Software Operating Instructions: Quadnet / Duonet OSP - V3.0x
Software Operating Instructions: Quadnet / Duonet OSP - V3.0x
Software Operating Instructions: Quadnet / Duonet OSP - V3.0x
0x
(Suitable for Quadnet / Duonet control and repeater panels from V3.00)
26-1006 Issue 5
1
Quadnet / Duonet OSP Software Operating Instructions
Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care
has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in
respect of such contents.
Due to the complexity and inherent importance of a life risk type system, training on this equipment is essential and commissioning should only
be carried out by competent persons.
Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with, without variation.
E&OE.
Fike equipment is protected by one or more of the following patent no’s: GB2426367, GB2370670, EP1158472, PT1035528T, GB2346758,
EP0917121, GB2329056, EP0980056, GB2325018, GB2305284, EP1174835, EP0856828, GB2327752, GB2313690
© 2010 Fike Safety Technology Ltd. All rights reserved. Document revised January 2013.
2
Quadnet / Duonet OSP Software Operating Instructions
Contents
Introduction .......................................................................................................................... 6
3
Quadnet / Duonet OSP Software Operating Instructions
4
Quadnet / Duonet OSP Software Operating Instructions
Technical Data...................................................................................................................... 81
Duonet Control Panel ............................................................................................... 81
Quadnet Control Panel ............................................................................................. 81
OSP Version Compatibility. ...................................................................................... 82
Technical Support ..................................................................................................... 82
5
Quadnet / Duonet OSP Software Operating Instructions
Introduction
Quadnet / Duonet OSP is the name given to the high level software package written to enable the
individual configuration of the Duonet and Quadnet fire alarm systems. The Windows based program
allows the system to be set up for each application. This includes the setting of detection modes,
subsequent actions to be taken and individual sound patterns. Note that whichever panel is used, there is
no difference in the mode of operation of the program.
Much thought has taken place to implement operations in as simple a way as possible whilst not losing
flexibility through over-simplification. Hence, complicated arrangements with three alarm stages may be
arranged as required in order to tailor system operation to the client’s building or safety procedures.
Tools are also included to enable you to create reports and specifications from your programming,
including both configuration and event log reports.
Getting Started
System Requirements
The Quadnet / Duonet OSP configuration software is available on the Fike Software CD. In order to run the
program you will require the following:
IMPORTANT NOTE:
6
Quadnet / Duonet OSP Software Operating Instructions
Physical Connections
The USB Interface lead connects between the USB port on the control panel and any USB port on the PC.
Software Installation
In order to commence installation, insert the OSP CD-ROM in your CD-ROM drive. The disc will
automatically run and open up a browser style menu screen containing a number of different directories,
including one that is titled ‘Software’. Open this directory and then open the directory titled ‘Fike Quadnet
v30x’ (or Duonet OSP 3.0x.exe) - as the version may vary, simply choose the latest available. Run the
‘Setup.exe’ file and follow the instructions while the software loads onto your hard disk drive.
or
A shortcut from the file titled ‘Quadnet OSP 3.0x’. (or ‘Duonet OSP 3.0x’) may then be copied onto the
desktop for ease of access, and labelled with the correct version number to prevent confusion with possible
future releases, as shown below.
Note that USB drivers for the Quadnet / Duonet will have to be installed before the panel can be connected
to the USB port.
7
Quadnet / Duonet OSP Software Operating Instructions
Data Transfer.
The Quadnet / Duonet is defined as an Addressable Intelligent Detector System, or an Addressable
Fire Detection and Alarm System with Independent Distributed Intelligence. Distributed intelligence
signifies that the signal processing is spread throughout the system in the form of a microprocessor in
every device, in order that the decisions about fires and faults are taken within the detector itself.
The detector is capable of being remotely programmed for different modes of detection, sound patterns,
etc. Thus we have two separate data transfer functions - get-config / re-config between devices and control
panel, and upload / download between control panel and computer.
The get-config / re-config functions are operated from the control panel at ‘Access level 3 (Engineer)’. If
you have not entered Engineer mode at the PC, the functions will not work and the PC will display warning
messages. Generally the configuration must be loaded to the control panel (get-config), before any upload
to computer, and vice versa - the configuration must be loaded to the devices (re-config) after any
download from computer to control panel.
If a device is to be replaced with a similar type, then after re-initialising the loop the system must be
reconfigured. The control panel memory holds the system configuration data, so in the event of a device
replacement, a PC is not necessarily required to reconfigure the device.
8
Quadnet / Duonet OSP Software Operating Instructions
At Access Level 3 (Engineer), the main Fire Alarm Controls are enabled, and the following System
Controls are accessible:
4. Network
5. Aux I/O
6. View No of Devices Programmed
7. View No of Devices in Last Init
NEW
INITIALISATION
NO INVESTIGATE FAULTS AND
LOOP CONTINUITY AND
INSULATION TEST RESULTS OK? RECTIFY
YES
EXTENSION NEW
YES
YES
HAVE YOU PRE-PROGRAMMED OPEN PREVIOUSLY
YOUR CONFIGURATION? PROGRAMMED FILE
NO
PROGRAMMING
IS THE LOOP UNCHANGED SINCE NO INITIALISE THE LOOP
THE LOOP WAS STOPPED?
YES
REMOVE DEVICES, INVESTIGATE FAULTS
START LOOP AND RECTIFY. THEN REPLACE DEVICES
NO
DID THE LOOP START UP
AND RUN CORRECTLY?
YES
10
Quadnet / Duonet OSP Software Operating Instructions
Main Screen
The ‘Status & Menu’ screen is the front page, index and guide for programming using Quadnet / Duonet
OSP. Functions are controlled via the various on-screen buttons (arranged vertically to the left of the
screen) and menus (arranged horizontally at the top of the screen).
When features in the OSP program are selected by pressing buttons, Cancel and OK buttons will appear at
the bottom of the screen. OK is pressed to accept any changes to the data that you make. Cancel is
pressed to leave the feature without saving any data changes.
11
Quadnet / Duonet OSP Software Operating Instructions
‘File’ Menu
New Site
This feature will create a ‘New’ configuration file with extension (*.site).
This file type may be classed as ‘unlocked’, allowing modifications to be made to the loop configuration.
Open Site
This feature will open an existing, or ‘Old’ configuration file. This function is also repeated in the form of an
on-screen button in the toolbar immediately below the file menu.
i.e.
This file type may be classed as ‘locked’, allowing no modifications to be made to the loop configuration.
Thus you are prevented from downloading an incorrect file into a system.
Save As
This feature will save configuration file to the file name and address of your choice. This function is also
repeated in the form of an on-screen button in the toolbar immediately below the file menu.
i.e.
This feature has two sub options as shown in the sub-menu below.
12
Quadnet / Duonet OSP Software Operating Instructions
This allows you to send a summary of all the devices to the printer. There is also a print button on the
device details screen for this operation.
Loop Number
Device Number
Device Label
Serial Number
Device Type
No of Spurs
Zone No
Smoke Detection details if applicable
Heat Detection details if applicable
Sound Pattern 1 if applicable
Volume Level 1 if applicable
Sound Pattern 2 if applicable
Volume Level 2 if applicable
Sound Pattern 3 if applicable
Volume Level 3 if applicable
Alarm Confirmation (ON/OFF)
This allows you to send a summary of further information about all the devices (including DLU details) to
the printer.
Loop Number
Device Number
Device Label
Serial Number
Device Type
Sub Type
Sound Pattern 1 if applicable
Volume Level 1 if applicable
13
Quadnet / Duonet OSP Software Operating Instructions
Open Backup
This allows you to open the backup of the previously saved configuration file. It will have been
automatically created in the format *.sitebak
Exit
New Files
You will be first be prompted with a “Save As” screen for a name for the site. Site data files are saved with
type “.site”.
A new site data file will now be created. Initially it will consist of a single panel (Panel 001) with a single
loop. With a Duonet system, up to 2 loops may be configured. With a Quadnet system, up to 4 loops may
be configured.
You may now amend the configuration file as described in the following pages. This ‘New’ file does not
contain initialised device address details or serial numbers.
The file may then be sent to the control panel with the download command. After download, remember to
carry out the following:
14
Quadnet / Duonet OSP Software Operating Instructions
1. ‘Initialise’ Loop
3. ‘Reset’ system
Tools Menu
Engineer Notes
This feature allows the Engineer to enter assorted notes in free-form format. The file can be saved in “.txt”
format by pressing “Save”.
15
Quadnet / Duonet OSP Software Operating Instructions
The Site Config Report option allows the creation of text files from your configuration, in the *.txt format.
The following screen offers options that may be ticked so that you can select which details are included in
the site report.
16
Quadnet / Duonet OSP Software Operating Instructions
The site report file may be saved in the format ‘file_name’.txt by utilising the ‘Save As’ command in the File
menu at the top of the screen. The file may be opened in Microsoft WordPad or imported into Microsoft
Word. However, some fonts will cause the tabulation to alter when using Microsoft Word. The print function
may be used directly from the ‘File’ menu, from within Word or WordPad.
The Event Log Report option allows the creation of text files from any event logs which have previously
been uploaded from the panel. The files will be in the *.txt format. The following screen offers options that
may be ticked so that you can select which details are included in the event log report.
17
Quadnet / Duonet OSP Software Operating Instructions
18
Quadnet / Duonet OSP Software Operating Instructions
As with the site report file, the event log report may be saved in the format ‘file_name’.txt by utilising the
‘Save As’ command in the File menu at the top of the screen. The file may be opened in Microsoft
WordPad or imported into Microsoft Word. However, some fonts will cause the tabulation to alter when
using Microsoft Word. The print function may be used directly from the ‘File’ menu, from within Word or
WordPad.
A network event log report may be made in the same way as an event log report. Note that the options
which can be selected are fewer as this event log only covers network events.
19
Quadnet / Duonet OSP Software Operating Instructions
This feature can be used to reset the default Zone to Zone cause and effect data for the currently selected
panel to the original factory settings. An “Are You Sure” prompt is given.
For each of the 128 detection zones, the settings will be as follows
Group 1 – ALL Zones (1-28) selected. Links for Smoke alarm /MCP/heat/input set to Alarm stage 3. No
delays used.
Engineer Functions
Certain functions are provided for use by qualified engineers only. These have the drastic effect of deleting
all zone to zone Cause and Effect or deleting all point to point Cause and Effect and so they are password
protected.
Before any of the Engineer Functions can be used, the engineer must enter an AL4 security code.
20
Quadnet / Duonet OSP Software Operating Instructions
Engineer Controls
The Engineer Controls option is for the use of our engineers only. They can access this feature using a
special security code.
‘Help’ Menu
The Help Menu contains a single option which will display the current software version.
About Page
The About Page obtained from the Help menu gives details of the current software version of the OSP
program. An example is shown below.
21
Quadnet / Duonet OSP Software Operating Instructions
Prior to an Upload of the configuration from the control panel to the PC, or a Download of the configuration
from PC to the control panel, it is necessary for the panel to be in ‘Access Level 3 (Engineer Mode)’. The
panel must be connected to the PC via a USB lead.
Note that if the panel is left for a period of time, it will log itself out of Access Level 3 (Engineer Mode) so it
is best to check that it is in Engineer mode before doing anything at the PC.
Add
The Add button on the upload screen allows you to add a new panel to the current configuration on the PC.
This feature is also available on the “Panel Details” screen available from the “Panel Details” button.
Delete
The Delete button on the upload screen allows you to delete a panel to the current configuration on the PC.
This feature is also available on the “Panel Details” screen available from the “Panel Details” button.
22
Quadnet / Duonet OSP Software Operating Instructions
Copy
The Copy button on the upload screen allows you to copy the details from an existing panel to a new panel
number on the PC. This feature is also available on the “Panel Details” screen available from the “Panel
Details” button.
In the above example, we have selected Panel 001 from that site and the data from that panel will be
copied into Panel 008 in our configuration. The data may only be copied to a panel number that does not
already exist in the configuration. If you want to copy the data to an existing panel, the existing panel
should first be deleted using the Delete button.
Import
The Import button allows you to browse for a DIFFERENT site and copy the details of a panel on that site
to any panel number on the PC. This feature is also available on the “Panel Details” screen available from
the “Panel Details” button.
In the above example, we have picked a different site named Test 30-06-11.site. We have selected Panel
001 from that site and the data from that panel will be copied into Panel 003 in our configuration. It does
not matter whether Panel 003 already exists in our configuration, but if it does, any data will be overwritten.
23
Quadnet / Duonet OSP Software Operating Instructions
Upload Data
The Upload Data button allows you to upload data from the currently connected panel. A progress bar is
shown while the data is uploading. If there is a problem, a warning will be given. If this happens, you should
disconnect the USB and re-connect it before trying again. Also remember that the panel must be in
Engineer Mode.
Note that you must select a panel in the PC configuration which will be given the uploaded data. When this
has been selected you can press the Accept Upload button as shown in the example screen below.
If the panel that you have chosen already has data assigned to it, a prompt as follows will be given so that
you can change your mind.
It is possible to upload the event log from a panel. It is necessary for the panel to be in ‘Access Level 3
(Engineer Mode)’ and the panel must be connected to the PC via a USB lead.
You can save event logs with different dates and times from more than one panel on the PC.
Event logs can be viewed at a later date and a hard copy made using the Event Log Report feature in the
Tools menu.
24
Quadnet / Duonet OSP Software Operating Instructions
It is possible to upload the network event log from a panel. It is necessary for the panel to be in ‘Access
Level 3 (Engineer Mode)’ and the panel must be connected to the PC via a USB lead.
You can save network event logs with different dates and times on the PC.
Network event logs can be viewed at a later date and a hard copy made using the Network Event Log
feature in the Tools menu.
Prior to a Download of configuration data from PC to the control panel, it is necessary for the panel to be in
‘Access Level 3 (Engineer Mode)’. The panel must be connected to the PC via a USB lead.
Note that if the panel is left for a period of time, it will log itself out of Access Level 3 (Engineer Mode) so it
is best to check that it is in Engineer mode before doing anything at the PC.
The download button is found to the left of the main screen. On pressing it, the following screen is
obtained.
The Download button on this screen allows you to download configuration data from a selected panel in the
PC configuration to the panel to which the PC is connected. A progress bar is shown while the data is
downloading (as shown below).
25
Quadnet / Duonet OSP Software Operating Instructions
If there is a problem, a warning will be given. If this happens, you should disconnect the USB and re-
connect it before trying again. Also remember that the panel must be in Engineer Mode.
It is recommended that you do not use the Cancel Download button once downloading has begun.
Panel Details
Clicking on the ‘Panel Details’ button brings up the following screen.
26
Quadnet / Duonet OSP Software Operating Instructions
Note that there are eight tabs on this screen, each of which is described below.
Panel Summary
On this tab you can use the four buttons at the bottom of the screen to add/delete panels from the
configuration data as follows.
Add
The Add button on the upload screen allows you to add a new panel to the current configuration on
the PC. This feature is also available on the “Upload Data” screen available from the “Upload from
Control Panel” button.
Delete
The Delete button on the upload screen allows you to delete a panel to the current configuration on
the PC. This feature is also available on the “Upload Data” screen available from the “Upload from
Control Panel” button.
Copy
The Copy button on the upload screen allows you to copy the details from an existing panel to a
new panel number on the PC. This feature is also available on the “Upload Data” screen available
from the “Upload from Control Panel” button.
In the above example, we have selected Panel 001 from that site and the data from that panel will
be copied into Panel 002 in our configuration. The data may only be copied to a panel number that
does not already exist in the configuration. If you want to copy the data to an existing panel, the
existing panel should first be deleted using the Delete button.
Import
The Import button allows you to browse for a DIFFERENT site and copy the details of a panel on
that site to a panel number in the current configuration. This feature is also available on the
“Upload Data” screen available from the “Upload from Control Panel” button.
27
Quadnet / Duonet OSP Software Operating Instructions
In the above example, we have picked a different site named Test 30-06-11.site. We have selected Panel
001 from that site and the data from that panel will be copied into Panel 003 in our configuration. It does
not matter whether Panel 003 already exists in our configuration, but if it does, any data will be overwritten.
Panel Details
In the top section you can select the panel and the details of the selected panel will appear in the bottom
half of the screen where they may be edited.
Panel Modes
Panel Description
Loop Details
In the Loop Details section the quantity of the different types of devices on each loop are shown.
You can set up four lines of user-definable text which is shown on the panel when it is in a
quiescent state. The default text is shown in the sample screen above.
28
Quadnet / Duonet OSP Software Operating Instructions
Codes
The control panel access codes may be changed as required on this screen.
The default codes for Access Level 2A (user), Access Level 2B (user) and Access Level 3
(engineer) are shown above. They may be changed to any combination of 4 digits.
Upload and download may only be carried out from Access Level 3 (engineer). Changing the
engineer code will restrict access to those unauthorised to make such changes.
A Back Door code can be provided if the codes chosen are lost. If this is required, contact your
supplier with the following information:
29
Quadnet / Duonet OSP Software Operating Instructions
Alarm Delays
Four alarm delays can be programmed with values between 0:00 and 10:00 minutes.
An Alarm Confirmation delay may be set up so that when an alarm occurs, it is not immediately
reported. The system will wait until the end of the delay time and then check that the alarm is still
present. If it has cleared, the device which was in alarm will be reset and no further action need be
taken.
The delay time for alarm confirmation can be programmed from 1:00 – 4.00 minutes. You must
ensure that stage 1 sound pattern is active for every device with alarm confirmation. This option
cannot be used at the same time as alarm delay.
There is a tick box to decide whether any unconfirmed alarm warning should be displayed at the
panel.
Panel Timers
You can program how often the service timer is to occur so that the end-user is prompted to call for
a service. Options are 90, 180 and 360 days.
You can also specify a day and a time (hours and minutes on the 24 hour clock) for a weekly test to
be performed on the panel. Leave the fields blank if you do not want a weekly test.
Day/Night Mode
You can set times throughout the week (hours and minutes on the 24 hour clock) for day/night
mode to be operational by filling in the Days “From To” Table as shown in the tab. There can only
be one such time range set up per day.
30
Quadnet / Duonet OSP Software Operating Instructions
You can also specify (using the zone tick boxes) which zones are to be disabled during the
selected times. This could for example be used to disable smoke detection in a zone during the day
while enabling it at night.
Note that the zone list can be scrolled down and that there are 128 possible zones. Zones with MP
or MPS devices are shown with an asterisk by their number (e.g. Zones 002 and 005 in the
example above).
The “Select Zones” button will put a tick in all the zone boxes. The “Select No Zones” button will
clear all the zone tick boxes.
With this option, you can configure the system so that day / night mode will follow any panel inputs
set to day/night mode.
The “Select All Inputs” button will put a tick in all the input tick boxes. The “Select No Inputs” button
will clear all the input tick boxes.
Panel Inputs
For the Quadnet panel, up to 4 Panel Inputs can be configured on this tab.
For the Duonet panel, up to 2 Panel Inputs can be configured on this tab.
A Panel event can be configured as a Fire Event, a Control Event, a Technical Event, or left unconfigured.
31
Quadnet / Duonet OSP Software Operating Instructions
Fire Event
A Panel Input configured as a Fire Event will have an associated zone (Zone 1 in the above
example). It can also be selected to be latching or non-latching. These values may be changed
using the pull-down selection lists.
Control Event
A Panel input can be configured as any of the types of Control Event as shown in the pull-down
selection list below. Note that “Day Night Mode” may not be possible unless Day/Night mode has
been selected (with zones) on the Day/Night mode tab.
Technical Event
A Panel Input configured as a Technical Event will have an associated zone. It can also be
selected to be latching or non-latching. These values may be changed using the pull-down
selection lists. Note that when a Technical Event takes place, there will be no indication on the
panel display and the Fire LED will not light.
Panel Outputs
32
Quadnet / Duonet OSP Software Operating Instructions
Relay Outputs
For the Quadnet panel, four relay outputs (1-4) may be configured so that they will be activated
when certain conditions occur. Selection is made via radio buttons.
For the Duonet panel, outputs 3 and 4 are not available and they are greyed out.
A Zonal Fire Output (a zone must be specified in the range 1-128) is activated by a Fire in the
specified zone.
Monitored Outputs
Two monitored outputs (numbered 5-6 for the Quadnet and 1-2 for the Duonet) may be configured
so that they will be activated when certain conditions occur. Selection is made via radio buttons.
Note that on the Duonet backplane (Rev B), these outputs are labelled outputs 3 and 4.
Sounder Output (a zone must be specified in the range 1-128) is activated by Sounders in the
specified zone and stops on silence command.
A (Zonal) Fire Output (a zone must be specified in the range 1-128) is activated by a Fire in the
specified zone and stops on reset command.
Network
On this tab you can specify (for your chosen panel) which events are transmitted to the panel network. This
is done by ticking the relevant boxes in the “Transmit Event to Network” list.
You can also select whether the chosen panel is to react to any events received from the network. The
choices are made by ticking the relevant boxes in the “Action if Received” list.
33
Quadnet / Duonet OSP Software Operating Instructions
Printer
You can select whether the printer is to be enabled on the panel and if so, you can specify which types of
event are printed. Options are Fire Events, Fault Events, Panel Events and All Events.
34
Quadnet / Duonet OSP Software Operating Instructions
You can right click on fields as follows to edit the fields. The selection lists below have a tick by the default
values.
35
Quadnet / Duonet OSP Software Operating Instructions
Alarm Stages for Sounders (3 Stages) (if applicable for the type)
The system may operate with a total of two out of three Alarm Stages where the sound pattern selected at
‘Sound Stage X’ will operate.
3. Evacuate Full alarm condition, sounders and remote fire outputs are -
activated.
Volume Levels for Sounders (3 stages) (if applicable for the type)
AC (Alarm Confirmation)
36
Quadnet / Duonet OSP Software Operating Instructions
The activation of any Heat detector (even in the same device as the smoke detector in ‘Alarm
Confirmation’) generates an instant alarm (depending on the programming of the system ‘Cause & Effect’).
An ‘Alarm Stage 1’ sound pattern must be used for every multipoint detector requiring the ‘Alarm
Confirmation Delay’.
Edit Labels
The device labels are of critical importance in an addressable fire alarm system, so in order to avoid
accidentally changing them, the labels are ‘write protected’ by the Edit Labels button. Simply click on this
button to activate the ‘Edit Mode’, and click again to deactivate it when you have finished.
Device labels may be up to 23 alphanumeric characters long. Remember to press ENTER on your PC
keyboard to indicate that you have finished editing the selected label.
Edit Zone
The zone numbers may be edited in a similar way as the labels. In order to avoid accidentally changing
them, the zones are ‘write protected’ by the Edit Zone button. Simply click on this button to activate the
‘Edit Mode’, and click again to deactivate it when you have finished.
Sort by Address
This button will rearrange the order of the devices as seen on the screen so that they are in order of
address. It does NOT renumber the actual order of the devices on a loop.
Sort by Zone
This button will rearrange the order of the devices as seen on the screen so that they are in order of zone.
It does NOT renumber the actual order of the devices on a loop.
Device Details
This button allows you to edit properties as shown for the current device. You can also double-click on the
current device to obtain this screen.
The ‘Device Details’ button changes only the fields that have had entries changed. This is done for the
selected device only.
Zone Details
37
Quadnet / Duonet OSP Software Operating Instructions
This button allows you to edit properties as shown for the zone associated with the point that was currently
highlighted when the button was pressed.
Note that you can select which loop(s) are to have their details changed using the loop tickboxes.
The ‘Zone Details’ screen changes only the fields that have had entries changed. This is done for all the
devices that are in the same zone in the selected loops.
All Details
This button allows you to edit properties as shown for all points on selected loop(s) in the currently chosen
panel.
Note that you can select which loop(s) are to have their details changed using the loop tickboxes.
The ‘All Details’ screen changes only the fields that have had entries changed. This is done for all devices
that are in the selected loops in the panel and should be used with great caution.
38
Quadnet / Duonet OSP Software Operating Instructions
Add Device
This button allows you to add one or more new devices to the system. The prompt given is as follows.
Note that the start address must either be in the existing range of addresses or be the address immediately
after the last address in the list. The system will not allow any gaps.
If the start address lies within the range, the specified number of new devices will be added and devices
with higher addresses will be moved down the list to make room for the new devices.
The new devices will have default values as shown in the example below where 5 new devices have been
added starting with address 42 on loop 1. You can then edit the fields so that the correct types are used
together with your choice of alarm stage parameters.
Delete Device
This button allows you to delete one or more new devices from the system. The prompt given is as follows.
Note that the start address must be in the existing range of addresses.
When the devices have been deleted, devices with higher addresses will be moved up the list to remove
any gap.
39
Quadnet / Duonet OSP Software Operating Instructions
Data Entry
The “Data Entry” button allows you to modify data fields quickly.
Enter the loop number and the range of addresses that you wish to modify.
Tick only the boxes for fields that you want to modify.
Prompts will be given with the possible entries for each field in turn. Select your choice and press OK. The
fields already configured will be shown on the screen above the option box.
The Back button allows you to undo any changes that you have made. This will only work on the current
device being edited. You cannot go back to the previous device.
In the above example, all the fields except for the last two (Alarm Stage 3 Sound and Alarm Stage 3
Volume) have been configured and the user is being prompted to select a value for Alarm Stage 3 Sound.
The Cancel button allows you to discard all changes made in the “Data Entry” section.
40
Quadnet / Duonet OSP Software Operating Instructions
Sound Demo
The seven available sound patterns may be demonstrated audibly if your computer has suitable sound
facilities by using the “Sounds” button.
The following screen will be displayed. Clicking the buttons marked SP1 – SP7 will demonstrate that sound
pattern through the computer speakers.
Apply Zone
This button allows you to quickly transfer addresses to a chosen zone. Highlight a device in the table with
the desired zone number. Now click the Apply Zone button. A prompt will appear as shown below.
After pressing OK, you can double click on any other devices in the list and they will be assigned to your
chosen zone. To exit from this feature, click on the Apply Zone button again.
Apply Format
41
Quadnet / Duonet OSP Software Operating Instructions
This button allows you to quickly copy configured data from one address to another. Highlight the device to
be copied from in the table. Now click the Apply Format button. A prompt will appear as shown below. In
the example, the data will be copied from Loop 1 Device 10.
After pressing OK, you can double click on any other devices in the list and the data from your selected
device will be copied to them. Note that the label (text description) and serial number will not be copied.
To exit from this feature, click on the Apply Format button again.
This button allows you to print the table of device details on a printer. A prompt is given as follows so that
you can select printer details.
Press the Print button to send the data to the chosen printer. Note that the “Save as CSV” button can be
used to save the data in CSV (Comma Separated Values) format. The file could then be opened in a
spreadsheet program such as Microsoft Excel.
42
Quadnet / Duonet OSP Software Operating Instructions
The Quadnet / Duonet OSP programming software v3.00 or later (v3.04 or later required for the latest
devices) automatically keeps control of the quantity and will provide warnings if the limits are exceeded.
The main types of current (and earlier) devices and their loadings are listed below.
OSP will not be able to identify all subtypes of devices on existing systems but can identify all subtypes in
production as of March 2010.
43
Quadnet / Duonet OSP Software Operating Instructions
To get details about the DLU values, use the “Loop Load Calculations” button on the Device Details screen.
A typical display is shown below.
The lower section of the screen provides a summary of attributes for the highlighted device. Note that the
device serial number is located in the lower left hand corner of this box.
Versions of the Quadnet / Duonet OSP before V2.02 did not identify the subtype. V2.02 and above of the
Quadnet / Duonet OSP uses the type and serial number to calculate the subtype and all devices produced
from March 2010 can be identified as well as many previous ones. However, it is not always possible to do
this with early devices (as noted in the table above).
The loop loading calculations box gives a running total of the DLU values for the alarm stages on each
loop, together with a breakdown of each loop by device type. If any Alarm Stage DLU totals exceed 450,
they are printed in bold red text and a warning is given on leaving the screen so that the system can be
reconfigured with lower volume stages 1-3 or possibly with devices deleted or put onto a different loop.
This button will reset the subtypes of any devices which have had their sub-types reconfigured by the user.
The sub-types of any such devices will be returned to the default type.
44
Quadnet / Duonet OSP Software Operating Instructions
Device Types
The device types are listed below. The device is depicted pictorially in the left hand lower corner in order to
provide quick verification, as follows:
Picture Type
MP Multipoint Detector
Subtypes
Sub Types: Multipoint Mk 1
Multipoint Mk 2
Multipoint Mk 3
ASD Mk 1
ASD Mk 2
ASD Mk 3
Picture Type
Subtypes
Sub Types: Multipoint with sounder Mk 1
Multipoint with sounder Mk 2
Multipoint with sounder Mk 3
ASD with sounder Mk 1
ASD with sounder Mk 2
ASD with sounder Mk 3
45
Quadnet / Duonet OSP Software Operating Instructions
Picture Type
Subtypes
Sub Types: Manual Call Point Mk 1
Manual Call Point Mk 2
Manual Call Point Mk 3
Picture Type
Subtypes
46
Quadnet / Duonet OSP Software Operating Instructions
Picture Type
SDR Sounders
Note: Early devices with subtypes SoundPoint, HiPoint or Bell will be reported
as “Flashpoint”.
Picture Type
Subtypes
Sub Types: Loop I/O Module Mk 1
Loop I/O Module Mk 2
47
Quadnet / Duonet OSP Software Operating Instructions
Picture Type
Versions of the Quadnet / Duonet OSP before V2.02 did not identify the subtype. Quadnet / Duonet OSP
v2.02 and later use the device type and serial number to calculate the subtype. With this version all devices
produced from March 2010 can be identified as well as many previous ones. It is possible to override the
detected subtype on the “Manual Loop Loading Calculations” screen by highlighting the subtype field and
right-clicking on the field. A list of available subtypes for that type of device is then shown. Note however,
that these override values are NOT sent to the panel and will be lost the next time the loop data is
uploaded from the panel.
Overriding the subtype is only to be used when the correct item cannot be automatically detected by the
system. This feature should be used with caution and on the advice of Fike technical support. It must not
be used to artificially reduce the configured loop loading as this could have an adverse effect on the system
during an alarm condition,
48
Quadnet / Duonet OSP Software Operating Instructions
The I/O labels are of critical importance in an addressable fire alarm system, so in order to avoid
accidentally changing them, the labels are ‘write protected’ by the Edit I/O Labels button. Simply click on
this button to activate the ‘Edit Mode’, and click again to deactivate it when you have finished.
I/O labels may be up to 24 alphanumeric characters long. Remember to press ENTER on your PC
keyboard to indicate that you have finished editing the selected label.
The I/O zone numbers may be edited in a similar way as the labels. In order to avoid accidentally changing
them, the I/O zone numbers are ‘write protected’ by the Edit Zone button. Simply click on this button to
activate the ‘Edit Mode’, and click again to deactivate it when you have finished. Note that you cannot edit
the I/O zone number if it has not yet been set up. This can be done with the “Device I/O Details” button.
Sort by Address
This button will rearrange the order of the devices as seen on the screen so that they are in order of
address. It does NOT renumber the actual order of the devices on a loop.
Sort by Zone
This button will rearrange the order of the devices as seen on the screen so that they are in order of zone.
It does NOT renumber the actual order of the devices on a loop.
49
Quadnet / Duonet OSP Software Operating Instructions
The following is only applicable to devices of the following types - MP, MPS or I/O - which can be
configured for Auxiliary I/O properties. Devices of other types will be “Not Configured”. If this button is
pressed, you can edit the auxiliary I/O properties for the chosen device only.
This can be selected with a radio button. Note that if selected, this will increase the DLU value for
the loop.
2 Monitored Input
This can be selected with a radio button. Note that if selected, you will have to specify whether it is
to be a Fire Event, a Control Event or a Technical Event. Note that there are several types of
Control event as shown below.
If Disable is chosen as the Control event you will have to further specify whether Sounders, Fire
Outputs or Fault Outputs are to be disabled.
50
Quadnet / Duonet OSP Software Operating Instructions
3 Monitored Output
This can be selected with a radio button. Note that if selected, you will have to specify whether it is
to be a Device Output, Sounder Output (linked to a zone) or a Fire Output
The following is only applicable if you have highlighted a device which has one of the following types - MP,
MPS or I/O.
If this button is pressed, you can edit the auxiliary I/O properties as shown for the zone associated with the
point that was currently highlighted.
Note that you can select which loop(s) are to have their details changed for devices in the same zone using
the loop tickboxes.
The ‘Zone Details’ button changes only the fields that have had entries changed. This is done for all the
devices that are in the selected loops in the zone.
51
Quadnet / Duonet OSP Software Operating Instructions
This button allows you to edit auxiliary I/O properties as shown for all relevant points (i.e. with type MP,
MPS or I/O) on selected loop(s) in the currently chosen panel.
Note that you can select which loop(s) are to have their details changed using the loop tickboxes.
The ‘All Details’ button changes only the fields that have had entries changed. This is done for all devices
that are in the selected loops in the panel and should be used with great caution.
There is a different symbol for each possible type of device. A typical display is shown above.
Zones which currently contain devices are shown in bold type on the left hand side of the screen.
The “Hide Empty Zones” tickbox can be used to remove zones which currently have no devices configured
from the list.
52
Quadnet / Duonet OSP Software Operating Instructions
The “Highlight Devices” button can be used so that devices of the selected sort are shown with a thick
black border around them on the diagram. The list of options is given below.
Editing a Device
If you right-click on a device, a menu similar to that shown below will be shown.
You can now edit any of the available fields for the device. The options are as described in the Device
Details Tab section of this manual.
Note that if you click on Properties, you will get the Edit Properties screen for editing the properties of a
single device as described in the Device Details Tab section of this manual.
Apply Format
This button allows you to quickly copy configured data from one address to another.
53
Quadnet / Duonet OSP Software Operating Instructions
Click on the OK on the prompt. Now click on the device from which you would like to copy data. The
chosen device will turn blue.
Click on the OK on the prompt and then click on the devices which are to receive the same formatting as
the first device. They will turn black as you click on them When all devices have been selected, click on the
OK button at the bottom of the screen. The following prompt will be shown, allowing you to cancel if
necessary by clicking on “No”.
Note that this feature can only be used once. To perform more formatting, you must exit the Graphical View
tab and then select the tab again
54
Quadnet / Duonet OSP Software Operating Instructions
This tab shows a graphical display showing how the devices on a selected loop are connected.
The loop is selected with the loop radio buttons at the top of the screen. More details are shown on this
screen than on the Graphical View tab and you will need the scrollbars to see all the devices on the loop.
Note that the same symbols as on the Graphical View tab are used.
A Print button is available to send a copy of the connection map to the printer.
55
Quadnet / Duonet OSP Software Operating Instructions
Note that you can select the page to be printed using the pull-down selection box at the top left of the
screen. However, when you press Print, there is no option to select a printer. Your default Windows printer
will be used.
You can exit this screen without printing by clicking on the Close (X) box in the top right of the screen.
56
Quadnet / Duonet OSP Software Operating Instructions
Sometimes it may be desirable to delay the alarm response, or maybe only to sound the alarms in a certain
area, and this may well depend upon the area of origin of the activated device. This is known as ‘Phased
Evacuation’.
The ‘Cause & Effect’ area allows programming of different types of zonal based ‘Phased Evacuation’.
The flow chart below explains how the Quadnet / Duonet ‘Cause & Effect’ operates:
57
Quadnet / Duonet OSP Software Operating Instructions
Clicking on the ‘Cause & Effect’ button will bring you to the following screen.
For the majority of simple systems we recommend that a full alarm (stage 3) should be given in all zones
for any input type (one out, all out).
If any different ‘Cause & Effect’ actions are required then follow the instructions in the “Cause and Effect
Wizard” which can be found on the Alarm Stage 1 tab. These will remind you of the steps to carry out as
listed below.
The initial tab shown on the Zone to Zone Cause and Effect Screen is a summary. Alarm zones 1-5 have
been selected for Alarm Stage 1. Cause and Effect links have been set up in Group 1. Group 2 has not
had any links set up.
Please note that only two Groups of Zone to Zone Cause and Effect can be set up. Groups 3-6 are
currently not available.
Select the detection zone which contains the inputs which will CAUSE the outputs to be turned on at the
top of the screen.
As there are 128 possible detection zones, a tickbox “Hide Empty Detection Zones” has been provided. If
ticked, this will remove all “empty” detection zones from the pull-down zone list, i.e. all detection zones
which do not contain input devices. This makes selecting the correct zone easier to carry out.
Note that you can edit a description for the selected zone. The default text provided is of the form ZONE
xxx.
58
Quadnet / Duonet OSP Software Operating Instructions
Note that there is a “Hide Empty Alarm Zones for Alarm Stage 1” tick box. If this is ticked only zones which
have output devices in them will be included in the list. If this box is NOT ticked, all 128 zones are shown
(as in the above screen) and you will have to use the scroll bar to see them all. Note that zones which are
not empty (i.e. with output devices in them) are shown with their description underlined. In the above
example, these are zones 1 to 5.
Put ticks in the boxes for the alarm zones to be affected when the chosen detection zone (zone 1 in our
example) has an input in alarm.
There are four buttons which may make ticking the boxes easier.
Select No Zones – This will remove the ticks from all 128 boxes.
Select All Alarm Zones – This will put ticks in all the non-empty alarm zone tickboxes – i.e. the
ones that have output devices in them and which have their descriptions underlined. In the above
example, these are zones 1 to 5.
Select No Alarm Zones – This will remove all ticks from all the non-empty alarm zone tickboxes –
i.e. the ones that have output devices in them and which have their descriptions underlined. In the
above example, these are zones 1 to 5.
59
Quadnet / Duonet OSP Software Operating Instructions
A summary of all the currently programmed links is given in the box labelled Link.
Smoke alarm
MCP/heat/input
nd
2 smoke alarm
These links are like filters, and only the options selected will allow a following action to happen (i.e.
sounders on). The Alarm Stage chosen here will cause the sounders activated to operate with the sound
pattern set earlier in the Device Details screen.
You can program which alarm stages are to result when your chosen link type occurs.
Note that the 4 possible delay lengths are configured in the Panel Details Delays and Timers tab. This must
be done before any delay type is selected here. Otherwise an error message will be given.
nd
Note that you cannot select both Smoke alarm and 2 smoke alarm simultaneously for your links.
Use the summary box labelled Link at the top to check your selections before proceeding.
60
Quadnet / Duonet OSP Software Operating Instructions
Select the required Alarm Zones for Group 1. These are the areas in which the sounders and outputs will
operate when a Group 1 link is activated. Alarm Zones left unchecked will not operate.
Put ticks in the boxes for the alarm zones to be affected when the links from the chosen detection zone
(zone 1 in our example) cause further alarm stages to occur.
There are four buttons which may make ticking the boxes easier.
Select No Zones – This will remove the ticks from all 128 boxes.
Select All Alarm Zones – This will put ticks in all the non-empty alarm zone tickboxes – i.e. the
ones that have output devices in them and which have their descriptions underlined. In the above
example, these are zones 1 to 5.
Select No Alarm Zones – This will remove all ticks from all the non-empty alarm zone tickboxes –
i.e. the ones that have output devices in them and which have their descriptions underlined. In the
above example, these are zones 1 to 5.
Use the summary box labelled Link at the top to check your selections before proceeding.
Data for the detection zone is saved by clicking on OK. Cancel can be used to leave the screen without
saving data.
61
Quadnet / Duonet OSP Software Operating Instructions
As well as configuring Zone to Zone cause and effects, it is also possible to configure point input to output
cause and effects. Up to 50 of these “Actions” may be set up. If both zone to zone & point to point cause &
effects are used together, the zone to zone actions will be acted on first. Point to point cause and effect
should not be used for time critical actions.
A typical screen is shown below. The Cause and Effect tab is shown. A summary tab is also available.
OR Function With the OR function the configured outputs will be activated whenever ANY of the
inputs in the input list occur.
AND Function With the AND function the configured outputs will only be activated whenever ALL
of the inputs in the input list occur.
Double Knock Function The configured outputs will only be activated when TWO OR MORE of
the inputs in the input list have occurred. They will not be activated if only one input has occurred.
The inputs and outputs are selected by putting ticks in the relevant boxes.
The Clear Action button will remove ALL ticks from ALL boxes for the currently selected Action.
Note that scroll bars are necessary to view all inputs and outputs current configured in the system.
In the Input Points list any devices which do not contain inputs are greyed out. For example, in the above
sample screen, address 7 is greyed out as it is a sounder.
In the Output Points list any devices which do not contain outputs are greyed out. For example, in the
above sample screen, address 15 is greyed out as it is a manual callpoint.
Note that devices such as MPS may have auxiliary outputs configured as fire outputs or device outputs as
well as sounders. If this is the case, you can select which is to be activated in the output list. The default
chosen is “Sounder” (as in the above example screen) but you can change this to Output if an auxiliary
62
Quadnet / Duonet OSP Software Operating Instructions
output has been configured. Auxiliary outputs are configured on the Device I/O tab in the Device Details
section.
You can use the summary tab to check your selections. A typical summary tab is shown below.
You can use the summary tab to check your configuration. A typical summary tab is shown below.
Note that the output devices will have (s) to indicate sounders and (o) to indicate outputs.
63
Quadnet / Duonet OSP Software Operating Instructions
Diagnostics
Before diagnostics can be used, the Quadnet Loop Diagnostic program must have been installed on the
PC. If this has not been done, a warning screen is displayed.
This program is primarily for the use of Fike engineers. There are 3 tabs as follows:
CIE Diagnostics
Loop Diagnostic
64
Quadnet / Duonet OSP Software Operating Instructions
CIE Diagnostic
This tab allows the engineer to view the data packets being sent around the system.
Loop Diagnostic
This tab allows the engineer to view the data packets being sent around the loops on the panel.
65
Quadnet / Duonet OSP Software Operating Instructions
This feature can be found under the Tools dropdown menu and allows the currently configured data to be
checked for inconsistencies and errors.
Device settings
Panel Settings
Zone to Zone Cause and Effects
Device to Device Cause and Effects
A typical report is shown below. In the example, alarm zones have been configured for cause and effect to
turn on outputs in zone 1 group 1. However, no such outputs have been set up.
66
Quadnet / Duonet OSP Software Operating Instructions
Routine Operations
1. Initialise the system. The control panel will interrogate the loop to build up a database of the
configuration. Ensure that the correct number of devices has been found and that initialisation is
complete.
2. Upload the configuration. Upload the original configuration from the control panel and save it as
‘Filename original’, i.e., ‘HarloweHouse original’. It is good practice to keep this file and not over-
write it with another. If any confusion exists it is handy to investigate the original configuration.
3. Verify the position of the devices. Use the device serial numbers to ensure that your ‘As-wired’
drawings or connection schematic is correct. The upload configuration will be correct so amend your
notes to reflect this.
4. Program as required. Configure the control panel and device attributes as required.
5. Save this file. Save the file as ‘Filename final’, i.e., ‘HarloweHouse final’. The download option is
available without saving the file, but it is good practice to save the file in any case.
6. Download the file into the control panel. After download remember to carry out the following:
67
Quadnet / Duonet OSP Software Operating Instructions
6. Upload from the fire panel and save the file. The data will now have the correct serial numbers
for any devices which have been added. This will be the finished version of the file.
68
Quadnet / Duonet OSP Software Operating Instructions
I/O Options
I/O options may be configured to suit your individual applications as described below. Further details of the
electrical configuration may be found in the Engineering and Commissioning Instructions. The Loop
Powered I/O Module is programmed in a similar manner, but with fewer options. The table indicates
whether an EOL resistor is necessary. Note that if Auxiliary I/O is set to ‘Not Configured’, it will not require
an EOL resistor.
2. REMOTE Output will follow the fire and fault indication of the Multipoint. LED None Y N
INDICATOR The LED will require a 10K series resistor -
Default setting
3. MONITORED The input will monitor for fire (680R) and fault (3K3 EOL), and 3K3
INPUT trigger the system into the fire state, indicating ‘Aux input’ on the
display.
4. MONITORED The output will monitor for fault (3K3 EOL) and the output will 3K3
OUTPUT cause the relay on the ‘I/O Interface Module’ to change state.
Device – The relay will follow the fire state of the host detector Device Y N
independent of control panel instruction, including during alarm
confirmation.
Alarm Zone – The relay will follow the Alarm Zone of the host Sounder Y Y
device.
Auxiliary (I/O) Zone – The relay will follow the I/O zone. Sounder Y Y
Setting the output type to either Sounder or Output (= Remote / Remote
Fire Output) in ‘Cause & Effect’ will determine the ‘Output Fire
Group’
Output Groups
The operations of the output groups are shown in the table below.
2. DEVICE Follow fire state of host device Alarm commencement of host Reset of host device
device
69
Quadnet / Duonet OSP Software Operating Instructions
They may be configured to suit your individual applications as described below. Further details of the
electrical configuration may be found in the Engineering and Commissioning Instructions. Note that if
monitored inputs or outputs are set as ‘Not Configured’, they will not require EOL resistors.
Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None
Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone
Common Fault The relay coil will de-energise in any fault condition None
2. OUTPUT 2 Not configured The relay will not change state None
Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None
Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone
Common Fault The relay coil will de-energise in any fault condition None
3. OUTPUT 3 Not configured The relay will not change state None
(NOT
AVAILABLE Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None
ON
DUONET) Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone
Common Fault The relay coil will de-energise in any fault condition None
4. OUTPUT 4 Not configured The relay will not change state None
(NOT
AVAILABLE Fire Output (Common) The relay coil will energise in any fire condition Fire Prot None
ON
DUONET) Fire Output (Zonal) The relay coil will energise in a fire condition from None
the specified zone
Common Fault The relay coil will de-energise in any fault condition None
5. MON Not configured The relay will not change state None
OUTPUT 5
(MON Sounder s Output The output will energise in any fire activation from Sounder 10k
OUTPUT 1 (Zone must be specified) specified zone, de-energise on silence
ON
DUONET) Fire Output The output will energise in any fire activation from Fire Prot 10k
(Zone must be specified) specified zone, de-energise on reset
Common Fault The relay coil will de-energise in any fault condition 10K
6. MON Not configured The relay will not change state None
OUTPUT 6
Sounder s Output The output will energise in any fire activation from Sounder 10k
(MON (Zone must be specified) specified zone, de-energise on silence
OUTPUT 2
ON Fire Output The output will energise in any fire activation from Fire Prot 10k
DUONET) (Zone must be specified) specified zone, de-energise on reset
Common Fault The relay coil will de-energise in any fault condition 10K
70
Quadnet / Duonet OSP Software Operating Instructions
Technical Event input A 680 ohm firing resistor will trigger a technical alarm 3k3
Latching (for specified state in specified Detection Zone) and clear on
zone) Reset System
Technical Event input Non- A 680 ohm firing resistor will trigger a fire state in 3k3
Latching (for specified specified Detection Zone) but will clear when the
zone) firing resistor is removed
If the EOL is O/C a fault will be generated.
INPUTS 2-4 have the same options as for INPUT 1 in the above table.
Output Groups
Quadnet Outputs
Outputs 1 to 4 are derived from single pole change over ‘volt-free’ relay contacts which are not fault
monitored. The relay contacts are rated at 30VDC / 1A max.
The default setting for output 1 causes the relay to operate as a Common Fire output where the relay is
energised in the fire condition. The default setting for output 2 causes the relay to operate as a Common
Fault output where the relay is de-energised in the fault condition. Various other states may also be set
using the OSP programming software. However, to meet the requirements of EN54-2, Outputs 1 and 2
must be left as Common Fire and Common Fault respectively.
The default setting for outputs 3 and 4 causes the relay to operate as a Common Fault output where the
relay is de-energised in the fault condition. Various other states may also be set using the OSP
programming software.
Monitored Outputs 5 and 6 are monitored circuits which may be configured to monitor for open and short
circuit faults with a 10k EOL resistor, and to be activated with a stage 3 alarm.
Quadnet Inputs
Inputs 1-4 may be configured to monitor for open and short circuit faults using a 3k3 EOL resistor, and to
activate an alarm link using a 680R ‘firing’ resistor.
71
Quadnet / Duonet OSP Software Operating Instructions
Duonet Outputs
Outputs 1 and 2 are derived from single pole change over ‘volt-free’ relay contacts which are not fault
monitored. The relay contacts are rated at 30VDC / 1A max.
The default setting for output 1 causes the relay to operate as a Common Fire output where the relay is
energised in the fire condition. The default setting for output 2 causes the relay to operate as a Common
Fault output where the relay is de-energised in the fault condition. Various other states may also be set
using the OSP programming software. However, to meet the requirements of EN54-2, Outputs 1 and 2
must be left as Common Fire and Common Fault respectively.
Monitored Outputs 5 and 6 are monitored circuits which may be configured to monitor for open and short
circuit faults with a 10k EOL resistor, and to be activated with a stage 3 alarm.
The default setting for these monitored outputs causes the circuits to operate as Common Fire Sounder
Circuits, where the outputs turn on in the alarm condition. Various other states may also be set using the
OSP programming software.
Duonet Inputs
Inputs 1-2 may be configured to monitor for open and short circuit faults using a 3k3 EOL resistor, and to
activate an alarm link using a 680R ‘firing’ resistor.
72
Quadnet / Duonet OSP Software Operating Instructions
Smoke is detected in
one room of an
apartment
3 OPTIONS TO CHOOSE
Either 1 or 2 or 3
This function affects the smoke detector only, and operates before the control panel enters the Fire state.
Thus, the system ‘Cause & Effect’ does not need to be adjusted as Alarm Confirmation takes place
before the programmed Cause & Effect sequence is reached.
In order to activate this function, set the attributes detailed in ‘System details’ and ensure that ‘Stage 1’
sound settings have been programmed for every device requiring Alarm Confirmation. Note that Alarm
Confirmation cannot be programmed at the panel. It must be done using the OSP program.
73
Quadnet / Duonet OSP Software Operating Instructions
An Alarm Confirmation delay may be set up so that when an alarm occurs, it is not immediately reported.
The system will wait until the end of the delay time and then check that the alarm is still present. If it has
cleared, the device which was in alarm will be reset and no further action need be taken.
The Alarm Confirmation Delay timers is located within the ‘Panel Details’ area on the ‘Delays and Timers’
tab and may be set to give the required Alarm Confirmation Delay time.
The use of this feature allows an automatic reset of an unconfirmed alarm from a smoke detector. It also
allows an Alarm Stage 1 sound pattern for each device required, in the ‘Device Details’ section.
At the end of the ‘Alarm Confirmation Delay’ time the system will check the detector again to see if the
activation has cleared. If so then the device will reset and no further action need be taken.
The sounder operates during the chosen ‘Alarm Confirmation Delay’ time, and stops for the final 20
seconds, during which time the device is reset to check for further smoke presence.
During the ‘Alarm Confirmation Delay’, the activation of an additional smoke detector into ‘Alarm
Confirmation’ will cause the delay time to cease and an instant alarm to be generated.
If, however, the detector is still activated when the alarm confirmation delay is finished, then the entire
system will go into alarm, operating all the sounders programmed in the ‘Cause & Effect’ area.
For a further time period (10 min - ‘Alarm Confirmation Delay’), the activation of the same smoke detector
will cause an instant alarm (depending on the programming of the system in ‘Cause & Effect’).
The activation of any Heat detector (even in the same device as the smoke detector in ‘Alarm
Confirmation’) generates an instant alarm (depending on the programming of the system ‘Cause & Effect’).
Alarm Stage 1
These attributes may be set for each device which is to utilise Alarm Confirmation. Smoke detectors
without the attributes will operate in a standard manner (depending on the programming of the system
‘Cause & Effect’).
The ‘Alarm Stage 1’ sound pattern must be used in conjunction with the ‘Alarm Confirmation Delay’.
If Alarm stage 1 is set then the sounder in that device only operates if its smoke detector is in alarm
(unless zonal confirmation is set - then all sounders on that zone will operate). This is ‘Alarm stage 1’. The
device will revert to ‘Alarm stage 2 or 3’ when Alarm stage 1 is off. (Any subsequent actions may need to
be programmed as required under the ‘Cause & Effect’ section).
If you require the alarm confirmation signal to operate sounders on other zones, then alarm confirmation
cause and effect can be programmed by selecting the zones in Alarm Stage 1 under the ‘Cause & Effect’
section
The activation of any Heat detector (even in the same device as the smoke detector in ‘Alarm
Confirmation’) generates an instant alarm (depending on the programming of the system ‘Cause & Effect’).
74
Quadnet / Duonet OSP Software Operating Instructions
Example Configurations
Following are some examples of the configuration required for varying single and multi stage alarm
scenarios.
Group 1 and/or group 2 may be set up as shown in the examples on the following pages. Remember that
these groups need to be configured for every ‘Detection Zone’ required. As the highest priority event
always overrides all lower priority events, the groups may be programmed in any order.
This list is not exhaustive and you may find many different ways of configuring your alarm response.
Consultation with the End User and the relevant Fire Authority is essential.
In these examples, the panel Monitored outputs 5 and 6 have been put into zones 67 and 68 respectively.
Panel Monitored outputs are configured on the Panel Outputs tab on the Panel Details screen.
Instant Alarms
If you require an instant alarm response to any detector, manual call point or input alarm then set Group 1
as follows. This is the standard default configuration supplied with new systems, so generally this will not
need any alterations.
75
Quadnet / Duonet OSP Software Operating Instructions
Any fire input (i.e. smoke, heat, call point input), from this Detection Zone (Zone 1) will cause an ‘Alarm
stage 3 (Evacuate)’ sound in Alarm Zones 1 - 128.
Remember that the group 1 and 2 configuration must be set for every ‘Detection Zone’ required (not just for
Zone 1), both on initial commissioning and during any future alterations to the system.
Note the selection of Alarm Zones 67 and 68 (in Group 1) to enable the operation of the two conventional
sounder circuits (Monitored Outputs 5 and 6) at the control panel.
‘Smoke Alert’
An early warning (Alert) maybe raised in the event of a smoke detector triggering, in order to give time for
staff to investigate. Heat detection and manual call points should normally be left with an instant response.
To achieve this result set Group 1 as follows.
Note that Group 2 should be set with all the links unticked as shown below.
76
Quadnet / Duonet OSP Software Operating Instructions
Any smoke alarm input on Detection Zone 1 (Zone Basement) will cause an ‘Alarm stage 2 (Alert)’ sound in
Alarm Zones 1 to 5. Note that the “Hide Empty Alarm Zones” box has been ticked, making it easier to see
which zones are actually involved in the outputs.
After a time delay (configured earlier as Alarm Delay 1 in the Delays and Timers tab on the Panel System
Details screen), the sound will change to an ‘Alarm stage 3 (Evacuate)’ sound.
This sound will also be used on a heat or call point activation but with no delay.
Note the selection of Alarm Zones 67 and 68 (in Group 1) to enable the operation of the two conventional
sounder circuits (Monitored Outputs 5 and 6) at the control panel. These are only triggered from the ‘Alarm
stage 3’ activation.
Remember that the group 1 and 2 configuration must be set for every ‘Detection Zone’ required (not just for
Zone 1), both on initial commissioning and during any future alterations to the system.
Phased Evacuation
Alternatively, an early warning (Alert) can be raised within the local area in the event of a smoke detector
triggering, in order to give time for staff to investigate. Heat detection and manual call points should
normally be left with an instant response, but possibly phasing the evacuation from the critical areas.
Note that Group1 has been configured to only report the event (using alarm stage 2) to zone 3. The result
is localised to the zone where the fire occurred.
77
Quadnet / Duonet OSP Software Operating Instructions
In this example, any smoke alarm input on Detection Zone 3 will cause an ‘Alarm stage 2’ sound in Alarm
Zone 3 only (because of the setting of Group 1). After a time delay (configured earlier as Alarm Delay 2 in
the Delays and Timers tab on the Panel System Details screen), or immediately after a heat or call point
activation, the sound will change to an ‘Alarm stage 3’ sound in Alarm Zones 3,4 and 5.
Thus, an Alarm Stage 2 (Alert) is generated on the same zone as the smoke detector activation. After a
time delay, or immediately after a heat alarm or manual call point activation, an Alarm Stage 3 (Evacuate)
is generated on that zone and also zones 4-5.
Thus, only the area at highest risk is initially evacuated, in order to avoid evacuating the entire site at one
go.
Remember that the group 1 and 2 configuration must be set for every input ‘Detection Zone’ required (not
just for Zone 3), both on initial commissioning and during any future alterations to the system.
It is required that the system will minimise false alarms from sheltered housing apartments, whilst providing
accurate warning of real fire situations.
The Multipoint detection in the apartments utilises the I/O Interface base to signal through the warden call
system to the warden (or central station if the warden is off site). This is combined with alarm confirmation
in order to provide a means of aborting a full alarm if the occupant is able to remove the cause of a false
alarm.
Panel Details
78
Quadnet / Duonet OSP Software Operating Instructions
Within the Panel Details section, select a value for the Alarm Confirmation Delay. This is done on the
Delays and Timers tab.
In our example, an Alarm Confirmation delay of 4 minutes 00 seconds has been set up.
Device Details
Set the devices within the apartments as follows, with the Alarm Stage 1 sound pattern selected to SP1,
SP2 or SP3.
Set the devices within communal areas, corridors and escape routes as follows, with the Alarm Stage 1
sound pattern set to SP0 (off).
Alarm confirmation has been turned ON for the devices within the apartments (Rooms 24, 25 and 26).
Also using the Device I/O tab, set the I/O linkage to Monitored Output / Device for each of the devices
within the apartments. Thus I/O Interface base relays will operate only when its host smoke detector
triggers.
Use the Device I/O Details button to obtain the following screen to select the I/O type Monitored Output –
Device output as follows. Device 10 is shown as an example.
79
Quadnet / Duonet OSP Software Operating Instructions
The Cause & Effect section should be set as for instant alarms as described previously (this is the default
setting). Set Group 1 as shown below. Remember to set this for each of the detection zones with inputs.
Group 2 does not need to be set.
The Alarm Confirmation routine takes place before the system enters the alarm state.
In this example, an ‘Alarm stage 3’ sound will operate in all Alarm Zones in response to the operation of the
following:
Whilst a single smoke detector within an apartment is in its alarm confirmation stage, it will operate its own
local sounder only, and trigger the I/O interface base relay to which it is attached. Thus, if this is connected
to the local warden call unit, the warden is able to rapidly establish contact with the occupier and verify the
alarm status of the alarm. If the cause of an unwanted is removed within the selected 4 minute Alarm
Confirmation delay period then the device will reset and a full alarm will be avoided.
Remember that the group 1 and 2 configuration must be checked for every input ‘Detection Zone’ required,
both on initial commissioning and during any future alterations to the system.
80
Quadnet / Duonet OSP Software Operating Instructions
Technical Data
81
Quadnet / Duonet OSP Software Operating Instructions
V0.367
V2.04
V3.04
PANEL VERSION
Panel Versions up to v1.29 √
Panel Versions v1.34 to v2.xx √
Panel Versions v3.xx √
Technical Support
For further technical support please contact your distributor. Do not call the Fike Safety Technology
technical support department unless your distributor has first given their advice and attempted to rectify the
issue.
Technical support will not be available if the instruction manual has not been read and understood. Please
have this instruction manual available whenever you call for technical support. Due to the complexity and
inherent importance of a life risk type system, training on this equipment is essential, and commissioning
should only be carried out by competent persons.
82
Quadnet / Duonet OSP Software Operating Instructions
Configuration Sheets
Device Details Record your device attributes on the following form. Copy as required for all devices in the
system.
SITE DETAILS:
DEVICE SERIAL DEVICE DESCRIPTION (23 CHARACTERS ZONE DEVICE SMOKE HEAT ALARM
ADDRESS NUMBER MAX) TYPE MODE MODE CONF’N
E.g., 1 35415 Gnd Flr Front Office 1 MPS SM2 HM2 NO
83
Quadnet / Duonet OSP Software Operating Instructions
Detection Zone/Alarm Zone Details Record your zonal ‘Cause & Effect’ here. Copy as required for
all zones.
Note:
On a network of control panels, there can be up to 128 zones on each panel (local zones). Version 3 repeater and
control panels will illuminate the zone LED corresponding to the zone in alarm on each networked control panel.
If there were 4 networked panels on a system there could be a total of 512 separate zones but all numbered in the
range 1-128. This means there could be four different zone 1s, four different zone 2s etc.
It is recommended that on networked systems using version 3 panels, zones are configured so there are a
maximum of 128 zones on the whole system and there are no duplications.
GROUP 1: GROUP 2:
Stage Stage Stage Stage
LINKS TO GROUP 1: LINKS TO GROUP 2:
2 3 2 3
LINK IF MCP/HEAT/INPUT LINK IF MCP/HEAT/INPUT
ALARM ZONES TO ACTIVATE FROM GROUP 1: ALARM ZONES TO ACTIVATE FROM GROUP 2:
ALARM ZONE 1 ALARM ZONE 65 ALARM ZONE 1 ALARM ZONE 65
84
Quadnet / Duonet OSP Software Operating Instructions
ALARM ZONE 36 ALARM ZONE 100 ALARM ZONE 36 ALARM ZONE 100
ALARM ZONE 37 ALARM ZONE 101 ALARM ZONE 37 ALARM ZONE 101
ALARM ZONE 38 ALARM ZONE 102 ALARM ZONE 38 ALARM ZONE 102
ALARM ZONE 39 ALARM ZONE 103 ALARM ZONE 39 ALARM ZONE 103
ALARM ZONE 40 ALARM ZONE 104 ALARM ZONE 40 ALARM ZONE 104
ALARM ZONE 41 ALARM ZONE 105 ALARM ZONE 41 ALARM ZONE 105
ALARM ZONE 42 ALARM ZONE 106 ALARM ZONE 42 ALARM ZONE 106
ALARM ZONE 43 ALARM ZONE 107 ALARM ZONE 43 ALARM ZONE 107
ALARM ZONE 44 ALARM ZONE 108 ALARM ZONE 44 ALARM ZONE 108
ALARM ZONE 45 ALARM ZONE 109 ALARM ZONE 45 ALARM ZONE 109
ALARM ZONE 46 ALARM ZONE 110 ALARM ZONE 46 ALARM ZONE 110
ALARM ZONE 47 ALARM ZONE 111 ALARM ZONE 47 ALARM ZONE 111
ALARM ZONE 48 ALARM ZONE 112 ALARM ZONE 48 ALARM ZONE 112
ALARM ZONE 49 ALARM ZONE 113 ALARM ZONE 49 ALARM ZONE 113
ALARM ZONE 50 ALARM ZONE 114 ALARM ZONE 50 ALARM ZONE 114
ALARM ZONE 51 ALARM ZONE 115 ALARM ZONE 51 ALARM ZONE 115
ALARM ZONE 52 ALARM ZONE 116 ALARM ZONE 52 ALARM ZONE 116
ALARM ZONE 53 ALARM ZONE 117 ALARM ZONE 53 ALARM ZONE 117
ALARM ZONE 54 ALARM ZONE 118 ALARM ZONE 54 ALARM ZONE 118
ALARM ZONE 55 ALARM ZONE 119 ALARM ZONE 55 ALARM ZONE 119
ALARM ZONE 56 ALARM ZONE 120 ALARM ZONE 56 ALARM ZONE 120
ALARM ZONE 57 ALARM ZONE 121 ALARM ZONE 57 ALARM ZONE 121
ALARM ZONE 58 ALARM ZONE 122 ALARM ZONE 58 ALARM ZONE 122
ALARM ZONE 59 ALARM ZONE 123 ALARM ZONE 59 ALARM ZONE 123
ALARM ZONE 60 ALARM ZONE 124 ALARM ZONE 60 ALARM ZONE 124
ALARM ZONE 61 ALARM ZONE 125 ALARM ZONE 61 ALARM ZONE 125
ALARM ZONE 62 ALARM ZONE 126 ALARM ZONE 62 ALARM ZONE 126
ALARM ZONE 63 ALARM ZONE 127 ALARM ZONE 63 ALARM ZONE 127
ALARM ZONE 64 ALARM ZONE 128 ALARM ZONE 64 ALARM ZONE 128
85
Quadnet / Duonet OSP Software Operating Instructions
Your Notes
86
Quadnet / Duonet OSP Software Operating Instructions
Your Notes
87
Quadnet / Duonet OSP Software Operating Instructions
Important Points
• You will need a PC with a serial port, the Quadnet / Duonet OSP
software and a Quadnet / Duonet USB Lead (page 6).
If you have any further queries, please contact your supplier for further information
88