MTU OE Genset A5
MTU OE Genset A5
MTU OE Genset A5
04 Rating definitions for power solutions 38 Continuous/Prime/Peak, Continuous + CHP (3A) MTU Onsite Energy is part of the Rolls-Royce Group well as medium-speed engines for land-based energy
08 New products: S4000 L64 Gas System, Diesel: 50 Hz; Gas: 50 Hz, 60 Hz and a world-leading provider of high- and medium solutions up to 12,000 kWe as part of the Rolls-Royce
S4000 G04- Diesel System, MTU EnergyPack 50 Continuous/Prime/Peak, Prime (3B) speed diesel and gas engines, complete drive systems Power Systems product portfolio. Additionally we
Diesel: 50 Hz, 60 Hz; Gas: 60 Hz and distributed energy generation and storage systems backup our portfolio with the EnergyPack battery
14 Service solutions
62 Continuous/Prime/Peak, Peak (3G) for the most demanding environments. MTU Onsite storage solutions, to maximize energy utilization and
16 Sizing and Specifying Software & Service Network Energy offers complete power system solutions: from integrate alternative energy sources efficiently. More
Diesel: 50 Hz
18 Digital solutions standard backup to mission critical power to continuous than 60 years of power generation systems expertise
64 Containerized Gensets + CHP,
20 Standby, Standardized Backup (3D) and peak power applications, as well as energy storage and over a century of diesel engine engineering
Enclosures - 50 Hz, 60 Hz, Power Modules 50/60Hz;
Diesel: 50 Hz, 60 Hz; Gas: 60 Hz and combined heat and cooling. We also provide a full experience have enabled us to provide complete
Gas: Power Modules 50/60Hz
line of service products to help you get the most from solutions all over the globe. We continue to develop
30 Standby, 74 MTU EnergyPack your equipment. Customers around the world trust us sustainable alternatives, with systems that produce
Prime Power for Stationary Emergency (3E) Battery Storage to provide reliable power for a wide range of applica- greener energy from climate-neutral, regenerative
Diesel: 50 Hz, 60 Hz
76 Classifications for Data Centers – tions. Our product portfolio covers diesel generator sets fuels, such as combined heat and power (CHP) plants.
34 Standby, Data Center Continuous (3F) according to the Uptime Institute for 50 Hz markets up to 4,000 kVA and for 60 Hz MTU products support renewable energies and are
Diesel: 50 Hz, 60 Hz markets up to 3,250 kWe. Furthermore we offer acting as backbone of modern energy systems,
77 Conversion Table
gas-powered cogeneration systems up to 2,500 kWe as designed to guarantee energy security.
78 Footnotes
Standby Continuous/Prime/Peak
Standardized Backup (3D) Continuous + CHP (3A)
Standardized backup applies to installations served by a reliable utility Continuous Power applies to installations where one or several
source. The standby ratings are applicable to varying loads for the generator sets serve as utility. At constant or varying load, the number
duration of a power outage. of generator set operating hours is unlimited. Typical application here
is CHP.
Standby Continuous/Prime/Peak
Standardized Backup (3D) MTU Onsite Energy ISO 8528-1 (ESP) Continuous + CHP (3A) MTU Onsite Energy ISO 8528-1 (COP)
Load variable variable Load constant constant
Load factor ≤ 85 % ≤ 70 % Load factor ≤ 100 % ≤ 100 %
10 % overload (ICXN) no not specified 10 % overload (ICXN) Gas: no not specified
Max. operating hours (per year) 500 h 200 h Diesel: yes
Uptime compliant Tier I & Tier II not specified Max. operating hours (per year) unlimited unlimited
HIGH-GRADE ELECTRICITY
// Superior transient behavior
// Protection for sensitive electrical infrastructure &
IT equipment
// Simplification of electrical infrastructure
Eliminate unexpected
maintenance costs
// Predefined rate per
operating hour for maintenance
and repairs
// Predefined prices for extended Gold also includes all
component maintenance and benefits of Silver level
major overhauls
// Quarterly reliability reporting
// Proactive remote engine
health monitoring, including
maintenance planning and
BRONZE troubleshooting
Ensure parts availability & With large investments, lifecycle costs can be ValueCare Agreements help you:
price stability significant. It’s often the unforeseen costs lurking
Increase operational uptime
// Only for customers with self below the surface—things like fuel consumption,
unplanned downtime and repairs—that have the Guarantee parts availability and service quality
service maintenance capabilities
// Predefined rate per operating greatest potential to impact your business. That’s
hour for basic maintenance Predict equipment-related costs
Silver also includes all Gold also includes all why it pays to plan ahead by investing in a superior
components
// Automatic delivery of benefits of Bronze level benefits of Bronze level MTU Onsite Energy power system and protecting Optimize maintenance planning
preventive spare parts based it with a ValueCare Agreement.
on operating hours Connect to MTU Onsite Energy, 24/7
// Quarterly maintenance reporting
and maintenance forecast
// Annual on-site engine
health check
From PS-SPEC sizing software to building information models (BIM) and The most important part of your equipment isn’t a Always on call, 24/7
spec sheets for all our products, MTU Onsite Energy has the tools and part at all—it’s your local service team. With more Whether it’s connecting you with a local service partner
software to assist you with all aspects of your project design. Case studies than 1,500 service locations worldwide—backed by or assigning an urgent problem to a dedicated team of
and technical articles are also available for download to reference existing regional MTU Onsite Energy Parts Logistics Centers MTU Onsite Energy experts, we’re ready to assist you—
MTU Onsite Energy projects. in Europe, Asia and America—You can count on wherever you are, whatever you need.
responsive support by expert technicians, wherever
PS-SPEC Power System Sizing and Specification Software:
work takes you. Europe, Middle East, Africa
PS-SPEC Power System Sizing and Specification is a powerful, fully-featured
+49 7541 90-77777
sizing and specification program for generator sets suitable for projects of
Asia/Pacific
any size. PS-SPEC is a tool for consulting engineers, contractors, and other
+65 6860 9669
professionals involved in the design, application load analysis or installation
North and Latin America
of generator sets. PS-SPEC asks you to supply basic information about your
+1 248 560 8888
project requirements and then provides you with all the information you need
To find your local dealer, please visit our website:
to select the appropriate equipment.
www.mtuonsiteenergy.com/find-a-dealer info@mtu-online.com
For detailed product information, please visit our website:
www.mtuonsiteenergy.com/products/diesel-generator-sets
For over 100 years, we’ve been known for digital solutions magnify the power of your MTU Service in your pocket Monitor your equipment
technological innovation and leadership—driving investment. From proactive failure prevention Designed to support on-site operators of Built for operators of MTU-powered equipment,
efficiency and reliability to new heights. Today, and intelligent troubleshooting to instant failure MTU-powered equipment, Go! Act: Go! Manage:
we’re applying that same spirit of innovation to support and smart maintenance planning, digital
digitalization. Fueled by your system’s data—and solutions unlock the full potential of your // Receives push notification of failure codes from // Provides a live overview of asset and
supplemented with MTU’s exclusive expertise, MTU Onsite Energy system. connected assets engine conditions
smart analytics and extensive database—our // Provides crew members with vital information // Displays active and closed alarms
about failure codes // Enables interaction and communication with
// Supports event reporting with convenient photo on-site staff via Go! Act
capture functionality // Shows maintenance schedule, with completed
// Enables direct communication with tasks clearly marked
fleet managers or the MTU Customer // Enables remote trouble shooting
Assistance Center
Standardized Backup
Standardized Backup (3D) – 50 Hz / 1500 rpm
(3D)
Power Available Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) voltages class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
97/68 EC Stage IIIA
97/68 EC Stage II
ISO 8528-5 - G2
ISO 8528-5 - G3
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE / IEC
ORDE
25°C 25°C
kVA kWe
MTU 0080/0113 DS
Standardized Backup
Standardized Backup (3D) – 50 Hz / 1500 rpm
(3D)
Power Available Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) voltages class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
97/68 EC Stage IIIA
97/68 EC Stage II
ISO 8528-5 - G2
ISO 8528-5 - G3
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE / IEC
ORDE
kVA kWe
Standardized Backup
Standardized Backup (3D) – 60 Hz / 1800 rpm
(3D)
Power Available voltages Emissions Certifications Uptime Housing Engine type Cooling Genset type
output (1) compliant variant (3)
Fuel consumption
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
EPA Tier 2
Enclosure
optimized
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Standardized Backup
Standardized Backup (3D) – 60 Hz / 1800 rpm
(3D)
Power Available voltages Emissions Certifications Uptime Housing Engine type Cooling Genset type
output (1) compliant variant (3)
Fuel consumption
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
EPA Tier 2
Enclosure
optimized
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Standardized Backup
Standardized Backup (3D) – 60 Hz / 1800 rpm
(3D)
Power Available voltages Emissions Certifications Fuel type Housing Engine type Genset type
output (1)
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
Liquid Propane
4160 V (3 Phase)
Propane Gas /
208 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
EPA certified
Natural Gas
Enclosure
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Power Available voltages Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
97/68 EC Stage IIIA
97/68 EC Stage II
6300 kV (3 Phase)
6600 kV (3 Phase)
10000 V (3 Phase)
10500 V (3 Phase)
ISO 8528-5 - G2
ISO 8528-5 - G3
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE/IEC
ORDE
Overload – 50 Hz
800 640 x x x x x x x x x x x x x x 12V 2000 G26F A2A MTU 12V2000 DS1000
MTU 2000 DS
Power Available voltages Emissions Certifications Uptime Housing Engine type Cooling Genset type
output (1) compl. variant (3)
13800 V (3 Phase)
12470 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
EPA Tier 2
Enclosure
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
240 V
240 V
kWe kVA
MTU 0096/0113 DS
Power Available voltages Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
97/68 EC Stage IIIA
97/68 EC Stage II
10000 V (3 Phase)
10500 V (3 Phase)
11000 V (3 Phase)
ISO 8528-5 - G2
ISO 8528-5 - G3
NOx emission
380 V (3 Phase)
400 V (3 Phase)
415 V (3 Phase)
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE/IEC
ORDE
kVA kWe
MTU 4000 DS MTU 2000 DS
Continuous – (3F)
1000 800 x x x x x x x x x x x x x x x x x 16V 2000 G26F A2A MTU 16V2000 DS1100
Data Center
1250 1000 x x x x x x x x x x x x x x x x 18V 2000 G26F A2A MTU 18V2000 DS1400
1600 1280 x x x x x x x x x x x x x x x x x 12V 4000 G14F W2A MTU 12V4000 DS1650
1700 1360 x x x x x x x x x x x x x x x x x 12V 4000 G14F W2A MTU 12V4000 DS1750
1880 1504 x x x x x x x x x x x x x x x x x 12V 4000 G24F W2A MTU 12V4000 DS2000
2160 1728 x x x x x x x x x x x x x x x x x 16V 4000 G14F W2A MTU 16V4000 DS2250
2360 1888 x x x x x x x x x x x x x x x x x 16V 4000 G24F W2A MTU 16V4000 DS2500
2640 2112 x x x x x x x x x x x x x x x x x 20V 4000 G14F W2A MTU 20V4000 DS2750
2910 2328 x x x x x x x x x x x x x x x x x 20V 4000 G24F W2A MTU 20V4000 DS3100
3110 2488 x x x x x x x x x x x x x x x x x 20V 4000 G34F W2A MTU 20V4000 DS3300
Power Available voltages Emissions Certifications Uptime Housing Engine type Cooling Genset type
output (1) compliant variant (3)
Fuel consumption
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
EPA Tier 2
Enclosure
optimized
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Continuous – (3F)
900 1125 x x x x x x x x x x x x x 16V 2000 G26S W2A MTU 16V2000 DS1000
MTU 4000 DS
Data Center
1135 1418 x x x x x x x x x x x x 12V 4000 G14S W2A MTU 12V4000 DS1250
1400 1750 x x x x x x x x x x x x 12V 4000 G14S W2A MTU 12V4000 DS1500
1600 2000 x x x x x x x x x x x x 12V 4000 G24S W2A MTU 12V4000 DS1750
1825 2281 x x x x x x x x x x x x x x x 16V 4000 G14S W2A MTU 16V4000 DS2000
2045 2556 x x x x x x x x x x x x x x x 16V 4000 G24S W2A MTU 16V4000 DS2250
2275 2843 x x x x x x x x x x x x x x x 20V 4000 G14S W2A MTU 20V4000 DS2500
2500 3125 x x x x x x x x x x x x x x x 20V 4000 G24S W2A MTU 20V4000 DS2800
2800 3500 x x x x x x x x x x x x x x x 20V 4000 G44S W2A MTU 20V4000 DS3000
800
750
kVA
1000
38 / // /
Power
output (1)
600
800
640
kWe
x
x
380 V (3 Phase)
x
x
400 V (3 Phase)
x
x
x
415 V (3 Phase)
6300 V (3 Phase)
Available voltages
6600 V (3 Phase)
10000 V (3 Phase)
10500 V (3 Phase)
Continuous + CHP (3A) – 50 Hz / 1500 rpm
11000 V (3 Phase)
Fuel consumption
x
x
x
optimized
Continuous/Prime/Peak – Diesel Generator Sets
Emissions
NOx emission
optimized
compliant
EPA Tier 2
Exhaust emission EU
97/68 EC Stage II
Exhaust emission EU
97/68 EC Stage IIIA
Exhaust emission EU
97/68 EC Stage IIIA
under FLEX program
x
x
x
ISO 8528
x
x
x
CE / IEC
x
x
x
NFPA 110
Certifications
x
x
x
ISO 8528-5 - G2
class (2)
x
x
ISO 8528-5 - G3
Perform.
x
x
x
x
x
Uptime
Enclosure
x
x
Container
Housing
Engine type
A2A
A2A
Cooling
variant (3)
Genset type
39
Continuous + CHP
(3A)
Continuous/Prime/Peak – Gas Generator Sets
Continuous + CHP (3A) – 50 Hz (400V / NOx < 500 mg/Nm3)
Fuel type Output Energy Efficiency Methane Options Engine type Genset type
input (9) number (10)
11000V alternator
6300V alternator
Water Temp (°C)
400V alternator
Mixture Cooling
Low Temp. kWth
415V alternator
Exhaust (8) kWth
Therm. (7) kWth
Landfill Gas
Reference
kW
x 182 126 143 120 70 506 36,0 53,2 89,1 70 x x L9 MTU 6R400 GS
MTU 400 GS
x 192 106 149 120 29 50 534 36,0 47,8 83,7 70 x x L9 MTU 6R400 GS
x 202 109 154 120 36 40 560 36,1 47,0 83,0 70 x x L9 MTU 6R400 GS
x 221 120 134 120 17 40 558 39,6 45,5 85,1 80 x x Z5 MTU 6R400 GS
x 357 235 256 120 70 952 37,5 51,6 89,1 70 x x L9 MTU 12V400 GS
x 370 194 263 120 52 50 988 37,4 46,3 83,7 70 x x L9 MTU 12V400 GS
Continuous + CHP
x 390 233 241 120 28 40 995 39,2 47,6 86,8 70 x x Z6 MTU 12V400 GS
x 420 247 257 120 31 40 1064 39,5 47,4 86,8 80 x x Z6 MTU 12V400 GS
(3A)
x 221 130 132 120 17 40 559 39,5 46,9 86,4 120 x x Z8 MTU 6R400 GS
x 370 190 235 120 48 50 943 39,2 45,1 84,3 120 x x L8 MTU 12V400 GS
x 400 245 262 120 29 40 1015 39,4 50,0 89,4 120 x x Z7 MTU 12V400 GS
Cogeneration Module 100°/80°C heating water circuit
x 166 114 130 120 80 465 35,7 52,5 88,2 70 x x LH9 MTU 6R400 GS
x 323 206 250 120 80 879 36,7 51,9 88,6 70 x x LH9 MTU 12V400 GS
x 352 182 267 120 49 50 954 36,9 47,1 84,0 70 x x LH9 MTU 12V400 GS
x 420 239 269 120 36 40 1068 39,3 47,6 86,9 80 x x ZH6 MTU 12V400 GS
Fuel type Output Energy Efficiency Methane Options Engine type Genset type
input (9) number (10)
11000V alternator
6300V alternator
Water Temp (°C)
400V alternator
Mixture Cooling
Low Temp. kWth
415V alternator
Exhaust (8) kWth
Therm. (7) kWth
Landfill Gas
Reference
kW
x 776 401 422 120 47 40 1832 42,4 44,9 87,3 70 x x L33 MTU 8V4000 GS
MTU 4000 GS
x 854 403 431 120 51 43 1953 43,7 42,7 86,4 70 x x L64 MTU 8V4000 GS
x 999 476 482 120 67 43 2275 43,9 42,1 86,0 79 x x x L64 MTU 8V4000 GS
x 1013 483 486 120 68 43 2304 44,0 42,1 86,0 80 x x L64 MTU 8V4000 GS
x 1287 664 659 120 88 40 2974 43,3 44,5 87,8 80 x x x x x L33 MTU 12V4000 GS
x 1521 734 691 120 104 43 3438 44,2 41,4 85,7 80 x x x x x x L64 MTU 12V4000 GS
Continuous + CHP
x 1714 1005 821 120 113 40 3991 42,9 45,8 88,7 80 x x x x x L33 MTU 16V4000 GS
x 1999 950 928 120 125 43 4511 44,3 41,6 85,9 79 x x x x x L64 MTU 16V4000 GS
(3A)
x 2028 965 936 120 127 43 4573 44,3 41,6 85,9 80 x x x x x x L64 MTU 16V4000 GS
x 2145 1158 1077 120 142 40 4985 43,0 44,8 87,9 80 x x x x L33 MTU 20V4000 GS
x 2538 1241 1212 120 176 43 5751 44,1 42,7 86,8 80 x x x x x x L64 MTU 20V4000 GS
x 776 379 396 120 74 40 1806 43,0 42,9 85,9 120 x x L32 MTU 8V4000 GS
x 800 392 326 180 78 40 1861 43,0 38,6 81,6 120 x x L32 MTU 8V4000 GS
x 1169 571 602 120 103 40 2716 43,0 43,2 86,2 120 x x x x x L32 MTU 12V4000 GS
x* 1560 652 180 180 313 40 3616 43,1 44,5 87,7 120 x x x x x L32 MTU 16V4000 GS
x* 1950 734 873 180 97 40 4493 43,4 41,7 85,1 120 x x x x L32 MTU 20V4000 GS
Hot ambient conditions
x 776 446 420 120 32 53 1853 41,8 46,7 88,6 80 x x x x L32 MTU 8V4000 GS
x 1169 632 638 120 43 53 2747 42,6 46,2 88,8 80 x x x x x L32 MTU 12V4000 GS
x 1560 890 805 120 76 53 3651 42,7 46,4 89,2 80 x x x x x L32 MTU 16V4000 GS
x 1948 1035 1101 120 78 53 4577 42,6 46,7 89,2 80 x x x x x L32 MTU 20V4000 GS
x 2028 1203 985 120 95 58 4672 43,4 46,6 90,2 80 x x x x x L64FNER MTU 16V4000 GS
x 776 418 424 120 67 53 1854 41,9 45,4 87,3 120 x x L32 MTU 8V4000 GS
x 1169 619 631 120 90 53 2755 42,4 45,4 87,8 120 x x x x x L32 MTU 12V4000 GS
x* 1560 666 671 180 330 53 3652 42,7 45,6 88,4 120 x x x x L32 MTU 16V4000 GS
x* 1950 764 1044 120 425 53 4576 42,6 48,8 91,4 120 x x x L32 MTU 20V4000 GS
Low methane number
x 1560 951 937 120 99 53 3848 40,5 49,1 89,6 60 x x x x x L32ER MTU 16V4000 GS
x 1948 1143 1181 120 99 53 4812 40,5 48,3 88,8 60 x x x x x L32ER MTU 20V4000 GS
* with HT-extraction
Fuel type Output Energy Efficiency Methane Options Engine type Genset type
input (9) number (10)
11000V alternator
6300V alternator
Water Temp (°C)
400V alternator
Mixture Cooling
Low Temp. kWth
415V alternator
Exhaust (8) kWth
Therm. (7) kWth
Landfill Gas
Reference
kW
x 173 125 150 120 70 503 34,4 54,7 89,1 70 x x L9 MTU 6R400 GS
MTU 400 GS
x 245 230 154 100 675 36,3 56,9 93,2 80 x x D4 MTU 12V400 GS
x 366 189 276 120 64 40 1008 36,3 46,1 82,4 70 x x L9 MTU 12V400 GS
Cogeneration Module 100°/80°C heating water circuit
x 166 119 141 120 80 484 34,3 53,7 88,0 70 x x LH9 MTU 6R400 GS
x 240 221 156 110 666 36,0 56,6 92,6 70 x x DH4 MTU 12V400 GS
Continuous + CHP
x 776 416 443 120 48 40 1883 41,2 45,6 86,8 70 x L33 MTU 8V4000 GS
MTU 4000 GS
x 854 408 454 120 57 43 2017 42,3 42,7 85,1 70 x x L64 MTU 8V4000 GS
(3A)
x 1169 622 652 120 82 40 2795 41,8 45,6 87,4 70 x x x x L33 MTU 20V4000 GS
x 1521 766 713 120 111 43 3551 42,8 41,7 84,5 80 x x x x x x L64 MTU 8V4000 GS
x 2028 1010 696 120 136 43 4748 42,7 41,7 84,4 80 x x x x x L64 MTU 12V4000 GS
x 2145 1073 1090 120 136 43 5093 42,1 42,5 84,6 70 x x x x x L64 MTU 20V4000 GS
x 2538 1334 1220 120 190 43 5965 42,5 42,8 85,4 80 x x x x x L64 MTU 20V4000 GS
Hot ambient conditions
x 776 464 442 120 34 53 1906 40,7 47,5 88,2 80 x L32 MTU 8V4000 GS
x 1169 646 663 120 48 53 2823 41,4 46,4 87,8 80 x x L32 MTU 12V4000 GS
x 1560 921 841 120 84 53 3774 41,3 46,7 88,0 80 x x L32 MTU 16V4000 GS
x 2028 1260 1028 120 103 58 4826 42,0 45,5 89,4 80 x x x x x L64FNER MTU 16V4000 GS
Fuel type Output Energy Efficiency Methane Options Engine type Genset type
input (9) number (10)
132800V alternator
480V alternator
Mixture Cooling
Low Temp. kWth
Exhaust (8) kWth
Therm. (7) kWth
Landfill Gas
Reference
kW
x 358 257 268 120 981 36,5 53,5 90,0 70 x x Z6 MTU 12V400 GS
MTU 400 GS
on request 420 248 297 120 1110 37,8 49,1 86,9 80 x x Z6 MTU 12V400 GS
x 349 239 233 180 951 36,7 49,6 86,3 120 x x Z7 MTU 12V400 GS
on request 421 262 263 180 1123 37,5 46,7 84,2 120 x x Z7 MTU 12V400 GS
x 762 416 427 120 48 40 1859 41,0 45,3 86,3 70 x L33 MTU 8V4000 GS
MTU 4000 GS
x 840 457 451 120 49 40 2010 41,8 45,2 87,0 80 x L33 MTU 8V4000 GS
Continuous + CHP
x 1151 621 633 120 81 40 2773 41,5 45,2 86,7 70 x x x L33 MTU 12V4000 GS
x 1268 681 662 120 89 40 2997 42,3 44,8 87,1 80 x x x L33 MTU 12V4000 GS
(3A)
x 1550 938 784 120 101 40 3698 41,9 46,6 88,5 70 x x x x L33 MTU 16V4000 GS
x 1704 1025 825 120 115 40 4024 42,3 46,0 88,3 80 x x x x L33 MTU 16V4000 GS
x 1936 1112 1026 120 127 40 4622 41,9 46,3 88,1 70 x x x x L33 MTU 20V4000 GS
x 2129 1218 1082 120 144 40 5022 42,4 45,8 88,2 80 x x x x L33 MTU 20V4000 GS
x 762 391 323 180 75 40 1823 41,8 39,2 81,0 120 x L32 MTU 8V4000 GS
x 1151 586 490 180 105 40 2741 42,0 39,3 81,2 120 x x L32 MTU 12V4000 GS
x* 1550 656 656 180 313 40 3653 42,4 44,5 86,9 120 x x x L32 MTU 16V4000 GS
x* 1936 766 879 180 373 40 4535 42,7 44,5 87,2 120 x x x L32 MTU 20V4000 GS
Hot ambient conditions
x 762 458 423 120 32 53 1868 40,8 47,2 88,0 80 x L32 MTU 8V4000 GS
x** 1151 648 641 120 43 53 2767 41,6 46,6 88,2 80 x x x L32 MTU 12V4000 GS
x** 1550 909 810 120 77 53 3680 42,1 46,7 88,8 80 x x x x L32 MTU 16V4000 GS
x** 1936 1088 1108 120 79 53 4611 42,0 47,6 89,6 80 x x x x L32 MTU 20V4000 GS
x** 2014 1198 1000 120 98 58 4696 42,9 46,8 89,7 80 x L64FNER MTU 16V4000 GS
x 762 431 353 180 69 53 1877 40,6 41,8 82,4 120 x L32 MTU 8V4000 GS
x 1151 636 523 180 92 53 2787 41,3 41,6 82,9 120 x x L32 MTU 12V4000 GS
x* 1550 677 662 180 330 53 3698 41,9 45,1 87,0 120 x x x L32 MTU 16V4000 GS
x* 1936 797 864 180 425 53 4633 41,8 45,0 86,8 120 x x x L32 MTU 20V4000 GS
Low methane number
x 1550 939 942 120 85 53 3877 40,0 48,5 88,5 60 x x x x L32ER MTU 16V4000 GS
x 1936 1164 1188 120 100 53 4848 39,9 48,5 88,4 60 x x x x L32ER MTU 20V4000 GS
* with HT-extraction
** NOx 0.5g/bhph version available on request
Fuel type Output Energy Efficiency Methane Options Engine type Genset type
input (9) number (10)
13800V alternator
4160V alternator
Water Temp (°C)
440V alternator
480V alternator
600V alternator
Mixture Cooling
Low Temp. kWth
Exhaust (8) kWth
Therm. (7) kWth
Landfill Gas
Reference
kW
x 358 257 268 120 981 36,5 53,5 90,0 70 x x Z6 MTU 12V400 GS
MTU 400 GS
on request 420 248 297 120 1110 37,8 49,1 86,9 80 x x x Z6 MTU 12V400 GS
x 349 239 233 180 951 36,8 49,6 86,4 120 x x Z7 MTU 12V400 GS
on request 421 262 263 180 1123 37,5 46,7 84,2 120 x x x Z7 MTU 12V400 GS
x 764 409 422 120 47 40 1832 41,7 45,4 87,1 70 x x L33 MTU 8V4000 GS
MTU 4000 GS
x 841 452 448 120 49 40 1993 42,2 45,2 87,4 80 x x L33 MTU 8V4000 GS
Continuous + CHP
x 1152 610 628 120 80 40 2731 42,2 45,3 87,5 70 x x x L33 MTU 12V4000 GS
x 1272 675 659 120 88 40 2974 42,8 44,9 87,6 80 x x x L33 MTU 12V4000 GS
(3A)
x 1549 896 777 120 99 40 3649 42,4 45,8 88,3 70 x x x x L33 MTU 16V4000 GS
x 1705 984 821 120 113 40 3991 42,7 45,2 87,9 80 x x x x L33 MTU 16V4000 GS
x 1936 1095 1017 120 125 40 4560 42,5 46,3 88,8 70 x x x x L33 MTU 20V4000 GS
x 2129 1208 1077 120 142 40 4985 42,7 45,8 88,5 80 x x x x L33 MTU 20V4000 GS
x 764 388 321 180 74 40 1806 42,3 39,3 81,6 120 x x L32 MTU 8V4000 GS
x 1152 581 488 180 103 40 2716 42,4 39,4 81,8 120 x x x L32 MTU 12V4000 GS
x* 1549 638 652 180 313 40 3616 42,8 35,7 78,5 120 x x x L32 MTU 16V4000 GS
x* 1936 766 873 180 373 40 4493 43,1 36,5 79,6 120 x x x x L32 MTU 20V4000 GS
Hot ambient conditions
x 764 454 420 120 32 53 1853 41,2 47,2 88,4 80 x x x x L32 MTU 8V4000 GS
x 1152 642 638 120 43 53 2747 41,9 46,6 88,5 80 x x L32 MTU 12V4000 GS
x 1549 873 805 120 76 53 3651 42,4 46,0 88,4 80 x x x L32 MTU 16V4000 GS
x 1936 1080 1101 120 78 53 4577 42,3 47,7 89,9 80 x x x x L32 MTU 20V4000 GS
x 764 427 349 180 67 53 1854 41,2 41,9 83,1 120 x x L32 MTU 8V4000 GS
x 1152 629 519 180 90 53 2755 41,8 41,7 83,5 120 x x x L32 MTU 12V4000 GS
x* 1549 659 671 180 330 53 3652 42,4 36,4 78,8 120 x x x x x L32 MTU 16V4000 GS
x* 1936 797 856 180 425 53 4576 42,3 36,1 78,4 120 x x x x L32 MTU 20V4000 GS
Low methane number
x 1538 932 937 120 84 53 3848 40,0 48,6 88,5 60 x x x L32ER MTU 16V4000 GS
x 1936 1154 1181 120 99 53 4812 40,2 48,5 88,8 60 x x x x L32ER MTU 20V4000 GS
* with HT-extraction
Power Available Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) voltages class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
10000 -11000 V (3 Ph.)
6300 - 6600 kV (3 Ph.)
97/68 EC Stage II
380 - 415V (3 Phase)
ISO 8528-5 - G2
ISO 8528-5 - G3
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE / IEC
ORDE
25°C kVA 25°C kWe
MTU 0080/0113 DS
Prime
(3B)
50 / // / MTU Onsite Energy MTU Onsite Energy / // / 51
Continuous/Prime/Peak – Diesel Generator Sets
Prime (3B) – 50 Hz / 1500 rpm
Power Available Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) voltages class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
10000 -11000 V (3 Ph.)
6300 - 6600 kV (3 Ph.)
97/68 EC Stage II
380 - 415V (3 Phase)
ISO 8528-5 - G2
ISO 8528-5 - G3
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE / IEC
ORDE
kVA kWe
Prime
(3B)
1700 1360 x x x x x x x x x x x x 12V 4000 G14F W2A MTU 12V4000 DS1750
1880 1504 x x x x x x x x x x x x 12V 4000 G24F W2A MTU 12V4000 DS2000
2160 1728 x x x x x x x x x x x x 16V 4000 G14F W2A MTU 16V4000 DS2250
2360 1888 x x x x x x x x x x x x 16V 4000 G24F W2A MTU 16V4000 DS2500
2640 2112 x x x x x x x x x x x x 20V 4000 G14F W2A MTU 20V4000 DS2750
2910 2328 x x x x x x x x x x x x 20V 4000 G24F W2A MTU 20V4000 DS3100
3110 2488 x x x x x x x x x x x x 20V 4000 G34F W2A MTU 20V4000 DS3300
3390 2712 x(11) x x x x x x x x(11) x x x 20V 4000 G44F W2A MTU 20V4000 DS3600
Power Available voltages Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
97/68 EC Stage IIIA
97/68 EC Stage II
10000 V (3 Phase)
10500 V (3 Phase)
11000 V (3 Phase)
ISO 8528-5 - G2
ISO 8528-5 - G3
NOx emission
220 V (1 Phase)
220 V (3 Phase)
380 V (3 Phase)
400 V (3 Phase)
415 V (3 Phase)
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
ORDE
kVA kWe
MTU 0120 DS MTU 0096 DS
Prime
(3B)
54 / // / MTU Onsite Energy MTU Onsite Energy / // / 55
Continuous/Prime/Peak – Diesel Generator Sets
Prime (3B) – 60 Hz / 1800 rpm
Power Available voltages Emissions Certifications Uptime Housing Engine type Cooling Genset type
output (1) compliant variant (3)
Fuel consumption
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
Enclosure
optimized
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Prime
(3B)
111 139 x x x x x x x x x x x x x x OM924LA A2A MTU 4R0120 DS125
135 169 x x x x x x x x x x x x x x OM926LA A2A MTU 6R0120 DS150
163 204 x x x x x x x x x x x x x x OM926LA A2A MTU 6R0120 DS180
180 225 x x x x x x x x x x x x x x OM926LA A2A MTU 6R0120 DS200
Power Available voltages Emissions Certifications Uptime Housing Engine type Cooling Genset type
output (1) compliant variant (3)
Fuel consumption
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
Enclosure
optimized
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Prime
(3B)
2500 3125 x x x x x x x x x x x x x 20V 4000 G24S W2A MTU 20V4000 DS2800
2800 3500 x x x x x x x x x x x x x 20V 4000 G44S W2A MTU 20V4000 DS3000
Power Available voltages Emissions Certifications Fuel type Housing Engine type Genset type
output (1)
13800 V (3 Phase)
13200 V (3 Phase)
12470 V (3 Phase)
4160 V (3 Phase)
208 V (3 Phase)
380 V (3 Phase)
480 V (3 Phase)
600 V (3 Phase)
240 V (3 Phase)
EPA certified
Natural Gas
Propan Gas
Enclosure
Container
NFPA 110
ISO 8528
IBC 2012
UL2200
kWe kVA
Prime
(3B)
60 / // / MTU Onsite Energy MTU Onsite Energy / // / 61
Continuous/Prime/Peak – Diesel Generator Sets
Peak (3G) – 50 Hz / 1500 rpm
Power Available voltages Emissions Certifications Perform. Uptime Housing Engine type Cooling Genset type
output (1) class (2) compl. variant (3)
Exhaust emission EU
Exhaust emission EU
Exhaust emission EU
97/68 EC Stage IIIA
97/68 EC Stage II
10000 V (3 Phase)
10500 V (3 Phase)
11000 V (3 Phase)
ISO 8528-5 - G2
ISO 8528-5 - G3
NOx emission
380 V (3 Phase)
400 V (3 Phase)
415 V (3 Phase)
Enclosure
optimized
optimized
Container
NFPA 110
ISO 8528
CE / IEC
ORDE
kVA kWe
MTU 4000 DS MTU 2000 DS
Peak
(3G)
62 / // / MTU Onsite Energy MTU Onsite Energy / // / 63
Diesel Generator Sets
Enclosures – 50 Hz / 1500 rpm
Height (mm)
Width (mm)
Capacity (l)
dBA @ 7m
2100 957 1349 60,0 100 MTU 4R0080 DS45
MTU 0080/0113 DS
Containerized
Gensets
64 / // / MTU Onsite Energy MTU Onsite Energy / // / 65
Diesel Generator Sets
Enclosures – 60 Hz / 1800 rpm
IBC 2012/OSHPD
ISO 9001:2008
UL 2200
CSA
79,2 72,4 69,6 79,2 72,4 69,6 x x x x MTU 4R0060 DS30
MTU 0060/0113 DS
Containerized
90,7 86,0 74,0 91,0 86,5 74,5 x x x x MTU 10V1600 DS450
Gensets
91,0 86,5 74,5 91,0 86,6 74,9 x x x x MTU 10V1600 DS500
92,8 88,0 81,0 92,9 88,0 84,7 x x x x MTU 12V1600 DS550
92,9 88,0 81,2 92,8 89,0 84,2 x x x x MTU 12V1600 DS600
C/F C/F C/F C/F C/F C/F x x x x MTU 12V1600 DS650
IBC 2012/OSHPD
ISO 9001:2008
UL 2200
CSA
89,0 86,4 71,9 89,0 86,4 71,9 x x x x MTU 12V2000 DS750
MTU 2000 DS
Containerized
Gensets
68 / // / MTU Onsite Energy MTU Onsite Energy / // / 69
Diesel Generator Sets
Power Modules(5) - 50/60Hz – Europe, Africa, Asia and Australia
Power Available Emissions Noise Dimensions Frequency Application Certifications Engine type Cooling Genset type
output (1) voltages level variant (3)
50/60Hz switchable
Continuous Power
Fuel consumption
CSC certification
Standby Power
Length (mm)
Prime Power
Height (mm)
Width (mm)
EPA Tier 2
optimized
NFPA 110
ISO 8528
280 V
400 V
480 V
600 V
dBA @
Size
kWe kVA 1m Hz
640 790 x x 80(4) 20ft HC 6058 2438 2896 50 x x x 16V 2000 G26F A2A MTU 16V2000 DS1250
MTU 2000 DS
908 1110 x x x 80(4) 20ft HC 6058 2438 2896 50 x x x 16V 2000 G36F A2A MTU 16V2000 DS1250
1000 1230 x x 80(4) 20ft HC 6058 2438 2896 50 x x x 16V 2000 G86F A2A MTU 16V2000 DS1250
1100 1250 x x x 80(4) 20ft HC 6058 2438 2896 50 x x x 18V 2000 G26F A2A MTU 16V2000 DS1400
1120 1390 x x 80(4) 20ft HC 6058 2438 2896 50 x x x 18V 2000 G76F A2A MTU 16V2000 DS1400
1531 1914 x x 99 40ft HC 12192 2438 2896 50 x x x x 16V 4000 B24F W2A MTU 16V4000 DS2560
MTU 4000 DS
1807 2259 x x 103 40ft HC 12192 2438 2896 60 x x x x 16V 4000 B24S W2A MTU 16V4000 DS2560
1836 2295 x x 99 40ft HC 12192 2438 2896 50 x x x x 16V 4000 G24F W2A MTU 16V4000 DS2560
2109 2636 x x 103 40ft HC 12192 2438 2896 60 x x x x 16V 4000 G24S W2A MTU 16V4000 DS2560
2048 2560 x x 99 40ft HC 12192 2438 2896 50 x x x x 16V 4000 G84F W2A MTU 16V4000 DS2560
2321 2901 x x 105 40ft HC 12192 2438 2896 60 x x x x 16V 4000 G84S W2A MTU 16V4000 DS2560
1888 2360 x x (11)
40ft HC 12192 2438 2896 60 x x x 16V 4000 G24S Tabletop radiator Caribic Configuration
1440 1800 x x (11)
40ft HC 12192 2438 2896 60 x x x 16V 4000 B24S Tabletop radiator Caribic Configuration
Containerized
Gensets
70 / // / MTU Onsite Energy MTU Onsite Energy / // / 71
Gas Generator Sets – Continuous/Prime/Peak
Power Modules - 50/60Hz
Power Available Emissions Dimensions Frequency Application Engine type Fuel type Genset type
output (1) voltages
Gas (Biogas/Sewage/
NNG = Non-Natural
NOx<500 mg/Nm³
NOx<250 mg/Nm³
Continuous Power
NG = Natural Gas
Length (mm)
Height (mm)
Width (mm)
Landfill)
400 V
480 V
50 Hz
60 Hz
Size
kWe
Power Application
762 - 1013 x x 40ft HC 12203 2438 2896 x x L32/L33/(L64) NG/NNG MTU 8V4000 GS
1151 - 1523 x x x 40ft HC 12203 2438 2896 x x x L32/L33/(L64) NG/NNG MTU 12V4000 GS
1537 - 2030 x x 40ft HC 12203 2438 2896 x x L32/L33/(L64) NG/NNG MTU 16V4000 GS
1948 - 2535 x x 40ft HC 12203 2438 2896 x x L32/L33/(L64) NG/NNG MTU 20V4000 GS
CHP Application
180 - 220 x x x 30+ 12203 2438 2896 x x x L/Z NG/NNG MTU 6R400 GS
40ft HC 9000 3000 3000
245 - 420 x x x 31+ 12203 2438 2896 x x x L/Z NG/NNG MTU 12V400 GS
40ft HC 9000 3000 3000
762 - 1013 x x 40+ 12203 3200 3200 x x L32/L33/L64 NG/NNG MTU 8V4000 GS
1151 - 1523 x x 40+ 12203 3200 3200 x x L32/L33/L64 NG/NNG MTU 12V4000 GS
1537 - 2030 x x 47+ 14200 3200 3200 x x L32/L33/L64 NG/NNG MTU 16V4000 GS
1948 - 2535 x x 47+ 14200 3200 3200 x x L32/L33/L64 NG/NNG MTU 20V4000 GS
Gensets + CHP
Containerized
72 / // / MTU Onsite Energy MTU Onsite Energy / // / 73
Energy Pack
Battery Storage
Round trip
Length (mm)
Height (mm)
Width (mm)
efficiency
(max) kV
0.3C (RTE) 2C
(min) V
25°C 2C at BOL* 80% DoD**
Size
UL
CE
kWh kVA (max) % 25°C
Energy Pack
74 / // / MTU Onsite Energy MTU Onsite Energy / // / 75
CLASSIFICATION FOR DATA CONVERSION TABLE
CENTER CONTINUOUS POWER NUMBERS TO BACK YOU UP.
ACCORDING TO THE
UPTIME INSTITUTE
Suitable MTU Onsite Energy Standardized Backup (3D) Data Center Continuous (3F)
application Prime Power for Continuous (3A)
Stationary Emergency (3E)
Prime (3B)
Peak (3G)
For complete definition see http://uptimeinstitute.com/
A Only available for 50Hz markets Available power for diesel generator sets – C/F: Consult factory
50Hz/1500 rmp
B Unlimited hours in data center application where D: Lambda = 1 with 2-way-catalyst
Standard:
a reliable grid/utility is present.
Site altitude above sea level: 400 m L: Leanburn with single stage intercooling
// Intake air temperature: 40° C
Application descriptions, e.g. load factor, applies to MTU Z: Leanburn with two stage intercooling
powered equipment. NOx emission optimized:
// Site altitude above sea level: 100 m Cooling variants:
(1) P
ower output based on 400V, fuel consumption opt. (6) Rated power at nominal voltage, // Intake air temperature: 25° C A2A: air-to-air charge air cooling (TD)
emission level and standard or optional generator. power factor = 1,0 and nominal frequency
For arrangements with other emissions, voltages NEA Singapore: W2A: water-to-air charge air cooling (TB)
(7) Heat output from engine cooling // Site altitude above sea level: 100 m
and/or optional generators, ratings may vary.
with tolerance of ± 8% // Intake air temperature:
Series 4000 without cooling package. 40° C
(8) Heat output from exhaust with tolerance of ± 8%
(2) Ambient conditions and load application
Available power for diesel generator sets –
acc. to ISO 8528 (9) Performance data in accordance with
60Hz/1800 rmp
ISO 3046/I-2002 with tolerance of 5%
(3) Cooling variants: A2A: air-to-air charge air cooling Standard:
(TD); W2A: water-to-air charge air cooling (TB) (10) Referenced methane number // Site altitude above sea level: 400 m
// Intake air temperature: 25° C
(4) Sound levels in accordance with European Noise (11) Availability on request
Directive (2000/14/EC), for further information on
(12) Planned for Q2/2019
acoustic data see datasheets
(13) Single-phase units only
(5) Data Center configuration available