Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
313 views88 pages

Software Operating Instructions: Quadnet / Duonet OSP - V3.0x

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 88

Quadnet / Duonet OSP – V3.

0x
(Suitable for Quadnet / Duonet control and repeater panels from V3.00)

Software Operating Instructions


(TO BE RETAINED BY THE COMMISSIONING ENGINEER)

26-1006 Issue 5

1
Quadnet / Duonet OSP Software Operating Instructions

Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care
has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in
respect of such contents.

Due to the complexity and inherent importance of a life risk type system, training on this equipment is essential and commissioning should only
be carried out by competent persons.

Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with, without variation.

E&OE.

Fike equipment is protected by one or more of the following patent no’s: GB2426367, GB2370670, EP1158472, PT1035528T, GB2346758,
EP0917121, GB2329056, EP0980056, GB2325018, GB2305284, EP1174835, EP0856828, GB2327752, GB2313690

© 2010 Fike Safety Technology Ltd. All rights reserved. Document revised January 2013.

2
Quadnet / Duonet OSP Software Operating Instructions

Contents

Introduction .......................................................................................................................... 6

Getting Started ..................................................................................................................... 6


System Requirements .............................................................................................. 6
Physical Connections ............................................................................................... 7
Software Installation ................................................................................................. 7
Data Transfer ............................................................................................................ 8
Control Panel Menu Operation ................................................................................. 9
Map of System Operations ....................................................................................... 10

Quadnet / Duonet OSP Layout ........................................................................................... 11


Main Screen .............................................................................................................. 11
File Menu .................................................................................................................. 12
New .............................................................................................................. 12
Open............................................................................................................. 12
Save As. ....................................................................................................... 12
Print .............................................................................................................. 12
Print Device Details ...................................................................................... 13
Print DLU Details .......................................................................................... 13
Open Backup ............................................................................................... 14
Exit ............................................................................................................... 14
New Files .................................................................................................................. 14
Tools Menu ............................................................................................................... 15
Engineer Notes ............................................................................................ 15
Panel Integrity Check ................................................................................... 16
Site Config Report ........................................................................................ 16
Event Log Report ......................................................................................... 17
Network Event Log Report ........................................................................... 19
Default Zone to Zone Cause & Effects. ....................................................... 20
Engineer Functions ...................................................................................... 20
Engineer Controls ........................................................................................ 21
Help Menu................................................................................................................. 21
About Page .................................................................................................. 21
Upload Data from Panel. .......................................................................................... 22
Add ............................................................................................................... 22
Delete ........................................................................................................... 22
Copy ............................................................................................................. 23
Import ........................................................................................................... 23
Upload Data .............................................................................................................. 24
Upload Event Log ..................................................................................................... 24
Upload Network Event Log ....................................................................................... 25
Download Data to Panel. .......................................................................................... 25
Panel Details ............................................................................................................. 26
Panel Summary............................................................................................ 27
Panel Details ................................................................................................ 28
Delays & Timers ........................................................................................... 29
Day/Night Mode ........................................................................................... 30
Panel Inputs ................................................................................................. 31
Panel Outputs .............................................................................................. 32
Network ........................................................................................................ 33
Printer ........................................................................................................... 34

3
Quadnet / Duonet OSP Software Operating Instructions

Device Details – Device Details Tab. ....................................................................... 35


Type ............................................................................................................ 35
Zone ............................................................................................................ 35
Smoke Detector ........................................................................................... 35
Heat Detector ............................................................................................... 36
Alarm Stages for Sounders (3 Stages) ....................................................... 36
Volume Levels for Sounders (3 stages) ...................................................... 36
AC (Alarm Confirmation) .............................................................................. 36
Edit Labels ................................................................................................... 37
Edit Zone ...................................................................................................... 37
Sort by Address ............................................................................................ 37
Sort by Zone ................................................................................................. 37
Device Details .............................................................................................. 37
Zone Details ................................................................................................. 38
All Details ..................................................................................................... 38
Add Device ................................................................................................... 39
Delete Device ............................................................................................... 39
Data Entry .................................................................................................... 40
Sound Demo ................................................................................................ 41
Apply Zone ................................................................................................... 41
Apply Format ................................................................................................ 42
Print .............................................................................................................. 42
Device Details – Loop Loading Screen. ................................................................... 43
Loop Load Calcs .......................................................................................... 44
Reset DLU .................................................................................................... 44
Device Types ............................................................................................... 45
Device Details – Device I/O Tab. .............................................................................. 49
Edit I/O Labels .............................................................................................. 49
Edit I/O Zone ................................................................................................ 49
Sort by Address ............................................................................................ 49
Sort by Zone ................................................................................................. 49
Device I/O Details ........................................................................................ 50
Zone I/O Details ........................................................................................... 51
All I/O Details ............................................................................................... 52
Device Details – Graphical View Tab. ...................................................................... 52
Editing a Device ........................................................................................... 53
Device Details – Connection Map Tab. .................................................................... 55
Cause and Effect ...................................................................................................... 57
Zone to Zone Cause and Effect ................................................................... 58
Point to Point Cause and Effect ................................................................... 62
Diagnostics ............................................................................................................... 64
CIE Diagnostic ............................................................................................. 65
Loop Diagnostic ........................................................................................... 65
Panel Integrity Check ................................................................................... 66

Routine Operations ............................................................................................................. 67


Programming a New Installation ............................................................................... 67
Adding and Deleting Devices on Existing Systems .................................................. 68
Programming Loop Inputs and Outputs .................................................................... 69
I/O Options ................................................................................................... 69
Output Groups .............................................................................................. 69
Programming Panel Inputs and Outputs .................................................................. 70
I/O Options ................................................................................................... 70
Output Groups .............................................................................................. 71
Programming Alarm Confirmation ............................................................................ 73
Alarm Confirmation Delay ............................................................................ 74
Alarm Stage 1 .............................................................................................. 74

4
Quadnet / Duonet OSP Software Operating Instructions

Example Configurations ..................................................................................................... 75


Instant Alarms ........................................................................................................... 75
Smoke Alert .............................................................................................................. 76
Phased Evacuation ................................................................................................... 77
Alarm Confirmation with Warden Call ....................................................................... 78
Panel Details ................................................................................................ 79
Device Details .............................................................................................. 79
Cause & Effect ............................................................................................. 80

Technical Data...................................................................................................................... 81
Duonet Control Panel ............................................................................................... 81
Quadnet Control Panel ............................................................................................. 81
OSP Version Compatibility. ...................................................................................... 82
Technical Support ..................................................................................................... 82

Configuration Sheets .......................................................................................................... 83


Device Details ........................................................................................................... 83
Detection Zone/Alarm Zone Details .......................................................................... 84
Your Notes ................................................................................................................ 86

Important Points .................................................................................................................. 87

5
Quadnet / Duonet OSP Software Operating Instructions

Introduction
Quadnet / Duonet OSP is the name given to the high level software package written to enable the
individual configuration of the Duonet and Quadnet fire alarm systems. The Windows based program
allows the system to be set up for each application. This includes the setting of detection modes,
subsequent actions to be taken and individual sound patterns. Note that whichever panel is used, there is
no difference in the mode of operation of the program.

Much thought has taken place to implement operations in as simple a way as possible whilst not losing
flexibility through over-simplification. Hence, complicated arrangements with three alarm stages may be
arranged as required in order to tailor system operation to the client’s building or safety procedures.

Tools are also included to enable you to create reports and specifications from your programming,
including both configuration and event log reports.

Getting Started

System Requirements
The Quadnet / Duonet OSP configuration software is available on the Fike Software CD. In order to run the
program you will require the following:

• A desktop or laptop PC running the Windows XP or Windows 7 operating system (32-bit


versions) with at least 1GB RAM.
o The PC must have a CD drive in order to install your software.
o The PC must have a USB port for connection to the panel.
• A USB interface lead for connection of the PC to the control panel.

IMPORTANT NOTE:

OSP v3.xx must not be used with panels prior to v3.00.

6
Quadnet / Duonet OSP Software Operating Instructions

Physical Connections
The USB Interface lead connects between the USB port on the control panel and any USB port on the PC.

Software Installation
In order to commence installation, insert the OSP CD-ROM in your CD-ROM drive. The disc will
automatically run and open up a browser style menu screen containing a number of different directories,
including one that is titled ‘Software’. Open this directory and then open the directory titled ‘Fike Quadnet
v30x’ (or Duonet OSP 3.0x.exe) - as the version may vary, simply choose the latest available. Run the
‘Setup.exe’ file and follow the instructions while the software loads onto your hard disk drive.

The software will be installed in the following location:

C:\ Program Files \ Fike \ QuadnetOSP \

or

C:\ Program Files \ Fike \ DuonetOSP \

A shortcut from the file titled ‘Quadnet OSP 3.0x’. (or ‘Duonet OSP 3.0x’) may then be copied onto the
desktop for ease of access, and labelled with the correct version number to prevent confusion with possible
future releases, as shown below.

Note that USB drivers for the Quadnet / Duonet will have to be installed before the panel can be connected
to the USB port.

7
Quadnet / Duonet OSP Software Operating Instructions

Data Transfer.
The Quadnet / Duonet is defined as an Addressable Intelligent Detector System, or an Addressable
Fire Detection and Alarm System with Independent Distributed Intelligence. Distributed intelligence
signifies that the signal processing is spread throughout the system in the form of a microprocessor in
every device, in order that the decisions about fires and faults are taken within the detector itself.

The detector is capable of being remotely programmed for different modes of detection, sound patterns,
etc. Thus we have two separate data transfer functions - get-config / re-config between devices and control
panel, and upload / download between control panel and computer.

The get-config / re-config functions are operated from the control panel at ‘Access level 3 (Engineer)’. If
you have not entered Engineer mode at the PC, the functions will not work and the PC will display warning
messages. Generally the configuration must be loaded to the control panel (get-config), before any upload
to computer, and vice versa - the configuration must be loaded to the devices (re-config) after any
download from computer to control panel.

If a device is to be replaced with a similar type, then after re-initialising the loop the system must be
reconfigured. The control panel memory holds the system configuration data, so in the event of a device
replacement, a PC is not necessarily required to reconfigure the device.

8
Quadnet / Duonet OSP Software Operating Instructions

Control Panel Menu Operation

At Access Level 3 (Engineer), the main Fire Alarm Controls are enabled, and the following System
Controls are accessible:

1. View Logs 1. Current Warnings


2. Test Display 2. Current Faults
3. Current Disablements
4. Current Tests
5. Event Logs 1. All Events
2. By Event Type 1. User Action
3. Disable / Enable 1. Detection Zone
2. Panel Event
2. Device
3. Fire Event
3. Sounders
4. Fault Event
4. Fire Outputs
5. Fault Outputs 3. By Device Type 1. Multipoint with sounder
6. Default to All Enabled 4. By Loop No - Device No 2. Multipoint
5. By Date 3. Manual Call Point with
sounder
4. Set Time & Date 4. Manual Call Point
5. Test Modes 1. Silent Test 5. Sounders & Strobes
2. Local Audible Test 6. Input / Output Modules
7. Conventional Zone Module
3. System Test
6. Network Events 1. All Events
2. By Event Type
6. Day / Night Mode 1. Override into Day Mode 3. By Panel
2. Override into Night Mode 4. By Date
3. End all Overrides
4. View Day / Night settings

7. Engineer Controls 1. Loop Controls 1. Stop Loop


2. Fast Init : Restart an Unmodified Loop

3. Std Init: : Autolearn Loop & Re-address


4. Get Configuration from Devices
5. Re Configure Devices

2. View / Edit Attributes 1. Device


2. Control Panel 1. Change Codes
2. Loop Card Version
3. Panel Serial No.
4. Panel ID
5. Panel Mode

3. Zone 6. Enable Buzzer Beep on Keypress

4. Network
5. Aux I/O
6. View No of Devices Programmed
7. View No of Devices in Last Init

3. Direct Commands 1. Find Device


4. Loops
5. Printer
6. Clear all OSP Labels
9
Quadnet / Duonet OSP Software Operating Instructions

Map of System Operations

NEW SYSTEM EXTENSION


START
IS THIS A NEW SYSTEM OR AN EXTENSION , UPLOAD TO
STOP LOOP, SELECT OSP MODE
EXTENSION TO AN EXISTING ONE? PC, SAVE NEW FILE

NEW

FINISH INSTALLATION OF CABLE, ADD/DELETE DEVICES AND SAVE THE FILE.


BASES, BACK BOXES & LINKS THEN TREAT AS PRE-PROGRAMMED SYSTEM
INITIALISATION

INITIALISATION
NO INVESTIGATE FAULTS AND
LOOP CONTINUITY AND
INSULATION TEST RESULTS OK? RECTIFY

YES

IF THIS IS A NEW INSTALLATION


THEN FIT ONE DEVICE ONLY

EXTENSION NEW

DOES THE SYSTEM INITIALISE NO REMOVE DEVICE, INVESTIGATE


CORRECTLY? FAULT AND RECTIFY

YES

INSTALL A SUITABLE BATCH OF


DEVICES, NOTING SERIAL NOs

REMOVE DEVICES, INVESTIGATE


DOES THE SYSTEM INITIALISE NO
FAULTS AND RECTIFY
CORRECTLY?
YES

NO ARE ALL THE DEVICES NOW


INSTALLED AND INITIALISED OK?
YES

YES
HAVE YOU PRE-PROGRAMMED OPEN PREVIOUSLY
YOUR CONFIGURATION? PROGRAMMED FILE

NO

STOP LOOP, SELECT OSP MODE, ALTER THE CONFIGURATION


UPLOAD TO PC TO SUIT

PROGRAM ANY ATTRIBUTES AS


REQUIRED AND SAVE THE FILE

DOWNLOAD DATA TO PANEL CHECK THE FILE, ALTER AS


REQUIRED AND SAVE
PROGRAMMING

PROGRAMMING
IS THE LOOP UNCHANGED SINCE NO INITIALISE THE LOOP
THE LOOP WAS STOPPED?

YES
REMOVE DEVICES, INVESTIGATE FAULTS
START LOOP AND RECTIFY. THEN REPLACE DEVICES

NO
DID THE LOOP START UP
AND RUN CORRECTLY?
YES

RECONFIG THE LOOP DEVICES

RESET THE CONTROL PANEL

EXIT AL3 AND TEST THE SYSTEM


FOR CORRECT OPERATION

ENSURE RESPONSIBLE PERSON


IS TRAINED AND FILL IN LOG BOOK

NEW SYSTEM EXTENSION

10
Quadnet / Duonet OSP Software Operating Instructions

Quadnet / Duonet OSP Layout

Main Screen

The ‘Status & Menu’ screen is the front page, index and guide for programming using Quadnet / Duonet
OSP. Functions are controlled via the various on-screen buttons (arranged vertically to the left of the
screen) and menus (arranged horizontally at the top of the screen).

When features in the OSP program are selected by pressing buttons, Cancel and OK buttons will appear at
the bottom of the screen. OK is pressed to accept any changes to the data that you make. Cancel is
pressed to leave the feature without saving any data changes.

11
Quadnet / Duonet OSP Software Operating Instructions

‘File’ Menu

The ‘File’ menu contains the following options:

New Site

This feature will create a ‘New’ configuration file with extension (*.site).

This file type may be classed as ‘unlocked’, allowing modifications to be made to the loop configuration.

Note that a site may consist of more than one panel.

Open Site

This feature will open an existing, or ‘Old’ configuration file. This function is also repeated in the form of an
on-screen button in the toolbar immediately below the file menu.

i.e.

This file type may be classed as ‘locked’, allowing no modifications to be made to the loop configuration.
Thus you are prevented from downloading an incorrect file into a system.

Save As

This feature will save configuration file to the file name and address of your choice. This function is also
repeated in the form of an on-screen button in the toolbar immediately below the file menu.

i.e.

Print

This feature has two sub options as shown in the sub-menu below.

12
Quadnet / Duonet OSP Software Operating Instructions

Print Device Details

This allows you to send a summary of all the devices to the printer. There is also a print button on the
device details screen for this operation.

Landscape orientation (not portrait) is recommended.

For each device, the following information is given.

Loop Number
Device Number
Device Label
Serial Number
Device Type
No of Spurs
Zone No
Smoke Detection details if applicable
Heat Detection details if applicable
Sound Pattern 1 if applicable
Volume Level 1 if applicable
Sound Pattern 2 if applicable
Volume Level 2 if applicable
Sound Pattern 3 if applicable
Volume Level 3 if applicable
Alarm Confirmation (ON/OFF)

Print DLU Details

This allows you to send a summary of further information about all the devices (including DLU details) to
the printer.

Landscape orientation (not portrait) is recommended.

For each device, the following information is given.

Loop Number
Device Number
Device Label
Serial Number
Device Type
Sub Type
Sound Pattern 1 if applicable
Volume Level 1 if applicable

13
Quadnet / Duonet OSP Software Operating Instructions

Sound Pattern 2 if applicable


Volume Level 2 if applicable
Sound Pattern 3 if applicable
Volume Level 3 if applicable
DLU1 value
DLU2 value
DLU3 value

Open Backup

This allows you to open the backup of the previously saved configuration file. It will have been
automatically created in the format *.sitebak

The screen prompt is shown below.

Exit

Exit the Quadnet / Duonet OSP program.

New Files
You will be first be prompted with a “Save As” screen for a name for the site. Site data files are saved with
type “.site”.

There will then be a prompt for the language to be used.

English (United Kingdom) is the default.

A new site data file will now be created. Initially it will consist of a single panel (Panel 001) with a single
loop. With a Duonet system, up to 2 loops may be configured. With a Quadnet system, up to 4 loops may
be configured.

You may now amend the configuration file as described in the following pages. This ‘New’ file does not
contain initialised device address details or serial numbers.

The file may then be sent to the control panel with the download command. After download, remember to
carry out the following:

14
Quadnet / Duonet OSP Software Operating Instructions

1. ‘Initialise’ Loop

2. ‘Reconfig’ data to loop devices

3. ‘Reset’ system

4. Test system for correct operation

Tools Menu

Engineer Notes

This feature allows the Engineer to enter assorted notes in free-form format. The file can be saved in “.txt”
format by pressing “Save”.

15
Quadnet / Duonet OSP Software Operating Instructions

Panel Integrity Check

Site Config Report

The Site Config Report option allows the creation of text files from your configuration, in the *.txt format.
The following screen offers options that may be ticked so that you can select which details are included in
the site report.

Before the report is shown, the engineer is prompted to enter a name.

16
Quadnet / Duonet OSP Software Operating Instructions

A typical report is shown below.

The site report file may be saved in the format ‘file_name’.txt by utilising the ‘Save As’ command in the File
menu at the top of the screen. The file may be opened in Microsoft WordPad or imported into Microsoft
Word. However, some fonts will cause the tabulation to alter when using Microsoft Word. The print function
may be used directly from the ‘File’ menu, from within Word or WordPad.

Event Log Report

The Event Log Report option allows the creation of text files from any event logs which have previously
been uploaded from the panel. The files will be in the *.txt format. The following screen offers options that
may be ticked so that you can select which details are included in the event log report.

17
Quadnet / Duonet OSP Software Operating Instructions

A typical report is shown below.

18
Quadnet / Duonet OSP Software Operating Instructions

As with the site report file, the event log report may be saved in the format ‘file_name’.txt by utilising the
‘Save As’ command in the File menu at the top of the screen. The file may be opened in Microsoft
WordPad or imported into Microsoft Word. However, some fonts will cause the tabulation to alter when
using Microsoft Word. The print function may be used directly from the ‘File’ menu, from within Word or
WordPad.

Network Event Log Report

A network event log report may be made in the same way as an event log report. Note that the options
which can be selected are fewer as this event log only covers network events.

19
Quadnet / Duonet OSP Software Operating Instructions

Default Zone to Zone Cause & Effects

This feature can be used to reset the default Zone to Zone cause and effect data for the currently selected
panel to the original factory settings. An “Are You Sure” prompt is given.

For each of the 128 detection zones, the settings will be as follows

Group 1 – ALL Zones (1-28) selected. Links for Smoke alarm /MCP/heat/input set to Alarm stage 3. No
delays used.

Group 2 – NO Zones selected. No links set.

Engineer Functions

Certain functions are provided for use by qualified engineers only. These have the drastic effect of deleting
all zone to zone Cause and Effect or deleting all point to point Cause and Effect and so they are password
protected.

Before any of the Engineer Functions can be used, the engineer must enter an AL4 security code.

20
Quadnet / Duonet OSP Software Operating Instructions

Engineer Controls

The Engineer Controls option is for the use of our engineers only. They can access this feature using a
special security code.

‘Help’ Menu

The Help Menu contains a single option which will display the current software version.

About Page

The About Page obtained from the Help menu gives details of the current software version of the OSP
program. An example is shown below.

21
Quadnet / Duonet OSP Software Operating Instructions

Upload Data from Panel


Note that before uploading panel data, a site data file (either newly created or an existing file) must have
been opened on the PC.

Prior to an Upload of the configuration from the control panel to the PC, or a Download of the configuration
from PC to the control panel, it is necessary for the panel to be in ‘Access Level 3 (Engineer Mode)’. The
panel must be connected to the PC via a USB lead.

Note that if the panel is left for a period of time, it will log itself out of Access Level 3 (Engineer Mode) so it
is best to check that it is in Engineer mode before doing anything at the PC.

The upload button is found to the left of the main screen

Add

The Add button on the upload screen allows you to add a new panel to the current configuration on the PC.
This feature is also available on the “Panel Details” screen available from the “Panel Details” button.

Delete

The Delete button on the upload screen allows you to delete a panel to the current configuration on the PC.
This feature is also available on the “Panel Details” screen available from the “Panel Details” button.

22
Quadnet / Duonet OSP Software Operating Instructions

Copy

The Copy button on the upload screen allows you to copy the details from an existing panel to a new panel
number on the PC. This feature is also available on the “Panel Details” screen available from the “Panel
Details” button.

In the above example, we have selected Panel 001 from that site and the data from that panel will be
copied into Panel 008 in our configuration. The data may only be copied to a panel number that does not
already exist in the configuration. If you want to copy the data to an existing panel, the existing panel
should first be deleted using the Delete button.

Import

The Import button allows you to browse for a DIFFERENT site and copy the details of a panel on that site
to any panel number on the PC. This feature is also available on the “Panel Details” screen available from
the “Panel Details” button.

In the above example, we have picked a different site named Test 30-06-11.site. We have selected Panel
001 from that site and the data from that panel will be copied into Panel 003 in our configuration. It does
not matter whether Panel 003 already exists in our configuration, but if it does, any data will be overwritten.

23
Quadnet / Duonet OSP Software Operating Instructions

Upload Data

The Upload Data button allows you to upload data from the currently connected panel. A progress bar is
shown while the data is uploading. If there is a problem, a warning will be given. If this happens, you should
disconnect the USB and re-connect it before trying again. Also remember that the panel must be in
Engineer Mode.

Note that you must select a panel in the PC configuration which will be given the uploaded data. When this
has been selected you can press the Accept Upload button as shown in the example screen below.

If the panel that you have chosen already has data assigned to it, a prompt as follows will be given so that
you can change your mind.

Upload Event Log

It is possible to upload the event log from a panel. It is necessary for the panel to be in ‘Access Level 3
(Engineer Mode)’ and the panel must be connected to the PC via a USB lead.

You can save event logs with different dates and times from more than one panel on the PC.

Event logs can be viewed at a later date and a hard copy made using the Event Log Report feature in the
Tools menu.

24
Quadnet / Duonet OSP Software Operating Instructions

Upload Network Event Log

It is possible to upload the network event log from a panel. It is necessary for the panel to be in ‘Access
Level 3 (Engineer Mode)’ and the panel must be connected to the PC via a USB lead.

You can save network event logs with different dates and times on the PC.

Network event logs can be viewed at a later date and a hard copy made using the Network Event Log
feature in the Tools menu.

Download Data to Panel

Prior to a Download of configuration data from PC to the control panel, it is necessary for the panel to be in
‘Access Level 3 (Engineer Mode)’. The panel must be connected to the PC via a USB lead.

Note that if the panel is left for a period of time, it will log itself out of Access Level 3 (Engineer Mode) so it
is best to check that it is in Engineer mode before doing anything at the PC.

The download button is found to the left of the main screen. On pressing it, the following screen is
obtained.

The Download button on this screen allows you to download configuration data from a selected panel in the
PC configuration to the panel to which the PC is connected. A progress bar is shown while the data is
downloading (as shown below).

25
Quadnet / Duonet OSP Software Operating Instructions

If there is a problem, a warning will be given. If this happens, you should disconnect the USB and re-
connect it before trying again. Also remember that the panel must be in Engineer Mode.

It is recommended that you do not use the Cancel Download button once downloading has begun.

When the downloading is complete, press the Finish button.

Panel Details
Clicking on the ‘Panel Details’ button brings up the following screen.

26
Quadnet / Duonet OSP Software Operating Instructions

Note that there are eight tabs on this screen, each of which is described below.

Panel Summary

On this tab you can use the four buttons at the bottom of the screen to add/delete panels from the
configuration data as follows.

Add

The Add button on the upload screen allows you to add a new panel to the current configuration on
the PC. This feature is also available on the “Upload Data” screen available from the “Upload from
Control Panel” button.

Delete

The Delete button on the upload screen allows you to delete a panel to the current configuration on
the PC. This feature is also available on the “Upload Data” screen available from the “Upload from
Control Panel” button.

Copy

The Copy button on the upload screen allows you to copy the details from an existing panel to a
new panel number on the PC. This feature is also available on the “Upload Data” screen available
from the “Upload from Control Panel” button.

In the above example, we have selected Panel 001 from that site and the data from that panel will
be copied into Panel 002 in our configuration. The data may only be copied to a panel number that
does not already exist in the configuration. If you want to copy the data to an existing panel, the
existing panel should first be deleted using the Delete button.

Import

The Import button allows you to browse for a DIFFERENT site and copy the details of a panel on
that site to a panel number in the current configuration. This feature is also available on the
“Upload Data” screen available from the “Upload from Control Panel” button.

27
Quadnet / Duonet OSP Software Operating Instructions

In the above example, we have picked a different site named Test 30-06-11.site. We have selected Panel
001 from that site and the data from that panel will be copied into Panel 003 in our configuration. It does
not matter whether Panel 003 already exists in our configuration, but if it does, any data will be overwritten.

Panel Details

The Panel Details tab is shown below.

In the top section you can select the panel and the details of the selected panel will appear in the bottom
half of the screen where they may be edited.

Panel Modes

The available panel modes are

Quadnet (with up to 4 loops)


Duonet (with up to 2 loops)
Repeater (with no loops) – this is purely to relay information to remote parts of a panel
network.

Panel Description

A panel description (up to 14 characters) may be allocated to the panel.

Loop Details

In the Loop Details section the quantity of the different types of devices on each loop are shown.

Quiescent Display Text

You can set up four lines of user-definable text which is shown on the panel when it is in a
quiescent state. The default text is shown in the sample screen above.

28
Quadnet / Duonet OSP Software Operating Instructions

Codes

The control panel access codes may be changed as required on this screen.

The default codes for Access Level 2A (user), Access Level 2B (user) and Access Level 3
(engineer) are shown above. They may be changed to any combination of 4 digits.

Upload and download may only be carried out from Access Level 3 (engineer). Changing the
engineer code will restrict access to those unauthorised to make such changes.

A Back Door code can be provided if the codes chosen are lost. If this is required, contact your
supplier with the following information:

1. The control panel serial number


2. The control panel software version number
3. The site name and details
4. Your details
5. Written authorisation from the legal owner of the system to request back door
codes for the system.

Delays & Timers

The Delays and Timers tab is shown below.

29
Quadnet / Duonet OSP Software Operating Instructions

Alarm Delays

Four alarm delays can be programmed with values between 0:00 and 10:00 minutes.

An Alarm Confirmation delay may be set up so that when an alarm occurs, it is not immediately
reported. The system will wait until the end of the delay time and then check that the alarm is still
present. If it has cleared, the device which was in alarm will be reset and no further action need be
taken.

The delay time for alarm confirmation can be programmed from 1:00 – 4.00 minutes. You must
ensure that stage 1 sound pattern is active for every device with alarm confirmation. This option
cannot be used at the same time as alarm delay.

There is a tick box to decide whether any unconfirmed alarm warning should be displayed at the
panel.

Panel Timers

You can program how often the service timer is to occur so that the end-user is prompted to call for
a service. Options are 90, 180 and 360 days.

You can also specify a day and a time (hours and minutes on the 24 hour clock) for a weekly test to
be performed on the panel. Leave the fields blank if you do not want a weekly test.

Day/Night Mode

The Day / Night mode tab is shown below.

Pre-programmed Times (RTC) Enabled

You can set times throughout the week (hours and minutes on the 24 hour clock) for day/night
mode to be operational by filling in the Days “From To” Table as shown in the tab. There can only
be one such time range set up per day.

30
Quadnet / Duonet OSP Software Operating Instructions

You can also specify (using the zone tick boxes) which zones are to be disabled during the
selected times. This could for example be used to disable smoke detection in a zone during the day
while enabling it at night.

Note that the zone list can be scrolled down and that there are 128 possible zones. Zones with MP
or MPS devices are shown with an asterisk by their number (e.g. Zones 002 and 005 in the
example above).

The “Select Zones” button will put a tick in all the zone boxes. The “Select No Zones” button will
clear all the zone tick boxes.

Panel Input Event

With this option, you can configure the system so that day / night mode will follow any panel inputs
set to day/night mode.

The “Select All Inputs” button will put a tick in all the input tick boxes. The “Select No Inputs” button
will clear all the input tick boxes.

Panel Inputs

The Panel Inputs tab is shown below.

For the Quadnet panel, up to 4 Panel Inputs can be configured on this tab.

For the Duonet panel, up to 2 Panel Inputs can be configured on this tab.

A Panel event can be configured as a Fire Event, a Control Event, a Technical Event, or left unconfigured.

31
Quadnet / Duonet OSP Software Operating Instructions

Fire Event

A Panel Input configured as a Fire Event will have an associated zone (Zone 1 in the above
example). It can also be selected to be latching or non-latching. These values may be changed
using the pull-down selection lists.

Control Event

A Panel input can be configured as any of the types of Control Event as shown in the pull-down
selection list below. Note that “Day Night Mode” may not be possible unless Day/Night mode has
been selected (with zones) on the Day/Night mode tab.

Technical Event

A Panel Input configured as a Technical Event will have an associated zone. It can also be
selected to be latching or non-latching. These values may be changed using the pull-down
selection lists. Note that when a Technical Event takes place, there will be no indication on the
panel display and the Fire LED will not light.

Panel Outputs

The Panel Outputs tab is shown below.

32
Quadnet / Duonet OSP Software Operating Instructions

Relay Outputs

For the Quadnet panel, four relay outputs (1-4) may be configured so that they will be activated
when certain conditions occur. Selection is made via radio buttons.

For the Duonet panel, outputs 3 and 4 are not available and they are greyed out.

A Common Fire Output is activated by any Fire on the system.

A Zonal Fire Output (a zone must be specified in the range 1-128) is activated by a Fire in the
specified zone.

A Common Fault Output is activated by any Fault on the system.

Monitored Outputs

Two monitored outputs (numbered 5-6 for the Quadnet and 1-2 for the Duonet) may be configured
so that they will be activated when certain conditions occur. Selection is made via radio buttons.
Note that on the Duonet backplane (Rev B), these outputs are labelled outputs 3 and 4.

Sounder Output (a zone must be specified in the range 1-128) is activated by Sounders in the
specified zone and stops on silence command.

A (Zonal) Fire Output (a zone must be specified in the range 1-128) is activated by a Fire in the
specified zone and stops on reset command.

A Common Fault Output is activated by any Fault on the system.

Network

The network tab is shown below.

On this tab you can specify (for your chosen panel) which events are transmitted to the panel network. This
is done by ticking the relevant boxes in the “Transmit Event to Network” list.

You can also select whether the chosen panel is to react to any events received from the network. The
choices are made by ticking the relevant boxes in the “Action if Received” list.

33
Quadnet / Duonet OSP Software Operating Instructions

Printer

The printer tab is shown below.

You can select whether the printer is to be enabled on the panel and if so, you can specify which types of
event are printed. Options are Fire Events, Fault Events, Panel Events and All Events.

34
Quadnet / Duonet OSP Software Operating Instructions

Device Details - Device Details Tab

Clicking on the ‘Device Details’ button leads to the following screen:

You can right click on fields as follows to edit the fields. The selection lists below have a tick by the default
values.

Type (only available with NEW data)

Zone (only available with NEW data)

A list of all 128 zones is displayed (128 is default)

Smoke Detector (if applicable for the type)

35
Quadnet / Duonet OSP Software Operating Instructions

Heat Detector (if applicable for the type)

Alarm Stages for Sounders (3 Stages) (if applicable for the type)

The system may operate with a total of two out of three Alarm Stages where the sound pattern selected at
‘Sound Stage X’ will operate.

Alarm Description Actions Next Stage


Stage
1. Alarm Confirmation Allows local warning and automatic reset of an Either 2 or 3
unconfirmed alarm from a smoke detector. The system
does not enter a Fire state until the alarm is confirmed.

2. Alert Early warning stage. Sounders only are activated. 3

3. Evacuate Full alarm condition, sounders and remote fire outputs are -
activated.

Volume Levels for Sounders (3 stages) (if applicable for the type)

AC (Alarm Confirmation)

The Multipoint detector/sounder incorporates ‘Alarm Confirmation Technology’ to reduce unwanted


alarms. This enables a detector to generate a local warning in response to the presence of smoke, allowing
any persons within the area to react accordingly. If the presence of smoke is removed within the Alarm
Confirmation Delay time then the sounder will reset automatically, but if the smoke presence continues
after the alarm confirmation delay time, then an alarm will be generated.

36
Quadnet / Duonet OSP Software Operating Instructions

The activation of any Heat detector (even in the same device as the smoke detector in ‘Alarm
Confirmation’) generates an instant alarm (depending on the programming of the system ‘Cause & Effect’).

An ‘Alarm Stage 1’ sound pattern must be used for every multipoint detector requiring the ‘Alarm
Confirmation Delay’.

Edit Labels

The device labels are of critical importance in an addressable fire alarm system, so in order to avoid
accidentally changing them, the labels are ‘write protected’ by the Edit Labels button. Simply click on this
button to activate the ‘Edit Mode’, and click again to deactivate it when you have finished.

Device labels may be up to 23 alphanumeric characters long. Remember to press ENTER on your PC
keyboard to indicate that you have finished editing the selected label.

Edit Zone

The zone numbers may be edited in a similar way as the labels. In order to avoid accidentally changing
them, the zones are ‘write protected’ by the Edit Zone button. Simply click on this button to activate the
‘Edit Mode’, and click again to deactivate it when you have finished.

Sort by Address

This button will rearrange the order of the devices as seen on the screen so that they are in order of
address. It does NOT renumber the actual order of the devices on a loop.

Sort by Zone

This button will rearrange the order of the devices as seen on the screen so that they are in order of zone.
It does NOT renumber the actual order of the devices on a loop.

Device Details

This button allows you to edit properties as shown for the current device. You can also double-click on the
current device to obtain this screen.

The ‘Device Details’ button changes only the fields that have had entries changed. This is done for the
selected device only.

Zone Details

37
Quadnet / Duonet OSP Software Operating Instructions

This button allows you to edit properties as shown for the zone associated with the point that was currently
highlighted when the button was pressed.

Note that you can select which loop(s) are to have their details changed using the loop tickboxes.

The ‘Zone Details’ screen changes only the fields that have had entries changed. This is done for all the
devices that are in the same zone in the selected loops.

All Details

This button allows you to edit properties as shown for all points on selected loop(s) in the currently chosen
panel.

Note that you can select which loop(s) are to have their details changed using the loop tickboxes.

The ‘All Details’ screen changes only the fields that have had entries changed. This is done for all devices
that are in the selected loops in the panel and should be used with great caution.

38
Quadnet / Duonet OSP Software Operating Instructions

Add Device

This button allows you to add one or more new devices to the system. The prompt given is as follows.

Note that the start address must either be in the existing range of addresses or be the address immediately
after the last address in the list. The system will not allow any gaps.

If the start address lies within the range, the specified number of new devices will be added and devices
with higher addresses will be moved down the list to make room for the new devices.

Note that the maximum number of devices per list is 200.

The new devices will have default values as shown in the example below where 5 new devices have been
added starting with address 42 on loop 1. You can then edit the fields so that the correct types are used
together with your choice of alarm stage parameters.

Delete Device

This button allows you to delete one or more new devices from the system. The prompt given is as follows.

Note that the start address must be in the existing range of addresses.

When the devices have been deleted, devices with higher addresses will be moved up the list to remove
any gap.

39
Quadnet / Duonet OSP Software Operating Instructions

Data Entry

The “Data Entry” button allows you to modify data fields quickly.

Enter the loop number and the range of addresses that you wish to modify.

Tick only the boxes for fields that you want to modify.

Then click on OK. A prompt screen will then be shown.

Prompts will be given with the possible entries for each field in turn. Select your choice and press OK. The
fields already configured will be shown on the screen above the option box.

The Back button allows you to undo any changes that you have made. This will only work on the current
device being edited. You cannot go back to the previous device.

In the above example, all the fields except for the last two (Alarm Stage 3 Sound and Alarm Stage 3
Volume) have been configured and the user is being prompted to select a value for Alarm Stage 3 Sound.

The Cancel button allows you to discard all changes made in the “Data Entry” section.

40
Quadnet / Duonet OSP Software Operating Instructions

Sound Demo

The seven available sound patterns may be demonstrated audibly if your computer has suitable sound
facilities by using the “Sounds” button.

The following screen will be displayed. Clicking the buttons marked SP1 – SP7 will demonstrate that sound
pattern through the computer speakers.

Apply Zone

This button allows you to quickly transfer addresses to a chosen zone. Highlight a device in the table with
the desired zone number. Now click the Apply Zone button. A prompt will appear as shown below.

After pressing OK, you can double click on any other devices in the list and they will be assigned to your
chosen zone. To exit from this feature, click on the Apply Zone button again.

Apply Format

41
Quadnet / Duonet OSP Software Operating Instructions

This button allows you to quickly copy configured data from one address to another. Highlight the device to
be copied from in the table. Now click the Apply Format button. A prompt will appear as shown below. In
the example, the data will be copied from Loop 1 Device 10.

After pressing OK, you can double click on any other devices in the list and the data from your selected
device will be copied to them. Note that the label (text description) and serial number will not be copied.

To exit from this feature, click on the Apply Format button again.

Print

This button allows you to print the table of device details on a printer. A prompt is given as follows so that
you can select printer details.

Press the Print button to send the data to the chosen printer. Note that the “Save as CSV” button can be
used to save the data in CSV (Comma Separated Values) format. The file could then be opened in a
spreadsheet program such as Microsoft Excel.

42
Quadnet / Duonet OSP Software Operating Instructions

Device Details - Loop Loading Screen


In order to allow a method of calculating the maximum loop loading that the system will support, each
device has a rating assigned in Device Loading Units (DLUs). A maximum of 450 DLU are permissible on
the loop. This relates to the load presented in alarm and does not necessarily affect an input device.

The Quadnet / Duonet OSP programming software v3.00 or later (v3.04 or later required for the latest
devices) automatically keeps control of the quantity and will provide warnings if the limits are exceeded.

The main types of current (and earlier) devices and their loadings are listed below.

PRODUCT DESCRIPTION DLU RATING


Product
Type Subtype SP0 - Off Low Medium High
Code
203 0003 Multipoint Mk3 1 - - -
MP
205 0003 ASD Mk3 1 - - -
203 0001 Multipoint with Sounder Mk3 1 1.5 4.5 6
MPS 205 0001 ASD with Sounder Mk3 1 1.5 4.5 6
205 0012 ASD with Sounder/Strobe Mk3 4.5 5 8 10
403 0006
MCP Manual Call Point Mk3 3 - - -
403 0007
313 0001
Soundpoint Mk3 1.5 2 4 5.5
313 0002
323 0001 Hipoint Mk3 1.5 2 4 5.5
303 0013 Bell Mk2 2 22 22 22
303 0012
Flashpoint 1.5 4.5 6.5 8
SOUNDER 303 0022
326 0021
Sounder/Strobe 9 9.5 11.5 13
326 0023
326 0001
Sounder 1.5 2 4 5.5
326 0003
326 0015 Strobe 9 - - -
I/O 803 0006 Loop I/O Module Mk2 10.5 - - -
Conventional Zone Module
803 0010 23.5 - - -
(Loop Powered)
CZM
Conventional Zone Module
803 0010 3.5 - - -
(Ext PSU)
Multipoint I/O Module (in Relay
803 0003
Base) 3 - - -
ANCILLARY 803 0005
Multipoint I/O Module (in Box)
600 0092 Remote Indicator 0.5 - - -

OSP will not be able to identify all subtypes of devices on existing systems but can identify all subtypes in
production as of March 2010.

43
Quadnet / Duonet OSP Software Operating Instructions

Loop Load Calculations

To get details about the DLU values, use the “Loop Load Calculations” button on the Device Details screen.
A typical display is shown below.

The lower section of the screen provides a summary of attributes for the highlighted device. Note that the
device serial number is located in the lower left hand corner of this box.

Versions of the Quadnet / Duonet OSP before V2.02 did not identify the subtype. V2.02 and above of the
Quadnet / Duonet OSP uses the type and serial number to calculate the subtype and all devices produced
from March 2010 can be identified as well as many previous ones. However, it is not always possible to do
this with early devices (as noted in the table above).

The loop loading calculations box gives a running total of the DLU values for the alarm stages on each
loop, together with a breakdown of each loop by device type. If any Alarm Stage DLU totals exceed 450,
they are printed in bold red text and a warning is given on leaving the screen so that the system can be
reconfigured with lower volume stages 1-3 or possibly with devices deleted or put onto a different loop.

Reset DLU button

This button will reset the subtypes of any devices which have had their sub-types reconfigured by the user.
The sub-types of any such devices will be returned to the default type.

44
Quadnet / Duonet OSP Software Operating Instructions

Device Types

The device types are listed below. The device is depicted pictorially in the left hand lower corner in order to
provide quick verification, as follows:

Picture Type

MP Multipoint Detector

Subtypes
Sub Types: Multipoint Mk 1
Multipoint Mk 2
Multipoint Mk 3
ASD Mk 1
ASD Mk 2
ASD Mk 3

Note: Early Multipoint detectors with no sounders may be reported as the


equivalent MPS device (with sounder) in which case the sound
patterns must be configured to SP0.

Picture Type

MPS Multipoint Detector with Sounder.

Subtypes
Sub Types: Multipoint with sounder Mk 1
Multipoint with sounder Mk 2
Multipoint with sounder Mk 3
ASD with sounder Mk 1
ASD with sounder Mk 2
ASD with sounder Mk 3

Note: Early Multipoint detectors with no sounders may be reported as the


equivalent MPS device (with sounder) in which case the sound
patterns must be configured to SP0.

Subtypes ASD with sounder/strobe Mk 1


ASD with sounder/strobe Mk 2
ASD with sounder/strobe Mk 3
ASD
Sounder
Strobe Note: Early Multipoint detectors with sounders and strobes may be reported as
the equivalent ASD device with sounder but no strobe.

45
Quadnet / Duonet OSP Software Operating Instructions

Picture Type

MCP Manual Call Point

Subtypes
Sub Types: Manual Call Point Mk 1
Manual Call Point Mk 2
Manual Call Point Mk 3

Picture Type

MCPS Manual Call Point with sounder

Subtypes

Sub Types: Manual Call Point with sounder Mk 1


Manual Call Point with sounder Mk 2

46
Quadnet / Duonet OSP Software Operating Instructions

Picture Type

SDR Sounders

Subtypes Sub Types: Soundpoint Mk 1


Soundpoint Mk 2
Soundpoint Mk 3
Hipoint Mk 1
Hipoint Mk 2
Hipoint Mk 3
Bell Mk1
Bell Mk2
Flashpoint
NSR Sounder / Strobe
NSR Sounder without Strobe
NSR Strobe without Sounder

Note: Early devices with subtypes SoundPoint, HiPoint or Bell will be reported
as “Flashpoint”.

Picture Type

I/O Loop I/O Module

Subtypes
Sub Types: Loop I/O Module Mk 1
Loop I/O Module Mk 2

47
Quadnet / Duonet OSP Software Operating Instructions

Picture Type

CZM Conventional Zone Module

Subtypes Sub Types: Conventional Zone Module Mk 1


Conventional Zone Module Mk 2

Versions of the Quadnet / Duonet OSP before V2.02 did not identify the subtype. Quadnet / Duonet OSP
v2.02 and later use the device type and serial number to calculate the subtype. With this version all devices
produced from March 2010 can be identified as well as many previous ones. It is possible to override the
detected subtype on the “Manual Loop Loading Calculations” screen by highlighting the subtype field and
right-clicking on the field. A list of available subtypes for that type of device is then shown. Note however,
that these override values are NOT sent to the panel and will be lost the next time the loop data is
uploaded from the panel.

Overriding the subtype is only to be used when the correct item cannot be automatically detected by the
system. This feature should be used with caution and on the advice of Fike technical support. It must not
be used to artificially reduce the configured loop loading as this could have an adverse effect on the system
during an alarm condition,

48
Quadnet / Duonet OSP Software Operating Instructions

Device Details - Device I/O Tab

Edit I/O Labels

The I/O labels are of critical importance in an addressable fire alarm system, so in order to avoid
accidentally changing them, the labels are ‘write protected’ by the Edit I/O Labels button. Simply click on
this button to activate the ‘Edit Mode’, and click again to deactivate it when you have finished.

I/O labels may be up to 24 alphanumeric characters long. Remember to press ENTER on your PC
keyboard to indicate that you have finished editing the selected label.

Edit I/O Zone

The I/O zone numbers may be edited in a similar way as the labels. In order to avoid accidentally changing
them, the I/O zone numbers are ‘write protected’ by the Edit Zone button. Simply click on this button to
activate the ‘Edit Mode’, and click again to deactivate it when you have finished. Note that you cannot edit
the I/O zone number if it has not yet been set up. This can be done with the “Device I/O Details” button.

Sort by Address

This button will rearrange the order of the devices as seen on the screen so that they are in order of
address. It does NOT renumber the actual order of the devices on a loop.

Sort by Zone

This button will rearrange the order of the devices as seen on the screen so that they are in order of zone.
It does NOT renumber the actual order of the devices on a loop.

49
Quadnet / Duonet OSP Software Operating Instructions

Device I/O Details

The following is only applicable to devices of the following types - MP, MPS or I/O - which can be
configured for Auxiliary I/O properties. Devices of other types will be “Not Configured”. If this button is
pressed, you can edit the auxiliary I/O properties for the chosen device only.

There are 3 possible auxiliary types.

1 Remote Indicator (LED).

This can be selected with a radio button. Note that if selected, this will increase the DLU value for
the loop.

2 Monitored Input

This can be selected with a radio button. Note that if selected, you will have to specify whether it is
to be a Fire Event, a Control Event or a Technical Event. Note that there are several types of
Control event as shown below.

If Disable is chosen as the Control event you will have to further specify whether Sounders, Fire
Outputs or Fault Outputs are to be disabled.

50
Quadnet / Duonet OSP Software Operating Instructions

3 Monitored Output

This can be selected with a radio button. Note that if selected, you will have to specify whether it is
to be a Device Output, Sounder Output (linked to a zone) or a Fire Output

Zone I/O Details

The following is only applicable if you have highlighted a device which has one of the following types - MP,
MPS or I/O.

If this button is pressed, you can edit the auxiliary I/O properties as shown for the zone associated with the
point that was currently highlighted.

Note that you can select which loop(s) are to have their details changed for devices in the same zone using
the loop tickboxes.

The ‘Zone Details’ button changes only the fields that have had entries changed. This is done for all the
devices that are in the selected loops in the zone.

51
Quadnet / Duonet OSP Software Operating Instructions

All I/O Details

This button allows you to edit auxiliary I/O properties as shown for all relevant points (i.e. with type MP,
MPS or I/O) on selected loop(s) in the currently chosen panel.

Note that you can select which loop(s) are to have their details changed using the loop tickboxes.

The ‘All Details’ button changes only the fields that have had entries changed. This is done for all devices
that are in the selected loops in the panel and should be used with great caution.

Device Details – Graphical View Tab


This tab can be used to display an overall view of all the devices configured for the currently selected
panel.

There is a different symbol for each possible type of device. A typical display is shown above.

Zones which currently contain devices are shown in bold type on the left hand side of the screen.

The “Hide Empty Zones” tickbox can be used to remove zones which currently have no devices configured
from the list.

52
Quadnet / Duonet OSP Software Operating Instructions

The “Highlight Devices” button can be used so that devices of the selected sort are shown with a thick
black border around them on the diagram. The list of options is given below.

Note that the device types are shown in a sub-menu.

Editing a Device

If you right-click on a device, a menu similar to that shown below will be shown.

You can now edit any of the available fields for the device. The options are as described in the Device
Details Tab section of this manual.

Note that if you click on Properties, you will get the Edit Properties screen for editing the properties of a
single device as described in the Device Details Tab section of this manual.

Apply Format

This button allows you to quickly copy configured data from one address to another.

Press the button and the following prompt appears.

53
Quadnet / Duonet OSP Software Operating Instructions

Click on the OK on the prompt. Now click on the device from which you would like to copy data. The
chosen device will turn blue.

The following prompt will appear.

Click on the OK on the prompt and then click on the devices which are to receive the same formatting as
the first device. They will turn black as you click on them When all devices have been selected, click on the
OK button at the bottom of the screen. The following prompt will be shown, allowing you to cancel if
necessary by clicking on “No”.

Click on “Yes” for the copy process to take place.

Note that this feature can only be used once. To perform more formatting, you must exit the Graphical View
tab and then select the tab again

54
Quadnet / Duonet OSP Software Operating Instructions

Device Details – Connection Map Tab

This tab shows a graphical display showing how the devices on a selected loop are connected.

The loop is selected with the loop radio buttons at the top of the screen. More details are shown on this
screen than on the Graphical View tab and you will need the scrollbars to see all the devices on the loop.

Note that the same symbols as on the Graphical View tab are used.

A Print button is available to send a copy of the connection map to the printer.

55
Quadnet / Duonet OSP Software Operating Instructions

Note that you can select the page to be printed using the pull-down selection box at the top left of the
screen. However, when you press Print, there is no option to select a printer. Your default Windows printer
will be used.

You can exit this screen without printing by clicking on the Close (X) box in the top right of the screen.

56
Quadnet / Duonet OSP Software Operating Instructions

Cause & Effect


Many systems simply operate all sounders and fire protection outputs immediately following the activation
of any device. This is known as ‘Instant Alarms’.

Sometimes it may be desirable to delay the alarm response, or maybe only to sound the alarms in a certain
area, and this may well depend upon the area of origin of the activated device. This is known as ‘Phased
Evacuation’.

The ‘Cause & Effect’ area allows programming of different types of zonal based ‘Phased Evacuation’.

The flow chart below explains how the Quadnet / Duonet ‘Cause & Effect’ operates:

57
Quadnet / Duonet OSP Software Operating Instructions

Clicking on the ‘Cause & Effect’ button will bring you to the following screen.

Zone to Zone Cause and Effect

For the majority of simple systems we recommend that a full alarm (stage 3) should be given in all zones
for any input type (one out, all out).

If any different ‘Cause & Effect’ actions are required then follow the instructions in the “Cause and Effect
Wizard” which can be found on the Alarm Stage 1 tab. These will remind you of the steps to carry out as
listed below.

The initial tab shown on the Zone to Zone Cause and Effect Screen is a summary. Alarm zones 1-5 have
been selected for Alarm Stage 1. Cause and Effect links have been set up in Group 1. Group 2 has not
had any links set up.

Please note that only two Groups of Zone to Zone Cause and Effect can be set up. Groups 3-6 are
currently not available.

Step 1 – Select Detection Zone

Select the detection zone which contains the inputs which will CAUSE the outputs to be turned on at the
top of the screen.

As there are 128 possible detection zones, a tickbox “Hide Empty Detection Zones” has been provided. If
ticked, this will remove all “empty” detection zones from the pull-down zone list, i.e. all detection zones
which do not contain input devices. This makes selecting the correct zone easier to carry out.

Note that you can edit a description for the selected zone. The default text provided is of the form ZONE
xxx.

58
Quadnet / Duonet OSP Software Operating Instructions

Step 2 – Select Alarm Stage 1 Tab Alarm Conformation

Select the Alarm Stage 1 tab. A typical screen is shown below.

Note that there is a “Hide Empty Alarm Zones for Alarm Stage 1” tick box. If this is ticked only zones which
have output devices in them will be included in the list. If this box is NOT ticked, all 128 zones are shown
(as in the above screen) and you will have to use the scroll bar to see them all. Note that zones which are
not empty (i.e. with output devices in them) are shown with their description underlined. In the above
example, these are zones 1 to 5.

Step 3 – Select Alarm Zones for Alarm Stage 1

Put ticks in the boxes for the alarm zones to be affected when the chosen detection zone (zone 1 in our
example) has an input in alarm.

There are four buttons which may make ticking the boxes easier.

Select All Zones – This will tick all 128 boxes.

Select No Zones – This will remove the ticks from all 128 boxes.

Select All Alarm Zones – This will put ticks in all the non-empty alarm zone tickboxes – i.e. the
ones that have output devices in them and which have their descriptions underlined. In the above
example, these are zones 1 to 5.

Select No Alarm Zones – This will remove all ticks from all the non-empty alarm zone tickboxes –
i.e. the ones that have output devices in them and which have their descriptions underlined. In the
above example, these are zones 1 to 5.

59
Quadnet / Duonet OSP Software Operating Instructions

Step 4 – Select Group 1 Tab

A summary of all the currently programmed links is given in the box labelled Link.

Step 5 – Select Links for Group 1

There are 3 link types as follows

Smoke alarm
MCP/heat/input
nd
2 smoke alarm

These links are like filters, and only the options selected will allow a following action to happen (i.e.
sounders on). The Alarm Stage chosen here will cause the sounders activated to operate with the sound
pattern set earlier in the Device Details screen.

You can program which alarm stages are to result when your chosen link type occurs.

The options are

Alarm stage 2 – Delay 1– Alarm Stage 3


Alarm stage 2 – Delay 2– Alarm Stage 3
Alarm stage 2 – Delay 3– Alarm Stage 3
Alarm stage 2 – Delay 4– Alarm Stage 3
Alarm stage 2 – No Delay
Alarm stage 3 – No Delay

Note that the 4 possible delay lengths are configured in the Panel Details Delays and Timers tab. This must
be done before any delay type is selected here. Otherwise an error message will be given.
nd
Note that you cannot select both Smoke alarm and 2 smoke alarm simultaneously for your links.

Use the summary box labelled Link at the top to check your selections before proceeding.

60
Quadnet / Duonet OSP Software Operating Instructions

Step 6 – Select Alarm Zones for Group 1

Select the required Alarm Zones for Group 1. These are the areas in which the sounders and outputs will
operate when a Group 1 link is activated. Alarm Zones left unchecked will not operate.

Put ticks in the boxes for the alarm zones to be affected when the links from the chosen detection zone
(zone 1 in our example) cause further alarm stages to occur.

There are four buttons which may make ticking the boxes easier.

Select All Zones – This will tick all 128 boxes.

Select No Zones – This will remove the ticks from all 128 boxes.

Select All Alarm Zones – This will put ticks in all the non-empty alarm zone tickboxes – i.e. the
ones that have output devices in them and which have their descriptions underlined. In the above
example, these are zones 1 to 5.

Select No Alarm Zones – This will remove all ticks from all the non-empty alarm zone tickboxes –
i.e. the ones that have output devices in them and which have their descriptions underlined. In the
above example, these are zones 1 to 5.

Use the summary box labelled Link at the top to check your selections before proceeding.

Step 7 – Select Group 2 Tab (Optional)

This is done in the same way as Step 4 above.

Step 8 – Select Links for Group 2 (Optional)

This is done in the same way as Step 5 above.

Step 9 – Select Alarm Zones for Group 2 (Optional)

This is done in the same way as Step 6 above.

Step 10 – Save Data

Data for the detection zone is saved by clicking on OK. Cancel can be used to leave the screen without
saving data.

61
Quadnet / Duonet OSP Software Operating Instructions

Point to Point Cause and Effect

As well as configuring Zone to Zone cause and effects, it is also possible to configure point input to output
cause and effects. Up to 50 of these “Actions” may be set up. If both zone to zone & point to point cause &
effects are used together, the zone to zone actions will be acted on first. Point to point cause and effect
should not be used for time critical actions.

A typical screen is shown below. The Cause and Effect tab is shown. A summary tab is also available.

Three different modes of input combination are possible.

OR Function With the OR function the configured outputs will be activated whenever ANY of the
inputs in the input list occur.

AND Function With the AND function the configured outputs will only be activated whenever ALL
of the inputs in the input list occur.

Double Knock Function The configured outputs will only be activated when TWO OR MORE of
the inputs in the input list have occurred. They will not be activated if only one input has occurred.

The inputs and outputs are selected by putting ticks in the relevant boxes.

The Clear Action button will remove ALL ticks from ALL boxes for the currently selected Action.

Note that scroll bars are necessary to view all inputs and outputs current configured in the system.

In the Input Points list any devices which do not contain inputs are greyed out. For example, in the above
sample screen, address 7 is greyed out as it is a sounder.

In the Output Points list any devices which do not contain outputs are greyed out. For example, in the
above sample screen, address 15 is greyed out as it is a manual callpoint.

Note that devices such as MPS may have auxiliary outputs configured as fire outputs or device outputs as
well as sounders. If this is the case, you can select which is to be activated in the output list. The default
chosen is “Sounder” (as in the above example screen) but you can change this to Output if an auxiliary

62
Quadnet / Duonet OSP Software Operating Instructions

output has been configured. Auxiliary outputs are configured on the Device I/O tab in the Device Details
section.

You can use the summary tab to check your selections. A typical summary tab is shown below.

Note that each Action has to be configured separately.

You can use the summary tab to check your configuration. A typical summary tab is shown below.

Note that the output devices will have (s) to indicate sounders and (o) to indicate outputs.

63
Quadnet / Duonet OSP Software Operating Instructions

Diagnostics

Before diagnostics can be used, the Quadnet Loop Diagnostic program must have been installed on the
PC. If this has not been done, a warning screen is displayed.

A typical warning screen is shown below.

This program is primarily for the use of Fike engineers. There are 3 tabs as follows:

CIE Diagnostics
Loop Diagnostic

64
Quadnet / Duonet OSP Software Operating Instructions

CIE Diagnostic

This tab allows the engineer to view the data packets being sent around the system.

Loop Diagnostic

This tab allows the engineer to view the data packets being sent around the loops on the panel.

65
Quadnet / Duonet OSP Software Operating Instructions

Panel Integrity Check

This feature can be found under the Tools dropdown menu and allows the currently configured data to be
checked for inconsistencies and errors.

The following are checked.

Device settings
Panel Settings
Zone to Zone Cause and Effects
Device to Device Cause and Effects

A typical report is shown below. In the example, alarm zones have been configured for cause and effect to
turn on outputs in zone 1 group 1. However, no such outputs have been set up.

66
Quadnet / Duonet OSP Software Operating Instructions

Routine Operations

Programming a New Installation


Generally, the simplest manner in which to program a new installation is to let the control panel find its own
loop configuration upon initialisation, and then to modify this. It is suggested that you proceed as follows:

1. Initialise the system. The control panel will interrogate the loop to build up a database of the
configuration. Ensure that the correct number of devices has been found and that initialisation is
complete.

2. Upload the configuration. Upload the original configuration from the control panel and save it as
‘Filename original’, i.e., ‘HarloweHouse original’. It is good practice to keep this file and not over-
write it with another. If any confusion exists it is handy to investigate the original configuration.

3. Verify the position of the devices. Use the device serial numbers to ensure that your ‘As-wired’
drawings or connection schematic is correct. The upload configuration will be correct so amend your
notes to reflect this.

4. Program as required. Configure the control panel and device attributes as required.

5. Save this file. Save the file as ‘Filename final’, i.e., ‘HarloweHouse final’. The download option is
available without saving the file, but it is good practice to save the file in any case.

6. Download the file into the control panel. After download remember to carry out the following:

‘Start’ or ‘Initialise’ Loop


‘Reconfig’ data to loop devices
‘Reset’ system
Test system for correct operation.

67
Quadnet / Duonet OSP Software Operating Instructions

Adding and Deleting Devices on Existing Systems


As the address of a device may change if the loop configuration is modified it is important to carry out the
operation in a certain manner in order to avoid the need to reprogram the system from that point onwards.
This is only necessary if the configuration of devices on the loop is changed, i.e., adding or removing
devices. This procedure is not required if a ‘like’ device is swapped, or if an optical chamber is replaced.
1. Upload the original. Upload the original configuration from the control panel and save it as
‘Filename original’, i.e., ‘HarloweHouse original’. It is important to keep this file and not over-write it
with another in case anything goes wrong.
2. Physically add or remove the required devices Physically add or remove the required devices to
the system, record the serial numbers of the detectors, and initialise the system to find the modified
loop configuration. Make sure that you know which address numbers are to be added and which are
to be deleted as the system will renumber the addresses to remove any gaps.
3. Add or remove the required devices to the configuration file. It is generally easier to add or
remove devices in order, starting at the lowest address and working up towards the highest address.
4. Set the new devices as required. Configure the device type, smoke and heat modes, sound
patterns and volumes, I/O types and set the zone allocation. Any added devices will not yet have
serial numbers.
5. Download the file into the control panel. First check and save the configuration file as ‘Filename
new’, i.e., ‘HarloweHouse new’. After download remember to carry out the following:
Start or Initialise Loop
Re-config data to loop devices
Reset system
Test system for correct operation.

6. Upload from the fire panel and save the file. The data will now have the correct serial numbers
for any devices which have been added. This will be the finished version of the file.

68
Quadnet / Duonet OSP Software Operating Instructions

Programming Loop Inputs and Outputs


The Multipoint detector/sounder has an inbuilt input/output function known as the Multipoint Auxiliary I/O.
This may be programmed within the ‘Device Details’ + Device I/O Tab section by selecting the required
device and then clicking on ‘Device I/O Details’ at the bottom. The required attributes may then be
selected.

I/O Options

I/O options may be configured to suit your individual applications as described below. Further details of the
electrical configuration may be found in the Engineering and Commissioning Instructions. The Loop
Powered I/O Module is programmed in a similar manner, but with fewer options. The table indicates
whether an EOL resistor is necessary. Note that if Auxiliary I/O is set to ‘Not Configured’, it will not require
an EOL resistor.

Description Action Group EOL MP Loop


I/O I/O

1. NOT The aux I/O will not change state None Y Y


CONFIGURED

2. REMOTE Output will follow the fire and fault indication of the Multipoint. LED None Y N
INDICATOR The LED will require a 10K series resistor -
Default setting

3. MONITORED The input will monitor for fire (680R) and fault (3K3 EOL), and 3K3
INPUT trigger the system into the fire state, indicating ‘Aux input’ on the
display.

4. MONITORED The output will monitor for fault (3K3 EOL) and the output will 3K3
OUTPUT cause the relay on the ‘I/O Interface Module’ to change state.

Device – The relay will follow the fire state of the host detector Device Y N
independent of control panel instruction, including during alarm
confirmation.

Alarm Zone – The relay will follow the Alarm Zone of the host Sounder Y Y
device.

Auxiliary (I/O) Zone – The relay will follow the I/O zone. Sounder Y Y
Setting the output type to either Sounder or Output (= Remote / Remote
Fire Output) in ‘Cause & Effect’ will determine the ‘Output Fire
Group’

Output Groups

The operations of the output groups are shown in the table below.

Group Description Activate/Start Deactivate/Stop


1. LED Remote Indicator Mimic host device fire and fault LED

2. DEVICE Follow fire state of host device Alarm commencement of host Reset of host device
device

3. SOUNDER Sounder output Alarm commencement Silence

4. REMOTE FIRE Fire Protection Output Alarm commencement Reset

69
Quadnet / Duonet OSP Software Operating Instructions

Programming Panel Inputs and Outputs


I/O Options for Panel Inputs / Outputs

They may be configured to suit your individual applications as described below. Further details of the
electrical configuration may be found in the Engineering and Commissioning Instructions. Note that if
monitored inputs or outputs are set as ‘Not Configured’, they will not require EOL resistors.

Description Option Action Group EOL


1. OUTPUT 1 Not configured The relay will not change state None

Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None

Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone

Common Fault The relay coil will de-energise in any fault condition None

2. OUTPUT 2 Not configured The relay will not change state None

Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None

Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone

Common Fault The relay coil will de-energise in any fault condition None

3. OUTPUT 3 Not configured The relay will not change state None
(NOT
AVAILABLE Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None
ON
DUONET) Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone

Common Fault The relay coil will de-energise in any fault condition None

4. OUTPUT 4 Not configured The relay will not change state None
(NOT
AVAILABLE Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None
ON
DUONET) Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone

Common Fault The relay coil will de-energise in any fault condition None

5. MON Not configured The relay will not change state None
OUTPUT 5
(MON Sounder s Output The output will energise in any fire activation from Sounder 10k
OUTPUT 1 (Zone must be specified) specified zone, de-energise on silence
ON
DUONET) Fire Output The output will energise in any fire activation from Fire Prot 10k
(Zone must be specified) specified zone, de-energise on reset

Common Fault The relay coil will de-energise in any fault condition 10K

6. MON Not configured The relay will not change state None
OUTPUT 6
Sounder s Output The output will energise in any fire activation from Sounder 10k
(MON (Zone must be specified) specified zone, de-energise on silence
OUTPUT 2
ON Fire Output The output will energise in any fire activation from Fire Prot 10k
DUONET) (Zone must be specified) specified zone, de-energise on reset

Common Fault The relay coil will de-energise in any fault condition 10K

70
Quadnet / Duonet OSP Software Operating Instructions

7. INPUTs Not configured The input is inactive None


1 to 4
(Inputs Fire Event input Latching A 680 ohm firing resistor will trigger a fire state in 3k3
3 & 4 NOT (for specified zone) specified Detection Zone) and clear on Reset
AVAILABLE System
ON
DUONET) Fire Event input Non- A 680 ohm firing resistor will trigger a technical alarm 3k3
Latching (for specified state in specified Detection Zone) but will clear when
zone) the firing resistor is removed

Technical Event input A 680 ohm firing resistor will trigger a technical alarm 3k3
Latching (for specified state in specified Detection Zone) and clear on
zone) Reset System

Technical Event input Non- A 680 ohm firing resistor will trigger a fire state in 3k3
Latching (for specified specified Detection Zone) but will clear when the
zone) firing resistor is removed
If the EOL is O/C a fault will be generated.

Control event Silence Alarms 3k3


Reset System
Sound Alarm
Silence Buzzer
Day/Night Mode
Disable Sounders
Disable Fire Outputs
Disable Fault Outputs

INPUTS 2-4 have the same options as for INPUT 1 in the above table.

Output Groups

The operations of the output groups are described below:

Group Description Activate/Start Deactivate/Stop


1. SOUNDER Sounder output Alarm commencement Silence
2. FIRE PROT Fire Protection Output Alarm commencement Reset

Quadnet Outputs

Outputs 1 to 4 are derived from single pole change over ‘volt-free’ relay contacts which are not fault
monitored. The relay contacts are rated at 30VDC / 1A max.

The default setting for output 1 causes the relay to operate as a Common Fire output where the relay is
energised in the fire condition. The default setting for output 2 causes the relay to operate as a Common
Fault output where the relay is de-energised in the fault condition. Various other states may also be set
using the OSP programming software. However, to meet the requirements of EN54-2, Outputs 1 and 2
must be left as Common Fire and Common Fault respectively.

The default setting for outputs 3 and 4 causes the relay to operate as a Common Fault output where the
relay is de-energised in the fault condition. Various other states may also be set using the OSP
programming software.

Monitored Outputs 5 and 6 are monitored circuits which may be configured to monitor for open and short
circuit faults with a 10k EOL resistor, and to be activated with a stage 3 alarm.

Quadnet Inputs

Inputs 1-4 may be configured to monitor for open and short circuit faults using a 3k3 EOL resistor, and to
activate an alarm link using a 680R ‘firing’ resistor.

71
Quadnet / Duonet OSP Software Operating Instructions

Duonet Outputs

Outputs 1 and 2 are derived from single pole change over ‘volt-free’ relay contacts which are not fault
monitored. The relay contacts are rated at 30VDC / 1A max.

The default setting for output 1 causes the relay to operate as a Common Fire output where the relay is
energised in the fire condition. The default setting for output 2 causes the relay to operate as a Common
Fault output where the relay is de-energised in the fault condition. Various other states may also be set
using the OSP programming software. However, to meet the requirements of EN54-2, Outputs 1 and 2
must be left as Common Fire and Common Fault respectively.

Monitored Outputs 5 and 6 are monitored circuits which may be configured to monitor for open and short
circuit faults with a 10k EOL resistor, and to be activated with a stage 3 alarm.

The default setting for these monitored outputs causes the circuits to operate as Common Fire Sounder
Circuits, where the outputs turn on in the alarm condition. Various other states may also be set using the
OSP programming software.

Duonet Inputs

Inputs 1-2 may be configured to monitor for open and short circuit faults using a 3k3 EOL resistor, and to
activate an alarm link using a 680R ‘firing’ resistor.

72
Quadnet / Duonet OSP Software Operating Instructions

Programming Alarm Confirmation


Alarm Confirmation Technology (ACT) is the process whereby a smoke detector may be configured to
issue a localised warning in specific regions, prior to sounding a general alarm. This is generally of great
benefit in dwelling areas where smoke, steam or cooking fumes may trigger a Multipoint detector.

The following diagram demonstrates some of the possibilities:

Smoke is detected in
one room of an
apartment
3 OPTIONS TO CHOOSE

Either 1 or 2 or 3

The sounder in that All the sounders in The sounders in a


detector will sound that zone will sound linked zone will
for 30 seconds. sound
i.e., care taker

SMOKE MORE SMOKE SMOKE


REMAINS DETECTED/FIRE CLEARS

The above process will


continue for a predetermined If at any time during If there is no smoke in the
time (1-4 Minutes). ‘Alarm-Confirmation, a room between
If smoke is detected after second detector detects predetermined time and 10
this time, and up to 10 smoke/heat/MCP/IO. min
minutes from the start.

The alarm is reset automatically


FULL ALARM and only the occupant in one
Or any required actions programmed. apartment is disturbed

If a call point or heat detector is activated before,

! during or after the ‘Alarm–Confirmation’ then the


system will activate the alarms immediately.

This function affects the smoke detector only, and operates before the control panel enters the Fire state.
Thus, the system ‘Cause & Effect’ does not need to be adjusted as Alarm Confirmation takes place
before the programmed Cause & Effect sequence is reached.

In order to activate this function, set the attributes detailed in ‘System details’ and ensure that ‘Stage 1’
sound settings have been programmed for every device requiring Alarm Confirmation. Note that Alarm
Confirmation cannot be programmed at the panel. It must be done using the OSP program.

73
Quadnet / Duonet OSP Software Operating Instructions

Alarm Confirmation Delay

An Alarm Confirmation delay may be set up so that when an alarm occurs, it is not immediately reported.
The system will wait until the end of the delay time and then check that the alarm is still present. If it has
cleared, the device which was in alarm will be reset and no further action need be taken.

The Alarm Confirmation Delay timers is located within the ‘Panel Details’ area on the ‘Delays and Timers’
tab and may be set to give the required Alarm Confirmation Delay time.

The use of this feature allows an automatic reset of an unconfirmed alarm from a smoke detector. It also
allows an Alarm Stage 1 sound pattern for each device required, in the ‘Device Details’ section.

At the end of the ‘Alarm Confirmation Delay’ time the system will check the detector again to see if the
activation has cleared. If so then the device will reset and no further action need be taken.

The sounder operates during the chosen ‘Alarm Confirmation Delay’ time, and stops for the final 20
seconds, during which time the device is reset to check for further smoke presence.

During the ‘Alarm Confirmation Delay’, the activation of an additional smoke detector into ‘Alarm
Confirmation’ will cause the delay time to cease and an instant alarm to be generated.

If, however, the detector is still activated when the alarm confirmation delay is finished, then the entire
system will go into alarm, operating all the sounders programmed in the ‘Cause & Effect’ area.

For a further time period (10 min - ‘Alarm Confirmation Delay’), the activation of the same smoke detector
will cause an instant alarm (depending on the programming of the system in ‘Cause & Effect’).

The activation of any Heat detector (even in the same device as the smoke detector in ‘Alarm
Confirmation’) generates an instant alarm (depending on the programming of the system ‘Cause & Effect’).

Alarm Stage 1

These attributes may be set for each device which is to utilise Alarm Confirmation. Smoke detectors
without the attributes will operate in a standard manner (depending on the programming of the system
‘Cause & Effect’).

The ‘Alarm Stage 1’ sound pattern must be used in conjunction with the ‘Alarm Confirmation Delay’.

If Alarm stage 1 is set then the sounder in that device only operates if its smoke detector is in alarm
(unless zonal confirmation is set - then all sounders on that zone will operate). This is ‘Alarm stage 1’. The
device will revert to ‘Alarm stage 2 or 3’ when Alarm stage 1 is off. (Any subsequent actions may need to
be programmed as required under the ‘Cause & Effect’ section).

If you require the alarm confirmation signal to operate sounders on other zones, then alarm confirmation
cause and effect can be programmed by selecting the zones in Alarm Stage 1 under the ‘Cause & Effect’
section

The activation of any Heat detector (even in the same device as the smoke detector in ‘Alarm
Confirmation’) generates an instant alarm (depending on the programming of the system ‘Cause & Effect’).

74
Quadnet / Duonet OSP Software Operating Instructions

Example Configurations
Following are some examples of the configuration required for varying single and multi stage alarm
scenarios.

Group 1 and/or group 2 may be set up as shown in the examples on the following pages. Remember that
these groups need to be configured for every ‘Detection Zone’ required. As the highest priority event
always overrides all lower priority events, the groups may be programmed in any order.

This list is not exhaustive and you may find many different ways of configuring your alarm response.
Consultation with the End User and the relevant Fire Authority is essential.

In these examples, the panel Monitored outputs 5 and 6 have been put into zones 67 and 68 respectively.
Panel Monitored outputs are configured on the Panel Outputs tab on the Panel Details screen.

Instant Alarms
If you require an instant alarm response to any detector, manual call point or input alarm then set Group 1
as follows. This is the standard default configuration supplied with new systems, so generally this will not
need any alterations.

Group 2 should be set with the links unticked.

75
Quadnet / Duonet OSP Software Operating Instructions

Any fire input (i.e. smoke, heat, call point input), from this Detection Zone (Zone 1) will cause an ‘Alarm
stage 3 (Evacuate)’ sound in Alarm Zones 1 - 128.

Remember that the group 1 and 2 configuration must be set for every ‘Detection Zone’ required (not just for
Zone 1), both on initial commissioning and during any future alterations to the system.

Note the selection of Alarm Zones 67 and 68 (in Group 1) to enable the operation of the two conventional
sounder circuits (Monitored Outputs 5 and 6) at the control panel.

‘Smoke Alert’
An early warning (Alert) maybe raised in the event of a smoke detector triggering, in order to give time for
staff to investigate. Heat detection and manual call points should normally be left with an instant response.
To achieve this result set Group 1 as follows.

Note that Group 2 should be set with all the links unticked as shown below.

In this example, we have programmed Zone 1.

76
Quadnet / Duonet OSP Software Operating Instructions

Any smoke alarm input on Detection Zone 1 (Zone Basement) will cause an ‘Alarm stage 2 (Alert)’ sound in
Alarm Zones 1 to 5. Note that the “Hide Empty Alarm Zones” box has been ticked, making it easier to see
which zones are actually involved in the outputs.

After a time delay (configured earlier as Alarm Delay 1 in the Delays and Timers tab on the Panel System
Details screen), the sound will change to an ‘Alarm stage 3 (Evacuate)’ sound.

This sound will also be used on a heat or call point activation but with no delay.

Note the selection of Alarm Zones 67 and 68 (in Group 1) to enable the operation of the two conventional
sounder circuits (Monitored Outputs 5 and 6) at the control panel. These are only triggered from the ‘Alarm
stage 3’ activation.

Remember that the group 1 and 2 configuration must be set for every ‘Detection Zone’ required (not just for
Zone 1), both on initial commissioning and during any future alterations to the system.

Phased Evacuation
Alternatively, an early warning (Alert) can be raised within the local area in the event of a smoke detector
triggering, in order to give time for staff to investigate. Heat detection and manual call points should
normally be left with an instant response, but possibly phasing the evacuation from the critical areas.

To achieve this result set Group 1 as follows.

Note that Group1 has been configured to only report the event (using alarm stage 2) to zone 3. The result
is localised to the zone where the fire occurred.

Set Group 2 as follows.

77
Quadnet / Duonet OSP Software Operating Instructions

In this example, any smoke alarm input on Detection Zone 3 will cause an ‘Alarm stage 2’ sound in Alarm
Zone 3 only (because of the setting of Group 1). After a time delay (configured earlier as Alarm Delay 2 in
the Delays and Timers tab on the Panel System Details screen), or immediately after a heat or call point
activation, the sound will change to an ‘Alarm stage 3’ sound in Alarm Zones 3,4 and 5.

Thus, an Alarm Stage 2 (Alert) is generated on the same zone as the smoke detector activation. After a
time delay, or immediately after a heat alarm or manual call point activation, an Alarm Stage 3 (Evacuate)
is generated on that zone and also zones 4-5.

Thus, only the area at highest risk is initially evacuated, in order to avoid evacuating the entire site at one
go.

Remember that the group 1 and 2 configuration must be set for every input ‘Detection Zone’ required (not
just for Zone 3), both on initial commissioning and during any future alterations to the system.

Alarm Confirmation / Warden Call


The following example shows a configuration suitable for use in sheltered housing complexes. This
configuration was originally designed in response to an enquiry from a client, and has since been
implemented effectively on many sites.

It is required that the system will minimise false alarms from sheltered housing apartments, whilst providing
accurate warning of real fire situations.

The Multipoint detection in the apartments utilises the I/O Interface base to signal through the warden call
system to the warden (or central station if the warden is off site). This is combined with alarm confirmation
in order to provide a means of aborting a full alarm if the occupant is able to remove the cause of a false
alarm.

To achieve this result, configure the system as follows:

Panel Details

78
Quadnet / Duonet OSP Software Operating Instructions

Within the Panel Details section, select a value for the Alarm Confirmation Delay. This is done on the
Delays and Timers tab.

In our example, an Alarm Confirmation delay of 4 minutes 00 seconds has been set up.

Device Details

Set the devices within the apartments as follows, with the Alarm Stage 1 sound pattern selected to SP1,
SP2 or SP3.

Set the devices within communal areas, corridors and escape routes as follows, with the Alarm Stage 1
sound pattern set to SP0 (off).

Alarm confirmation has been turned ON for the devices within the apartments (Rooms 24, 25 and 26).

Also using the Device I/O tab, set the I/O linkage to Monitored Output / Device for each of the devices
within the apartments. Thus I/O Interface base relays will operate only when its host smoke detector
triggers.

Use the Device I/O Details button to obtain the following screen to select the I/O type Monitored Output –
Device output as follows. Device 10 is shown as an example.

79
Quadnet / Duonet OSP Software Operating Instructions

Cause & Effect

The Cause & Effect section should be set as for instant alarms as described previously (this is the default
setting). Set Group 1 as shown below. Remember to set this for each of the detection zones with inputs.
Group 2 does not need to be set.

The Alarm Confirmation routine takes place before the system enters the alarm state.

In this example, an ‘Alarm stage 3’ sound will operate in all Alarm Zones in response to the operation of the
following:

1. A heat detector anywhere on the system


2. A manual call point anywhere on the system
3. A smoke detector (excluding those set for Alarm Confirmation in the apartments)
4. Final confirmation of a smoke detector within an apartment.
5. The start of Alarm Confirmation from a second smoke detector within an apartment

Whilst a single smoke detector within an apartment is in its alarm confirmation stage, it will operate its own
local sounder only, and trigger the I/O interface base relay to which it is attached. Thus, if this is connected
to the local warden call unit, the warden is able to rapidly establish contact with the occupier and verify the
alarm status of the alarm. If the cause of an unwanted is removed within the selected 4 minute Alarm
Confirmation delay period then the device will reset and a full alarm will be avoided.

Remember that the group 1 and 2 configuration must be checked for every input ‘Detection Zone’ required,
both on initial commissioning and during any future alterations to the system.

80
Quadnet / Duonet OSP Software Operating Instructions

Technical Data

Duonet Control Panel

Duonet Control and Indicating Equipment


No. of zones 128 zones
Number of loops Up to 2 loops via plug- (1 included as standard with panel)
in loop cards
No of devices Maximum of 200 (whichever is reached first)
devices or maximum of
450 DLUs per loop
Device labels 23 characters
LCD display Graphic display
Field 1 (top) Control Panel Information Window
Field 2 Active Information Window
Field 3 Prompt Window
Field 4 (bottom) Network Information Window
Event log 1000 events
Inputs and Outputs Relay Outputs x2 Volt free contacts SPCO
30V DC @ 1A max per contact
Monitored Outputs x2 2 x 24V conventional monitored outputs
Fire, Fault, Signal, Technical Alarm
10k EOL, 200mA max per circuit
Monitored Inputs x2 2 x resistance monitored inputs
3k3 EOL, 680R firing resistor

Quadnet Control Panel


Quadnet Control and Indicating Equipment
No. of zones 128 zones
Number of loops Up to 4 loops via plug- (1 included as standard with panel)
in loop cards
No of devices Maximum of 200 (whichever is reached first)
devices or maximum of
450 DLUs per loop
Device labels 23 characters
LCD display Graphic display
Field 1 (top) Control Panel Information Window
Field 2 Active Information Window
Field 3 Prompt Window
Field 4 (bottom) Network Information Window
Event log 1000 events
Inputs and Outputs Relay Outputs x 4 Volt free contacts SPCO
30V DC @ 1A max per contact
Monitored Outputs x 2 2 x 24V conventional monitored outputs
Fire, Fault, Signal, Technical Alarm
10k EOL, 200mA max per circuit
Monitored Inputs x 4 4 x resistance monitored inputs
3k3 EOL, 680R firing resistor

81
Quadnet / Duonet OSP Software Operating Instructions

OSP Version Compatibility


The following table explains the compatibility of the various versions of the Duonet/Quadnet system:

RECOMMENDED OSP VERSION

V0.367

V2.04

V3.04
PANEL VERSION
Panel Versions up to v1.29 √
Panel Versions v1.34 to v2.xx √
Panel Versions v3.xx √

Technical Support
For further technical support please contact your distributor. Do not call the Fike Safety Technology
technical support department unless your distributor has first given their advice and attempted to rectify the
issue.

Technical support will not be available if the instruction manual has not been read and understood. Please
have this instruction manual available whenever you call for technical support. Due to the complexity and
inherent importance of a life risk type system, training on this equipment is essential, and commissioning
should only be carried out by competent persons.

82
Quadnet / Duonet OSP Software Operating Instructions

Configuration Sheets
Device Details Record your device attributes on the following form. Copy as required for all devices in the
system.
SITE DETAILS:

DEVICE SERIAL DEVICE DESCRIPTION (23 CHARACTERS ZONE DEVICE SMOKE HEAT ALARM
ADDRESS NUMBER MAX) TYPE MODE MODE CONF’N
E.g., 1 35415 Gnd Flr Front Office 1 MPS SM2 HM2 NO

SOUND PATTERN IN SOUND PATTERN ALARM CONFIRMATION DEVICE TYPE OPTIONS:


ALARM CONFIRMATION: IN ALARM: DELAY TIME (0:30 – 7:00 MIN): MP / MPS / MCP / MCPS / IO / CZM /
FP / SP / HP / BELL / SS

83
Quadnet / Duonet OSP Software Operating Instructions

Detection Zone/Alarm Zone Details Record your zonal ‘Cause & Effect’ here. Copy as required for
all zones.

Note:
On a network of control panels, there can be up to 128 zones on each panel (local zones). Version 3 repeater and
control panels will illuminate the zone LED corresponding to the zone in alarm on each networked control panel.

If there were 4 networked panels on a system there could be a total of 512 separate zones but all numbered in the
range 1-128. This means there could be four different zone 1s, four different zone 2s etc.

It is recommended that on networked systems using version 3 panels, zones are configured so there are a
maximum of 128 zones on the whole system and there are no duplications.

SYSTEM DETAILS: DETECTION ZONE:

GROUP 1: GROUP 2:
Stage Stage Stage Stage
LINKS TO GROUP 1: LINKS TO GROUP 2:
2 3 2 3
LINK IF MCP/HEAT/INPUT LINK IF MCP/HEAT/INPUT

LINK IF SMOKE LINK IF SMOKE

LINK IF SECOND SMOKE LINK IF SECOND SMOKE

DELAY (1,2 3 or 4) DELAY (1,2 3 or 4)

ALARM ZONES TO ACTIVATE FROM GROUP 1: ALARM ZONES TO ACTIVATE FROM GROUP 2:
ALARM ZONE 1 ALARM ZONE 65 ALARM ZONE 1 ALARM ZONE 65

ALARM ZONE 2 ALARM ZONE 66 ALARM ZONE 2 ALARM ZONE 66

ALARM ZONE 3 ALARM ZONE 67 ALARM ZONE 3 ALARM ZONE 67

ALARM ZONE 4 ALARM ZONE 68 ALARM ZONE 4 ALARM ZONE 68

ALARM ZONE 5 ALARM ZONE 69 ALARM ZONE 5 ALARM ZONE 69

ALARM ZONE 6 ALARM ZONE 70 ALARM ZONE 6 ALARM ZONE 70

ALARM ZONE 7 ALARM ZONE 71 ALARM ZONE 7 ALARM ZONE 71

ALARM ZONE 8 ALARM ZONE 72 ALARM ZONE 8 ALARM ZONE 72

ALARM ZONE 9 ALARM ZONE 73 ALARM ZONE 9 ALARM ZONE 73

ALARM ZONE 10 ALARM ZONE 74 ALARM ZONE 10 ALARM ZONE 74

ALARM ZONE 11 ALARM ZONE 75 ALARM ZONE 11 ALARM ZONE 75

ALARM ZONE 12 ALARM ZONE 76 ALARM ZONE 12 ALARM ZONE 76

ALARM ZONE 13 ALARM ZONE 77 ALARM ZONE 13 ALARM ZONE 77

ALARM ZONE 14 ALARM ZONE 78 ALARM ZONE 14 ALARM ZONE 78

ALARM ZONE 15 ALARM ZONE 79 ALARM ZONE 15 ALARM ZONE 79

ALARM ZONE 16 ALARM ZONE 80 ALARM ZONE 16 ALARM ZONE 80

ALARM ZONE 17 ALARM ZONE 81 ALARM ZONE 17 ALARM ZONE 81

ALARM ZONE 18 ALARM ZONE 82 ALARM ZONE 18 ALARM ZONE 82

ALARM ZONE 19 ALARM ZONE 83 ALARM ZONE 19 ALARM ZONE 83

ALARM ZONE 20 ALARM ZONE 84 ALARM ZONE 20 ALARM ZONE 84

ALARM ZONE 21 ALARM ZONE 85 ALARM ZONE 21 ALARM ZONE 85

ALARM ZONE 22 ALARM ZONE 86 ALARM ZONE 22 ALARM ZONE 86

ALARM ZONE 23 ALARM ZONE 87 ALARM ZONE 23 ALARM ZONE 87

ALARM ZONE 24 ALARM ZONE 88 ALARM ZONE 24 ALARM ZONE 88

84
Quadnet / Duonet OSP Software Operating Instructions

ALARM ZONE 25 ALARM ZONE 89 ALARM ZONE 25 ALARM ZONE 89

ALARM ZONE 26 ALARM ZONE 90 ALARM ZONE 26 ALARM ZONE 90

ALARM ZONE 27 ALARM ZONE 91 ALARM ZONE 27 ALARM ZONE 91

ALARM ZONE 28 ALARM ZONE 92 ALARM ZONE 28 ALARM ZONE 92

ALARM ZONE 29 ALARM ZONE 93 ALARM ZONE 29 ALARM ZONE 93

ALARM ZONE 30 ALARM ZONE 94 ALARM ZONE 30 ALARM ZONE 94

ALARM ZONE 31 ALARM ZONE 95 ALARM ZONE 31 ALARM ZONE 95

ALARM ZONE 32 ALARM ZONE 96 ALARM ZONE 32 ALARM ZONE 96

ALARM ZONE 33 ALARM ZONE 97 ALARM ZONE 33 ALARM ZONE 97

ALARM ZONE34 ALARM ZONE 98 ALARM ZONE34 ALARM ZONE 98

ALARM ZONE 35 ALARM ZONE 99 ALARM ZONE 35 ALARM ZONE 99

ALARM ZONE 36 ALARM ZONE 100 ALARM ZONE 36 ALARM ZONE 100

ALARM ZONE 37 ALARM ZONE 101 ALARM ZONE 37 ALARM ZONE 101

ALARM ZONE 38 ALARM ZONE 102 ALARM ZONE 38 ALARM ZONE 102

ALARM ZONE 39 ALARM ZONE 103 ALARM ZONE 39 ALARM ZONE 103

ALARM ZONE 40 ALARM ZONE 104 ALARM ZONE 40 ALARM ZONE 104

ALARM ZONE 41 ALARM ZONE 105 ALARM ZONE 41 ALARM ZONE 105

ALARM ZONE 42 ALARM ZONE 106 ALARM ZONE 42 ALARM ZONE 106

ALARM ZONE 43 ALARM ZONE 107 ALARM ZONE 43 ALARM ZONE 107

ALARM ZONE 44 ALARM ZONE 108 ALARM ZONE 44 ALARM ZONE 108

ALARM ZONE 45 ALARM ZONE 109 ALARM ZONE 45 ALARM ZONE 109

ALARM ZONE 46 ALARM ZONE 110 ALARM ZONE 46 ALARM ZONE 110

ALARM ZONE 47 ALARM ZONE 111 ALARM ZONE 47 ALARM ZONE 111

ALARM ZONE 48 ALARM ZONE 112 ALARM ZONE 48 ALARM ZONE 112

ALARM ZONE 49 ALARM ZONE 113 ALARM ZONE 49 ALARM ZONE 113

ALARM ZONE 50 ALARM ZONE 114 ALARM ZONE 50 ALARM ZONE 114

ALARM ZONE 51 ALARM ZONE 115 ALARM ZONE 51 ALARM ZONE 115

ALARM ZONE 52 ALARM ZONE 116 ALARM ZONE 52 ALARM ZONE 116

ALARM ZONE 53 ALARM ZONE 117 ALARM ZONE 53 ALARM ZONE 117

ALARM ZONE 54 ALARM ZONE 118 ALARM ZONE 54 ALARM ZONE 118

ALARM ZONE 55 ALARM ZONE 119 ALARM ZONE 55 ALARM ZONE 119

ALARM ZONE 56 ALARM ZONE 120 ALARM ZONE 56 ALARM ZONE 120

ALARM ZONE 57 ALARM ZONE 121 ALARM ZONE 57 ALARM ZONE 121

ALARM ZONE 58 ALARM ZONE 122 ALARM ZONE 58 ALARM ZONE 122

ALARM ZONE 59 ALARM ZONE 123 ALARM ZONE 59 ALARM ZONE 123

ALARM ZONE 60 ALARM ZONE 124 ALARM ZONE 60 ALARM ZONE 124

ALARM ZONE 61 ALARM ZONE 125 ALARM ZONE 61 ALARM ZONE 125

ALARM ZONE 62 ALARM ZONE 126 ALARM ZONE 62 ALARM ZONE 126

ALARM ZONE 63 ALARM ZONE 127 ALARM ZONE 63 ALARM ZONE 127

ALARM ZONE 64 ALARM ZONE 128 ALARM ZONE 64 ALARM ZONE 128

85
Quadnet / Duonet OSP Software Operating Instructions

Your Notes

86
Quadnet / Duonet OSP Software Operating Instructions

Your Notes

87
Quadnet / Duonet OSP Software Operating Instructions

Important Points

• You will need a PC with a serial port, the Quadnet / Duonet OSP
software and a Quadnet / Duonet USB Lead (page 6).

• How to get your set-up ready Getting Started (page 7).

• How to go about programming your first system (page 67).

• Cause & Effect and how to program it (page 57).

• How to program Loop Inputs and Outputs to interface the system to


other equipment (page 69).

• How to program Alarm Confirmation to reduce unwanted alarms in


dwelling places (pages 36 + 73).

• Programming Examples of different approaches to your system


operation (page 75).

• How to Add/Delete/Swap devices on a software allocated


addressing system (page 68).

If you have any further queries, please contact your supplier for further information

88

You might also like