELERATE RATE
THEN
ACCELERATE RATE IS SET BY OPERATOR
ELSE
SET RATE BY EMPIRICAL CURVE

TARGET SET

CHECK FOR BREAKER CONDITION


IF BREAKER IS JUST OFF
THEN
TARGET SET IS 3000
ELSE
TARGET SET IS DETERMINED BY CCS CONDITIONS
IF CCS IN
THEN
TARGET SET IS CCS TARGET DEMAND
ELSE
TARGET SET IS DETERMINED BY TARGET FOLLOW DEMAND

IF MODE IS TARGET FOLLOW DEMAND


THEN
AUTO CHANGE SET POINT
ELSE
CHECK FOR ATC RUN CONDITION

IF ATC RUN
THEN
TARGET SET IS ATC SET TARGET
ELSE
CHECK FOR ASS CONTROL

IF ASS(AUTOMATIC SYNCHRONISED SYSTEM) ON CONTROL


THEN
TARGET SET IS ASS TARGET (2985<SPEED<3015)
ELSE
TARGET SET IS THE SMALLEST OUT OF THE TWO SPEEDS 1 & 2

1.
CHECK FOR BREAKER CONDITION

IF BREAKER IS OFF
THEN
CHECK FOR OVERSPEED TEST
IF OVERSPEED TEST
THEN
SPEED =3360
ELSE
SPEED=3060

IF BREAKER IS ON
THEN
CHECK FOR LOAD LOOP CONDITION
IF LOAD LOOP OUT
THEN
SPEED IS THE SMALLEST OUT OF OPERATOR SET TARGET & VALVE LIMIT
ELSE
SPEED IS THE MAX LOAD
2.
IF OPERATOR NOT SET & BREAKER IS OFF
THEN
SPEED =3000
ELSE
SPEED=OPERATOR SET TARGET

AUTO CHANGE SET POINT(DEMAND)


IF TURBINE TRIPPED OR TURBINE TRIP COMMAND
THEN
DEMAND=0
ELSE
CHECK FOR BREAKER CONDITION

IF BREAKER IS ON
DEMAND IS INITIAL LOAD IS 30
ELSE
CHECK FOR LOAD LOOP CONDITIONS

IF LOAD LOOP JUST IN


THEN
DEMAND=GENERATOR LOAD
ELSE CHECK FOR TURBINE RUN CONDITIONS

IF TURBINE JUST RUN


THEN
DEMAND=ACTUAL SPEED
ELSE
CHECK FOR TURBINE HOLD/WARMING CONDITIONS

IF TURBINE HOLD/WARMING CONDITION


THEN
DEMAND=ACCELERATE RATE/LOAD RATE
ELSE
DEMAND=TARGET SET

IF TURBINE NOT TRIPPED OR NO TURBINE TRIP COMMAND


THEN
SUMMATION OF ACTUAL SPEED,TARGET SPEED,DEMAND & TPC ACT IN
VALUE
MAIN CONTROL PROCEDURE

IF TURBINE TRIPPED OR TURBINE TRIP COMMAND


THEN
REFERENCE=0
ELSE
REFERENCE IS THE SUM OF 2 OUTPUTS(1 & 2)
1.
CHECK FOR BREAKER CONDITIONS
IF BREAKER OFF
THEN
REFERENCE=CV/ICV UP SPEED COMMAND
ELSE
CHECK FOR CCS CONTROL CONDITIONS

IF CCS CONTROL IN
THEN
REFERENCE=CCS COMMAND
ELSE
CHECK FOR LOAD LOOP CONDITIONS

IF LOAD LOOP IN
THEN
REFERENCE IS PID CONTROL OF GENERATOR LOAD & SUMMATION OF
DEMAND & FREQUENCY VALUE 1
ELSE
REFERENCE=OPERATOR MANUAL SET

2.
CHECK FOR LOAD LOOP CONDITIONS
IF LOAD LOOP OUT
THEN
REFERENCE=0
ELSE
REFERENCE=FREQUENCY VALUE 2

CV1,CV2,CV3,CV4 CONTROL

CV1 CONTROL

REFERENCE FED TO F1(X)


SERVO MODULE IS FED WITH SUMMATION OF F1(X) & VALVE TEST
OUTPUT
VALVE TEST OUTPUT

IF VALVE TEST
THEN
VALVE TEST OUTPUT=VALVE TEST DIFFERENCE
ELSE
VALVE TEST OUTPUT=0

OUTPUT OF SERVO MODULE IS FED TO CV1


POSITION FEEDBACK IS THE FEEDBACK FROM CV1

CV2 CONTROL

REFERENCE FED TO F2(X)


SERVO MODULE IS FED WITH SUMMATION OF F2(X) & VALVE TEST
OUTPUT

VALVE TEST OUTPUT

IF VALVE TEST
THEN
VALVE TEST OUTPUT=VALVE TEST DIFFERENCE
ELSE
VALVE TEST OUTPUT=0

OUTPUT OF SERVO MODULE IS FED TO CV2


POSITION FEEDBACK IS THE FEEDBACK FROM CV2

CV3 CONTROL

REFERENCE FED TO F3(X)


SERVO MODULE IS FED WITH SUMMATION OF F3(X) & VALVE TEST
OUTPUT

VALVE TEST OUTPUT

IF VALVE TEST
THEN
VALVE TEST OUTPUT=VALVE TEST DIFFERENCE
ELSE
VALVE TEST OUTPUT=0

OUTPUT OF SERVO MODULE IS FED TO CV3


POSITION FEEDBACK IS THE FEEDBACK FROM CV3
CV4 CONTROL

REFERENCE FED TO F4(X)


SERVO MODULE IS FED WITH SUMMATION OF F4(X) & VALVE TEST
OUTPUT

VALVE TEST OUTPUT

IF VALVE TEST
THEN
VALVE TEST OUTPUT=VALVE TEST DIFFERENCE
ELSE
VALVE TEST OUTPUT=0

OUTPUT OF SERVO MODULE IS FED TO CV4


POSITION FEEDBACK IS THE FEEDBACK FROM CV4

ICV1,ICV2 CONTROL

ICV1 CONTROL

REFERENCE FED TO F5(X)


SERVO MODULE IS FED WITH SUMMATION OF F5(X)(CORRECTION CURVE)
& VALVE TEST OUTPUT

VALVE TEST OUTPUT

IF VALVE TEST
THEN
VALVE TEST OUTPUT=VALVE TEST DIFFERENCE
ELSE
VALVE TEST OUTPUT=0

OUTPUT OF SERVO MODULE IS FED TO ICV1


POSITION FEEDBACK IS THE FEEDBACK FROM ICV1
ICV2 CONTROL

REFERENCE FED TO F5(X)


SERVO MODULE IS FED WITH SUMMATION OF F5(X)(CORRECTION CURVE)
& VALVE TEST OUTPUT

VALVE TEST OUTPUT


IF VALVE TEST
THEN
VALVE TEST OUTPUT=VALVE TEST DIFFERENCE
ELSE
VALVE TEST OUTPUT=0

OUTPUT OF SERVO MODULE IS FED TO ICV2


POSITION FEEDBACK IS THE FEEDBACK FROM ICV2

HEAT STATUS LOGIC

IF IPIC SIGNAL FAULT


THEN
HPIB INNER WALL TEMPERATURE
ELSE
HPIC INNER WALL TEMPERATURE

IF T>445C,VERY HOT MODE


IF 445>T>420,HOT MODE
IF 420>T>320,WARM MODE
320>T,COLD MODE

IF IPIC SIGNAL FAULT


THEN
HPIB INNER WALL TEMPERATURE
ELSE
HPIC INNER WALL TEMPERATURE

IF T>490C,VERY HOT MODE


IF 490>T>420,HOT MODE
IF 420>T>305,WARM MODE
305>T,COLD MODE

LATCH CONDITIONS

LATCH COMMAND & LATCH SOLENOID WHEN

OUTPUT OF SR FF
OR
[HP SAFE OIL SET UP
AND
EMERGENCY GOVERNOR RESET POSITION (DELAY 2s)] FOR A DELAY OF 20s
OR
SPRAY OIL TEST LATCH COMMAND
OUTPUT OF SR FF
EMERGENCY GOVERNOR TRIPPED POS
AND
OIS LATCH COMMAND
AND
ALL VALVES FULL CLOSED
AND
TURBINE TRIPPED
IN SET BIT OF SR FF

HP SAFE OIL SET UP


AND
EMERGENCY GOVERNOR RESET POSITION (DELAY 2s)
IN THE RESET BIT OF SR FF

CCS IN LOGIC

CCS IN DEMAND
AND
DIFF BETWEEN CCS DEMAND & REFERENCE (5%)
AND
LOAD UP COMPLETE
IN THE SET BIT OF SR FF

TURBINE TRIPPED
OR
CCS OUT DEMAND
OR
BREAKER OFF
OR
CCS NO REQUEST
OR
CCS COMMAND ERROR IN THE RESET BIT OF SR FF